Rohini Transformer Basic
Rohini Transformer Basic
The equation which relates the rated kVA output of a transformer to the
area of core and window is called output equation.
The flux density is related to core area and the ampere-turns is related to
window area.
Each limb carries the low voltage and high voltage winding of a phase.
𝐸 = 4 ⋅ 44𝑓𝜙𝑚 𝑇
Volts
𝐴𝐶
𝑘𝑤 =
𝐴𝑤
Conductor area in window,
𝐴𝐶 = 𝑘𝑊 𝐴𝑊
The current density is same in both the windings. Therefore Current density,
𝐼𝑝 𝐼𝑆
𝛿= =
𝐴𝑝 𝐴𝑠
𝐼𝑃
𝐴𝑃 =
𝛿
Area of cross - section of secondary conductor,
𝐼𝑆
𝐴𝑆 =
𝛿
𝐴𝑇 = 𝐼𝑝 𝑇𝑝 = 𝐼𝑆 𝑇𝑆
Total copper area in window,
4𝐴𝑇
𝐴𝐶 =
𝛿
EE8002 DESIGN OF ELECTRICAL APPARATUS
ROHINI COLLEGE OF ENGINEERING & TECHNOLOGY
4𝐴𝑇
𝐾𝑊 𝐴𝑊 =
𝛿
Therefore, Ampere turns,
1
𝐴𝑇 = 𝑘 𝐴
4 𝑊 𝑤
𝑄 = 3𝑣𝑝 𝐼𝑝 ∗ 1𝑂 −3
𝑄 = 3.33𝑓𝜙𝑚 𝑘𝑤 𝐴𝑣 𝛿𝑥1𝑂 −3