INSTALLATION ENVIRONMENT
The UPS and the Battery Box must be installed in ventilated, clean environments which are sheltered from bad weather.
The relative humidity in the environment must not exceed the maximum values shown in the Technical Data table.
The ambient temperature, whilst the UPS is in operation, must remain between 0 and 40°C, and the UPS must not be
positioned in places which are exposed to direct sunlight or to hot air.
The recommended operating temperature for the UPS and the batteries is between 20 and 25°C. The actual
operating life of the batteries is 5 years on average with an operating temperature of 20°C. If the operating
temperature reaches 30°C, the operating life is halved.
This is a category C2 UPS product. In a residential environment, this product may cause radio interference,
in which case the user may be required to take additional measures.
USE
4) After a few moments, the UPS will switch on, the display will light up, there will be a beep and the icon will start to flash.
The UPS is in stand-by mode: meaning that it is only consuming a small amount of power. The microcontroller supervising
the self-diagnoses is powered; the batteries are charging; and everything is ready for UPS activation. Battery operation is also
in stand-by mode provided that the timer is active.
5) Ensure that the cables connecting any devices to the output sockets of the UPS do not exceed a maximum of 10m in length.
6) Check which operating mode is set on the display and, if necessary, see the “Configuring operating modes” paragraph to set
the required mode. For advanced UPS configurations execute the software UPSTools which can be downloaded from the web
site www.ups-technet.com.
2) The load must continue to be powered, the icon on the display must light up and there must be a beep every 4
seconds.
3) When power is reconnected, the UPS must go back to operating from the mains.
10
10 Fixed Indicates a fault
The UPS is operating from the battery. In this condition, the UPS emits an
Fixed
acoustic signal (beep) at regular 4-second intervals.
Indicates the percentage of charge applied to the UPS compared with the
Dynamic
nominal value.
Flashing 1 minute until the UPS switches back on or 3 minutes until it switches off
* For more information about the configuration of the EnergyShare sockets, see "Additional Features"