Vibrating Fork Point Level Switch For Liquids
Vibrating Fork Point Level Switch For Liquids
Instruction Manual
sensing matters
Electronics of LFV excites the piezo-electric-crystals inside the tuning fork, which
makes the fork tines vibrate at their natural resonance frequency in free air.
When the fork tines are immersed in liquid, the frequency of fork vibration falls due
to the density of liquid.
ΔT
This change in frequency is detected by the electronic circuit.
lfv-manual-page01 www.trumen.in 1
Technical Specification
Features Specifications
1. Fast Switching Response 1 sec EIUD / ERUD Integral / Remote Electronics DPDT Output
2. ½" screw mountings available Supply & Output Universal Supply DPDT Out
15 to 80 VDC
3. High pressure 15 bar forks
15 to 260 VAC 50/60Hz
4. High Tempreture up-to 250°C available Relay Contact 5 A each @ 24VDC or 220VAC
5. Calibration-less operation
6. Remote electronics with std 10 meters cable length EIDP / ERDP Integral / Remote Electronics for PNP Output
7. External indication LED available Supply & Output 12 to 60 VDC, PNP
Output Limit 250mA max. Short Circuit Safe
8. Threaded & Flanged Mountings
9. NAMUR (L-H / H-L) as per IEC-60947-5-6 EINL/EINH NAMUR (L-H / H-L) as per IEC-60947-5-6
10. Ingress protection : IP 68/65 (as per IS-13947) Supply & Output 8.2 VDC 1KΩ series resistance
11. Ex-proof (Ex d T6 IP-66 IIC )
- Flameproof as per IS/IEC 60079-1:2007 EIUSP / ERUSP Integral / Remote Electronics SPDT + PNP Output
Supply & Output Universal Supply for SPDT Output
- Weatherproof (IP-66) as per IS/IEC 60529:2001
15 to 80 VDC
- Suitable for Gas Group : IIC 15 to 260 VAC 50/60Hz
- Suitable for Zone 1 & 2 atmospheres DC Supply for PNP Output
12. Compact size 15 to 60 VDC
Relay Type and Rating Potential Free SPDT Relay Output
13. Low power consumption
5 A each @ 24VDC or 220VAC
PNP Output 250mA max. Short Circuit Safe
Applications
EIAR Integral Electronics AC series relay
1. Free flowing liquids Supply & Output Two Wire 18 to 260 VAC, Series Relay
not less than 4mA to release external relay
2. Suitable for side as well as top mounting
maximum 150mA to magnetize relay
3. Minimum and maximum failsafe field selectable Output Limit Use relays/contactors will more than
4. Process temperature max 200°C 4mA holding current
Process Connections NPT / BSP / Hygienic ½", ¾", 1", 1¼", 1½",
& Flanged ANSI/JIS/DIN/ASA/custom
Extensions Tube SS 304, SS 316, SS 316L
Material & Length 50mm to 3,000mm
lfv-manual-page02 www.trumen.in 2
Do's and Don'ts
Features
Installation Precaution
1. Always connect the "Earth" to the external "Earthing" screw
1
3 2. Tighten the cable entries & glands properly
3. Secure the top aluminium cover at its place properly once the
2
electrical connections and other settings are completed
lfv-manual-page03 www.trumen.in 3
Troubleshooting
Indication Probable cause Work-around Solution
No switching output or Power is not available See if 'power' LED is ON Sensor electronic insert is needed to be replaced.
Fork is not vibrating when fork tines Sensor electronic insert fork oscillator Sensor electronic insert is needed to be replaced.
are touched by hand failed
Abrupt switching Material is agitated Set time delay to 5 second in both dry and Time delay solves switching issues in agitated
wet condition (turn switch 2, 3 ON) materials.
Fork settings are all OK but fork fails Power supply carrying extra noise and Make necessary arrangements to filter the Device contains sufficient filtering of power supply
to switch to 'no material' at random fork amplifier picking the noise noise in power-line before being fed to the noise inside, but sometimes external earth is
times device needed to make filters sink the extra power supply
noise back to earth.
Provide an exclusive earthing to terminal#
3, fork enclosure earthing screw and fork
process connection (device mounting
screw or flange)
Device worked for few months / years Device senses fork frequency and Select proper fork surface while ordering as Care is needed to be taken while ordering.
but now fails to switch with respect to amplitude to ascertain presence / per service material to mitigate fork errosion
material while power conditions are all absence of Material. Possible reasons as well as deposition Scheduled cleaning of fork tines in sticky material
same are application is recommended.
Order device of proper thermal grade for
1. fork frequency shift due to fork wear / proper service life of device
In case of fork tine wear or temperature stress, fork
errosion by service material
Clean up deposited materials on fork sensor is needed to be replaced.
2. Material deposition on fork leads sense as a part of maintenance schedule
Applications
3. Over temperature of service material
causing fork drive damage
Fork extension (longer for low level) Connect the new replaced sensor. 4-way connector is unidirectional
and only connects in proper direction.
Fork tines
Set the electronics properly to its position.
For mechanical issues please send the entire device back to Trumen.
lfv-manual-page04 www.trumen.in 04
Annexure-1
Introduction - LFV-UD (EIUD / ERUD)
controls & indicators
A Alarm Indicating LED
BA B Configuration Switches
LFV-UD C Power ON LED Indicator
C D Connecting Terminals
turn-on
E to set E External Earthing Terminal
ON
status
power
sensitive 5 Sec
15... 80V DC
dry delay
wet delay
connection terminals
U 15... 260V AC min failsafe
configuration switches
1 sensitivity control
LFV-UD sensitive setting for low density fluids
OFF Position (turn-on for low density fluids)
turn-on (keep turned-off for normal fluids)
to set ON Position
2 “dry” (or uncovered) delay (5 second delay)
(turn-on when 5 second more time is needed for
sensitive 5 Sec fork out of fluid confirmation)
dry delay
wet delay
min failsafe 3 “wet” (or covered) delay (5 second delay)
(turn-on when 5 second more time is needed for
fork dipped in the fluid confirmation)
No material at
ON Off
high level. 1 2 3 4
Indicating
min failsafe
normal or 4 5 6 7 8 9 4 5 6 7 8 9
healthy Relay ON Relay OFF
Switch no. 4
High level / overflow detection
Material is
above the high ON On
1 2 3 4
level or fork is
covered with min failsafe 4 5 6 7 8 9 4 5 6 7 8 9
Indicating
material. alarm Relay OFF Relay OFF
Switch no. 4
is off, failsafe status. alarm contacts. alarm contacts.
high/maximum (as it is)
No material at
low level. ON On
1 2 3 4
4 5 6 7 8 9 4 5 6 7 8 9
min failsafe
Indicating
alarm Relay OFF Relay OFF
Low level / underflow detection
Switch no. 4
status. alarm contacts. alarm contacts.
is on, failsafe
(as it is)
low/minimum
Material is Off
above the low ON
1 2 3 4
level or fork is Indicating 4 5 6 7 8 9 4 5 6 7 8 9
covered with min failsafe normal or
material. healthy Relay ON Relay OFF
Switch no. 4 normal or healthy alarm contacts.
status.
is on, failsafe contacts. (due to power
low/minimum failure)
LFV-UD LFV-UD
turn-on turn-on
to set to set
ON ON
status
power
status
power
sensitive sensitive
dry delay dry delay
15... 80V DC wet delay 15... 80V DC wet delay
U 15... 260V AC min failsafe U 15... 260V AC min failsafe
L1 N L1 N
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
LFV-UD
turn-on
to set
ON 1 2 3 4
status
power
sensitive 5 Sec
Red
Black
Green
White
dry delay
15... 80V DC wet delay
U 15... 260V AC min failsafe
L1 N
1 2 3 4 5 6 7 8 9
Proper connection to supply earth terminal (3) and the external earth terminal (screw) is must.
lfv-manual-annexure-1 www.trumen.in Page 3
Annexure-2
Introduction - LFV-DP (EIDP / ERDP)
controls & indicators
BA A Alarm Indicating LED
E LFV-DP
B Configuration Switches
C C Power ON LED Indicator
turn-on
to set D Connecting Terminals
ON
E External Earthing Terminal
status
power
sensitive
5 sec min
dry delay
wet delay failsafe
PNP (alarm=float)
connection terminals
U 12 to 60V DC
D
1 + of DC Supply input
1 2 3 4 5 6 7 8 9 2 - of DC Supply input
Supply:
12 to 60VDC
configuration switches
1 sensitivity control
sensitive setting for low density fluids
LFV-DP (turn-on for low density fluids etc.)
OFF Position
(keep turned-off for normal density fluids)
turn-on
to set ON Position
2 “dry” (or uncovered) delay (5 second delay) setting
(turn-on when 5 second more time is needed for
sensitive 5 sec fork out of fluid confirmation)
dry delay
wet delay
min failsafe 3 “wet” (or covered) delay (5 second delay) setting
(turn-on when 5 second more time is needed for
fork dipped in the fluid confirmation)
No material at
ON Off 1 2 3 4 1 2 3 4
high level. 1 2 3 4
Indicating IL Ileak
min failsafe
normal or
High level / overflow detection
Material is
above the high ON On 1 2 3 4 1 2 3 4
1 2 3 4
level or fork is Ileak Ileak
min failsafe
covered with Indicating Ileak ≤ 0.1mA Ileak ≤ 0.1mA
material. alarm
Switch no. 4 Alarm output. Alarm output.
is off, failsafe status. (as it is)
high/maximum
No material at
low level. 1 2 3 4 1 2 3 4
ON
1 2 3 4
On
Ileak Ileak
Low level / underflow detection
min failsafe
Indicating Ileak ≤ 0.1mA Ileak ≤ 0.1mA
Switch no. 4 alarm Alarm output. Alarm output.
is on, failsafe status. (as it is)
low/minimum
Material is Off
above the low 1 2 3 4 1 2 3 4
ON
1 2 3 4
level or fork is Indicating IL Ileak
LFV-DP
turn-on
to set
ON
status
power
sensitive
5 sec min
dry delay
wet delay failsafe
PNP (alarm=float)
U 12 to 60V DC
1 2 3 4 5 6 7 8 9
12 to 60 VDC
LFV-DP
turn-on
to set
ON
1 2 3 4
status
power
sensitive
5 sec min
dry delay
Red
Black
Green
White
wet delay failsafe
PNP (alarm=float)
U 12 to 60V DC
1 2 3 4 5 6 7 8 9
Proper connection to supply earth terminal (3) and the external earth terminal (screw) is must.
lfv-manual-annexure-2 www.trumen.in Page 3
Annexure-3
Introduction - LFV-NL (EINL)
controls & indicators
B A A Alarm Indicating LED
B Configuration Switches
LFV-NL
C C Power ON LED Indicator
turn-on
to set 1 2 3 4
D Connecting Terminals
ON E External Earthing Terminal
E ON
alarm
power
x 5 sec
dry delay
NAMUR Output
(⩽1.2mA & ⩾2.2mA)
wet delay
low alarm
connection terminals
U 8.2V DC
x x x x x x D
1 + of 8.2VDC NAMUR Supply
1 2 3 4 5 6 7 8 9 2 - of 8.2VDC NAMUR Supply
This supply must be taken from certified
NAMUR Barrier or Amplifier
This input is not tolerant above 16VDC
Supplying more than 16V may damage
the device.
configuration switches
1 Not used
LFV-NL
OFF Position 2 “dry” (or uncovered) delay (5 second delay)
turn-on (turn-on when 5 second more time is needed for
to set ON Position fork out of fluid confirmation)
INAMUR⩽1.2mA
low alarm
is no material at high
switch point or fork
8.2 VDC from
is out of the fluid.
NAMUR barrier
no material at low
switch point or fork 8.2 VDC from
is out of the fluid. NAMUR barrier
dipped in fluid at
low switch point.
8.2 VDC from
NAMUR barrier
LFV-NL
turn-on
to set 1 2 3 4
ON
alarm
power
x 5 sec
dry delay
NAMUR Output wet delay
(⩽1.2mA & ⩾2.2mA)
low alarm
Barrier or U 8.2V DC
x x x x x x
Amplifier
Supply
NAMUR 1 2 3 4 5 6 7 8 9
24V DC 8.2V
DC unused terminals
Barrier or
Amplifier
LFV-NL
turn-on
to set 1 2 3 4
ON ON
alarm
power
x 5 sec
dry delay
NAMUR Output wet delay
(⩽1.2mA & ⩾2.2mA)
low alarm
U 8.2V DC
x x x x x x
1 2 3 4 5 6 7 8 9
Proper connection to supply earth terminal (3) and the external earth terminal (screw) is must.
lfv-manual-annexure-3 www.trumen.in Page 3
Annexure-4
Introduction - LFV-U(S+P) (EIUSP / ERUSP)
controls & indicators
A Alarm Indicating LED
BA B Configuration Switches
LFV-U(S+P) C Power ON LED Indicator
C D Connecting Terminals
turn-on
E to set E External Earthing Terminal
ON
status
power
sensitive 5 Sec
15... 80V DC
dry delay
wet delay
connection terminals
U 15... 260V AC min failsafe U
15... 60V DC !
L1 N PNP o/p
less than
60VDC only
D 1 (+) of DC or Live of AC Supply input
2 (-) of DC or Neutral of AC Supply input
1 2 3 4 5 6 7 8 9
Supply:
15 to 80VDC or 15 to 260VAC 50/60Hz
3 Earth terminal for safety
4 Normally connected terminal of SPDT
contact
5 Common terminal of SPDT contact
6 Normally open terminal of SPDT contact
7 (-) of DC for PNP output
8 (+) of DC for PNP output
9 DC PNP output with respect to -ve of DC
! Supply should be within 15 to 60VDC for
PNP output
configuration switches
1 sensitivity control
LFV-U(S+P) sensitive setting for low density fluids
OFF Position (turn-on for low density fluids)
turn-on (keep turned-off for normal fluids)
to set ON Position
2 “dry” (or uncovered) delay (5 second delay)
(turn-on when 5 second more time is needed for
sensitive 5 Sec fork out of fluid confirmation)
dry delay
wet delay
min failsafe 3 “wet” (or covered) delay (5 second delay)
(turn-on when 5 second more time is needed for
fork dipped in the fluid confirmation)
Material & Material Failsafe Status Relay Contacts & PNP Output
Installation Status Setting LED Power ON Power OFF
No material at Off
ON
high level. 1 2 3 4
Indicating 4 5 6 4 5 6
min failsafe normal or Relay ON normal Relay OFF alarm
Switch no. 4 healthy or healthy contacts. contacts. (due to
is off, failsafe status. power failure)
High level / overflow detection
high/maximum
7 8 9 7 8 9
IL Ileak
IL(max) = 250mA Ileak ≤ 0.1mA
Material is
above the high ON On
1 2 3 4
level or fork is 4 5 6 4 5 6
covered with min failsafe Indicating Relay OFF alarm Relay OFF alarm
material. alarm contacts. contacts. (as it is)
Switch no. 4
status.
is off, failsafe 7 8 9 7 8 9
high/maximum Ileak Ileak
Ileak ≤ 0.1mA Ileak ≤ 0.1mA
No material at
low level. ON On
1 2 3 4
4 5 6 4 5 6
min failsafe
Indicating Relay OFF alarm Relay OFF alarm
Low level / underflow detection
Material is Off
above the low ON
1 2 3 4
level or fork is Indicating 4 5 6 4 5 6
covered with min failsafe normal or Relay ON normal Relay OFF alarm
material. healthy or healthy contacts. contacts. (due to
Switch no. 4 power failure)
status.
is on, failsafe
low/minimum 7 8 9 7 8 9
IL Ileak
IL(max) = 250mA Ileak ≤ 0.1mA
LFV-U(S+P) LFV-U(S+P)
turn-on turn-on
to set to set
ON ON
status
power
status
power
sensitive 5 Sec sensitive 5 Sec
dry delay dry delay
15... 80V DC wet delay 15... 80V DC wet delay
U 15... 260V AC min failsafe U 15... 260V AC min failsafe
U U
15... 60V DC ! 15... 60V DC !
L1 N PNP o/p
less than
60VDC only L1 N PNP o/p
less than
60VDC only
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
LFV-U(S+P)
turn-on
to set
ON 1 2 3 4
status
power
sensitive 5 Sec
Red
Black
Green
White
dry delay
15... 80V DC wet delay
U 15... 260V AC min failsafe U
15... 60V DC !
L1 N PNP o/p
less than
60VDC only
1 2 3 4 5 6 7 8 9
Proper connection to supply earth terminal (3) and the external earth terminal (screw) is must.
lfv-manual-annexure-4 www.trumen.in Page 3
Annexure-5
Introduction - LFV-AR (EIAR)
controls & indicators
BA A Alarm Indicating LED
E LFV-AR
B Configuration Switches
C C Normal LED Indicator
turn-on
to set D Connecting Terminals
ON
E External Earthing Terminal
normal
alarm
x
5 sec
dry delay
2 wire AC series Relay
(<5mA holding current)
wet delay
min failsafe connection terminals
U 18... 260V AC
D
1 Live of AC Supply through fuse
1 2 3 4 5 6 7 8 9 2 Neutral of AC Supply input through
specified series relay
18 to 260VAC 50/60 Hz series
configuration switches
1 Not used
LFV-AR
OFF Position
2 “dry” (or uncovered) delay (5 second delay) setting
turn-on (turn-on when 5 second more time is needed for
to set ON Position
fork out of fluid confirmation)
L N L N
normal when there min failsafe
Green healthy Series relay Series relay
is no material at high on off (due to
switch point or fork On power
is out of the fluid. failure)
turn-on
to set
ON
normal
alarm
x
5 sec
dry delay
2 wire AC series Relay
wet delay
(<5mA holding current) min failsafe
U 18... 260V AC
1 2 3 4 5 6 7 8 9
L Not Used
AC Supply
18 to 260 VAC
N
LFV-AR
turn-on
to set
ON
normal
alarm
x
5 sec
dry delay
2 wire AC series Relay
wet delay
(<5mA holding current) min failsafe
U 18... 260V AC
1 2 3 4 5 6 7 8 9
Proper connection to supply earth terminal (3) and the external earth terminal (screw) is must.
lfv-manual-annexure-5 www.trumen.in Page 3
Annexure-6
Introduction - LFV-DL (EIDL)
4/20 - 8/16 mA Output
configuration switches
1 sensitivity control
4/20 sensitive setting for low density fluids
LFV-DL 8/16 (turn-on for low density fluids etc.)
OFF Position
(keep turned-off for normal density fluids)
turn-on
to set ON Position
2 “dry” (or uncovered) delay (5 second delay) setting
(turn-on when 5 second more time is needed for
sensitive 5 sec fork out of fluid confirmation)
dry delay
wet delay
min failsafe 3 “wet” (or covered) delay (5 second delay) setting
(turn-on when 5 second more time is needed for
fork dipped in the fluid, confirmation)
DC
normal when there min failsafe
IL IL
turn-on
to set
ON
alarm
power
sensitive
5 sec min
dry delay
Loop powered wet delay
4mA/8mA ±1mA (alarm)
failsafe
20mA/16mA ±1mA (normal)
U 12 to 60V DC
1 2 3 4 5 6 7 8 9
Not used
mA
Supply
12 to 60 VDC
Meter/Indicator/PLC/SCADA
LFV-DL 4/20
8/16
turn-on
to set
ON
alarm
power
sensitive
5 sec min
dry delay
Loop powered wet delay
4mA/8mA ±1mA (alarm)
failsafe
20mA/16mA ±1mA (normal)
U 12 to 60V DC
1 2 3 4 5 6 7 8 9
Proper connection to supply earth terminal (3) and the external earth terminal (screw) is must.
lfv-manual-annexure-6 www.trumen.in Page 3
Annexure-7
Introduction - LFV-PFM
controls & indicators
B A A Status Indicating LED
B Configuration Switches
LFV-PFM
C C Power ON LED Indicator
normal STD
Sensitivity 1 2 3 4 Test type D Connecting Terminals
sensitive EXT
ON E External Earthing Terminal
E
status
power
x x
PFM Output
(o/p: 50Hz/150Hz 200𝜇S, 10mA) connection terminals
Only U
PFM Tester
x x x x x D
from
PFM
Tester
1 + of PFM Tester Sourced Supply
1 2 3 4 5 6 7 8 9 2 - of PFM Tester Sourced Supply
This supply must be taken from LFV PFM
Tester Devices Only.
This input is not tolerant above 30VDC
Supplying more than 30V may damage
the device.
configuration switches
1 Normal/Light Material sensitivity selector.
LFV-PFM Turn ON this switch if density of material is smaller
normal than 7gm/cc.
STD
Sensitivity 1 2 3 4 Test type
sensitive EXT 2 Not Used
ON 3 Not Used
x x 4 Power ON Test Mode selection switch
STD: Standard Test
Performs Covered-Uncovered-Covered simulation
for first 12 seconds of power ON.
Ignores Power-ON Test when fork is inside the
material in accordance with overfill-safety
failsafe Off 12 11 10 9 8 7
4mA Off
Failsafe Low
max.
On 12 11 10 9 8 7
Level Detection
failsafe
Failsafe High
14mA
max.
min.
4mA On On 12 11 10 9 8 7
failsafe
Failsafe Low
50 Hz output max.
min.
Off 12 11 10 9 8 7
failsafe
Alarm
Fault LED
Fault Detection
12 11 10 9 8 7
4mA On
Blinking
Fault
Fault
Relay
0 Hz output or LED
SPST 3 4
no output On
status
power
x x
min. PFM Output
(o/p: 50Hz/150Hz 200𝜇S, 10mA)
1 2 3 4 5 6 unused terminals
LFV-PFM
normal STD
Sensitivity 1 2 3 4 Test type
sensitive EXT
ON
status
power
x x
PFM Output
(o/p: 50Hz/150Hz 200𝜇S, 10mA)
1 2 3 4 5 6 7 8 9
Proper connection to supply earth terminal (3) and the external earth terminal (screw) is must.
lfv-manual-annexure-7 www.trumen.in Page 3