0% found this document useful (0 votes)
237 views

MagFlow 2400-Electromagnetic Flow Meter Data Sheet

The document describes the MagFlow 2400 electromagnetic flow meter. It works by inducing a voltage proportional to flow rate when conductive fluid passes through a magnetic field. Key features include high accuracy, wide flow range, anti-corrosion materials, digital processing and communication interfaces. It provides flow measurement for water and other liquids in various industries and has specifications for operating conditions, materials, sizing and ordering codes.

Uploaded by

Prateek Dash
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
237 views

MagFlow 2400-Electromagnetic Flow Meter Data Sheet

The document describes the MagFlow 2400 electromagnetic flow meter. It works by inducing a voltage proportional to flow rate when conductive fluid passes through a magnetic field. Key features include high accuracy, wide flow range, anti-corrosion materials, digital processing and communication interfaces. It provides flow measurement for water and other liquids in various industries and has specifications for operating conditions, materials, sizing and ordering codes.

Uploaded by

Prateek Dash
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Electromagnetic flow meters

MagFlow 2400

Working Principle:
The working principle of a magnetic flow meter is based on Faraday’s law of electromagnetic
induction. According to Faraday’s law, when the conductive fluid flows through a magnetic
field of the sensor, an electromotive force proportional to the volume flow is generated be-
tween the pair of electrodes, which is perpendicular to the flow direction and the magnetic
field. The amplitude of the electromotive force can be expressed as:

E = kBDv
Where E:Induced electric potential,
K: constant,
B:Magnetic flux density,
D:The inner diameter of the measuring Tube,
V:The average velocity of the fluid in the
axial direction of the electrode cross-section inside
the measuring tube.

MIRRANT AUTOMATION PRIVATE LIMITED


Plot No:6A/5,IDA Phase-I, Patancheru, Phone: +91 9949306860
Sangareddy Dist.,Hyderabad-502032 Email: [email protected] Sense. Automate. Integrate
Telangana, India Website: www.mirrant.com
Electromagnetic flow meters
MagFlow 2400
Features:
1. Measurement result will not be affected by change of density, viscosity, temperature,
pressure and conductive rate
2. Product with good anti-corrosion and abrasion resistance performance
3. Full digital process, strong anti-interference performance, operating reliable with high
accuracy and wide range of flow rate
4. Super low voltage EMI switch power supply, which could ensure fast response for voltage
changes and good resistance on EMI
5. LCD Displays Flow Rate, Totaliser,Alarms,Analog output. All Standard Engineering Units
in m3.Litre,Gallon,ft3
6. Product is manufactured with SMD devices and SMT technology, which provides high
reliability circuits.
7. With self checking and diagnosis function and IOT Ready-AMR Network.

Specifica ons:
MagFlow 2400 Electromagnetic flow meter
Domestic water, industrial water, raw water, ground water, urban
Medium sewage, industrial waste water, Processed neutral pulp, pulp slurry,
Chemicals etc.
Diameter DN10~DN2000mm
Accuracy ±0.5%
Repeatability ±0.2% of Span
Medium temperature <180'C
Medium pressure (Kg/Cm2) 10,16,25,40
Flow rate 0.3~10m/s
Electrode Material SS316 Std.,Hastalloy C,Titanium,Tantalum,Platinum,etc
Lining Material PTFE,Rubber,Neoprene,PFA,HDPE,Polyurethane,CPVC etc
Flow Tube Material SS304 Std,SS316
Coil House Material Carbon steel,Stainless steel
Power supply 230VAC,24VDC,Battery
Signal output 4~20mA, Pulse and Relay
Communication Interface RS485,GSM/GPRS,HART,LORA
Display LCD Display In Engg.Units
Protection proof IP65; IP67,IP68
Flow Transmitter Integral, Remote
Enclosure Material Die Cast Aluminium
Electrical Connection 1/2" NPT
Work environment Ambient temperature:-20~+60H,Ambient humidity:5%~90%
End Connection Flange-end, Wafer, Tri-Clover etc.

MIRRANT AUTOMATION PRIVATE LIMITED


Plot No:6A/5,IDA Phase-I, Patancheru, Phone: +91 9949306860
Sangareddy Dist.,Hyderabad-502032 Email: [email protected] Sense. Automate. Integrate
Telangana, India Website: www.mirrant.com
Electromagnetic flow meters
MagFlow 2400

Flow Table:
Size (D) m3/h LPM LPS GPM
mm inch Min. Max. Min. Max. Min. Max. Min. Max.
10 3/8" 0.08 2.83 1.41 47.10 0.02 0.79 0.37 12.44
15 1/2" 0.19 6.36 3.18 106.03 0.05 1.77 0.84 28.01
20 3/4" 0.34 11.31 5.66 188.50 0.09 3.14 1.49 49.80
25 1" 0.53 17.67 8.84 294.50 0.15 4.91 2.33 77.81
32 1-1/4" 0.87 28.95 14.48 482.50 0.24 8.04 3.82 127.48
40 1-1/2" 1.36 45.24 22.63 754.00 0.38 12.57 5.98 199.21
50 2" 2.12 70.69 35.35 1178.17 0.59 19.64 9.34 311.27
65 2-1/2" 3.58 119.50 59.73 1991.67 1.00 33.19 15.78 526.20
80 3" 5.43 181.00 90.48 3016.67 1.51 50.28 23.91 797.01
100 4" 8.48 282.70 141.38 4711.67 2.36 78.53 37.35 1244.83
125 5" 13.26 441.80 221.00 7363.33 3.68 122.72 58.39 1945.40
150 6" 19.09 636.20 318.17 10603.33 5.30 176.72 84.06 2801.41
200 8" 33.93 1131.00 565.50 18850.00 9.43 314.17 149.41 4980.18
250 10" 53.02 1767.00 883.67 29450.00 14.73 490.83 233.47 7780.71
300 12" 76.35 2545.00 1272.50 42416.67 21.21 706.94 336.20 11206.52
350 14" 92.37 3079.00 1539.50 51316.67 25.66 855.28 406.74 13557.90
400 16" 135.80 4524.00 2263.33 75400.00 37.72 1256.67 597.97 19920.74
450 18" 171.80 5726.00 2863.33 95433.33 47.72 1590.56 756.49 25213.56
500 20" 212.10 7069.00 3535.00 117816.67 58.92 1963.61 933.95 31127.26
600 24" 305.40 10180.00 5090.00 169666.67 84.83 2827.78 1344.78 44826.07
700 28" 415.00 13850.00 6916.67 230833.33 115.28 3847.22 1827.39 60986.35
800 32" 542.00 18100.00 9033.33 301666.67 150.56 5027.78 2386.61 79700.57
900 36" 662.00 22900.00 11033.33 381666.67 183.89 6361.11 2915.02 100836.64
1000 40" 848.00 28260.00 14133.33 471000.00 235.56 7850.00 3734.04 124438.57

MIRRANT AUTOMATION PRIVATE LIMITED


Plot No:6A/5,IDA Phase-I, Patancheru, Phone: +91 9949306860
Sangareddy Dist.,Hyderabad-502032 Email: [email protected] Sense. Automate. Integrate
Telangana, India Website: www.mirrant.com
Electromagnetic flow meters
MagFlow 2400
Ordering Code: MagFlow 2400:
MagFlow 2400- 0025 M1 N1 L1 E1 H1 T1 F1 G1 I P1 S1 C1 A N Description
DN10-DN2000 (mm)
10,15,20,25,40,50,65,80,100,125,150,
Sensor Size XXXX 200,250,300,350,400,450,500,600,700,
800,900,1000,1200,1400,1600,1800,
2000..,
M1 Flange-end
M2 Wafer
End Connection Type M3 Tri-Clover / SMS
M4 Insertion
M5 Any Other..
N1 5 Kg/cm2
N2 10 Kg/cm2
Nominal Pressure Rating
N3 <40 Kg/Cm2
N4 Any Other..
L1 PTFE
L2 Rubber
Lining Material
L3 PFA
L4 Any Other..
E1 SS316
E2 SS316L
Electrode Material
E3 Hastelloy C
E4 Any Other..
H1 CS
H2 SS304
Coil Housing Material
H3 SS316
H4 Any Other..
T1 SS304
Flow Tube Material T2 SS316
T3 Any Other..
F1 CS
F2 SS304
Flange Material
F3 SS316
F4 Any Other..
G1 Not Applicable
G2 SS316
Grounding Rings Material
G3 SS316L
G4 Any Other..
I Integral
Flow Transmitter
R Remote
P1 85-265V AC
P2 24V DC
Power Supply
P3 3.6V lithium battery
P4 Any Other..
S1 4-20mA DC, Pulse & 2 Relays (Alarm)
Signal Output
S2 Any Other..
C1 Modbus RS485
C2 HART
Communication Protocol
C3 GSM/GPRS
C4 Any Other..
A IP 65
Enclosure Class B IP 67
C IP 68
N Not Applicable
Approval
F Flame Proof (FLP)

MIRRANT AUTOMATION PRIVATE LIMITED


Sense. Automate. Integrate
Plot No:6A/5,IDA Phase-I, Patancheru, Phone: +91 9949306860
Sangareddy Dist.,Hyderabad-502032 Email: [email protected] Sense. Automate. Integrate
Telangana, India Website: www.mirrant.com