Design of Eccentric Isolated Footing With Strap Beam: NMM Per Meter Run
Design of Eccentric Isolated Footing With Strap Beam: NMM Per Meter Run
Input Parameter
Column Size C1 = 0.355 m
Column Size C2 = 0.355 m
Load on C1 P1u = 445.62 kN
Load on C2 P2u = 829.33 kN
C/C distance of C1-C2 L = 3.9 m
SBC of Soil q = 150 kN/m2
Strength of concrete fck = 20 N/mm2
Strength of rebar fy = 500 N/mm2
fck = 20 N/mm2
fy = 500 N/mm2
Mu = 189.343 KN-m
b = 355.00 mm
d = 500.00 mm
Now Solving above equation,
2
Ast = 1016.51 mm
Dia of bar Ø = 16 mm
2
Area of bar A Ø = 201 mm
Number of bar required = 5.06
Hence provide 3 bars of 16 mm diat at bottom portion of the beam
2
Ast provided = 603.264 mm
Minimum steel Ast min = 301.75 < Ast provided
HENCE SAFE