Em-Rxyq-Taydu (Edus341703a-R1)
Em-Rxyq-Taydu (Edus341703a-R1)
RXYQ-TAYDU
3 phase
460 V, 60 Hz
EDUS341703A-R1
RXYQ-TAYDU
Heat Pump
3 phase
460 V, 60 Hz
2. Specifications
Model Name RXYQ72TAYDU RXYQ96TAYDU
Power Supply 3 phase, 460 V, 60 Hz 3 phase, 460 V, 60 Hz
1 Cooling Nominal Btu/h 72,000 (21.1) 96,000 (28.1)
Capacity Rated (kW) 69,000 (20.2) 92,000 (27.0)
2 Heating Nominal Btu/h 81,000 (23.7) 108,000 (31.7)
Capacity Rated (kW) 73,000 (21.4) 103,000 (30.2)
Casing Color Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
66-11/16 × 36-11/16 × 30-3/16 66-11/16 × 48-7/8 × 30-3/16
Dimensions: (H×W×D) in. (mm) (1,694 × 932 × 767) (1,694 × 1,242 × 767)
Heat Exchanger Cross Fin Coil Cross Fin Coil
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Displacement m3/h 14.7 19.3
Number of Revolutions r/min 6,954 6,072
Compressor
Motor Output ×
kW 4.2 × 1 6.3 × 1
Number of Units
Starting Method Soft Start Soft Start
Type Propeller Fan Propeller Fan
Motor Output kW 0.5 × 1 0.6 × 2
Fan cfm
Airflow Rate 5,544 (157) 5,827 (165)
(m3/min)
Drive Direct Drive Direct Drive
φ 3/8 (9.5) C1220T φ 3/8 (9.5) C1220T
Liquid Pipe in. (mm)
Connecting (Brazing Connection) (Brazing Connection)
Pipes φ 3/4 (19.1) C1220T φ 7/8 (22.2) C1220T
Gas Pipe in. (mm)
(Brazing Connection) (Brazing Connection)
Weight lbs (kg) 451 (205) 553 (251)
Sound Pressure Level
dB (A) 58 61
(Reference data)
Sound Power Level dB 78 81
(Reference data)
High Pressure Switch, High Pressure Switch,
Fan Driver Overload Protector, Fan Driver Overload Protector,
Safety Devices
Overcurrent Relay, Overcurrent Relay,
Inverter Overload Protector Inverter Overload Protector
Defrost Method Deicer Deicer
Capacity Control % 20-100 16-100
Refrigerant Name R410A R410A
Refrigerant Charge lbs (kg) 13.0 (5.9) 22.7 (10.3)
Control Electronic Expansion Valve Electronic Expansion Valve
Installation Manual, Installation Manual,
Standard Accessories Operation Manual, Operation Manual,
Connection Pipes, Clamps Connection Pipes, Clamps
Specification C: 4D106899A C: 4D087118C
Drawing No.
Sound Level C: 4D088142A C: 4D088143A
Notes:
1 Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / outdoor temp.: 95°FDB (35.0°CDB) / Equivalent piping length: 25 ft (7.6 m), level
difference: 0 ft (0 m).
2 Indoor temp.: 70°FDB (21.1°CDB) / outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Equivalent piping length: 25 ft (7.6 m), level
difference: 0 ft (0 m).
Dimensions: (H×W×D) in. (mm) 66-11/16 × 48-7/8 × 30-3/16 66-11/16 × 48-7/8 × 30-3/16
(1,694 × 1,242 × 767) (1,694 × 1,242 × 767)
Heat Exchanger Cross Fin Coil Cross Fin Coil
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Displacement m3/h 26.6 15.2 + 15.2
Number of Revolutions r/min 8,346 7,158 + 7,158
Compressor
Motor Output ×
Number of Units kW 8.7 × 1 (4.4 × 1) + (4.4 × 1)
Notes:
1 Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / outdoor temp.: 95°FDB (35.0°CDB) / Equivalent piping length: 25 ft (7.6 m), level
difference: 0 ft (0 m).
2 Indoor temp.: 70°FDB (21.1°CDB) / outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Equivalent piping length: 25 ft (7.6 m), level
difference: 0 ft (0 m).
Notes:
1 Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / outdoor temp.: 95°FDB (35.0°CDB) / Equivalent piping length: 25 ft (7.6 m), level
difference: 0 ft (0 m).
2 Indoor temp.: 70°FDB (21.1°CDB) / outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Equivalent piping length: 25 ft (7.6 m), level
difference: 0 ft (0 m).
Notes:
1 Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / outdoor temp.: 95°FDB (35.0°CDB) / Equivalent piping length: 25 ft (7.6 m), level
difference: 0 ft (0 m).
2 Indoor temp.: 70°FDB (21.1°CDB) / outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Equivalent piping length: 25 ft (7.6 m), level
difference: 0 ft (0 m).
Notes:
1 Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / outdoor temp.: 95°FDB (35.0°CDB) / Equivalent piping length: 25 ft (7.6 m), level
difference: 0 ft (0 m).
2 Indoor temp.: 70°FDB (21.1°CDB) / outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Equivalent piping length: 25 ft (7.6 m), level
difference: 0 ft (0 m).
Notes:
1 Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / outdoor temp.: 95°FDB (35.0°CDB) / Equivalent piping length: 25 ft (7.6 m), level
difference: 0 ft (0 m).
2 Indoor temp.: 70°FDB (21.1°CDB) / outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Equivalent piping length: 25 ft (7.6 m), level
difference: 0 ft (0 m).
Notes:
1 Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / outdoor temp.: 95°FDB (35.0°CDB) / Equivalent piping length: 25 ft (7.6 m), level
difference: 0 ft (0 m).
2 Indoor temp.: 70°FDB (21.1°CDB) / outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Equivalent piping length: 25 ft (7.6 m), level
difference: 0 ft (0 m).
Notes:
1 Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / outdoor temp.: 95°FDB (35.0°CDB) / Equivalent piping length: 25 ft (7.6 m), level
difference: 0 ft (0 m).
2 Indoor temp.: 70°FDB (21.1°CDB) / outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Equivalent piping length: 25 ft (7.6 m), level
difference: 0 ft (0 m).
3. Dimensions
RXYQ72TAYDU
3D085619B
RXYQ96-168TAYDU
C: 3D085620C
RXYQ192TAYDU
13
Dimensions
14
Dimensions
RXYQ216-336TAYDU
Notes :
1. Heights of walls of this example;
Front : 59 in. (1500 mm)
Suction side : 19-5/8 in. (500 mm)
Side : Height unrestricted
The installation space shown in this figure is based on the condition of cooling operation at the outdoor air
temperature of 95˚FDB (35˚CDB).
The installation space of suction side shown above must be expanded in the following case.
· Design outdoor temperature becomes over 95˚FDB (35˚CDB).
· Operating over max. operating load (In case of causing a heavy heating load at indoor unit side)
2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service
spaces respectively as shown in the following figure.
3. When installing the units the most appropriate pattern should be selected from “Installation and repair space
drawing” in order to obtain the best fit in the space available always bearing in mind the need to leave enough room
for a person to pass between units and wall and for the air to circulate freely.
(If more units are to be installed than are shown in “Installation and repair space drawing”, your layout should take
account of the possibility of short circuiting.)
4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried
out comfortably.
C: 3D087026C
RXYQ360-408TAYDU
15
Dimensions
16
Unit : in. (mm)
Service Space
RXYQ72-408TAYDU
4. Service Space
Notes:
1. Heights of walls in case of Patterns 1 and 2;
Front : 59 in. (1500 mm)
Suction side : 19-5/8 in. (500 mm)
Side : Height unrestricted
The installation space shown in this figure is based on the condition of cooling operation at the outdoor air temperature of 95˚FDB (35˚CDB).
The installation space of suction side shown above must be expanded in the following case.
·Design outdoor temperature becomes over 95˚FDB (35˚CDB).
· Operating over max. operating load (In case of causing a heavy heating load at indoor unit side)
2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in the
following figure.
3. When installing the units the most appropriate pattern should be selected from “Installation and repair space drawing” in order to obtain the best fit in the
space available always bearing in mind the need to leave enough room for a person to pass between units and wall and for the air to circulate freely.
(If more units are to be installed than are shown in “Installation and repair space drawing”, your layout should take account of the possibility of short
circuiting.)
4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.
C: 3D085503H
RXYQ72-408TAYDU
C: 3D085503H
Service Space
17
Piping Diagrams EDUS341703A-R1
5. Piping Diagrams
RXYQ72TAYDU
3D085567A
RXYQ96-120TAYDU
3D085598A
RXYQ144-168TAYDU
3D085568A
6. Wiring Diagrams
RXYQ72TAYDU
NOTES)
1. THIS WIRING DIAGRAM APPLIES ONLY TO THE OUTDOOR UNIT.
2. : FIELD WIRING, : TERMINAL BLOCK, : CONNECTOR,
: TERMINAL, : PROTECTIVE GROUND (SCREW), : NOISELESS GROUND.
3. WHEN USING THE OPTIONAL ADAPTOR, REFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR.
4. FOR CONNECTION WIRING TO INDOOR-OUTDOOR TRANSMISSION F1·F2, OUTDOOR-OUTDOOR TRANSMISSION F1·F2,
OUTDOOR-MULTI TRANSMISSION Q1·Q2, REFER TO THE INSTALLATION MANUAL.
5. HOW TO USE BS1~3 SWITCH, REFER TO “SERVICE PRECAUTIONS” LABEL ON
CONTROL BOX COVER.
6. WHEN OPERATING, DON'T SHORTCIRCUIT THE PROTECTION DEVICE (S1PH).
7. COLORS BLK : BLACK ; RED : RED ; BLU : BLUE ; WHT : WHITE ; GRN : GREEN.
8. CLASS 2 WIRE
C: 3D106438A
RXYQ72TAYDU
A1P PRINTED CIRCUIT BOARD (MAIN) R6T THERMISTOR (SUBCOOL GAS)
A2P PRINTED CIRCUIT BOARD (NOISE FILTER) R7T THERMISTOR (DEICER)
A3P PRINTED CIRCUIT BOARD (INV) R1 RESISTOR (CURRENT LIMITING) (A3P)
A4P PRINTED CIRCUIT BOARD (FAN) R11, R12 RESISTOR (A3P)
A5P PRINTED CIRCUIT BOARD (ABC I/P) R24 RESISTOR (CURRENT SENSOR) (A4P)
BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) R77 RESISTOR (CURRENT SENSOR) (A3P)
C32, C66 CAPACITOR (A3P) S1NPH PRESSURE SENSOR (HIGH)
DS1, DS2 DIP SWITCH (A1P) S1NPL PRESSURE SENSOR (LOW)
E1HC CRANKCASE HEATER S1PH PRESSURE SWITCH (HIGH)
F1U, F2U FUSE (A1P) SEG1~SEG3 7-SEGMENT DISPLAY (A1P)
F101U FUSE (A4P) T1A CURRENT SENSOR
F401U, F403U FUSE (A2P) T1R TRANSFORMER (460 V / 230 V)
F601U FUSE (A3P) V1R POWER MODULE (A3P) (A4P)
HAP PILOTLAMP (A1P, A3P, A4P) (SERVICE MONITOR-GREEN) X1A, X2A CONNECTOR (M1F)
K1M, K2M MAGNETIC CONTACTOR (A3P) X3A CONNECTOR (CHECK THE RESIDUAL CHARGE)
K3R MAGNETIC RELAY (A3P) X4A, X5A CONNECTOR (T1R)
K3R MAGNETIC RELAY (Y3S) (A1P) X6A CONNECTOR (Z7C)
K84R MAGNETIC RELAY (A3P) X1M TERMINAL BLOCK (POWER SUPPLY)
K4R MAGNETIC RELAY (Y2S, A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)
K6R MAGNETIC RELAY (OPTION) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A5P)
K7R MAGNETIC RELAY (E1HC) (A1P) Y1E ELECTRONIC EXPANSION VALVE (MAIN)
K11R MAGNETIC RELAY (Y1S) (A1P) Y2E ELECTRONIC EXPANSION VALVE (INJECTION)
L1R REACTOR Y1S SOLENOID VALVE (4 WAY VALVE)
M1C MOTOR (COMPRESSOR) Y2S SOLENOID VALVE (ACCUMULATOR OIL RETURN)
M1F MOTOR (FAN) Y3S SOLENOID VALVE (OS OIL RETURN)
PS SWITCHING POWER SUPPLY (A1P, A3P) Z1C~Z7C NOISE FILTER (FERRITE CORE)
Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Z1F NOISE FILTER (A2P) (WITH SURGE ABSORBER)
R1T THERMISTOR (AIR) (A1P) CONNECTOR FOR OPTIONAL ACCESSORIES
R21T THERMISTOR (M1C DISCHARGE) X37A CONNECTOR (POWER ADAPTOR) (A1P)
R3T THERMISTOR (ACCUMULATOR) COOL/HEAT SELECTOR
R4T THERMISTOR (HEAT EXC. LIQUID) S1S SELECTOR SWITCH (FAN/COOL·HEAT)
R5T THERMISTOR (SUBCOOL LIQUID) S2S SELECTOR SWITCH (COOL/HEAT)
C: 3D106438A
RXYQ96-120TAYDU
C: 2D106439A
23
Wiring Diagrams
Wiring Diagrams EDUS341703A-R1
RXYQ96-120TAYDU
A1P PRINTED CIRCUIT BOARD (MAIN) R3T THERMISTOR (ACCUMULATOR)
A2P PRINTED CIRCUIT BOARD (NOISE FILTER) R4T THERMISTOR (HEAT EXC. LIQUID)
A3P PRINTED CIRCUIT BOARD (INV) R5T THERMISTOR (SUBCOOL LIQUID)
A4P, A5P PRINTED CIRCUIT BOARD (FAN) R6T THERMISTOR (SUBCOOL GAS)
A6P PRINTED CIRCUIT BOARD (ABC I/P) R7T THERMISTOR (DEICER)
A7P PRINTED CIRCUIT BOARD (CURRENT LIMITING) R8T THERMISTOR (M1C BODY)
A8P PRINTED CIRCUIT BOARD (NOISE FILTER) S1NPH PRESSURE SENSOR (HIGH)
A9P PRINTED CIRCUIT BOARD (OPEN PHASE PROTECTION) S1NPL PRESSURE SENSOR (LOW)
BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) S1PH PRESSURE SWITCH (HIGH)
C47, C48 CAPACITOR (A3P) SEG1~SEG3 7-SEGMENT DISPLAY (A1P)
DS1, DS2 DIP SWITCH (A1P) T1R TRANSFORMER (460 V / 230 V)
E1HC CRANKCASE HEATER T1A CURRENT SENSOR
F1U FUSE (A1P) V1R POWER MODULE (A3P)
F101U FUSE (A4P, A5P) V1R POWER MODULE (A4P, A5P)
F401U, F403U FUSE (A2P) V2R POWER MODULE (A3P)
F601U FUSE (A3P) X1A~X4A CONNECTOR (M1F, M2F)
HAP PILOTLAMP (A1P, A3P, A4P, A5P) (SERVICE MONITOR-GREEN) X5A CONNECTOR (CHECK THE RESIDUAL CHARGE)
K1M MAGNETIC CONTACTOR (A3P, A7P) X6A, X7A CONNECTOR (T1R)
K3R MAGNETIC RELAY (A3P) X1M TERMINAL BLOCK (POWER SUPPLY)
K4R MAGNETIC RELAY (Y2S) (A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)
K5R MAGNETIC RELAY (Y3S) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A6P)
K6R MAGNETIC RELAY (OPTION) (A1P) Y1E ELECTRONIC EXPANSION VALVE (MAIN)
K7R MAGNETIC RELAY (E1HC) (A1P) Y2E ELECTRONIC EXPANSION VALVE (INJECTION)
K11R MAGNETIC RELAY (Y1S) (A1P) Y1S SOLENOID VALVE (4 WAY VALVE)
L1R, L2R REACTOR Y2S SOLENOID VALVE (ACCUMULATOR OIL RETURN)
M1C MOTOR (COMPRESSOR) Y3S SOLENOID VALVE (OS OIL RETURN)
M1F, M2F MOTOR (FAN) Z1C~Z6C NOISE FILTER (FERRITE CORE)
PS SWITCHING POWER SUPPLY (A1P, A3P) Z1F NOISE FILTER (A2P) (WITH SURGE ABSORBER)
Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Z2F NOISE FILTER (A8P)
R1 RESISTOR (CURRENT LIMITING) (A7P) CONNECTOR FOR OPTIONAL ACCESSORIES
R24 RESISTOR (CURRENT SENSOR) (A4P, A5P) X37A CONNECTOR (POWER ADAPTOR) (A1P)
R313 RESISTOR (CURRENT SENSOR) (A3P)
R851, R854 RESISTOR (A3P) COOL/HEAT SELECTOR
R1T THERMISTOR (AIR) (A1P) S1S SELECTOR SWITCH (FAN/COOL·HEAT)
R21T THERMISTOR (M1C DISCHARGE) S2S SELECTOR SWITCH (COOL/HEAT)
C: 2D106439A
RXYQ144-168TAYDU
C: 2D106440A
25
Wiring Diagrams
Wiring Diagrams EDUS341703A-R1
RXYQ144-168TAYDU
A1P PRINTED CIRCUIT BOARD (MAIN) R21T, R22T THERMISTOR (M1C, M2C DISCHARGE)
A2P, A5P PRINTED CIRCUIT BOARD (NOISE FILTER) R3T THERMISTOR (ACCUMULATOR)
A3P, A6P PRINTED CIRCUIT BOARD (INV) R4T THERMISTOR (HEAT EXC. LIQUID)
A4P, A7P PRINTED CIRCUIT BOARD (FAN) R5T THERMISTOR (SUBCOOL LIQUID)
A8P PRINTED CIRCUIT BOARD (ABC I/P) R6T THERMISTOR (SUBCOOL GAS)
BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) R7T THERMISTOR (DEICER)
C32, C66 CAPACITOR (A3P, A6P) S1NPH PRESSURE SENSOR (HIGH)
DS1, DS2 DIP SWITCH (A1P) S1NPL PRESSURE SENSOR (LOW)
E1HC, E2HC CRANKCASE HEATER S1PH, S2PH PRESSURE SWITCH (HIGH)
F1U FUSE (A1P) SEG1~SEG3 7-SEGMENT DISPLAY (A1P)
F101U FUSE (A4P, A7P) T1A CURRENT SENSOR
F401U, F403U FUSE (A2P, A5P) T1R TRANSFORMER (460 V / 230 V)
F601U FUSE (A3P, A6P) V1R POWER MODULE (A3P, A6P)
HAP PILOTLAMP (A1P, A3P, A4P, A6P, A7P) (SERVICE MONITOR-GREEN) V1R POWER MODULE (A4P, A7P)
K1M, K2M MAGNETIC CONTACTOR (A3P, A6P) X1A~X4A CONNECTOR (M1F, M2F)
K3R MAGNETIC RELAY (A3P, A6P) X5A, X6A CONNECTOR (CHECK THE RESIDUAL CHARGE)
K3R MAGNETIC RELAY (Y4S) (A1P) X7A, X8A CONNECTOR (T1R)
K84R MAGNETIC RELAY (A3P) (A6P) X9A CONNECTOR (Z8C)
K4R MAGNETIC RELAY (Y2S) (A1P) X1M TERMINAL BLOCK (POWER SUPPLY)
K5R MAGNETIC RELAY (Y3S) (A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)
K6R MAGNETIC RELAY (OPTION) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A8P)
K7R MAGNETIC RELAY (E1HC) (A1P) Y1E ELECTRONIC EXPANSION VALVE (MAIN)
K8R MAGNETIC RELAY (E2HC) (A1P) Y2E ELECTRONIC EXPANSION VALVE (INJECTION)
K11R MAGNETIC RELAY (Y1S) (A1P) Y1S SOLENOID VALVE (4 WAY VALVE)
L1R, L2R REACTOR Y2S SOLENOID VALVE (ACCUMULATOR OIL RETURN)
M1C, M2C MOTOR (COMPRESSOR) Y3S SOLENOID VALVE (OS OIL RETURN 1)
M1F, M2F MOTOR (FAN) Y4S SOLENOID VALVE (OS OIL RETURN 2)
PS SWITCHING POWER SUPPLY (A1P, A3P, A6P) Z1C~Z8C NOISE FILTER (FERRITE CORE)
Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Z1F NOISE FILTER (A2P, A5P) (WITH SURGE ABSORBER)
R1 RESISTOR (CURRENT LIMITING) (A3P, A6P) CONNECTOR FOR OPTIONAL ACCESSORIES
R11, R12 RESISTOR (A3P, A6P) X37A CONNECTOR (POWER ADAPTOR) (A1P)
R24 RESISTOR (CURRENT SENSOR) (A4P, A7P) COOL/HEAT SELECTOR
R77 RESISTOR (CURRENT SENSOR) (A3P, A6P) S1S SELECTOR SWITCH (FAN/COOL·HEAT)
R1T THERMISTOR (AIR) (A1P) S2S SELECTOR SWITCH (COOL/HEAT)
C: 2D106440A
Wiring should comply with applicable local and national codes. manner because this system consists of the equipment utilizing the multiple
RXYQ72-168TAYDU
power sources.
9) If there exists the possibility of reversed phase, lost phase, momentary blackout
or the power goes on and off while the product is operating, attach a reversed
7. Field Wiring
C: 3D087054C
27
Field Wiring
28
Notes 1) All wiring, components and materials to be procured 5) Unit shall be grounded in compliance with the applicable local and national codes.
on the site must comply with the 6) Wiring shown are general points-of-connection guides only and are not intended
applicable local and national codes. for or to include all details for a specific installation.
Field Wiring
2) Use copper conductors only. 7) Be sure to install the switch and the fuse/breaker to the power line of each piece
3) As for details, see wiring diagram. of equipment.
4) Field wiring diagram is to be used as a guideline only. 8) Install the main switch that can interrupt all the power sources in an integrated
Wiring should comply with applicable local and national codes. manner because this system consists of the equipment utilizing the multiple
power sources.
RXYQ192-336TAYDU
9) If there exists the possibility of reversed phase, lost phase, momentary blackout
or the power goes on and off while the product is operating, attach a reversed
phase protection circuit locally.
Running the product in reversed phase may break the compressor and other
parts.
C: 3D087055C
Wiring should comply with applicable local and national codes. manner because this system consists of the equipment utilizing the multiple
power sources.
RXYQ360-408TAYDU
9) If there exists the possibility of reversed phase, lost phase, momentary blackout
or the power goes on and off while the product is operating, attach a reversed
phase protection circuit locally.
Running the product in reversed phase may break the compressor and other
C: 3D087056D
29
Field Wiring
Electric Characteristics EDUS341703A-R1
8. Electric Characteristics
RXYQ72-408TAYDU
Units Power supply Comp. OFM
Model name SCCR
Hz Volts Min. Max. MCA MOP RLA kW FLA
RXYQ72TAYDU 60 460 416 508 12.3 20 7.1 0.5 0.8
RXYQ96TAYDU 60 460 416 508 20.6 25 10.2 0.6 × 2 1.0 × 2
RXYQ120TAYDU 60 460 416 508 20.6 25 11.7 0.6 × 2 1.0 × 2
RXYQ144TAYDU 60 460 416 508 25.9 35 7.6 + 7.6 0.6 × 2 1.0 × 2
RXYQ168TAYDU 60 460 416 508 25.9 35 8.5 + 8.5 0.6 × 2 1.0 × 2
RXYQ72TAYDU
RXYQ192TAYDU 60 460 416 508 12.3 + 20.6 20 + 25 7.1 + 11.7 0.5 + (0.6 × 2) 0.8 + (1.0 × 2)
RXYQ120TAYDU
RXYQ96TAYDU
RXYQ216TAYDU 60 460 416 508 20.6 + 20.6 25 + 25 10.2 + 11.7 (0.6 × 2) × 2 (1.0 × 2) × 2
RXYQ120TAYDU
RXYQ120TAYDU
RXYQ240TAYDU 60 460 416 508 20.6 + 20.6 25 + 25 11.7 + 11.7 (0.6 × 2) × 2 (1.0 × 2) × 2
RXYQ120TAYDU
RXYQ120TAYDU
RXYQ264TAYCU 60 460 416 508 20.6 + 25.9 25 + 35 11.7 + (7.6 + 7.6) (0.6 × 2) × 2 (1.0 × 2) × 2
RXYQ144TAYDU
RXYQ144TAYDU SCCR kA rms,
RXYQ288TAYDU 60 460 416 508 25.9 + 25.9 35 + 35 (7.6 + 7.6) × 2 (0.6 × 2) × 2 (1.0 × 2) × 2 Symmetrical
RXYQ144TAYDU @600 V MAX: 5
RXYQ144TAYDU (7.6 + 7.6)
RXYQ312TAYDU 60 460 416 508 25.9 + 25.9 35 + 35 (0.6 × 2) × 2 (1.0 × 2) × 2
RXYQ168TAYDU + (8.5 + 8.5)
RXYQ168TAYDU
RXYQ336TAYDU 60 460 416 508 25.9 + 25.9 35 + 35 (8.5 + 8.5) × 2 (0.6 × 2) × 2 (1.0 × 2) × 2
RXYQ168TAYDU
RXYQ120TAYDU
20.6 + 20.6 25 + 25 11.7 + 11.7
RXYQ360TAYDU RXYQ120TAYDU 60 460 416 508 (0.6 × 2) × 3 (1.0 × 2) × 3
+ 20.6 + 25 + 11.7
RXYQ120TAYDU
RXYQ96TAYDU
20.6 + 20.6 25 + 25 10.2 + 11.7
RXYQ384TAYDU RXYQ120TAYDU 60 460 416 508 (0.6 × 2) × 3 (1.0 × 2) × 3
+ 25.9 + 35 + (8.5 + 8.5)
RXYQ168TAYDU
RXYQ96TAYDU
20.6 + 25.9 25 + 35 10.2 + (7.6 + 7.6)
RXYQ408TAYDU RXYQ144TAYDU 60 460 416 508 (0.6 × 2) × 3 (1.0 × 2) × 3
+ 25.9 + 35 + (8.5 + 8.5)
RXYQ168TAYDU
Symbols:
MCA: Min. Circuit Amps. (A)
MOP: Max. Overcurrent Protector (A)
RLA: Rated Load Amps. (A)
OFM: Outdoor Fan Motor
kW: Rated Motor Output (kW)
FLA: Full Load Amps. (A)
SCCR: Short-Circuit Current Rating
Notes:
1. RLA is based on the following conditions.
Indoor temp. 80°FDB (26.7°CDB) / 67°FWB (19.4°CWB)
Outdoor temp. 95°FDB (35.0°CDB)
2. Voltage range
Units are designed to operate only at the rated voltage provided in the table above.
3. Maximum allowable voltage variation between phases is 2%.
4. Select wire size based on the value of MCA.
5. MOP is used to select the circuit breaker.
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
9.1.2 Celsius
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
9.2.2 Celsius
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
C: CA14A041
RXYQ72TAYDU
3D087588B
3D087593B
3D087592B
3D087590B
3D087591B
RXYQ216TAYDU
3D087589B
RXYQ72-408TAYDU
The capacity tables do not account for the reduction in capacity during frost accumulation or operation in defrost
mode. Heating capacity which takes the above mentioned factors into consideration can be calculated as follows:
Formula
Heating capacity = A × B
A = Capacity value given in the capacity tables
B = Correction factor for frost accumulation
Note:
Correction factor for frost accumulation calculated from integrated heating capacity while 1 cycle (between 2 defrosting
operations) as shown in figure below.
Accumulation of frost and / or snow on the outdoor unit heat exchanger leads to a temporary reduction in capacity.
The degree of capacity reduction depends on factors such as outdoor temperature (DB), relative humidity (RH),
amount of frost, etc.
3D085476C
C: 4D088142A
RXYQ96-120TAYDU
C: 4D088143A
RXYQ144TAYDU
C: 4D088144A
RXYQ168TAYDU
C: 4D088145A
12. Accessories
12.1 Optional Accessories
RXYQ72-408TAYDU
RXYQ192TAYDU
RXYQ216TAYDU
RXYQ120TAYDU RXYQ240TAYDU RXYQ360TAYDU
Optional accessories RXYQ72TAYDU RXYQ144TAYDU RXYQ264TAYDU RXYQ384TAYDU
RXYQ96TAYDU
RXYQ168TAYDU RXYQ288TAYDU RXYQ408TAYDU
RXYQ312TAYDU
RXYQ336TAYDU
KHRP26M22H9 KHRP26M22H9 (Max. 4 branch)
REFNET (Max. 4 branch) KHRP26M22H9 (Max. 4 branch) KHRP26M33H9 (Max. 8 branch)
KHRP26M33H9 (Max. 8 branch)
header KHRP26M33H9 KHRP26M72H9 (Max. 8 branch) KHRP26M72H9 (Max. 8 branch)
Distributive (Max. 8 branch) KHRP26M73HU9 (Max. 8 branch)
piping KHRP26A22T9
KHRP26A22T9
REFNET joint KHRP26A22T9 KHRP26A33T9 KHRP26A33T9
KHRP26A33T9 KHRP26M72TU9
KHRP26M72TU9 KHRP26M73TU9
Outdoor unit multi connection — BHFP22P100U BHFP22P151U
piping kit
C: 3D087057D
Specifications, designs and other content appearing in this brochure are current as of September 2018 but subject to change without notice.
c All rights reserved 09/18 FS