Lec 6 & 7 - Transmission Line Protection
Lec 6 & 7 - Transmission Line Protection
College of Engineering
School of Electrical & Computer
Engineering
UNIT PROTECTION
SUMMARY
2
INTRODUCTION
Most high-voltage transmission systems are interconnected in a network
Overcurrent relays, which were quite adequate protective devices for radial
circuits.
3
Cont’d…
4
Cont’d…
Directional overcurrent relays are the simplest and least expensive, but are the
most difficult to apply. Overcurrent relays also have the disadvantage in changing
their coordination characteristics as the network and generation sources
change.
Overcurrent relays are widely used for ground protection.
Distance relays are often a first choice for replacing overcurrent relays when the
overcurrent relays are found to be inadequate for an application. Distance relays are
very common in applications for phase and ground protection of transmission
lines.
5
Cont’d…
Pilot relays are considered as the most selective of all kinds of transmission
Almost all EHV systems are protected by pilot relaying because of the large
power transfers commonly carried on these lines, the need for fast relay action
for system stability,
6
PROTECTION WITH OVERCURRENT RELAYS
certain conditions. Consider the simple network shown in Figure.1, where two
parallel transmission lines interconnect two systems, each of which contains
sources of fault.
Fig.1. Parallel transmission lines interconnecting two systems with generating sources. 7
Cont’d…
maintain a coordinating time interval between adjacent relays. Thus, for a fault
on line A-B, we reason, by inspection, that
𝑡𝐴 < 𝑡𝐶
𝑡𝐵 < 𝑡𝐷 …………………….(1)
Where t is the relay time for a given fault current magnitude and the subscript
8
Cont’d…
Similarly, if the fault is on line CD,
𝑡𝐷 < 𝑡𝐵
𝑡𝐶 < 𝑡𝐴 …………………….(2)
For proper coordination. Clearly, it is not possible to satisfy both (1) and (2)
One way of improving the selectivity of the overcurrent relay is the addition
of a directional element.
9
Cont’d…
The criteria for deciding whether directional relays should be required are
sometimes determined by the ratio of currents flowing in relays at the two ends
of a line.
Consider a portion of a large system in Figure 2, where we have numbered three
fault locations and have defined currents in breaker A corresponding to each
fault.
11
Cont’d…
Both load and fault currents are sensed at the bus G side of breaker A. The need
for directional capability depends, then, on the ratio of currents seen at the
breaker, where the current might be caused to flow in different directions. Fault
current for fault (1) flows toward a fault "behind" the relay at A, while the
faults at (2) and (3) are "in front" of the relay.
If the load current from H to G (𝐼𝐿𝑑 𝑜𝑢𝑡 ) is greater than that from G to H (𝐼𝐿𝑑 𝐼𝑛 )
12
Loops with One Current Source
First, consider the case of a looped transmission system where there is only one
source of fault current, such as the system shown in figure 3.
The source of fault current is to the left of bus R. Therefore, it is permissible to use
nondirectional overcurrent relays at 1 and 10, since a fault on bus R will not cause
currents to flow in the transmission loop in either direction.
Figure .3 A Transmission loop circuit with only one source of fault current. 13
Loops with Multiple Current Sources
For looped transmission systems with multiple sources, the coordination process
is much more complex. Now, all overcurrent relays must be directional and each
pair of relays must be coordinated, moving around the loop in both directions.
15
Figure 5 Relay currents at R and Q for faults between R and Q.
Cont’d…
Figure 5 shows the fault current seen at relay locations 1 and 4 as the fault is
Usually, the process is cut and try, and it may require several attempts to
realize complete coordination.
16
DISTANCE PROTECTION OF LINES
The distance relay operates on the principle of comparing the voltage and
current in some way to obtain a measure of the ratio between these quantities.
between stations G and H . We call this fraction the "reach setting" of the distance relay.
This means that the relay will trip only with programmed time delay for faults beyond this
reach, but will trip without time delay for faults closer to bus G.
The reach thus becomes a "balance point" for the relay at A, or a tripping threshold that is
Now consider a solid three-phase fault at the balance point. For this condition we
compute
𝑉𝑅 = ℎ𝑆 𝑍𝐿 𝐼𝑅𝑆 ……………………………………………………………………….(4)
18
Cont’d…
Where VR = voltage at the relay, IRS = current at the relay, ZL = total line impedance
from G to H, and hS = fraction of line impedance to balance point.
Since the relay measures the ratio of relay voltage to relay current, compute the relay
apparent impedance, ZRS , which is defined as
VR
=ZRS = hS ZL …………………………………………………………………….….(5)
IRS
For this condition, tripping would be marginal, that is, tripping mayor may not occur.
However, if the fault is closer to G, the voltage at the relay will be slightly lower or the
current slightly higher. Then the measured impedance is
ZR ≤ hS ZL …………………………………………….……………………………..(6)
19
Zoned Distance Relays
A distance relay will trip a faulted line in a very short time as long as the fault is
This is done by providing more than one distance relaying element within the
same relay package and setting the different elements to different thresholds and
with different relaying times.
Figure 7 shows a typical application. In the system illustrated, the distance relays
20
Cont’d…
Distance protection for all types of faults makes this technique very difficult and the
The final method of transmission protection that will be addressed is the concept
With this concept, the protected line is defined by its protective zone, as shown in
figure 9. The zone of protection includes everything inside the current transformers
where current measurements are made for the protected component.
24
Cont’d…
All faults that occur on the protected line are monitored at the current
but it is the current transformers that define the protective zone boundaries.
Each terminal of the protected line to have two circuit breakers. Indeed,
25
Cont’d…
To clear a fault on the protected line in figure 9, six circuit breakers, A
through F, must all clear successfully. If even one breaker fails to open, the
fault is still attached to the system and must be cleared by backup relays.
26
Figure 9: A protected line and its protective zone.
GROUND FAULT PROTECTION
An important aspect of transmission line protection is related to the fast
detection and clearing of ground faults on transmission systems that have
grounded neutrals. In the protection of transmission lines, ground faults are
given special treatment.
Most high-voltage and extra-high voltage transmission lines are grounded
neutral transmission systems, either solidly grounded or grounded through a
resistance or a reactance. It has been estimated that, on these high-voltage
systems, Over 90% of all transmission line faults are ground faults.
27
Types of Ground Relays
There are three basic types of relays that are used for ground relaying; overcurrent
Ground relays are almost always completely independent of phase relays, even
though any fault current, including ground fault current, will flow through one or
more of the phase relays.
The ground relays can be provided with much greater sensitivity to the zero-
sequence currents by using higher tap settings. This means that the ground relays
will pick up much faster than phase relays for a fault involving the ground.
28
Cont’d…
about one cycle in many cases, for faults on a large fraction of the line
length.
29
Cont’d…
Directional ground distance relays are responsive to impedance or reactance
These relays, although more expensive than overcurrent relays, can provide almost
Pilot relaying is used for ground protection in special cases where the other
methods are inadequate for reasons of security or dependability. Pilot relays use
either directional comparison or phase comparison to determine if the fault is within
the protected zone.
30
SUMMARY
Transmission protection is one of the most important tasks of the protection engineer.
Power systems have more transmission lines than any other type of component that
requires protection.
It has been noted that transmission protection using nondirectional overcurrent relays
31
Cont’d…
The next step up in relay performance is the distance relay, which is
32
Cont’d…
Pilot protection has been shown to treat the transmission line as a unit, by
measuring the inputs to the line from all terminals. This makes pilot
protection valuable for certain multi terminal lines.
It is more expensive than other types, but provides fast, secure protection,
33