Testing of Earth Leakage Relay
Testing of Earth Leakage Relay
Testing of Relay is very important to check the healthiness of relay as well as it's circuit. In ELR testing
whole circuit being checked.
CBCT sense zero sequence current so it's called zero sequence current detector, we simply pass one wire
through CBCT and flow single phase current. as current reach it' s setting limit ELR tripped, and it will trip
MCCB. Sometimes it happens that ELR not operate at its set point but above it's set point, so if difference
is high then your CBCT has error. Require replacement with new CBCT.
For better performance you need to mount same CBCT which is came with relay, because different
manufacturers are has its own ratio of CBCT.
CBCT always installed at incoming side cable so you can protect the whole circuit to load. both red wires
are for relay input and other 2 wires for test signal output.
In monsoon season IR of cable to earth become low due to moisture in air so at that time leakage
current will be more so it happens that your ELR malfunction and trip your MCCB so set your set leakage
current wisely.