0% found this document useful (0 votes)
160 views

ELECTRICAL

The document contains schedules of loads for two electrical circuits, PBG1 and PBG5. PBG1 supplies various lighting outlets and has a total power of 7357 Watts. PBG5 supplies several fan coil units and has a total power of 17664 Watts. Both schedules include details of the loads, voltages, currents, wire sizes and pipe sizes. Load computations are also provided to determine the required feeder conductor and main breaker sizes.

Uploaded by

Aggasid Arnel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
160 views

ELECTRICAL

The document contains schedules of loads for two electrical circuits, PBG1 and PBG5. PBG1 supplies various lighting outlets and has a total power of 7357 Watts. PBG5 supplies several fan coil units and has a total power of 17664 Watts. Both schedules include details of the loads, voltages, currents, wire sizes and pipe sizes. Load computations are also provided to determine the required feeder conductor and main breaker sizes.

Uploaded by

Aggasid Arnel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

SCHEDULE 

OF LOADS PBG1 SCHEDULE OF LOADS PBG5
CKT. TOTAL CIRCUIT
LOAD DESCRIPTION QTY VOLT AMPS WIRE SIZE PIPE SIZE CKT. TOTAL CIRCUIT
NO. POWER PROTECTION DESCRIPTION QTY VOLT AMPS WIRE SIZE PIPE SIZE
1 LIGHTING OUTLET 9 45 230 0.20 15 AT, 2P 2 
20mmф PVC NO. POWER PROTECTION
2‐3.5mm , #12 AWG, THHN COPPER WIRE

2 LIGHTING OUTLET (CR) 16 122 230 0.53 15 AT, 2P 2 
2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC 1 FCU ‐ 2HP 1 1564 230 6.80 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC

3 LIGHTING OUTLET (VICINITY) 22 210 230 0.91 15 AT, 2P 2 
2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC 2 FCU ‐ 1.5HP 1 1380 230 6.00 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC

4 LIGHTING OUTLET (VICINITY) 20 100 230 0.43 15 AT, 2P 2 
2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC 3 FCU ‐ 1.5HP 1 1380 230 6.00 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC
2  2 
5 CONVENIENCE OUTLET 6 2160 230 9.39 20 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC 4 FCU ‐ 4HP 1 2852 230 12.40 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC

6 CONVENIENCE OUTLET (CR) 2 720 230 3.13 20 AT, 2P 2‐3.5mm , #12 AWG, THWN COPPER WIRE 20mmф PVC 5 FCU ‐ 5HP 1 3496 230 15.20 30 AT, 3P 2 
3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC

7 MOTOR LOAD  1 3000 230 13.04 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 20mmф PVC 6 FCU ‐5HP 1 3496 230 15.20 30 AT, 3P 2 
25mmф PVC
3‐5.5mm , #10 AWG, THHN COPPER WIRE
8 FACP (2 ZONES) 1 1000 230 4.35 20 AT, 2P 2‐3.5mm2 , #12 AWG, THHN COPPER WIRE 20mmф PVC 2 
7 FCU ‐ 5HP 1 3496 230 15.20 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC
TOTAL POWER 7357 31.99
TOTAL POWER 17664 76.80
LOAD COMPUTATION
LOAD COMPUTATION
        FEEDER CONDUCTOR  =  [TOTAL CURRENT + (25% OF HIGHEST MOTOR CURRENT)] / 1.732 MAIN BREAKER   =  (TOTAL CURRENT + 250% OF HIGHEST MOTOR CURRENT) / 1.732
        FEEDER CONDUCTOR  =  [TOTAL CURRENT + (25% OF HIGHEST MOTOR CURRENT)] / 1.732 MAIN BREAKER   =  (TOTAL CURRENT + 250% OF HIGHEST MOTOR CURRENT) / 1.732
   =   [31.99 + (25% x 13.04)] / 1.732 = 20.35 A                         =   [18.95 + (250%x12.4)] / 1.732  =  29.76 A                                  
2 2 
USE: 1‐60AT, 3P, 10 KAIC MCCB
   =   [76.8 + (25% x 15.2)] / 1.732 = 46.54 A    =   [61.6 + (250% x 15.2)] / 1.732 = 57.51 A
USE: 2‐14mm  + 1‐14mm (neutral), #6 AWG, THW COPPER WIRE in a 25mmф PVC
2 2 
USE: 2‐30mm  + 1‐30mm (neutral), #2 AWG, THW COPPER WIRE in a 32mmф PVC USE: 1‐100AT, 3P, Bolt‐on Type Circuit Breaker
SCHEDULE OF LOADS PBG2
SCHEDULE OF LOADS PBG6
CKT. TOTAL CIRCUIT
DESCRIPTION QTY VOLT AMPS WIRE SIZE PIPE SIZE
NO. POWER PROTECTION CKT. TOTAL CIRCUIT
DESCRIPTION QTY VOLT AMPS WIRE SIZE PIPE SIZE
1 LIGHTING OUTLET 20 735 230 3.20 15 AT, 2P 2 
2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC NO. POWER PROTECTION

2 LIGHTING OUTLET 18 690 230 3.00 15 AT, 2P 2 
20mmф PVC 1 LIGHTING OUTLET 4 160 230 0.70 15 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC
2‐3.5mm , #12 AWG, THHN COPPER WIRE

3 CONVENIENCE OUTLET 9 3240 230 14.09 20 AT, 2P 2 
20mmф PVC 2 LIGHTING OUTLET 16 640 230 2.78 20 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC
2‐3.5mm , #12 AWG, THHN COPPER WIRE

2  3 CONVENIENCE OUTLET 7 2520 230 10.96 20 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC
4 CONVENIENCE OUTLET 9 3240 230 14.09 20 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC

2  4 CONVENIENCE OUTLET 10 3600 230 15.65 20 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC
5 CONVENIENCE OUTLET 8 2880 230 12.52 20 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC

2  5 CONVENIENCE OUTLET 9 3240 230 14.09 20 AT, 2P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 20mmф PVC
6 CONVENIENCE OUTLET 8 2880 230 12.52 20 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC
2  TOTAL POWER 10160 44.17
7 CONVENIENCE OUTLET 8 2880 230 12.52 20 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC
8 CONVENIENCE OUTLET 4 1440 230 6.26 20 AT, 2P 2 
2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC SUB SERVICE REQUIREMENT

TOTAL POWER 17985 78.20 CONDUCTOR AND CONDUIT SIZE SIZE OF THE MAIN CIRCUIT BREAKER


TOTAL CURRENT = 44.17A TOTAL CURRENT = 44.17A
SUB SERVICE REQUIREMENT

USE: 2‐14mm , #6 AWG, THW COPPER WIRE in a 25mmф PVC USE: 1‐60AT, 2P, 10 KAIC, Bolt‐on Type Circuit Breaker
CONDUCTOR AND CONDUIT SIZE SIZE OF THE MAIN CIRCUIT BREAKER
TOTAL CURRENT = 78.2A TOTAL CURRENT = 78.2A SCHEDULE OF LOADS PBG7

USE: 2‐30mm , #2 AWG, THW COPPER WIRE in a 32mmф PVC USE: 1‐100AT, 2P, 10 KAIC, Bolt‐on Type Circuit Breaker CKT. TOTAL CIRCUIT
LOAD DESCRIPTION QTY VOLT AMPS WIRE SIZE PIPE SIZE
NO. POWER PROTECTION
SCHEDULE OF LOADS PBG3 1 LIGHTING OUTLET 14 126 230 0.55 15 AT, 2P 2 
2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC

CKT. TOTAL CIRCUIT 2 LIGHTING OUTLET 23 241 230 1.05 15 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC
DESCRIPTION QTY VOLT AMPS WIRE SIZE PIPE SIZE
NO. POWER PROTECTION 3 LIGHTING OUTLET 12 64 230 0.28 20 AT, 2P 2 
20mmф PVC

2‐3.5mm , #12 AWG, THHN COPPER WIRE
1 FCU ‐ 5HP 1 3496 230 15.20 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC 2 

4 CONVENIENCE OUTLET 4 1440 230 6.26 20 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC
2 FCU ‐ 5HP 1 3496 230 15.20 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC 2 
2  4 CONVENIENCE OUTLET 7 2520 230 10.96 20 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC
3 FCU ‐ 5HP 1 3496 230 15.20 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC
4 FCU ‐ 5HP 1 3496 230 15.20 30 AT, 3P 2 
3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC TOTAL POWER 4391 19.09

5 FCU ‐ 4HP 1 2852 230 12.40 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC SUB SERVICE REQUIREMENT
TOTAL POWER 16836 73.20 CONDUCTOR AND CONDUIT SIZE SIZE OF THE MAIN CIRCUIT BREAKER
LOAD COMPUTATION TOTAL CURRENT = 19.09A TOTAL CURRENT = 19.09A

        FEEDER CONDUCTOR  =  [TOTAL CURRENT + (25% OF HIGHEST MOTOR CURRENT)] / 1.732 MAIN BREAKER   =  (TOTAL CURRENT + 250% OF HIGHEST MOTOR CURRENT) / 1.732 USE: 2‐14mm , #6 AWG, THW COPPER WIRE in a 25mmф PVC USE: 1‐60AT, 2P, 10 KAIC, Bolt‐on Type Circuit Breaker
   =   [73.2 + (25% x 15.2)] / 1.732 = 44.45 A    =   [58 + (250% x 15.2)] / 1.732 = 55.42 A
2 2 
SCHEDULE OF LOADS MPBG
USE: 2‐30mm  + 1‐30mm (neutral), #2 AWG, THW COPPER WIRE in a 32mmф PVC USE: 1‐100AT, 3P, Bolt‐on Type Circuit Breaker
CKT. TOTAL CIRCUIT
LOAD DESCRIPTION QTY VOLT AMPS WIRE SIZE PIPE SIZE
NO. POWER PROTECTION
SCHEDULE OF LOADS PBG4 1 PBG1 7357 230 31.99 60 AT, 3P 2‐14mm2 + 1‐14mm2 (neutral), #6 AWG, THW COPPER WIRE 25mmф PVC
CKT. TOTAL CIRCUIT 2 PBG2 17985 230 78.20 75 AT, 2P 2‐22mm2 , #2 AWG, THW COPPER WIRE  25mmф PVC
DESCRIPTION QTY VOLT AMPS WIRE SIZE PIPE SIZE
NO. POWER PROTECTION 3 PBG3 16836 230 73.20 100 AT, 3P 2‐22mm2 + 1‐22mm2 (neutral), #4 AWG, THW COPPER WIRE 32mmф PVC

1 LIGHTING OUTLET 20 180 230 0.78 15 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC
4 PBG4 6062 230 26.36 60 AT, 2P  2‐14mm2 , #6 AWG, THW COPPER WIRE  25mmф PVC

2 LIGHTING OUTLET (CR) 16 122 230 0.53 15 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC

5 PBG5 17664 230 76.80 100 AT, 3P 2‐22mm2 + 1‐22mm2 (neutral), #4 AWG, THW COPPER WIRE 32mmф PVC
3 CONVENIENCE OUTLET 8 2880 230 12.52 20 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC

6 PBG6 10160 230 44.17 60 AT, 2P  2‐14mm2 , #6 AWG, THW COPPER WIRE  25mmф PVC
4 CONVENIENCE OUTLET 6 2160 230 9.39 20 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC
2  7 PBG7 4391 230 19.09 60 AT, 2P  2‐14mm2 , #6 AWG, THW COPPER WIRE  25mmф PVC
5 CONVENIENCE OUTLET (CR) 2 720 230 3.13 20 AT, 2P 2‐3.5mm , #12 AWG, THWN COPPER WIRE 20mmф PVC
TOTAL POWER 80455 201.97
TOTAL POWER 6062 26.36
LOAD COMPUTATION
SUB SERVICE REQUIREMENT
CONDUCTOR AND CONDUIT SIZE SIZE OF THE MAIN CIRCUIT BREAKER         FEEDER CONDUCTOR  =  [TOTAL CURRENT + (25% OF HIGHEST MOTOR CURRENT)]  MAIN BREAKER   =  (TOTAL CURRENT + 250% OF HIGHEST MOTOR CURRENT)
TOTAL CURRENT = 26.36A TOTAL CURRENT = 26.36A    =   [201.97 + (25% x 15.2)]= 205.77 A                         =   [186.77+ (250%x15.2)]  =  224.77 A                                  
2  2 2 
USE: 2‐14mm , #6 AWG, THW COPPER WIRE in a 25mmф PVC USE: 1‐60AT, 2P, 10 KAIC, Bolt‐on Type Circuit Breaker USE: 2‐100mm  + 1‐100mm (neutral), 4/0 AWG, THW COPPER WIRE in a 50mmф PVC USE: 1‐225AT, 3P, Bolt‐on Type MCCB
SCHEDULE OF LOADS PBS1 SCHEDULE OF LOADS PBS5
CKT. TOTAL CIRCUIT
LOAD DESCRIPTION QTY VOLT AMPS WIRE SIZE PIPE SIZE CKT. TOTAL CIRCUIT
NO. POWER PROTECTION LOAD DESCRIPTION QTY VOLT AMPS WIRE SIZE PIPE SIZE

NO. POWER PROTECTION
1 LIGHTING OUTLET 18 130 230 0.57 15 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC 1 LIGHTING OUTLET 15 95 230 0.41 15 AT, 2P 2  2 
20mmф PVC

2‐3.5mm , #12 AWG, THHN COPPER WIRE
2 LIGHTING OUTLET 10 122 230 0.53 15 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC LIGHTING OUTLET 21 230 0.46 2 
20mmф PVC
2 105 15 AT, 2P 2‐3.5mm2 , #12 AWG, THHN COPPER WIRE

3 LIGHTING OUTLET 8 290 230 1.26 15 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC 3 LIGHTING OUTLET 15 120 230 0.52 15 AT, 2P 2 
2  20mmф PVC
3 LIGHTING OUTLET 15 120 230 0.52 15 AT, 2P 2‐3.5mm
2‐3.5mm , #12 AWG, THHN COPPER WIRE
, #12 AWG, THHN COPPER WIRE 20mmф PVC

4 CONVENIENCE OUTLET 8 2880 230 12.52 20 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC 5 LIGHTING OUTLET 14 70 230 0.30 15 AT, 2P 2 
2  20mmф PVC
5 LIGHTING OUTLET 14 70 230 0.30 15 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE
2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC

5 CONVENIENCE OUTLET 8 2880 230 12.52 20 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC 6 CONVENIENCE OUTLET 7 2520 230 10.96 20 AT, 2P 2 
20mmф PVC
6 CONVENIENCE OUTLET 7 2520 230 10.96 20 AT, 2P 2‐3.5mm
2‐3.5mm , #12 AWG, THHN COPPER WIRE

, #12 AWG, THHN COPPER WIRE 20mmф PVC

6 RANGE 1 3000 230 13.04 30 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC TOTAL POWER 2910 12.65
TOTAL POWER 2910 12.65
TOTAL POWER 9302 40.44
SUB SERVICE REQUIREMENT
SUB SERVICE REQUIREMENT
SUB SERVICE REQUIREMENT
CONDUCTOR AND CONDUIT SIZE
CONDUCTOR AND CONDUIT SIZE SIZE OF THE MAIN CIRCUIT BREAKER
SIZE OF THE MAIN CIRCUIT BREAKER
CONDUCTOR AND CONDUIT SIZE SIZE OF THE MAIN CIRCUIT BREAKER TOTAL CURRENT = 12.65A TOTAL CURRENT = 12.65A
TOTAL CURRENT = 12.65A TOTAL CURRENT = 12.65A

USE: 2‐14mm USE: 1‐60AT, 2P, 10 KAIC, Bolt‐on Type Circuit Breaker
TOTAL CURRENT = 40.44A TOTAL CURRENT = 40.44A USE: 2‐14mm , #6 AWG, THW COPPER WIRE in a 25mmф PVC

, #6 AWG, THW COPPER WIRE in a 25mmф PVC USE: 1‐60AT, 2P, 10 KAIC, Bolt‐on Type Circuit Breaker

USE: 2‐14mm , #6 AWG, THW COPPER WIRE in a 25mmф PVC USE: 1‐60AT, 2P, 10 KAIC, Bolt‐on Type Circuit Breaker

SCHEDULE OF LOADS PBS2 SCHEDULE OF LOADS PBS6
CKT. TOTAL CIRCUIT
CKT. TOTAL CIRCUIT LOAD DESCRIPTION QTY VOLT AMPS WIRE SIZE PIPE SIZE
LOAD DESCRIPTION QTY VOLT AMPS WIRE SIZE PIPE SIZE NO. POWER PROTECTION
NO. POWER PROTECTION 2 

1 FCU ‐ 1.5HP 1 1380 230 6.00 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC
1 FCU ‐ 4HP 1 2852 230 12.40 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC 2 

2 FCU ‐ 1.5HP 1 1380 230 6.00 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC
2 FCU ‐ 4HP 1 2852 230 12.40 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC 2 
3 FCU ‐ 1.5HP 1 1380 230 6.00 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC

3 FCU ‐ 4HP 1 2852 230 12.40 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC 2 
4 FCU ‐ 4HP 1 2852 230 12.40 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC

4 FCU ‐ 2HP 1 1564 230 6.80 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC 2 
5 FCU ‐ 4HP 1 2852 230 12.40 30 AT, 3P 3‐5.5mm , #10 AWG, THHN COPPER WIRE 25mmф PVC
TOTAL POWER 10120 44.00 TOTAL POWER 9844 42.80
LOAD COMPUTATION LOAD COMPUTATION
        FEEDER CONDUCTOR  =  [TOTAL CURRENT + (25% OF HIGHEST MOTOR CURRENT)]  MAIN BREAKER   =  (LARGEST ITD BREAKER + SUM OF OTHER CURRENT LOADS)         FEEDER CONDUCTOR  =  [TOTAL CURRENT + (25% OF HIGHEST MOTOR CURRENT)]  MAIN BREAKER   =  (LARGEST ITD BREAKER + SUM OF OTHER CURRENT LOADS)
   =   [44 + (25% x 12.4)] = 47.1 A    =   [30+12.4+12.4+6.8] =  61.6A    =   [42.8 + (25% x 12.4)] = 45.9 A    =   [30+12.4+12.4+6+6] =  60.4A
2 2 
2 2  USE: 2‐22mm  + 1‐22mm (neutral), #4 AWG, THW COPPER WIRE in a 32mmф PVC USE: 1‐100AT, 3P, Bolt‐on Type Circuit Breaker
USE: 2‐22mm  + 1‐22mm (neutral), #4 AWG, THW COPPER WIRE in a 32mmф PVC USE: 1‐100AT, 3P, Bolt‐on Type Circuit Breaker

SCHEDULE OF LOADS PBS3 SCHEDULE OF LOADS MPBS

CKT. TOTAL CIRCUIT CKT. TOTAL CIRCUIT


LOAD DESCRIPTION QTY VOLT AMPS WIRE SIZE PIPE SIZE LOAD DESCRIPTION QTY VOLT AMPS WIRE SIZE PIPE SIZE
NO. POWER PROTECTION
NO. POWER PROTECTION

1 PBS1 1 9302 230 40.44 60 AT, 2P 2‐14mm2 , #6 AWG, THW COPPER WIRE 25mmф PVC
1 LIGHTING OUTLET 11 425 230 1.85 15 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC
2 PBS2 1 10120 230 44.00 100 AT, 3P 2‐22mm2 + 1‐22mm2 (neutral), #4 AWG, THW COPPER WIRE 32mmф PVC

2 LIGHTING OUTLET 9 220 230 0.96 15 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC 3 PBS3 1 5837 230 25.38 60 AT, 2P 2‐14mm2 , #6 AWG, THW COPPER WIRE 25mmф PVC

3 LIGHTING OUTLET 14 152 230 0.66 15 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC 4 PBS4 1 5568 230 24.21 60 AT, 2P 2‐14mm2 , #6 AWG, THW COPPER WIRE 25mmф PVC

4 CONVENIENCE OUTLET 8 2880 230 12.52 20 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC 5 PBS5 1 2910 230 12.65 60 AT, 2P 2‐14mm2 , #6 AWG, THW COPPER WIRE 25mmф PVC
2  6 PBS6 1 9844 230 42.80 100 AT, 3P 2‐22mm2 + 1‐22mm2 (neutral), #4 AWG, THW COPPER WIRE 32mmф PVC
5 CONVENIENCE OUTLET 6 2160 230 9.39 20 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC
TOTAL POWER 5837 25.38  
TOTAL POWER 43581 109.40 THREE PHASE ( TOTAL CURRENT OVER 1.732)
SUB SERVICE REQUIREMENT
LOAD COMPUTATION
CONDUCTOR AND CONDUIT SIZE SIZE OF THE MAIN CIRCUIT BREAKER
        FEEDER CONDUCTOR  =  [TOTAL CURRENT + (25% OF HIGHEST MOTOR CURRENT)] MAIN BREAKER   =  (TOTAL CURRENT + 250% OF HIGHEST MOTOR CURRENT)
TOTAL CURRENT = 25.38A TOTAL CURRENT = 25.38A

USE: 1‐60AT, 2P, 10 KAIC, Bolt‐on Type Circuit Breaker    =   [109.4 + (25% x 12.4)]= 112.5 A                            =   [97 + (250%x12.4)] = 128 A                                  
USE: 2‐14mm , #6 AWG, THW COPPER WIRE in a 25mmф PVC 2  2  
USE: 2‐38mm + 1‐38mm (neutral) , #1 AWG, THW Copper Wire in a 40mmф PVC USE: 1‐125AT, 3P MCCB

SCHEDULE OF LOADS PBS4

CKT. TOTAL CIRCUIT SCHEDULE OF LOADS FIRE PROTECTION PANEL


LOAD DESCRIPTION QTY VOLT AMPS WIRE SIZE PIPE SIZE
NO. POWER PROTECTION
1 LIGHTING OUTLET 25 113 230 0.49 15 AT, 2P 2 
20mmф PVC CKT. RATED RATED FULL  CIRCUIT PROTECTION
2‐3.5mm , #12 AWG, THHN COPPER WIRE LOAD DESCRIPTION QTY VOLT WIRE SIZE PIPE SIZE
2  NO. H.POWER LOAD CURRENT OVERCURRENT
2 LIGHTING OUTLET 9 55 230 0.24 15 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC
2  1 FIRE PUMP 1 25 230 68.00 200 AT, 3P 2‐22mm2 + 1‐22mm2 (neutral), #4 AWG, THW COPPER WIRE 32mmф IMC
3 CONVENIENCE OUTLET 11 3960 230 17.22 20 AT, 2P 2‐3.5mm , #12 AWG, THHN COPPER WIRE 20mmф PVC
4 CONVENIENCE OUTLET 4 1440 230 6.26 20 AT, 2P 2 
20mmф PVC
2 JOCKEY PUMP 1 3 230 9.60 60 AT, 3P 2‐8.0mm2 + 1‐8.0mm2(neutral) , #8 AWG, THW Copper Wire 25mmф IMC
2‐3.5mm , #12 AWG, THHN COPPER WIRE
TOTAL POWER 5568 24.21
SUB SERVICE REQUIREMENT TOTAL POWER in WATTS 20888 77.60
LOAD COMPUTATION
CONDUCTOR AND CONDUIT SIZE SIZE OF THE MAIN CIRCUIT BREAKER         FEEDER CONDUCTOR  =  [TOTAL CURRENT + (25% OF HIGHEST MOTOR CURRENT)] MAIN BREAKER   =  (LARGEST ITD BREAKER + SUM OF OTHER CURRENT LOADS)
TOTAL CURRENT = 24.21A TOTAL CURRENT = 24.21A    =   [77.6 + (25% x 68)] = 94.6 A    =   [200+9.6] =  209.6A
2  USE: 2‐100mm2 + 1‐100mm2 (neutral), 4/0 AWG, THW COPPER WIRE in a 50mmф RSC USE: 1‐225AT, 3P, Bolt‐on Type Circuit Breaker
USE: 2‐14mm , #6 AWG, THW COPPER WIRE in a 25mmф PVC USE: 1‐60AT, 2P, 10 KAIC, Bolt‐on Type Circuit Breaker
SCHEDULE OF LOADS MDP

CKT. TOTAL CIRCUIT


LOAD DESCRIPTION QTY VOLT AMPS WIRE SIZE PIPE SIZE
NO. POWER PROTECTION
1 MPBG 80455 230 201.97 225 AT, 3P 2‐100mm2 + 1‐100mm2 (neutral), 4/0 AWG, THW COPPER WIRE 50mmф PVC
2 MPBS 43581 230 109.40 125 AT, 3P 2‐38mm2 + 1‐38mm2(neutral) , #1 AWG, THW Copper Wire 40mmф PVC
3 ELEV 6440 230 28.00 100 AT, 3P 2‐30mm2 + 1‐30mm2(neutral) , #2 AWG, THW Copper Wire 32mmф PVC

TOTAL POWER 130476 339.37


LOAD COMPUTATION
        FEEDER CONDUCTOR  =  [TOTAL CURRENT + (25% OF HIGHEST MOTOR CURRENT)] x DF MAIN BREAKER   =  [TOTAL CURRENT + 250% OF HIGHEST MOTOR CURRENT)] x DF
   =   [339.37 + (25% x 28)] *  0.8 = 277.1 A                             =   [311.37+ (250%x28)] * 0.8  =  305.1 A                                
2   
USE: 2bdls 50mm (1/0MCM) THW per phase 6 Conductor Sets Total in a 40mmф RSC Pipe USE: 1‐300AT, 3P, MCCB

You might also like