Chapter 1 Liquid Overfeed Systems
Chapter 1 Liquid Overfeed Systems
CHAPTER 1
TERMINOLOGY
Low-pressure receiver. Sometimes referred to as an accumulator, this vessel acts as the separator for the mixture of vapor and
liquid returning from the evaporators. A constant refrigerant level is usually maintained by conventional control devices.
Pumping unit. One or more mechanical pumps or gas-operated liquid circulators are arranged to pump overfeed liquid to the
evaporators. The pumping unit is located below the low-pressure receiver.
Wet returns. These are connections between the evaporator outlets and low-pressure receiver through which the mixture of vapor
and overfeed liquid is drawn.
Liquid feeds. These are connections between the pumping unit outlet and evaporator inlets.
Flow control regulators. These devices regulate overfeed flow into the evaporators. They may be needle valves, fixed orifices,
calibrated manual regulating valves, or automatic valves designed to provide a fixed liquid rate.
The evaporator surface is used efficiently through good refrigerant distribution and completely wetted internal tube surfaces.
The compressors are protected. Liquid slugs resulting from fluctuating loads or malfunctioning controls are separated from
suction gas in the low-pressure receiver.
Low-suction superheats are achieved where suction lines between the low-pressure receiver and the compressors are short.
This minimizes discharge temperature, preventing lubrication breakdown and minimizing condenser fouling.
With simple controls, evaporators can be hot-gas defrosted with little disturbance to the system.
Refrigerant feed to evaporators is unaffected by fluctuating ambient and condensing conditions. Flow control regulators do not
need to be adjusted after initial setting because overfeed rates are not generally critical.
Flash gas resulting from refrigerant throttling losses is removed at the low-pressure receiver before entering the evaporators.
This gas is drawn directly to the compressors and eliminated as a factor in system low-side design. It does not contribute to
increased pressure drops in the evaporators or overfeed lines.
Refrigerant level controls, level indicators, refrigerant pumps, and oil drains are generally located in equipment rooms, which
are under operator surveillance or computer monitoring.
Because of ideal entering suction gas conditions, compressors last longer. There is less maintenance and fewer breakdowns.
The oil circulation rate to the evaporators is reduced as a result of the low compressor discharge superheat and separation at
the low-pressure receiver (Scotland 1963).
Automatic operation is convenient.
In some cases, refrigerant charges are greater than those used in other systems.
Higher refrigerant flow rates to and from evaporators cause liquid feed and wet return lines to be larger in diameter than
high-pressure liquid and suction lines for other systems.
Piping insulation, which is costly, is generally required on all feed and return lines to prevent condensation, frosting, or heat
gain.
Installed cost may be greater, particularly for small systems or those with fewer than three evaporators.
Operation of the pumping unit requires added expenses that are offset by the increased efficiency of the overall system.
Pumping units may require maintenance.
Pumps sometimes have cavitation problems caused by low available net positive suction head.
Generally, the more evaporators used, the more favorable the initial costs for liquid overfeed compared to a gravity recirculated or
flooded system (Scotland 1970). Liquid overfeed systems compare favorably with thermostatic valve feed systems for the same reason.
For small systems, the initial cost for liquid overfeed may be higher than for direct expansion.
Ammonia Systems. Easy operation and lower maintenance are attractive features for even small ammonia systems. However, for
ammonia systems operating below 0°F evaporating temperature, some manufacturers do not supply direct-expansion evaporators
because of unsatisfactory refrigerant distribution and control problems.
https://handbook.ashrae.org/Handbooks/R06/IP/r06_ch01/r06_ch01_ip.aspx 09/07/2010
CHAPTER 1. LIQUID OVERFEED SYSTEMS Page 2 of 14
Mechanical Pump
Figure 1 shows a simplified pumped overfeed system in which a constant liquid level is maintained in a low-pressure receiver. A
mechanical pump circulates liquid through the evaporator(s). The two-phase return mixture is separated in the low-pressure receiver.
Vapor is directed to the compressor(s). Makeup refrigerant enters the low-pressure receiver by means of a refrigerant metering device.
Figure 2 shows a horizontal low-pressure receiver with a minimum pump pressure, two service valves in place, and a strainer on the
suction side of the pump. Valves from the low-pressure receiver to the pump should be selected for minimal pressure drop. The
strainer protects hermetic pumps when oil is miscible with the refrigerant. It should have a free area twice the transverse cross-
sectional area of the line in which it is installed. With ammonia, consider using a suction strainer. Open-drive pumps do not require
strainers. If no strainer is used, a dirt leg should be used to reduce the risk of solids getting into the pump.
Generally, minimum pump pressure should be at least double the net positive suction pressure to avoid cavitation. Liquid velocity to
the pump should not exceed 3 fps. Net positive suction head and flow requirements vary with pump type and design; consult the
pump manufacturer for specific requirements. The pump should be evaluated over the full range of operation at low and high flow.
Centrifugal pumps have a flat curve and have difficulty with systems in which discharge pressure fluctuates.
https://handbook.ashrae.org/Handbooks/R06/IP/r06_ch01/r06_ch01_ip.aspx 09/07/2010
CHAPTER 1. LIQUID OVERFEED SYSTEMS Page 3 of 14
Gas Pump
Figure 3 shows a basic gas-pumped liquid overfeed system, with pumping power supplied by gas at condenser pressure. In this
system, a level control maintains the liquid level in the low-pressure receiver. There are two pumper drums; one is filled by the low-
pressure receiver, and the other is drained as hot gas pushes liquid from the pumper drum to the evaporator. Pumper drum B drains
when hot gas enters the drum through valve B. To function properly, the pumper drums must be correctly vented so they can fill
during the fill cycle.
https://handbook.ashrae.org/Handbooks/R06/IP/r06_ch01/r06_ch01_ip.aspx 09/07/2010
CHAPTER 1. LIQUID OVERFEED SYSTEMS Page 4 of 14
Another common arrangement is shown in Figure 4. In this system, high-pressure liquid is flashed into a controlled-pressure receiver
that maintains constant liquid pressure at the evaporator inlets, resulting in continuous liquid feed at constant pressure. Flash gas is
drawn into the low-pressure receiver through a receiver pressure regulator. Excess liquid drains into a liquid dump trap from the low-
pressure receiver. Check valves and a three-way equalizing valve transfer liquid into the controlled-pressure receiver during the dump
cycle. Refined versions of this arrangement are used for multistage systems.
REFRIGERANT DISTRIBUTION
To prevent underfeeding and excessive overfeeding of refrigerants, metering devices regulate the liquid feed to each evaporator
and/or evaporator circuit. An automatic regulating device continuously controls refrigerant feed to the design value. Other common
devices are hand expansion valves, calibrated regulating valves, orifices, and distributors.
It is time-consuming to adjust hand expansion valves to achieve ideal flow conditions. However, they have been used with some
success in many installations before more sophisticated controls were available. One factor to consider is that standard hand expansion
valves are designed to regulate flows caused by the relatively high pressure differences between condensing and evaporating pressure.
In overfeed systems, large differences do not exist, so valves with larger orifices may be needed to cope with the combination of
increased refrigerant quantity and relatively small pressure differences. Caution is necessary when using larger orifices because
controllability decreases as orifice size increases.
Calibrated, manually operated regulating valves reduce some of the uncertainties involved in using conventional hand expansion
valves. To be effective, the valves should be adjusted to the manufacturer’s recommendations. Because refrigerant in the liquid feed
lines is above saturation pressure, the lines should not contain flash gas. However, liquid flashing can occur if excessive heat gains by
the refrigerant and/or high pressure drops build up in feed lines.
Orifices should be carefully designed and selected; once installed, they cannot be adjusted. They are generally used only for top- and
horizontal-feed multicircuit evaporators. Foreign matter and congealed oil globules can restrict flow; a minimum orifice of 0.1 in. is
recommended. With ammonia, the circulation rate may have to be increased beyond that needed for the minimum orifice size because
of the small liquid volume normally circulated. Pumps and feed and return lines larger than minimum may be needed. This does not
apply to halocarbons because of the greater liquid volume circulated as a result of fluid characteristics.
Conventional multiple-outlet distributors with capillary tubes of the type usually paired with thermostatic expansion valves have been
used successfully in liquid overfeed systems. Capillary tubes may be installed downstream of a distributor with oversized orifices to
achieve the required pressure reduction and efficient distribution.
Existing gravity-flooded evaporators with accumulators can be connected to liquid overfeed systems. Changes may be needed only for
the feed to the accumulator, with suction lines from the accumulator connected to the system wet return lines. An acceptable
arrangement is shown in Figure 5. Generally, gravity-flooded evaporators have different circuiting arrangements from overfeed
evaporators. In many cases, the circulating rates developed by thermosiphon action are greater than those used in conventional
overfeed systems.
Figure 5. Liquid Overfeed System Connected on Common System with Gravity-Flooded Evaporators
Example 1
Find the orifice diameter of an ammonia overfeed system with a refrigeration load per circuit of 1.27 tons and a circulating rate of 7.
Evaporating temperature is –30°F, pressure drop across the orifice is 8 psi, and the coefficient of discharge for the orifice is 0.61. The
circulation per circuit is 0.528 gpm.
Solution: Orifice diameter may be calculated as follows:
(1)
where
d = orifice diameter, in.
a = units conversion, 29.81
https://handbook.ashrae.org/Handbooks/R06/IP/r06_ch01/r06_ch01_ip.aspx 09/07/2010
CHAPTER 1. LIQUID OVERFEED SYSTEMS Page 5 of 14
Note: As noted in the text, use a 0.1 in. diameter orifice to avoid clogging.
OIL IN SYSTEM
Despite reasonably efficient compressor discharge oil separators, oil finds its way into the system low-pressure sides. In ammonia
overfeed systems, most of this oil can be drained from low-pressure receivers with suitable oil drainage facilities. In low-temperature
systems, a separate valved and pressure-protected, noninsulated oil drain pot can be placed in a warm space at the accumulator. The
oil/ammonia mixture flows into the pot, and the refrigerant evaporates. This arrangement is shown in Figure 6. At subatmospheric
pressures, high-pressure vapor must be piped into the oil pot to force oil out. Because of oil’s low solubility in liquid ammonia, thick oil
globules circulate with the liquid and can restrict flow through strainers, orifices, and regulators. To maintain high efficiency, oil should
be removed from the system by regular draining.
Except at low temperatures, halocarbons are miscible with oil. Therefore, positive oil return to the compressor must be ensured.
There are many methods, including oil stills using both electric heat and heat exchange from high-pressure liquid or vapor. Some
arrangements are discussed in Chapter 2. At low temperatures, oil skimmers must be used because oil migrates to the top of the low-
pressure receiver.
Build-up of excessive oil in evaporators must not be allowed because it rapidly decreases efficiency. This is particularly critical in
evaporators with high heat transfer rates associated with low volumes, such as flake ice makers, ice cream freezers, and scraped-
surface heat exchangers. Because refrigerant flow rate is high, excessive oil can accumulate and rapidly reduce efficiency.
CIRCULATING RATE
In a liquid overfeed system, the circulating number or rate is the mass ratio of liquid pumped to amount of vaporized liquid. The
amount of liquid vaporized is based on the latent heat for the refrigerant at the evaporator temperature. The overfeed rate is the
ratio of liquid to vapor returning to the low-pressure receiver. When vapor leaves an evaporator at saturated vapor conditions with no
excess liquid, the circulating rate is 1 and the overfeed rate is 0. With a circulating rate of 4, the overfeed rate at full load is 3; at no
load, it is 4. Most systems are designed for steady flow. With few exceptions, load conditions may vary, causing fluctuating
temperatures outside and within the evaporator. Evaporator capacities vary considerably; with constant refrigerant flow to the
evaporator, the overfeed rate fluctuates.
Table 1. Recommended Minimum Circulating Rate
https://handbook.ashrae.org/Handbooks/R06/IP/r06_ch01/r06_ch01_ip.aspx 09/07/2010
CHAPTER 1. LIQUID OVERFEED SYSTEMS Page 6 of 14
Figure 7. Charts for Determining Rate of Refrigerant Feed (No Flash Gas)
For each evaporator, there is an ideal circulating rate for every loading condition that gives the minimum temperature difference and
best evaporator efficiency (Lorentzen 1968; Lorentzen and Gronnerud 1967). With few exceptions, it is impossible to predict ideal
circulating rates or to design a plant for automatic adjustment of the rates to suit fluctuating loads. The optimum rate can vary with
heat load, pipe diameter, circuit length, and number of parallel circuits to achieve the best performance. High circulating rates can
cause excessively high pressure drops through evaporators and wet return lines. Return line sizing (see the section on Line Sizing) can
affect the ideal rates. Many evaporator manufacturers specify recommended circulating rates for their equipment. Rates in Table 1
agree with these recommendations.
Because of distribution considerations, higher circulating rates are common with top-feed evaporators. In multicircuit systems,
refrigerant distribution must be adjusted to provide the best possible results. Incorrect distribution can cause excessive overfeed or
starvation in some circuits. Manual or automatic regulating valves can control flow for the optimum or design value.
Halocarbon densities are about twice that of ammonia. If halocarbons R-22, R-134a, and R-502 are circulated at the same rate as
ammonia, they require 6 to 8.3 times more energy for pumping to the same height than the less-dense ammonia. Because pumping
https://handbook.ashrae.org/Handbooks/R06/IP/r06_ch01/r06_ch01_ip.aspx 09/07/2010
CHAPTER 1. LIQUID OVERFEED SYSTEMS Page 7 of 14
energy must be added to the system load, halocarbon circulating rates are usually lower than those for ammonia. Ammonia has a
relatively high latent heat of vaporization, so for equal heat removal, much less ammonia mass must be circulated compared to
halocarbons.
Although halocarbons circulate at lower rates than ammonia, the wetting process in the evaporators is still efficient because of the
liquid and vapor volume ratios. For example, at –40°F evaporating temperature, with constant flow conditions in the wet return
connections, similar ratios of liquid and vapor are experienced with a circulating rate of 4 for ammonia and 2.5 for R-22, R-502, and R-
134a. With halocarbons, some additional wetting is also experienced because of the solubility of the oil in these refrigerants.
When bottom feed is used for multicircuit coils, a minimum feed rate per circuit is not necessary because orifices or other distribution
devices are not required. The circulating rate for top-feed and horizontal feed coils may be determined by the minimum rates from the
orifices or other distributors in use.
Figure 7 provides a method for determining the liquid refrigerant flow (Niederer 1964). The charts indicate the amount of refrigerant
vaporized in a 1 ton system with circulated operation having no flash gas in the liquid feed line. The value obtained from the chart
may be multiplied by the desired circulating rate and total refrigeration to determine total flow.
Pressure drop through flow control regulators is usually 10 to 50% of the available feed pressure. Pressure at the outlet of the flow
regulators must be higher than the vapor pressure at the low-pressure receiver by an amount equal to the total pressure drop of the
two-phase mixture through the evaporator, any evaporator pressure regulator, and wet return lines. Pressure loss could be 5 psi in a
typical system. When using recommended liquid feed sizing practices, assuming a single-story building, the frictional pressure drop from
pump discharge to evaporators is about 10 psi. Therefore, a pump for 20 to 25 psi should be satisfactory in this case, depending on
the lengths and sizes of feed lines, quantity and types of fittings, and vertical lift involved.
Types of Pumps
Mechanical pumps, gas pressure pumping systems, and injector systems are available for liquid overfeed systems.
Types of mechanical pump drives include open, semihermetic, magnetic clutch, and hermetic. Rotor arrangements include positive
rotary, centrifugal, and turbine vane. Positive rotary and gear pumps are generally operated at slow speeds up to 900 rpm. Whatever
type of pump is used, take care to prevent flashing at the pump suction and/or within the pump itself.
Centrifugal pumps are typically used for larger volumes, whereas semihermetic pumps are best suited for halocarbons at or below
atmospheric refrigerant saturated pressure. Regenerative turbines are used with relatively high pressure and large swings in discharge
pressure.
Open pumps are fitted with a wide variety of packing or seals. For continuous duty, a mechanical seal with an oil reservoir or a liquid
refrigerant supply to cool, wash, and lubricate the seals is commonly used. Experience with the particular application or the
recommendations of an experienced pump supplier are the best guide for selecting the packing or seal. The motor and pump can be
magnetically coupled instead of shaft coupled to eliminate shaft seals. A small immersion electric heater in the oil reservoir can be used
with low-temperature systems to ensure that the oil remains fluid. Motors should have a service factor that compensates for drag on
the pump if the oil is cold or stiff.
Considerations should include ambient temperatures, heat leakage, fluctuating system pressures from compressor cycling, internal
bypass of liquid to pump suction, friction heat, motor heat conduction, dynamic conditions, cycling of automatic evaporator liquid and
suction stop valves, action of regulators, gas entrance with liquid, and loss of subcooling by pressure drop. Another factor to consider is
the time lag caused by the heat capacity of pump suction, cavitation, and net positive suction head factors (Lorentzen 1963).
The motor and stator of hermetic pumps are separated from the refrigerant by a thin nonmagnetic membrane. The metal membrane
should be strong enough to withstand system design pressures. Normally, the motors are cooled and the bearings lubricated by liquid
refrigerant bypassed from the pump discharge. It is good practice to use two pumps, one operating and one standby.
Because of the sensitive suction conditions of mechanical pumps on overfeed systems, the manufacturer’s application and installation
specifications must be followed closely. Suction connections should be as short as possible, without restrictions, valves, or elbows.
Angle or full-flow ball valves should be used. Using valves with horizontal valve spindles eliminates possible traps. Gas binding is more
likely with high evaporating pressures.
Installing discharge check valves prevents backflow. Relief valves should be used, particularly for positive-displacement pumps.
Strainers are not usually installed in ammonia pump suction lines because they plug with oil. Strainers, although a poor substitute for a
clean installation, protect halocarbon pumps from damage by dirt or pipe scale.
Pump suction connections to liquid legs (vertical drop legs from low-pressure receivers) should be made above the bottom of the legs
to allow collection space for solids and sludge. Consider using vortex eliminators, particularly when submersion of the suction inlet is
insufficient to prevent the intake of gas bubbles. Lorentzen (1963, 1965) gives more complete information.
Sizing the pump suction line is important. The general velocity should be about 3 fps. Small lines cause restrictions; oversized lines
can cause bubble formation during evaporator temperature decrease because of the heat capacity of the liquid and piping. Oversized
lines also increase heat gain from ambient spaces. Oil heaters for the seal lubrication system keep the oil fluid, particularly during
subzero operation . Thermally insulating all cold surfaces of pumps, lines, and receivers increases efficiency.
CONTROLS
The liquid level in the low-pressure receiver can be controlled by conventional devices such as low-pressure float valves, combinations
of float switch and solenoid valve with manual regulator, thermostatic level controls, electronic level sensors, or other proven automatic
devices. High-level float switches are useful in stopping compressors and/or operating alarms; they are mandatory in some areas.
Solenoid valves should be installed on liquid lines (minimum sized) feeding low-pressure receivers so that positive shutoff is
automatically achieved with system shutdown. This prevents excessive refrigerant from collecting in low-pressure receivers, which can
https://handbook.ashrae.org/Handbooks/R06/IP/r06_ch01/r06_ch01_ip.aspx 09/07/2010
CHAPTER 1. LIQUID OVERFEED SYSTEMS Page 8 of 14
EVAPORATOR DESIGN
Considerations
There is an ideal refrigerant feed and flow system for each evaporator design and arrangement. An evaporator designed for gravity-
flooded operation cannot always be converted to an overfeed arrangement, and vice versa; neither can systems always be designed to
circulate the optimum flow rate. When top feed is used to ensure good distribution, a minimum quantity per circuit must be circulated,
generally about 0.5 gpm. In bottom-feed evaporators, distribution is less critical than in top or horizontal feed because each circuit fills
with liquid to equal the pressure loss in other parallel circuits.
Circuit length in evaporators is determined by allowable pressure drop, load per circuit, tubing diameter, overfeed rate, type of
refrigerant, and heat transfer coefficients. The most efficient circuiting is determined in most cases through laboratory tests conducted
by the evaporator manufacturers. Their recommendations should be followed when designing systems.
System design must determine whether evaporators are to be top fed or bottom fed, although both feed types can be installed in a
single system. Each feed type has advantages; no arrangement is best for all systems.
Advantages of top feed include
For halocarbon systems with greater fluid densities, the refrigerant charge, oil return, and static pressure are very important.
Bottom feed is advantageous in that
The top-feed system is limited by the relative location of components. Because this system sometimes requires more refrigerant
circulation than bottom-feed systems, it has greater pumping load, possibly larger feed and return lines, and increased line pressure
drop penalties. In bottom-feed evaporators, multiple headers with individual inlets and outlets can be installed to reduce static pressure
penalties. For high lift of return overfeed lines from the evaporators, dual suction risers eliminate static pressure penalties (Miller 1974,
1979).
Distribution must be considered when using a vertical refrigerant feed, because of static pressure variations in the feed and return
header circuits. For example, for equal circuit loadings in a horizontal-airflow unit cooler, using gradually smaller orifices for bottom-
feed circuits than for upper circuits can compensate for pressure differences.
When the top-feed free-draining arrangement is used for air-cooling units, liquid solenoid control valves can be used during the
defrost cycle. This applies in particular to air, water, or electric defrost units. Any liquid remaining in the coils rapidly evaporates or
https://handbook.ashrae.org/Handbooks/R06/IP/r06_ch01/r06_ch01_ip.aspx 09/07/2010
CHAPTER 1. LIQUID OVERFEED SYSTEMS Page 9 of 14
REFRIGERANT CHARGE
Overfeed systems need more refrigerant than dry expansion systems. Top-feed arrangements have smaller charges than bottom-feed
systems. The amount of charge depends on evaporator volume, circulating rate, sizes of flow and return lines, operating temperature
differences, and heat transfer coefficients. Generally, top-feed evaporators operate with the refrigerant charge occupying about 25 to
40% of the evaporator volume. The refrigerant charge for the bottom-feed arrangement occupies about 60 to 75% of the evaporator
volume, with corresponding variations in the wet returns. Under some no-load conditions in up-feed evaporators, the charge may
occupy 100% of the evaporator volume. In this case, the liquid surge volume from full load to no load must be considered in sizing the
low-pressure receiver (Miller 1971, 1974).
Evaporators with high heat transfer rates, such as flake ice makers and scraped-surface heat exchangers, have small charges because
of small evaporator volumes. The amount of refrigerant in the low side has a major effect on the size of the low-pressure receiver,
especially in horizontal vessels. The cross-sectional area for vapor flow in horizontal vessels is reduced with increasing liquid level. It is
important to ascertain the evaporator refrigerant charge with fluctuating loads for correct vessel design, particularly for a low-pressure
receiver that does not have a constant level control but is fed through a high-pressure control.
Operating costs for overfeed systems are generally lower than for other systems (though not always, because of the various
inefficiencies that exist from system to system and from plant to plant). For existing dry expansion plants converted to liquid overfeed,
the operating hours, power, and maintenance costs are reduced. Efficiency of the early gas pump systems has been improved by using
high-side pressure to circulate overfeed liquid. This type of system is indicated in the controlled-pressure system shown in Figure 4.
Refinements of the double-pumper-drum arrangement (see Figure 3) have also been developed.
Gas-pumped systems, which use refrigerant gas to pump liquid to the evaporators or to the controlled-pressure receiver, require
additional compressor volume, from which no useful refrigeration is obtained. These systems consume 4 to 10% or more of the
compressor power to maintain refrigerant flow.
If condensing pressure is reduced as much as 10 psi, the compressor power per unit of refrigeration drops by about 7%. Where
outdoor dry- and wet-bulb conditions allow, a mechanical pump can be used to pump gas with no effect on evaporator performance.
Gas-operated systems must, however, maintain the condensing pressure within a much smaller range to pump the liquid and maintain
the required overfeed rate.
LINE SIZING
The liquid feed line to the evaporator and wet return line to the low-pressure receiver cannot be sized by the method described in
Chapter 22 of the ASHRAE Handbook—Fundamentals. Figure 7 can be used to size liquid feed lines. The circulating rate from Table 1 is
multiplied by the evaporating rate. For example, an evaporator with a circulating rate of 4 that forms vapor at a rate of 5 lb/min needs
a feed line sized for 4 × 5 = 20 lb/min.
Alternative methods that may be used to design wet returns include the following:
Use one pipe size larger than calculated for vapor flow alone.
Use a velocity selected for dry expansion reduced by the factor . This method suggests that the
wet-return velocity for a circulating rate of 4 is , or half that of the acceptable dry-vapor velocity.
Use the design method described by Chaddock et al. (1972). The report includes tables of flow capacities at 2°F drop per 100
ft of horizontal lines for R-717 (ammonia), R-12, R-22, and R-502.
When sizing refrigerant lines, the following design precautions should be taken:
Carefully size overfeed return lines with vertical risers because more liquid is held in risers than in horizontal pipe. This holdup
https://handbook.ashrae.org/Handbooks/R06/IP/r06_ch01/r06_ch01_ip.aspx 09/07/2010
CHAPTER 1. LIQUID OVERFEED SYSTEMS Page 10 of 14
increases with reduced vapor flow and increases pressure loss because of gravity and two-phase pressure drop.
Use double risers with halocarbons to maintain velocity at partial loads and to reduce liquid static pressure loss (Miller 1979).
Add the equivalent of a 100% liquid static height penalty to the pressure drop allowance to compensate for liquid holdup in
ammonia systems that have unavoidable vertical risers.
As alternatives in severe cases, provide traps and a means of pumping liquids, or use dual-pipe risers.
Install low-pressure drop valves so the stems are horizontal or nearly so (Chisholm 1971).
In selecting a gas-and-liquid separator, adequate volume for the liquid supply and a vapor space above the minimum liquid height for
liquid surge must be provided. This requires analysis of operating load variations. This, in turn, determines the maximum operating
liquid level. Figures 8 and 9 identify these levels and the important parameters of vertical and horizontal gravity separators.
Vertical separators maintain the same separating area with level variations, whereas separating areas in horizontal separators
change with level variations. Horizontal separators should have inlets and outlets separated horizontally by at least the vertical
separating distance. A useful arrangement in horizontal separators distributes the inlet flow into two or more connections to reduce
turbulence and horizontal velocity without reducing the residence time of the gas flow within the shell (Miller 1971).
https://handbook.ashrae.org/Handbooks/R06/IP/r06_ch01/r06_ch01_ip.aspx 09/07/2010
CHAPTER 1. LIQUID OVERFEED SYSTEMS Page 11 of 14
In horizontal separators, as the horizontal separating distance increases beyond the vertical separating distance, the residence time of
vapor passing through increases so that higher velocities than allowed in vertical separators can be tolerated. As the separating
distance reduces, the amount of liquid entrainment from gravity separators increases. Table 2 shows the gravity separation velocities.
For surging loads or pulsating flow associated with large step changes in capacity, the maximum steady-flow velocity should be reduced
to a value achieved by a suitable multiplier such as 0.75.
Table 2. Maximum Effective Separation Velocities for R-717, R-22, R-12, and R-502, with Steady Flow Conditions
Vertical
Separation Maximum Steady Flow Velocity, fpm
Distance,
Temp., °F in. R-717 R-22 R-12 R-502
+50 10 29 13 16 11
24 125 62 70 50
36 139 77 85 62
+20 10 42 19 22 15
24 172 86 96 69
36 195 102 115 83
–10 10 61 27 32 22
24 253 120 135 97
https://handbook.ashrae.org/Handbooks/R06/IP/r06_ch01/r06_ch01_ip.aspx 09/07/2010
CHAPTER 1. LIQUID OVERFEED SYSTEMS Page 12 of 14
The gas-and-liquid separator may be designed with baffles or eliminators to separate liquid from the suction gas returning from the
top of the shell to the compressor. More often, enough separation space is allowed above the liquid level for this purpose. Such a
design is usually of the vertical type, with a separation height above the liquid level of 24 to 36 in. The shell diameter is sized to keep
suction gas velocity low enough to allow liquid droplets to separate and not be entrained with the returning suction gas off the top of
the shell.
Although separators are made with length-to-diameter (L/D) ratios of 1/1 increasing to 10/1, the least expensive separators usually
have L/D ratios between 3/1 and 5/1. Vertical separators are normally used for systems with reciprocating compressors. Horizontal
separators may be preferable where vertical height is critical and/or where large volume space for liquid is required. The procedures for
designing vertical and horizontal separators are different.
A vertical gas-and-liquid separator is shown in Figure 9. The end of the inlet pipe C1 is capped so that flow dispersion is directed
down toward the liquid level. The suggested opening is four times the transverse internal area of the pipe. Height H1 with a 120°
dispersion of the flow reaches approximately 70% of the internal diameter of the shell.
An alternative inlet pipe with a downturned elbow or mitered bend can be used. However, the jet effect of entering fluid must be
considered to avoid undue splashing. The pipe outlet must be a minimum distance of IDS/5 above the maximum liquid level in the
shell. H2 is measured from the outlet to the inside top of the shell. It equals D + 0.5 times the depth of the curved portion of the
head.
For the alternative location of C2, determine IDS from the following equation:
(2)
The maximum liquid height in the separator is a function of the type of system in which the separator is being used. In some
systems this can be estimated, but in others, previous experience is the only guide for selecting the proper liquid height. Accumulated
liquid must be returned to the system by a suitable means at a rate comparable to its collection rate.
With a horizontal separator, the vertical separation distance used is an average value. The top part of the horizontal shell restricts
gas flow so that the maximum vertical separation distance cannot be used. If Ht represents the maximum vertical distance from the
liquid level to the inside top of the shell, the average separation distance as a fraction of IDS is as follows:
(3)
where
https://handbook.ashrae.org/Handbooks/R06/IP/r06_ch01/r06_ch01_ip.aspx 09/07/2010
CHAPTER 1. LIQUID OVERFEED SYSTEMS Page 13 of 14
(4)
where
RTL = residence time length, in.
Q = maximum flow for that portion of the shell, cfm
All connections must be sized for the flow rates and pressure drops permissible and must be positioned to minimize liquid splashing.
Internal baffles or mist eliminators can reduce vessel diameter; however, test correlations are necessary for a given configuration and
placement of these devices.
An alternative formula for determining separation velocities that can be applied to separators is
(5)
where
v = velocity of vapor, fps
ρl = density of liquid, lb/ft3
ρv = density of vapor, lb/ft3
k = factor based on experience without regard to vertical separation distance and surface tension for gravity separators
In gravity liquid/vapor separators that must separate heavy entrainment from vapors, use a k of 0.1. This gives velocities equivalent
to those used for 12 to 14 in. vertical separation distance for R-717 and 14 to 16 in. vertical separation distance for halocarbons. In
knockout drums that separate light entrainment, use a k of 0.2. This gives velocities equivalent to those used for 36 in. vertical
separation distance for R-717 and for halocarbons.
REFERENCES
Chaddock, J.B., D.P. Werner, and C.G. Papachristou. 1972. Pressure drop in the suction lines of refrigerant circulation systems.
ASHRAE Transactions 78(2):114-123.
Chisholm, D. 1971. Prediction of pressure drop at pipe fittings during two-phase flow. Proceedings of the IIR Conference, Washington,
D.C.
Lorentzen, G. 1963. Conditions of cavitation in liquid pumps for refrigerant circulation. Progress Refrigeration Science Technology
I:497.
Lorentzen, G. 1965. How to design piping for liquid recirculation. Heating, Piping & Air Conditioning (June):139.
Lorentzen, G. 1966. On the dimensioning of liquid separators for refrigeration systems. Kältetechnik 18:89.
Lorentzen, G. 1968. Evaporator design and liquid feed regulation. Journal of Refrigeration (November-December):160.
Lorentzen, G. and R. Gronnerud. 1967. On the design of recirculation type evaporators. Kulde 21(4):55.
Miller, D.K. 1971. Recent methods for sizing liquid overfeed piping and suction accumulator-receivers. Proceedings of the IIR
Conference, Washington, D.C.
Miller, D.K. 1974. Refrigeration problems of a VCM carrying tanker. ASHRAE Journal 11.
Miller, D.K. 1979. Sizing dual suction risers in liquid overfeed refrigeration systems. Chemical Engineering 9.
Niederer, D.H. 1964. Liquid recirculation systems—What rate of feed is recommended. The Air Conditioning & Refrigeration Business
(December).
Niemeyer, E.R. 1961. Check these points when designing knockout drums. Hydrocarbon Processing and Petroleum Refiner (June).
Scheiman, A.D. 1963. Size vapor-liquid separators quicker by nomograph. Hydrocarbon Processing and Petroleum Refiner (October).
Scheiman, A.D. 1964. Horizontal vapor-liquid separators. Hydrocarbon Processing and Petroleum Refiner (May).
Scotland, W.B. 1963. Discharge temperature considerations with multicylinder ammonia compressors. Modern Refrigeration (February).
Scotland, W.B. 1970. Advantages, disadvantages and economics of liquid overfeed systems. ASHRAE Symposium Bulletin KC-70-3:
Liquid overfeed systems.
Soling, S.P. 1971. Oil recovery from low temperature pump recirculating hydrocarbon systems. ASHRAE Symposium Bulletin PH-71-2:
Effect of oil on the refrigeration system.
Sonders, M. and G.G. Brown. 1934. Design of fractionating columns, entrainment and capacity. Industrial & Engineering Chemistry
(January).
Stoecker, W.F. 1960. How to design and operate flooded evaporators for cooling air and liquids. Heating, Piping & Air Conditioning
(December).
Younger, A.H. 1955. How to size future process vessels. Chemical Engineering (May).
BIBLIOGRAPHY
Chaddock, J.B. 1976. Two-phase pressure drop in refrigerant liquid overfeed systems—Design tables. ASHRAE Transactions 82(2):107-
133.
https://handbook.ashrae.org/Handbooks/R06/IP/r06_ch01/r06_ch01_ip.aspx 09/07/2010
CHAPTER 1. LIQUID OVERFEED SYSTEMS Page 14 of 14
Chaddock, J.B., H. Lau, and E. Skuchas. 1976. Two-phase pressure drop in refrigerant liquid overfeed systems—Experimental
measurements. ASHRAE Transactions 82(2):134-150.
Geltz, R.W. 1967. Pump overfeed evaporator refrigeration systems. Air Conditioning, Heating & Refrigeration News (January 30,
February 6, March 6, March 13, March 20, March 27).
Lorentzen, G. and A.O. Baglo. 1969. An investigation of a gas pump recirculation system. Proceedings of the Xth International
Congress of Refrigeration, p. 215. International Institute of Refrigeration, Paris.
Richards, W.V. 1959. Liquid ammonia recirculation systems. Industrial Refrigeration (June):139.
Richards, W.V. 1970. Pumps and piping in liquid overfeed systems. ASHRAE Symposium Bulletin KC-70-3: Liquid overfeed systems.
Slipcevic, B. 1964. The calculation of the refrigerant charge in refrigerating systems with circulation pumps. Kältetechnik 4:111.
Thompson, R.B. 1970. Control of evaporators in liquid overfeed systems. ASHRAE Symposium Bulletin KC-70-3: Liquid overfeed
systems.
Watkins, J.E. 1956. Improving refrigeration systems by applying established principles. Industrial Refrigeration (June).
The preparation of this chapter is assigned to TC 10.1, Custom Engineered Refrigeration Systems.
https://handbook.ashrae.org/Handbooks/R06/IP/r06_ch01/r06_ch01_ip.aspx 09/07/2010