0% found this document useful (0 votes)
124 views

Line List Template

This document provides notes on allocating categories according to the Pressure Equipment Directive for piping systems. It defines fluid groups, states of contents, and charts for determining the PED category based on the fluid group, state of contents, and maximum allowable pressure. It also provides clarification on terms like nominal size and notes exceptions for equipment already in use and installed before 1999.

Uploaded by

Meo
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
124 views

Line List Template

This document provides notes on allocating categories according to the Pressure Equipment Directive for piping systems. It defines fluid groups, states of contents, and charts for determining the PED category based on the fluid group, state of contents, and maximum allowable pressure. It also provides clarification on terms like nominal size and notes exceptions for equipment already in use and installed before 1999.

Uploaded by

Meo
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 3

CLIENT : Client name

PROJECT TITLE : Proj name

JOB No. : Job no

DOCUMENT No. : Doc no

DOCUMENT TITLE : Title

REVISION RECORD
ORIGINATED CHECKED APPROVED BY
REV DESCRIPTION
BY BY ENG. PROJ. CLIENT
CLIENT: Client name REV

LOCATION: DATE

PROJECT: Job no BY

DOC NO.: Doc no CHECKED

SHEET: APPROVED

NOTES ON PRESSURE EQUIPMENT DIRECTIVE (PED) FLUID GROUP AND CATEGORY:

THE FOLLOWING NOTES ON ALLOCATION OF PED CATEGORY ARE TAKEN DIRECTLY FROM THE PRESSURE EQUIPMENT DIRECTIVE (PED) 97/23/EC WITH

ADDITIONAL NOTES FOR CLARITY.


1. FLUID GROUP IS TO BE ENTERED IN ACCORDANCE WITH PRESSURE EQUIPMENT DIRECTIVE (PED) 97/23/EC AS FOLLOWS:

GROUP 1 COMPRISES THOSE FLUIDS CLASSIFIED, ACCORDING TO THE EC DIRECTIVE ON THE CLASSIFICATION OF DANGEROUS SUBSTANCES* AS:

* EXPLOSIVE
* EXTREMELY FLAMMABLE

* HIGHLY FLAMMABLE

* FLAMMABLE (WHERE THE MAXIMUM ALLOWABLE TEMPERATURE IS ABOVE FLASHPOINT)

* VERY TOXIC

* TOXIC

* OXIDISING

GROUP 2 COMPRISES ALL OTHER FLUIDS INCLUDING STEAM.

* COUNCIL DIRECTIVE 67/548/EEC OF 27 JUNE 1967 CAN BE OBTAINED FROM WWW.OPEN.GOV.UK/HSE

2. DETERMINE THE STATE OF INTENDED FLUID CONTENTS - GAS OR LIQUID - AS FOLLOWS:

IF A FLUID HAS A VAPOUR PRESSURE AT THE MAXIMUM ALLOWABLE TEMPERATURE OF THE EQUIPMENT (DESIGN TEMPERATURE) OF GREATER

THAN 0.5 BAR (7.25 PSI) ABOVE NORMAL ATMOSPHERIC PRESSURE (1013 MBAR), IT IS TREATED AS A GAS, OTHERWISE IT IS TREATED AS A LIQUID.

IF MIXED PHASE IS DESIGNATED ON THE LINE LIST, ITS STATE OF CONTENT IS TO BE DETERMINED IN ACCORDANCE WITH THE ABOVE PARAGRAPH, I.E

MOST HYDROCARBON STREAMS WILL BE DESIGNATED A GAS.

3. PED CATEGORY FOR PIPING IS DETERMINED USING THE CHARTS INDICATED IN THE FOLLOWING TABLE:

PIPING

State of contents Gas Liquid

Fluid Group 1 2 1 2

Chart 6 7 8 9

4. THE MAXIMUM ALLOWABLE PRESSURE (PS) IS THE MAXIMUM PRESSURE FOR WHICH THE PIPING IS DESIGNED, AS SPECIFIED BY THE MANUFACTURER. TO

ENSURE CONSISTENCY PRIOR TO MANUFACTURER DATA, THIS SHALL BE TAKEN AS THE DESIGN PRESSURE AS SPECIFIED BY PROCESS GROUP.

5. NOMINAL SIZE (DN) MEANS A NUMERICAL DESIGNATION OF SIZE (IN MM) WHICH IS COMMON TO ALL COMPONENTS IN A PIPING SYSTEM OTHER THAN
COMPONENTS INDICATED BY OUTSIDE DIAMETER OR BY THREAD SIZE.

6. PIPELINES, COMPRISING PIPING OR A SYSTEM OF PIPING DESIGNED FOR THE CONVEYANCE OF ANY FLUID OR SUBSTANCE TO OR FROM AN INSTALLATION

(ONSHORE OR OFFSHORE) STARTING FROM AND INCLUDING THE LAST ISOLATION DEVICE LOCATED WITHIN THE CONFINES OF THE INSTALLATION, INCLUDING

ALL THE ANNEXED EQUIPMENT DESIGNED SPECIFICALLY FOR PIPELINES, ARE EXCLUDED FROM THE SCOPE OF THE DIRECTIVE.

7. THE PED REGULATIONS DO NOT APPLY TO EQUIPMENT AND ASSEMBLIES IN USE, OR THEIR REPAIR OR MODIFICATION (UNLESS SIGNIFICANT), OR TO SERVICING.

8. THE PED REGULATIONS DO NOT APPLY TO EQUIPMENT AND ASSEMBLIES PLACED ON THE MARKET IN THE EEA BEFORE 29 NOVEMBER 1999, E.G. SECOND HAND.

9. SEP: SOUND ENGINEERING PRACTICE


CLIENT: Client name REV
LOCATION: DATE
PROJECT: Job no BY
DOC NO.: Doc no CHECKED
APPROVED
SHEET:

LINE NUMBER INSULATION FROM : DETAILS TO : DETAILS OP. PRESS. OP. TEMP. DESIGN PRESS. DESIGN TEMP TEST PRESS. CODES

Sequential Thk NORM MAX. NORM MIN. MAX. PED REMARKS REV
Service Line Size Specification Class From To P&ID Class barg Phase
Number mm barg barg deg C barg deg C deg C Categ.

NOTES
1
2
3
4
5

HOLDS
1
2
3
4
5