Piza Structural

1. This document provides specifications for concrete work including placement, reinforcement, formwork, and curing. Concrete must be placed without segregation using buckets, wheelbarrows or buggies, with vibrators used for proper consolidation. 2. Reinforcement shall be properly supported with chairs or equivalent at 1 meter spacing. Minimum slab reinforcement of 10mm bars at 250mm spacing is required. 3. Concrete must be kept moist for at least 7 days after pouring using curing compounds or other approved methods.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
228 views

Piza Structural

1. This document provides specifications for concrete work including placement, reinforcement, formwork, and curing. Concrete must be placed without segregation using buckets, wheelbarrows or buggies, with vibrators used for proper consolidation. 2. Reinforcement shall be properly supported with chairs or equivalent at 1 meter spacing. Minimum slab reinforcement of 10mm bars at 250mm spacing is required. 3. Concrete must be kept moist for at least 7 days after pouring using curing compounds or other approved methods.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

6d but min. of 75mm.

1. IN THE INTERPRETATION OF THE DRAWING THE DIMENSIONS

4d
INDICATED SHALL GOVERN. DISTANCES AND SIZES SHALL NOT BE 1. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT 5. TEMPERATURE BARS FOR SLAB SHALL BE GENERALLY PLACED NEAR
SCALED FOR CONSTRUCTION PURPOSES IF DIMENSIONS ARE PLACED. n = 5d
SEGREGATION, RE-HANDLING OR PLACING SHALL BE DONE THE FACE IN TENSION AND SHALL NOT BE LESS THAN 0.0025XGROSS

4d
PREFERABLY WITH BUCKETS, WHEELBARROWS OR BUGGIES. NO CROSS-SECTIONAL AREA OF THE SLAB. h = 12d

2d
2. DRAWINGS FOR DEPRESSIONS IN FLOOR SLABS, OPENINGS IN THE CHUTES SHALL BE ALLOWED EXCEPT TO TRANSFER CONCRETE FROM
WALLS AND SLABS, INTERIOR PARTITIONS, LOCATION OF DRAINS ETC. HOPPERS TO BUGGIES, WHEELBARROWS OR BUCKETS IN WHICH CASE 6. UNLESS OTHERWISE NOTED IN THE PLANS ALL BEDDED SLABS SHALL
SHALL BE REFERENCED TO THE ARCHITECTURAL PLANS. 3d

d
THEY SHALL NOT EXCEED SIX METERS IN AGGREGATE LENGTH. BE REINFORCED WITH DIAMETER 10 MM AT 250 MM O.C. EACH WAY TO L L
CENTER OF SLAB AND CONSTRUCTION JOINTS FOR SAME SHALL NOT
3. IN CASE THAT THERE IS A DISCREPANCY AS TO THE LAYOUT, 2. DEPOSITING OF CONCRETE SHALL NOT BE ALLOWED WITHOUT THE USE BE LESS THAN 3.65 M APART.
DIMENSION AND ELEVATIONS BETWEEN THE STRUCTURAL PLANS AND OF VIBRATORS UNLESS AUTHORIZED IN WRITING BY THE DESIGNER AND
THE ARCHITECTURAL PLANS, THE CONTRACTOR SHALL NOTIFY BOTH ONLY FOR UNUSUAL CONDITIONS WHERE VIBRATIONS ARE EXTREMELY 7. PROVIDE EXTRA REINFORCEMENT FOR CORNER SLABS. DEVELOPMENT LENGTH, dh SHALL BE AS FOLLOWS:
THE STRUCTURAL ENGINEER AND THE ARCHITECT. DIFFICULT TO ACCOMPLISH.
8. CONCRETE SLAB REINFORCEMENTS SHALL BE PROPERLY SUPPORTED (a) FOR BARS WITH SIDE COVER (NORMAL TO PLANE OF HOOK) NOT LESS
4. TYPICAL DETAILS AND CONSTRUCTION NOTES WILL APPLY TO ALL 3. ALL CONCRETE SHALL BE KEPT IN A MOIST CONDITION FOR A MINIMUM WITH 10MMØ STEEL CHAIR OR APPROVED EQUIVALENT SPACED AT 1.0 THAN 65mm, AND FOR 90 DEG. HOOK, COVER ON BAR EXTENSION
DRAWINGS UNLESS OTHERWISE SHOWN OR NOTED. SOME OF SEVEN CONSECUTIVE DAYS IMMEDIATELY AFTER POURING EITHER METER ON CENTER BOTHWAYS. BEYOND HOOK NOT LESS THAN 50mm, USE 0.7 hb.
MODIFICATIONS TO THE TYPICAL DETAIL CAN BE MADE TO MEET BY THE USE OF BURLAP, SPRAYING, CURING COMPOUNDS OR OTHER
SPECIAL CONDITIONS ON THE PROJECT. APPROVED METHOD. (b) FOR BARS WITH HOOKS ENCLOSED VERTICALLY OR HORIZONTALLY
9. SCHEDULE OF MINIMUM SLAB REINFORCEMENT WITHIN TIES OR STIRRUP - TIES SPACED ALONG THE FULL
5. ALL SHOP DRAWINGS WITH ERECTION AND PLACING DIAGRAMS OF 4. ALL ANCHOR BOLTS, DOWELS AND OTHER INSERTS SHALL BE DEVELOPMENT LENGTH dh NOT GREATER THAN 3db, USE 0.8 hb.
ALL FABRICATED STRUCTURAL MEMBERS SHALL BE SUBMITTED FOR PROPERLY POSITIONED AND SECURED IN PLACE PRIOR TO PLACING OF THICKNESS MINIMUM TEMPERATURE BARS
THE ENGINEERS APPROVAL BEFORE FABRICATION. MISCELLANEOUS CONCRETE. 100 mm (SOF) 12 mm Ø @ 400 mm O.C. EACHWAY (c) FOR BARS NOT INCLUDED IN (a) AND (b), USE 1.0 hb.
CURBS, SILLS, STOOLS, MECHANICAL BASES AND EQUIPMENTS THAT
100 mm (SS) 10 mm Ø @ 300mm O.C. EACHWAY
ARE REQUIRED BY THE CONSTRUCTION DRAWINGS. 5. THE CONTRACTOR SHALL SUBMIT THE SCHEDULE OF POURING AND (w/ 0.80mm. METAL DECKING)
THE LOCATION OF THE CONSTRUCTION JOINTS TO THE STRUCTURAL
6. THE RESULTS OF ALL MATERIAL TESTING FOR CONCRETE, ENGINEER AT LEAST 4 DAYS PRIOR TO THE POURING APPROVAL.. REBAR MIN. DEVELOPMENT
REINFORCING BARS AND STRUCTURAL STEEL MUST BE NOTED AND DIAMETER LENGTH d(mm)
APPROVED BY THE ENGINEER. 6. THE CONTRACTOR SHALL PROVIDE AND MAINTAIN ADEQUATE FORMS (mm) TOP BARS OTHERS
AND SHORING UNTIL THE CONCRETE MEMBERS HAVE ATTAINED THEIR 10 395 300
7. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE NOTED. WORKING CONDITION AD STRENGTH. 12 470 350
8. ALL BAR DIAMETERS AND SPACING ARE IN MILLIMETERS UNLESS 16 630 465
OTHER WISE NOTED. SECTION A-A' 20 785 585
STRIPPING OF FORMS AND SHORES DURATION
400
FOUNDATION 24 HRS
SUSPENDED SLAB 8 DAYS
1 GENERAL NOTES BEAMS 14 DAYS
COLUMNS 21DAYS HOOK DEVELOPMENT LENGTH
S 1

400
SCALE: N/A

0
60
7. MINIMUM CONCRETE COVER A A' REBAR BASIC DEVELOPMENT

0
SLAB DIAMETER

60
MINIMUM CONCRETE OPENING LENGTH dh(mm)
LOCATION (mm)
COVER (mm)
1. CONCRETE SPECIFICATION 10 150
SUSPENDED SLABS 20
12 175

60
28 DAY MAX SIZE OF SLAB ON GROUND 40
16

0
LOCATION STRENGTH AGGREGATE MAX SLUMP 234
WALLS ABOVE GROUND 25
(PSI) (mm) (mm) 20 292
BEAM STIRRUP AND COLUMN TIES 40
FOOTINGS 3500 25 100 WHERE CONCRETE IS EXPOSED TO
50 TYPICAL CORNER TYPICAL SLAB
SUSPENDED SLAB 3000 25 100 EARTH BUT POURED AGAINST FORMS
SLAB DETAIL OPENING DETAIL
BEAMS AND COLUMNS 3500 25 100 WHERE CONCRETE IS DEPOSITED
75
SLAB ON FILL OR GRADE 3500 25 100 DIRECTLY AGAINST EARTH BEND DEVELOPMENT LENGTH
STANDARD HOOKS

2. REINFORCING BARS REBAR DIAMETER HOOK BEND 180°HOOK 90°HOOK dh


a. FOR BARS 16 mm AND LARGER ---------------- GRADE 60 3 CONCRETE MIXING & PLACEMENT (mm) DIAMETER(mm) LENGTH LENGTH 150 (MIN)
b. FOR BARS 12 mm AND SMALLER --------------- GRADE 60 CRITICAL
S 1 SCALE: N/A 10 75 75 120 SECTION db
3. STRUCTURAL STEEL, ASTM-A36 12 75 75 110
a. FOR TRUSSES, BRACINGS AND STRUTS ----- fy=248MPa (36,000 PSI) 16 190 120 145
b. FOR STUCTURAL SECTIONS ---------------------- fy=248MPa (36,000 PSI)
20 240 150 240
1. REINFORCING BARS SHALL BE FREE OF RUST, GREASE OR OTHER
4. PURLINS: 90° HOOK
MATERIALS LIKELY TO IMPAIR BOND.
COLD FORMED LIGHT GAGE SHAPES ------------ fy=248MPa (36,000 PSI)
5. MASONRY CHB:NON-LOAD BEARING ---------------- fm'= 3.45 MPa (500 PSI) 2. ALL REINFORCING BARS SHALL BE ACCURATELY AND SECURELY PLACE d dh
BEFORE POURING CONCRETE OR APPLYING MORTAR OR GROUT. 300 (MIN) 150 (MIN)
6. WELDS-USE E-60xx ELECTRODE
3. BAR SPLICES SHALL BE SECURELY WIRED TOGETHER SPLICES IN HOOKS FOR TIES AND STIRRUPS CRITICAL CRITICAL
7. STRUCTURAL BOLTS, ASTM-A307---------------------- Ft=96.60 MPa (14,000 PSI) SECTION db SECTION db
REINFORCED CONCRETE BEAMS, COLUMNS AND WALLS SHALL BE AS REBAR DIAMETER HOOK BEND DIAMETER HOOK LENGTH
Fv=69 MPa (10,000 PSI) SHOWN IN THE DETAILS. FOR NON-STRUCTURAL WALLS, MASONRY (mm) (mm) 135°
WALLS AND SLABS, SPLICES SHALL LAP A MINIMUM OF 40 BAR
DIAMETERS AND SHALL BE STAGGERED WHEREVER POSSIBLE. 10 60 75
2 MATERIAL SPECIFICATION 12 75 100 180° HOOK
4. IF THE SLAB IS REINFORCED BOTHWAYS THE BAR ALONG THE SHORTER
S 1 SCALE: N/A SPAN SHALL BE PLACED BELOW THOSE ALONG THE LONG SPAN AT THE
4 REINFORCEMENT NOTES
CENTER AND OVER THE LONG SPAN FOR REINFORCING BARS NEAR THE
SUPPORTS.
S 1 SCALE: N/A

CIVIL / STRUCTURAL ENGINEER DRAWN PRP PROJECT TITLE PROJECT OWNER SHEET NO.
This document is owned and
CHECK PRP
solely property of Villa Preciosa PROPOSED TWO
Realty, Inc.(VPRI). Any alteration RICARDO D. LANTAJO JR. DATE 10/26/2022 SPS. GEOVANI LAZO PIZA &
STOREY RESIDENCE
and tampering of this document
without the consent of VPRI and
PRC 145324 Validity 6 - 02 -2025 REMARKS HILDA ARELLANO PIZA S-1
it's architect is not valid. PTR 734347 Issued 1 - 05 -2022 CONTENT GENERAL NOTES PROJECT LOCATION ADDRESS
Place ALAMINOS CITY STO NINO, CENTRAL BAKAKENG, BAGUIO CITY NO. 25-D RIMANDO ROAD, BAGUIO CITY, 2600
1. SEE NOTES ON SPECIFICATIONS.
1. LAPPED SPLICES FOR SLAB REBARS SHALL BE STAGGERED WHERE 1. UNLESS OTHER WISE SHOWN IN PLANS ALL CONCRETE HOLLOW BLOCKS 2. MATERIALS:
POSSIBLE. AND CERAMIC BLOCKS SHALL BE REINFORCES AS SHOWN IN THE W-SHAPES & WT-SHAPES................................................. ASTM A992
SCHEDULE OF CONCRETE HOLLOW BLOCK REINFORCEMENT. S-SHAPES, M-SHAPES, HP-SHAPES................................ ASTM A36
2. UNLESS OTHERWISE SHOWN ON PLANS SPLICES SHALL BE AS ST-SHAPES & MT-SHAPES.............................................. ASTM A36
FOLLOWS: 2. PROVIDE 150mmX300mm STIFFENER COLUMN REINFORCED WITH 4-12mm C-SHAPES & MC-SHAPES................................................ ASTM A36
WITH 6mm Ø TIES AT 150mm ON CENTER WHERE CONCRETE HOLLOW ANGLES & PLATES........................................................... ASTM A36
A. INTERMEDIATE BEAMS----TOP BARS SHALL BE SPLICED AT BLOCK TERMINATES AND AT EVERY 3.0m LENGTH OF CONCRETE HOLLOW HSS SHAPES..................................................................... ASTM A500, GRADE B
MID-SPAN AND BOTTOM BARS SHALL NOT BE SPLICED WITH IN BLOCK WALLS UNLESS NOTED IN400
STRUCTURAL PLANS. STEEL PIPE....................................................................... ASTM A53 (TYPE E OR S), GRADE B
THE COLUMN OR WITHIN A DISTANCE OF TWICE THE MEMBER HOOK HIGH STRENGTH BOLTS................................................. ASTM A325
DEPTH FROM THE FACE OF THE COLUMN. MACHINE BOLTS.............................................................. ASTM A307
ANCHOR RODS................................................................ ASTM F1554, GRADE 55 TYPE S1(UNO)
B. COLUMNS: LAP SPLICES SHALL BE MADE WITH IN THE CENTER WELDED HEADED STUDS.............................................. ASTM A108
HALF OF HEIGHT AND THE SPLICE SHALL NOT BE LESS THAN DEFORMED BAR ANCHORS............................................ ASTM A496
40 BAR DIAMETERS , WELDING OR THE USE OF APPROVED WELDING ELECTRODES.................................................. AWS D1.1, E70 SERIES
MECHANICAL DEVICES MAY BE PERMITTED PROVIDED THAT 3. NON-SHRINK, NON-METALLIC GROUT WITH A 28 DAY STRENGTH OF 5000 PSI SHALL BE USED UNDER BASE PLATES AND SHALL CONFORM TO
NOT MORE THAN ALTERNATE BARS ARE WELDED OR SPLICED CORPS OF ENGINEERS CRD-C621, FACTORY PREMIX GROUT. SEE SPECIFICATIONS FOR TESTING REQUIREMENTS.
AT ANY LEVEL AND THE MINIMUM VERTICAL DISTANCE 4. ENGINEER SHALL BE CONTACTED FOR APPROVAL OF ANY FIELD MODIFICATIONS OF ANCHOR BOLTS OR RODS AND COLUMN BASE PLATES
REBAR DETAIL ON CHB TO COLUMN
BETWEEN TWO ADJACENT BAR SPLICES SHALL BE 600 mm. (PER OSHA).
5. TEMPORARY BRACING OF STRUCTURAL STEEL ELEMENTS IS THE RESPONSIBILITY OF THE CONTRACTOR. STRUCTURAL STABILITY SHALL BE
C. CHB WALLS: VERTICAL BARS SHALL BE SPLICED AT THE TOP 3 CHB WALL NOTES MAINTAINED AT ALL TIMES DURING THE ERECTION PROCESS. CONTRACTOR MUST PROVIDE NOTIFICATION TO THE ERECTOR THAT, BY TESTING,
OF WALL FOOTINGS OR FOOTING TIE BEAMS AND AT THE THE FOUNDATION AND SUPPORTING WALLS HAVE ATTAINED SUFFICIENT STRENGTH TO SUPPORT THE STEEL TO BE ERECTED BEFORE
BOTTOM OF REINFORCES CONCRETE LINTEL BEAMS OR S 2 SCALE: N/A
ERECTING STRUCTURAL STEEL.
BEAMS. 6. PROVIDE ONE SHOP COAT OF PRIMER (TT-P-636) ON ALL STEEL EXCEPT FOR ITEMS TO BE HOT DIPPED GALVANIZED OR SPRAY FIREPROOFED.
DO NOT PAINT PORTIONS EMBEDDED IN CONCRETE.
3. SHOP DRAWINGS FOR REINFORCEMENT SHALL BE SUBMITTED FOR 7. FRAMING CONNECTIONS NOT DETAILED, OR CONNECTIONS THAT ARE MODIFIED FROM THOSE DETAILED, SHALL BE DESIGNED BY SUPPLIER
L
APPROVAL OF THE ENGINEER PRIOR TO FABRICATION AND FOR THE END REACTION SHOWN ON THE PLAN. IF NO REACTION IS PROVIDED, DESIGN FOR 1/2 THE BEAM MAXIMUM UNIFORM LOAD PER AISC
INSTALLATION. MANUAL FOR STEEL CONSTRUCTION. SUBMIT SIGNED AND SEALED CALCULATIONS.
L/4 L/4
4. THESE APPLICATION REQUIRES FOR SMALLER LENGTH OF PURCHASE 8. ALL WELD OPERATORS SHALL BE CURRENTLY AWS QUALIFIED.
REBARS 9. SHOP CONNECTIONS SHALL BE WELDED OR HIGH STRENGTH BOLTED. USE 3/16" FILLET WELD MINIMUM.
10. FIELD CONNECTIONS SHALL BE WELDED OR HIGH STRENGTH BOLTED AS DETAILED. NO FIELD WELDING OF HOT DIPPED GALVANIZED
6 REBAR OFFSET MEMBERS WILL BE ALLOWED. USE 3/16" FILLET WELD MINIMUM.
1

H/2
11. DURING THE ERECTION OF STEEL BEAMS AND DIAGONAL BRACING, ALL BOLTING AND FIELD WELDING SHALL BE COMPLETE BEFORE
RELEASING HOISTING CABLES.

H
12. SUBMIT FOR REVIEW SHOP DRAWINGS OF STEEL DETAILS PRIOR TO FABRICATING STRUCTURAL STEEL.

H/2
40 BAR DIAMETER 13. ALL EXTERIOR ELEMENTS AND THOSE ELEMENTS NOTED TO BE GALVANIZED SHALL BE HOT DIPPED GALVANIZED IN ACCORDANCE WITH ASTM
600mm MINIMUM A123 AFTER SANDBLAST CLEANING PER SSPC-SP10. USE ASTM A325 BOLTS HOT DIPPED GALVANIZED WITH GALVANIZED HARDENED WASHERS
B AND GALVANIZED HEAVY HEX NUTS FOR BOLTING OF GALVANIZED ITEMS.
REBAR SPLICE 14. STEEL COLUMNS, BASE PLATES AND ALL STEEL BELOW GRADE SHALL HAVE A MINIMUM 3" CONCRETE COVER PROTECTION.
15. MEMBERS NOTED AS "CONTINUOUS" SHALL BE FULLY WELDED AT ALL BUTT SPLICES OR CONNECTIONS SHALL BE DETAILED TO PROVIDE
CONTINUITY.

1 SPLICES NOTES
bf
S 2 SCALE: N/A
DESIGNATION W i ht Ar a bf d tf tw hw r LOCATION

tf
(W, /m) (mm ) (mm.) (mm.) (mm.) (mm.) (mm.) (mm.)

r
W10 x 15 22.38 2845 101.60 253.70 6.90 5.80 219 11.1 COLUMN

tw

hw
1. WHERE COLUMNS, VERTICAL REINFORCEMENTS. SHALL BE OFFSET AT

d
A SLOPE OF NOT MORE THAN 1 IN 6 AND EXTRA 10mm TIES AT 100 MM
SHALL BE PROVIDED THRU OUT THE OFFSET REGION.
4 NOTES ON PIPE SLEEVES W8 X 13 19.48 2477 101.60 202.90 6.50 5.80 168 11.1 MB-01

2. UNLESS OTHERWISE INDICATED IN THE PLANS, LAP SPICES FOR


S 2 SCALE: N/A
VERTICAL COLUMN REINFORCEMENT SHALL BE MADE WITHIN THE
CENTER HALF OF COLUMN HEIGHT AND THE SPLICE LENGTH SHALL
W8 x 10 15.02 1910 100.10 200.40 5.20 4.30 168 11.1 MB-02, EB, & RB
NOT BE LESS THAN 40 BAR DIAMETERS. WELDING OR APPROVED
MECHANICAL DEVICES MAY BE USED PROVIDED THAT NOT MORE THAN
ALTERNATE BARS ARE WELDED OR MECHANICALLY SPLICED AT ANY
LEVEL AND THE VERTICAL DISTANCES BETWEEN THESE WELDS OR
SPLICES OF ADJACENT BARS IS NOT LESS THAN 600mm.
5 NOTES ON STRUCTURAL STEEL
S 2 SCALE: N/A

2 COLUMN NOTES
S 2 SCALE: N/A

CIVIL / STRUCTURAL ENGINEER DRAWN PRP PROJECT TITLE PROJECT OWNER SHEET NO.
This document is owned and
CHECK PRP
solely property of Villa Preciosa PROPOSED TWO
Realty, Inc.(VPRI). Any alteration RICARDO D. LANTAJO JR. DATE 10/26/2022 SPS. GEOVANI LAZO PIZA &
STOREY RESIDENCE
and tampering of this document
without the consent of VPRI and
PRC 145324 Validity 6 - 02 -2025 REMARKS HILDA ARELLANO PIZA S-2
it's architect is not valid. PTR 734347 Issued 1 - 05 -2022 CONTENT GENERAL NOTES PROJECT LOCATION ADDRESS
Place ALAMINOS CITY STO NINO, CENTRAL BAKAKENG, BAGUIO CITY NO. 25-D RIMANDO ROAD, BAGUIO CITY, 2600
NOTE: FOR MASONRY WALL NOTE: FOR MASONRY WALL
1. 4" CHB w/ 2-SURFACED 25mm. THICK PLASTER 1. 4" CHB w/ 2-SURFACED 25mm. THICK PLASTER
@ FIREWALL @ FIREWALL
2. SRC PANEL w/ 2-SURFACED 25mm. THICK 2. SRC PANEL w/ 2-SURFACED 25mm. THICK
PLASTER @ REST OF THE WALL
B C D PLASTER @ REST OF THE WALL
B C D
2500 925
2500 925

A 1 A IA NC
E
E
IANC VAR
VA R

N E
L I
T Y
E R
O P
P R

F1 B
C1 E
4 1 1
F1 GB-0 MB-0
C1 PY
ANO
R E TE C C1
C
F2 GB-0
1 CON
MB-0
1

GB-01
C1

MB-02
C1
3

MB-01
E
C1 S-1

GB-01

N
I
SOF

L
1931

1931
GB-01

SOF DEPRESSED

CONCRETE CANOPY
DEPRESSED SLAB
C1

T
SLAB S-1 @ 25mm.
4231 Meter

4231 Meter
R
@ 25mm.

E
2

2
C1
MB-02

1
01

UP

P
F1

-0
O
GB-

MB

MB-02
R
GB-01
MB-02 DN

P
2300

2300
S-1 S-1

EB
DEPRESSED
F1 F1

EB
SEE STAIR SLAB EB
DETAIL SEE STAIR
C1 @ 50mm. C1 DETAIL
MB-01
C1
1

1
GB-01 GB-01 MB-01 EB

-02
C1 C1 C1
F2

EB
MB
EB

P R O P E R T Y L I N E

3 2
R O A D

1 GROUND FLOOR FRAMING PLAN 1 SECOND FLOOR FRAMING PLAN


S 3 SCALE: 1:75 Mts. S 3 SCALE: 1:75 Mts.
0 0.5 1 2 3 4 5 6 MTS. 0 0.5 1 2 3 4 5 6 MTS.

CIVIL / STRUCTURAL ENGINEER DRAWN PRP PROJECT TITLE PROJECT OWNER SHEET NO.
This document is owned and
CHECK PRP
solely property of Villa Preciosa
RICARDO D. LANTAJO JR. PROPOSED TWO
Realty, Inc.(VPRI). Any alteration DATE 10/26/2022 SPS. GEOVANI LAZO PIZA &
STOREY RESIDENCE
and tampering of this document
without the consent of VPRI and
PRC 145324 Validity 6 - 02 -2025 REMARKS HILDA ARELLANO PIZA S-3
it's architect is not valid. PTR 734347 Issued 1 - 05 -2022 CONTENT GENERAL NOTES PROJECT LOCATION ADDRESS
Place ALAMINOS CITY STO NINO, CENTRAL BAKAKENG, BAGUIO CITY NO. 25-D RIMANDO ROAD, BAGUIO CITY, 2600
B C D
2500 925

A IAN
CE
VAR

50 x 75 x 1.5mm. C- SECTION
PURLIN BATTEN SPACE @
600 mm

50 x 75 x 1.5mm. C- SECTION
PURLIN BATTEN SPACE @
ARD 300 mm
ASCIA BO C1
R LIN F
N PU RB RB
CTIO
INE C-SE
T ER L
GUT
C1

SAG ROD
RB
3

RB

RB
C1

RB
1931
4231 Meter
2

RB C1

CONCRETE CANOPY
RB
2300

C1
1

RB C1 RB C1

50 x 75 x 1.5mm. C- SECTION
PURLIN BATTEN SPACE @
300 mm
900 1200 1200 1200 1200 1200 900

1 ROOF FRAMING PLAN


S 4 SCALE: 1:75 Mts.
0 0.5 1 2 3 4 5 6 MTS.

CIVIL / STRUCTURAL ENGINEER DRAWN PRP PROJECT TITLE PROJECT OWNER SHEET NO.
This document is owned and
CHECK PRP
solely property of Villa Preciosa
RICARDO D. LANTAJO JR. PROPOSED TWO
Realty, Inc.(VPRI). Any alteration DATE 10/26/2022 SPS. GEOVANI LAZO PIZA &
STOREY RESIDENCE
and tampering of this document
without the consent of VPRI and
PRC 145324 Validity 6 - 02 -2025 REMARKS HILDA ARELLANO PIZA S-4
it's architect is not valid. PTR 734347 Issued 1 - 05 -2022 CONTENT STRUCTURAL DETAIL PROJECT LOCATION ADDRESS
Place ALAMINOS CITY STO NINO, CENTRAL BAKAKENG, BAGUIO CITY NO. 25-D RIMANDO ROAD, BAGUIO CITY, 2600
400 275
DESIGNATION DIMENSION FOOTING THICKNESS FOOTING DEPTH REINFORCEMENT MIN. CONCRETE COVER REMARKS

F1 1600 x 1600 mm. 300mm. 1500mm. (MIN) BOTTOM BARS: 16mm. Ø REBAR SPACED
@150mm. O.C. BOTH-WAYS

400

275
75mm. THICK

F2 2500 x 1500 mm. 400mm. 1500mm. (MIN) BOTTOM BARS: 16mm. Ø REBAR SPACED
@150mm. O.C. BOTH-WAYS

3/4" THICK BASE PLATE w/ 16mm.


Ø x 500mm. ANCHOR BOLT
W10 x 15 WIDE FLANGE
W10 x 15 WIDE FLANGE
3/4" THICK BASE PLATE w/ 16mm.
Ø x 500mm. ANCHOR BOLT GROUND FLOOR LINE
1600
F1 12mm.Ø DEFORM BAR
CONFINEMENT TIES SPACED @
6-50, REST 100mm.

GRADE LINE

1200
1600

1500

300
PLAN
16mm. Ø DEFORM BAR SPACED @ 150
16mm. Ø DEFORM BAR SPACED @ 150 O.C. BOTH-WAYS
O.C. BOTH-WAYS
1600

SECTION

1 FOOTING DETAIL & SCHEDULE


S 5 SCALE: 1:15 Mts.

CIVIL / STRUCTURAL ENGINEER DRAWN PRP PROJECT TITLE PROJECT OWNER SHEET NO.
This document is owned and
CHECK PRP
solely property of Villa Preciosa
RICARDO D. LANTAJO JR. PROPOSED TWO
Realty, Inc.(VPRI). Any alteration DATE 10/26/2022 SPS. GEOVANI LAZO PIZA &
STOREY RESIDENCE
and tampering of this document
without the consent of VPRI and
PRC 145324 Validity 6 - 02 -2025 REMARKS HILDA ARELLANO PIZA S-5
it's architect is not valid. PTR 734347 Issued 1 - 05 -2022 CONTENT FOUNDATION PLAN PROJECT LOCATION ADDRESS
Place ALAMINOS CITY STO NINO, CENTRAL BAKAKENG, BAGUIO CITY NO. 25-D RIMANDO ROAD, BAGUIO CITY, 2600
400 275

275
400
2500

3/4" THICK BASE PLATE w/ 16mm.


Ø x 500mm. ANCHOR BOLT
16mm. Ø DEFORM BAR SPACED @ 150
O.C. BOTH-WAYS
W10 x 15 WIDE FLANGE

GROUND FLOOR LINE

12mm.Ø DEFORM BAR


CONFINEMENT TIES SPACED @
6-50, REST 100mm.
1500

1100
1500
PLAN

400

16mm. Ø DEFORM BAR SPACED @ 150


O.C. BOTH-WAYS
2500
SECTION
1 FOOTING DETAIL & SCHEDULE (Cont....)
S 6 SCALE: 1:15 Mts.

CIVIL / STRUCTURAL ENGINEER DRAWN PRP PROJECT TITLE PROJECT OWNER SHEET NO.
This document is owned and
CHECK PRP
solely property of Villa Preciosa
RICARDO D. LANTAJO JR. PROPOSED TWO
Realty, Inc.(VPRI). Any alteration DATE 10/26/2022 SPS. GEOVANI LAZO PIZA &
STOREY RESIDENCE
and tampering of this document
without the consent of VPRI and
PRC 145324 Validity 6 - 02 -2025 REMARKS HILDA ARELLANO PIZA S-6
it's architect is not valid. PTR 734347 Issued 1 - 05 -2022 CONTENT FRAMING PLAN PROJECT LOCATION ADDRESS
Place ALAMINOS CITY STO NINO, CENTRAL BAKAKENG, BAGUIO CITY NO. 25-D RIMANDO ROAD, BAGUIO CITY, 2600
DESIGNATION FOUNDATION TO GROUND FLOOR GROUND FLOOR TO 2ND FLOOR 2ND FLOOR TO ROOF BEAM

400 10mm. MS PLATE


LATERAL STIFFENER
400 275

W10 x 15 WIDE FLANGE


COLUMN
400

400
275
C1
10mm. MS PLATE
LATERAL STIFFENER

REINFORCEMENT: W10 x 15 WIDE FLANGE COLUMN W10 x 15 WIDE FLANGE COLUMN


MAIN VERTICAL BARS: 4 - 20mm. Ø DEFORM BAR 3/4" BASE PLATE w/ 16mm.Ø x 500 ANCHOR BOLT
INTERMEDIARY: 4 - 20mm. Ø DEFORM BAR (VERIFY DIMENSION OF BASE PLATE)
TIES: 12mm. Ø DEFORM BAR
SPACING: 6 - 50mm, REST @ 100mm
CONFINEMENT TIES
10mm. MS PLATE
LATERAL STIFFENER

W10 x 15 WIDE FLANGE


COLUMN
1 COLUMN CROSS-SECTION DETAIL & SCHEDULE
S 7 SCALE: 1:15 Mts.
10mm. MS PLATE
LATERAL STIFFENER
GROUND FLOOR LINE
bf
DESIGNATION bf d tf tw hw r LOCATION
tf

(mm.) (mm.) (mm.) (mm.) (mm.) (mm.)

GRADE LINE
r

W10 x 15 101.60 253.70 6.90 5.80 219 11.1 COLUMN

tw 400
hw
d

W8 X 13 101.60 202.90 6.50 5.80 168 11.1 MB-01

400
W8 x 10 100.10 200.40 5.20 4.30 168 11.1 MB-02, EB, & RB

PEDESTAL COLUMN

2 WIDE FLANGE DESIGNATION SIZE


S 7 SCALE: NTS.
3 TYPICAL COLUMN SECTION DETAIL
S 7 SCALE: 1:15 Mts.

CIVIL / STRUCTURAL ENGINEER DRAWN PRP PROJECT TITLE PROJECT OWNER SHEET NO.
This document is owned and
CHECK PRP
solely property of Villa Preciosa
RICARDO D. LANTAJO JR. PROPOSED TWO
Realty, Inc.(VPRI). Any alteration DATE 10/26/2022 SPS. GEOVANI LAZO PIZA &
STOREY RESIDENCE
and tampering of this document
without the consent of VPRI and
PRC 145324 Validity 6 - 02 -2025 REMARKS HILDA ARELLANO PIZA S-7
it's architect is not valid. PTR 734347 Issued 1 - 05 -2022 CONTENT FRAMING PLAN PROJECT LOCATION ADDRESS
Place ALAMINOS CITY STO NINO, CENTRAL BAKAKENG, BAGUIO CITY NO. 25-D RIMANDO ROAD, BAGUIO CITY, 2600
LENGTH

10mm. Ø STIRRUPS SPACED @


4-50mm., 3-75mm., 3-100mm., REST @
120mm. TOWARD CENTER

1 GRADE BEAM DETAIL (GB-01)


S 8 SCALE: 1:15 Mts.

250 250 250


10mm. Ø STIRRUPS SPACED @
4-50mm., 3-75mm., 3-100mm., REST @
120mm. TOWARD CENTER
400

400

400
END SUPPORT MIDSPAN END SUPPORT
TOP BAR: 3 - 20mm. Ø REBAR TOP BAR: 3 - 20mm. Ø REBAR TOP BAR: 3 - 20mm. Ø REBAR
SFR: 2 - 20mm. Ø REBAR SFR: 2 - 20mm. Ø REBAR SFR: 2 - 20mm. Ø REBAR
BOTTOM BAR: 3 - 20mm. Ø REBAR BOTTOM BAR: 3 - 20mm. Ø REBAR BOTTOM BAR: 3 - 20mm. Ø REBAR
W10 x 15 LENGTH
WIDE FLANGE
COLUMN L/4 L/4

2 TYPICAL STEEL FRAME BEAM DETAIL


W8 x 13 WIDE FLANGE BEAM
S 8 SCALE: 1:15 Mts.

10mm. MS PLATE CONNECTOR 10mm. MS PLATE CONNECTOR 3


10mm. MS PLATE 10mm. MS PLATE BEAM SCHEDULE
STIFFENER STIFFENER S 8 SCALE: NTS
WELDING SYMBOL

BASE HEIGHT BAR DIAMETER (Ø) @ SUPPORT @ MIDSPAN STIRRUPS BAR Ø STIRRUPS SPACING

DESIGNATION
(mm.) (mm.) (mm.) TOP BOTTOM TOP BOTTOM (mm.) (mm.)

GROUND FLOOR

GB1 250 400 20 5 3 5 3 10 2 - 50, 3 - 75, 4 - 100, 5 - 150, REST @ 200 TOWARD CENTER

SECOND FLOOR

MB-01 W8 x 13

MB-02 W8 x 10

EB W8 x 10

ROOF BEAM

RB01 W8 x 10

CONCRETE LOAD @ 3500 PSI

CIVIL / STRUCTURAL ENGINEER DRAWN PRP PROJECT TITLE PROJECT OWNER SHEET NO.
This document is owned and
CHECK PRP
solely property of Villa Preciosa
RICARDO D. LANTAJO JR. PROPOSED TWO
Realty, Inc.(VPRI). Any alteration DATE 10/26/2022 SPS. GEOVANI LAZO PIZA &
STOREY RESIDENCE
and tampering of this document
without the consent of VPRI and
PRC 145324 Validity 6 - 02 -2025 REMARKS HILDA ARELLANO PIZA S-8
it's architect is not valid. PTR 734347 Issued 1 - 05 -2022 CONTENT FRAMING PLAN PROJECT LOCATION ADDRESS
Place ALAMINOS CITY STO NINO, CENTRAL BAKAKENG, BAGUIO CITY NO. 25-D RIMANDO ROAD, BAGUIO CITY, 2600
LENGTH
L/4 L/4

L/4
LENGTH
12mm. Ø CUT/BENT BAR SPACED
@ 0.20mm. O.C. BOTH-WAYS

L/4
12mm. Ø REBAR SPACED PLAN 10mm. Ø TEMP. BAR SPACED PLAN
@ 0.40mm. O.C. BOTH-WAYS @ 0.30mm. O.C. BOTH-WAYS 0.80mm. THICK METAL DECK
LENGTH
LENGTH
L/4 L/4

GB-01 GB-01
100

100
MB-01 MB-01
12mm. Ø REBAR SPACED
@ 0.40mm. O.C. BOTH-WAYS

0.80mm. THICK METAL DECK


12mm. Ø REBAR SPACED
@ 0.40mm. O.C. BOTH-WAYS
SECTION DESIGNATION THICKNESS TEMPERATURE BAR BEND BAR CUT BAR MIN. CONCRETE COVER REMARKS
SOF
SOF 100mm. 12mmØ @ 400mm. SPACING B.W. 12mmØ @ 200mm. SPACING B.W. 25mm. THICK

1 SLAB DETAIL & SCHEDULE S-1 100mm. 10mmØ @ 300mm. SPACING B.W. 0.80 mm. METAL DECK
S 9 SCALE: NTS

CIVIL / STRUCTURAL ENGINEER DRAWN PRP PROJECT TITLE PROJECT OWNER SHEET NO.
This document is owned and
CHECK PRP
solely property of Villa Preciosa
RICARDO D. LANTAJO JR. PROPOSED TWO
Realty, Inc.(VPRI). Any alteration DATE 10/26/2022 SPS. GEOVANI LAZO PIZA &
STOREY RESIDENCE
and tampering of this document
without the consent of VPRI and
PRC 145324 Validity 6 - 02 -2025 REMARKS HILDA ARELLANO PIZA S-9
it's architect is not valid. PTR 734347 Issued 1 - 05 -2022 CONTENT STRUCTURAL DETAIL PROJECT LOCATION ADDRESS
Place ALAMINOS CITY STO NINO, CENTRAL BAKAKENG, BAGUIO CITY NO. 25-D RIMANDO ROAD, BAGUIO CITY, 2600
2ND FLOOR
LINE
ELEV. 3400mm.

0
600

10
L/4

LE
NG
TH 10 mm. Ø NOSING BARS

12mm Ø 250mm. O.C.


TOP & BOTTOM BARS
L/4
10mm. Ø TEMP. BAR @
300mm. O.C.
2450

GROUND FLOOR
LINE
ELEV. 350mm.

ELEV. 300mm.
POWDER RM.
FLOOR LINE
SECTION

1 STAIR DETAIL
S 10 SCALE: 1:20 Mts.

CIVIL / STRUCTURAL ENGINEER DRAWN PRP PROJECT TITLE PROJECT OWNER SHEET NO.
This document is owned and
CHECK PRP
solely property of Villa Preciosa
RICARDO D. LANTAJO JR. PROPOSED TWO
Realty, Inc.(VPRI). Any alteration DATE 10/26/2022 SPS. GEOVANI LAZO PIZA &
STOREY RESIDENCE
and tampering of this document
without the consent of VPRI and
PRC 145324 Validity 6 - 02 -2025 REMARKS HILDA ARELLANO PIZA S-10
it's architect is not valid. PTR 734347 Issued 1 - 05 -2022 CONTENT STRUCTURAL DETAIL PROJECT LOCATION ADDRESS
Place ALAMINOS CITY STO NINO, CENTRAL BAKAKENG, BAGUIO CITY NO. 25-D RIMANDO ROAD, BAGUIO CITY, 2600
12mmØ TEMP. BAR SPACED
@ 250mm. O.C. BOTHWAYS
OVERALL LENGTH

650
MANHOLE
OVERALL WIDTH

650
MANHOLE

2850
MANHOLE
MANHOLE 10mmØ TEMP. BAR SPACED 200 LEGNTH 150 200
@ 250mm. O.C. BOTHWAYS
500 500
16mm. Ø REBAR
HANDLE 12mmØ TEMP. BAR SPACED
@ 200mm. O.C. BOTHWAYS

200
SEPTIC TANK SLAB COVER 12mmØ TEMP. BAR SPACED
@ 200mm. O.C. BOTHWAYS

1" THICK PLASTER @ BOTH SURFACE AREA


WALL FOOTING
12mmØ REINFORCEMENT 12mmØ
BAR SPACED @ 400mm. O.C. REINFORCEMENT
BOTHWAYS BAR SPACED

5" CHB EXTERIOR WALL w/

1" THICK PLASTER @ BOTH SURFACE AREA


SEE DEPTH @ PLUMBING PLANS
@ 400mm. O.C.
BOTHWAYS

1" THICK PLASTER @ BOTH SURFACE AREA


OVERALL DEPTH

5" CHB EXTERIOR WALL w/


SEE PLUMBING PLANS
NOTE: TYPE OF MORTARS &
PLASTER WILL BE GRADED

4" CHB BAFFLE WALL w/


AS CLASS A CONCRETE.
SLABS & WALL FOOTING
WILL BE CLASSIFIED AS
CLASS A.
OVERALL WIDTH

WALL FOOTING

WALL FOOTING
12mmØ REINFORCEMENT
BAR SPACED @ 400mm. O.C.
BOTHWAYS

12mmØ TEMP. BAR SPACED


@ 200mm. O.C. BOTHWAYS

150
200
12mmØ REINF. BAR SPACED 12mmØ REINF. BAR SPACED
@ 200mm. O.C. BOTHWAYS SECTION DETAIL @ 200mm. O.C. BOTHWAYS

WALL FOOTING
1 SEPTIC TANK STRUCTURAL DETAIL
OVERALL LENGTH

SEPTIC TANK FLOORING S 11 SCALE: 1:30 Mts.


SLAB
CIVIL / STRUCTURAL ENGINEER DRAWN PRP PROJECT TITLE PROJECT OWNER SHEET NO.
This document is owned and
CHECK PRP
solely property of Villa Preciosa
RICARDO D. LANTAJO JR. PROPOSED TWO
Realty, Inc.(VPRI). Any alteration DATE 10/26/2022 SPS. GEOVANI LAZO PIZA &
STOREY RESIDENCE
and tampering of this document
without the consent of VPRI and
PRC 145324 Validity 6 - 02 -2025 REMARKS HILDA ARELLANO PIZA S-11
it's architect is not valid. PTR 734347 Issued 1 - 05 -2022 CONTENT BEAM SCHEDULE PROJECT LOCATION ADDRESS
Place ALAMINOS CITY STO NINO, CENTRAL BAKAKENG, BAGUIO CITY NO. 25-D RIMANDO ROAD, BAGUIO CITY, 2600
300 300 600
600
600
VARIANCE
VARIANCE
600
600 300 300 300 300 300 300

1 TRUSS-RAFTER SECTION DETAIL


S 12 SCALE: 1:30 Mts.

A-A B-B

TEKSCREW w/ GUSSET 1.2 x 50 x 150mm.


PLATE TUBULAR BAR
1.2 x 50 x 150mm.
1.2 x 50 x 75mm. C-PURLIN 10mm. Ø SAG ROD
TUBULAR BAR
BATTEN
10mm. Ø SAG ROD 4 x 25 x 25mm. ∠ BAR HEAT FOAM INSULATOR WITH
CLEAT PROTECTIVE NET COVER
HEAT FOAM INSULATOR WITH ROOF SHEET
PROTECTIVE NET COVER GUTTER STRAP
BOX-TYPE GUTTER
ROOF SHEET
WALL FLASHING

8 x 75 x 75mm. ∠ BAR SUPPORT.


(Optional Support may allowed)

SRC PANEL w/ CEMENT


PLASTER @ BOTH SURFACE.
FLAT PAINTED FINISH

12mm. THICK FIBER CEMENT


BOARD (FASCIA)
2F CEILING LINE
ELEV. 6050mm.

1.2 x 50 x 250mm. C-PURLIN


HANGER
HANGER
EAVES: CEILING JOIST
CEILING JOIST (METAL (METAL FURRING FRAME w/
FURRING FRAME w/ STRUT STRUT CARRYING CHANNEL)
CARRYING CHANNEL) & & FIBER CEMENT BOARD
FIBER CEMENT BOARD FLAT FLAT PAINTED FINISH CEILING JOIST (METAL
PAINTED FINISH FURRING FRAME w/ STRUT
CARRYING CHANNEL) &
STEEL FRAME I-BEAM (See FIBER CEMENT BOARD FLAT
Structural Plan & Design) PAINTED FINISH

2 ROOF DETAIL @ B-B 3 ROOF DETAIL @ A-A


S 12 SCALE: 1:20 Mts. S 12 SCALE: 1:20 Mts.

CIVIL / STRUCTURAL ENGINEER DRAWN PRP PROJECT TITLE PROJECT OWNER SHEET NO.
This document is owned and
CHECK PRP
solely property of Villa Preciosa
RICARDO D. LANTAJO JR. PROPOSED TWO
Realty, Inc.(VPRI). Any alteration DATE 10/26/2022 SPS. GEOVANI LAZO PIZA &
STOREY RESIDENCE
and tampering of this document
without the consent of VPRI and
PRC 145324 Validity 6 - 02 -2025 REMARKS HILDA ARELLANO PIZA S-12
it's architect is not valid. PTR 734347 Issued 1 - 05 -2022 CONTENT SLAB DETAIL PROJECT LOCATION ADDRESS
Place ALAMINOS CITY STO NINO, CENTRAL BAKAKENG, BAGUIO CITY NO. 25-D RIMANDO ROAD, BAGUIO CITY, 2600
NOTE: ALL STRUCTURAL STEEL 10mm. THICK MS PLATE
FRAME CONNECTION WILL BE BEAM STIFFENER
WELDED TYPE

WELDING SYMBOL 10mm. THICK MS PLATE


CONNECTOR
10mm. THICK MS PLATE
BEAM STIFFENER
RB (W8 x 10)

RB (W8 x 10)

10mm. THICK MS PLATE


CONNECTOR
L/
4

it's architect is not valid.


10mm. THICK MS PLATE

This document is owned and


L/4
BEAM STIFFENER

and tampering of this document


solely property of Villa Preciosa

without the consent of VPRI and


Realty, Inc.(VPRI). Any alteration

PTR
PRC
10mm. THICK MS PLATE
RB (W8 x 10) COLUMN STIFFENER
(W10 x 15)

734347
145324
10mm. THICK MS PLATE
10mm. THICK MS PLATE CONNECTOR
SUPPORT

CIVIL / STRUCTURAL ENGINEER


10mm. THICK MS PLATE

Place
Issued
Validity
BEAM STIFFENER
SRC WALL PANEL w/ 25mm.
10mm. THICK MS PLATE THICK PLASTER @ BOTH
BEAM STIFFENER SURFACE

RICARDO D. LANTAJO JR.

1 - 05 -2022
6 - 02 -2025
10mm. THICK MS PLATE
S-1

ALAMINOS CITY
10mm. THICK MS PLATE
BEAM STIFFENER

DATE
MB-01 (W8 x 13)

CHECK
DRAWN

REMARKS
MB-01 (W8 x 13)

PRP
PRP
0.80mm. THICK METAL DECK
MB-02 (W8 x 10)

10/26/2022

CONTENT SLAB DETAIL


10mm. MS BASE PLATE w/
16mm. Ø x 500mm. LONG
ANCHOR BOLT
GRADE BEAM
GRADE BEAM

SLAB ON FILL (SOF)

PROJECT TITLE

PROJECT LOCATION
REINFORCED CONCRETE
PEDESTAL COLUMN (SEE
COLUMN SCHEDULE)
PROPOSED TWO
STOREY RESIDENCE

STO NINO, CENTRAL BAKAKENG, BAGUIO CITY


ADDRESS

FOOTING (SEE DETAIL)


PROJECT OWNER

NO. 25-D RIMANDO ROAD, BAGUIO CITY, 2600


HILDA ARELLANO PIZA
SPS. GEOVANI LAZO PIZA &

1 TYPICAL FRAMING CONNECTION DETAIL


S 13 SCALE: 1:15 Mts.
SHEET NO.

S-13