Module 5 - Power Factor Corrections
Module 5 - Power Factor Corrections
MODULE 5
Definitions
Power factor is the measure of how effectively the
electrical equipment converts electric power (supplied
by power utility) into useful power output.
It is a measure of how effectively the current is being
converted into useful work output. A good indicator
of the effect of the load current on the efficiency of
the supply system.
In technical terms, it is the ratio of Active Power
(kW) to the Apparent Power (kVA) of an electrical
installation.
2
1
Definitions
KW is Working Power (also called Actual Power or
Active Power or Real Power). It is the power that actually
powers the equipment and performs useful work.
KVAR is Reactive Power. It is the power that magnetic
equipment (transformer, motor and relay) needs to
produce the magnetizing flux.
KVA is Apparent Power. It is the product of the voltage and
the current . It comprises both active and reactive power .
It is the “vectorial summation” of KVAR and KW.
2
Causes of Low Power Factor
A distorted current waveform can be the result of a rectifier
variable speed drive, switched mode power supply, discharge
lighting or other electronic load.
Thus, Low power factor results when KW is small in relation
to KVA.
KVAR
Ø
KW
Ø
KW 6
3
Unwanted Effects of Low Power Factor
For a given load, the current will increase which
means larger size of wire is needed. Also increases
the losses and decreases the efficiency of the system.
Generators, transformers, switches and transmission
conductors becomes overloaded due to high current.
Voltage drop in transmission lines increases due to
increase in current.
4
Reasons for Improving Power Factor
Increase System Capacity
When the power factor is improved and the KW capacity of the
system is increased.
The amount of reactive current flowing is lowered thus reducing
transformer and distribution circuit loads, and releasing system
capacity.
10
5
Methods for Power Factor Corrections
Power factor correction is the process of increasing the power
factor without altering the voltage or current to the original load
A system to a desired Power Factor level is the difference
between the amount of KVAR in the uncorrected system and
the amount of desired KVAR in the corrected system.
One way to increase power factor is to add capacitive powers to
the system by installing a capacitors in parallel with the load.
The introduction of Power Factor Correction (PFC) capacitors
is a widely recognised method of reducing an electrical load,
thus minimising wasted energy and hence improving the
efficiency of a plant and reducing the electricity bill.
11
6
Methods for Power Factor Corrections
13
7
Methods for Power Factor Corrections
Fixed Capacitor Systems
Ideally suited for power factor
correction in applications where
the load is constant or where the
capacitor is switched with the
load, such as the load side of a
motor starter.
Fixed capacitor assemblies can be
designed for application at the
load, branch panel, or service
entrance.
15
16
8
Methods for Power Factor Corrections
Synchronous Condenser
It is a salient pole synchronous
generator without prime mover.
Synchronous condenser
stabilizes power system voltage
by supplying reactive power to
the power system and use for
power factor correction.
It is more economical than
capacitors.
17
18
9
Evaluation of Capacitor Ratings
19
QC P(tan θ1 − tan θ2 )
C= 2
= 2
ωVrms ωVrms
20
10
Applications
21
Drill Problems
1. EE/Oct’90] A single phase inductive load takes 50 kVA at 0.6
power factor lagging. Solve for kVAR of a capacitor required
to improved the power factor to unity.
2. [EE/Apr’84] A plant has a load of 290 kW with an average
power factor of 70%. The owner requires you to correct the
power factor to reduce its consumption. How much capacitor
kVAR is required to increase the power factor to 90%.
3.[EE/Oct’96] A single phase, 60 Hz, 5 hp squirrel cage induction
motor draws a current of 53 A at 117 V. If it has a 78.5%
electrical to mechanical conversion efficiency, what capacitance
should be connected at the terminal of the motor in order to
increase the power factor of the load combination to 92%?
22
11
Drill Problems
4. [EE/Oct’96] A 132 kV line 3-∅ system delivers 70.7 MVA of a
balanced delta load of power factor 70.70 % lagging. Determine
the reactance necessary to attain unity power factor.
5. [EE/Oct’90] A balanced, 500 kVA, 3-∅, 440 V, 60 Hz, inductive
load operates at a power factor of 75%. Determine the total
capacitor kVAR required improving the power factor to 95%.
6. [EE/Mar’98] A single phase induction motor is rated 5 Hp, 75%
power factor and 220 V. What approximate size of capacitor is
necessary to raise the power factor about 95%?
7.[EE/Oct’84] a balanced 3-∅ loads draws 150 A phase current at 7.5
kV phase to neutral, 0.891 power factor lagging. It is desired to
raise the power to 0.96 leading. Solve for the amount of capacitor
kVAR needed to achieve such power factor.
23
Drill Problems
8. [EE/Apr’81] A 3-∅, 3-wire, short transmission line has a resistance
of 3 Ω and a reactance of 8 Ω per wire. At the receiving end, a
balanced 3-∅ load draws a line current of 60 A, at 13,500 V line
to line, 0.90 power factor lagging. Assuming the receiving end
voltage is maintained at 13,500 V, solve the kVAR of the
capacitors needed to raise the power factor at the receiving end to
0.95 leading.
9. [EE/Oct’95] An inductive load consumes 10 kW at 0.75 lagging pf.
A synchronous motor with a pf of 0.90 leading is connected in
parallel with the inductive load. What is minimum required kW
size of the synchronous motor so that the combined load will
have a pf of 0.8 lagging?
24
12
Drill Problems
10. [EE/Apr’92] An industrial plant draws 500 kW at 0.6 power factor
from a 3-∅ system. In order to raise the power factor to 0.866
lagging and to supply needed additional power, a synchronous motor
is added. This motor draws 300 kW, bringing the new total to 800
kW. Neglecting the losses of the synchronous motor, calculate its
exact required kVA rating.
11. An alternator rated 530 kVA, is operating at 0.6 pf lagging. A
synchronous condenser is in parallel to improve the pf to 90%
lagging. Determine the operating power factor of the synchronous
condenser. Assume the alternator is not supposed overloaded.
12. An overexcited synchronous motor is connected across a 150 kVA,
0.70 lagging power factor load. The motor takes 12 kW while
running on no load. Calculate the kVA rating of the motor required
in order to bring the overall pf of the motor-inductive load
combination to unity. 25
Thank You!
13