Transformers
Transformers
The values of the resistances and inductances in the transformer equivalent circuis can
be found by the open-circuit test and the short-circuit test.
The open-circuit test: in this test, one of the transformer winding is open-circuited,
and the other winding is connected to full rated supply voltage, see the circuit below.
As seen from the transformer equivalent circuit, the input current flows through the
excitation branch of the transformer. The series elements, R P and X P are too small
in comparison to RC and X M , so essentially all the input voltage is dropped across
the excitation branch.
The open-circuit test connections are shown in the following figure.
Usually, full line voltage is applied to one side of the transformer, and the input
voltage, input current, and input power to the transformer are measured.
From the figure, we conclude that,:
- the magnitude of conductance of the excitation branch is:
I
YM OC
VOC
- The power factor angle of magnetization branch is:
P
OC cos 1 OC
VOC .I OC
Notice that the power factor is always lagging for a real transformer, so the angle of
the current always lags the angle of the voltage by degrees.
The short-circuit test: In the short-circuit test, the low-voltage terminals of the
transformer are short-circuited, and the high-voltage tenninals are connected to a
variable voltage source, as shown below.
The input voltage is adjusted until the current in the short-circuited windings is equal
to its rated value. The input voltage, current and power are again measured.
Since the input voltage is so low during the short-circuit test, negligible current flows
through the excitation branch. If the excitation current is ignored, then all the voltage
drop in the transfonner can be attributed to the series elements in the circuit.
The magnitude of the series impedances referred to the primary side of the
transformer is:
V
Z CS SC
I SC
- The power factor angle of circuit in the short-circuit test is:
P
SC cos 1 SC
VSC .I SC
Notice that the power factor is always lagging for a real transformer, so the angle of
the current always lags the angle of the voltage by degrees.
We know that, in the short-circuit test:
Z CS Z P a 2 Z S RP a 2 RS j X P a 2 X S
Thus:
V
RP a 2 RS Re{Z SC } Z SC . cos SC SC cos SC (1)
I SC
And:
V
X P a 2 X S Im{ Z SC } Z SC . sin SC SC sin SC (2)
I SC
For some simplification, the resistance of the primary winding , R P , can be estimated
by measuring it by an ohmmeter while the seconary winding is open-circuited. After
finding R P , the resistance of the secondary winding refered to primary,
RS' a 2 RS can be found from (1), as the transformation ratio a is usually knowown,
or easily can be found, the resistance RS is found.
Example:
Build the equivalent circuit of a 20kVA , 8000 / 240V , 60Hz transformer, knowing
that the open-circuit test was performed on the secondary side of the transformer (to
reduce the maximum voltage to be measured) and the short-circuit test were
performed on the primary side of the transformer (to reduce the maximum current to
be measured). The following data were taken:
Solution:
The transformation ratio of the transformer is:
V 8000
a P 33.33
VS 240
From the open-circuit test:
The power factor angle of magnetization branch is:
P 400
OC cos 1 OC cos 1 76.5
0
489 x 2.5
The magnitude of the series impedances is:
This method is suitable for systems with different voltage levels (sections connected
with transformers).
In this method base values are selected, and all the actual values are referred to their
respective base values, as:
actual value
value in p.u
base value
normally two base values, base VA, VAB and the base voltage, VB are chosen.
then for each section VB is found from the transformers ratios. then the base current
I B and the base impedance Z B are calculated for each section. the p.u values then are
found.
Solution:
a)
In the generator region: S base 10kVA , Vbase1 480V , thus:
Yasin A. Al Shiboul, Al Balqa Applied University, Faculty of Engineering Technology, EE Department
S base 10000
I base1 20.83 A
Vbase1 480
Vbase1 480
Z base1 23.04
I base1 20.83
In the transmission line region: S base 10kVA , Vbase2 4800V , thus:
S 10000
I base2 base 2.083 A
Vbase2 4800
Vbase2 4800
Z base2 2304
I base2 2.083
In the load region: S base 10kVA , Vbase3 240V , thus:
S 10000
I base3 base 41.67 A
Vbase3 240
Vbase3 240
Z base3 5.76
I base3 41.67
b) the per-unit values of the circuit parameters are:
the generator voltage in p.u:
VG ,actual 480
VG. pu 1.0 p.u
Vbase1 480
the impedance of the transmission line in p.u:
Z Line,actual 20 j 60
Z Line. pu 0.0087 j 0.026 p.u
Z base2 2304
the impedance of the load in p.u:
Z Load ,actual 1030 0
Z Load . pu 1.73630 0 p.u 1.503 j 0.868 p.u
Z base3 5.76
The per-unit equivalent circuit of the power system is shown below.