02 Iris1

The document is an operations and maintenance manual for IRIS NV elevator systems. It provides inspection guidelines and standards for maintenance technicians, with specific checklists for various control box components on a monthly basis. Technicians are instructed to cut power before working and take safety precautions. The manual focuses on IRIS NV systems only and refers readers to other manuals for more technical details. It includes a diagram labeling main control box components and their functions.

Uploaded by

Andioso
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
232 views

02 Iris1

The document is an operations and maintenance manual for IRIS NV elevator systems. It provides inspection guidelines and standards for maintenance technicians, with specific checklists for various control box components on a monthly basis. Technicians are instructed to cut power before working and take safety precautions. The manual focuses on IRIS NV systems only and refers readers to other manuals for more technical details. It includes a diagram labeling main control box components and their functions.

Uploaded by

Andioso
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

Name IRIS NV Elevator Maintenance Rev. Date 2011.02.

25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 33/N

Control box
3.2.1 Daily inspection items and standards - - - - - - - - - - - - - - - - - - - - - - - - - - - 34
3.2.2 Control box MCCB --------------------------------------- 38
3.2.3 Determine voltage and fuse - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 38
3.2.4 Insulation measuring and earthing- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 39
3.2.5 Electronic contactor --------------------------------------- 40
3.2.6 PCB base board --------------------------------------- 41
1) Main PCB --------------------------------------- 41
2) Synchromotor PG card - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 46
3) SM.02/1 PCB(TOC Controller Board) - - - - - - - - - - - - - - - - - - - - - - - - - - - - 47
4) SM.02/G PCB --------------------------------------- 49
5) SM-03 PCB(Car Call Board) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 50
6) SM.04V 12/A(Call & Display Control Board) - - - - - - - - - - - - - - - - - - - - - - 51
7) SM.04V 12/A --------------------------------------- 52
8) BST Door Controller - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 53
3.2.7 Transformer --------------------------------------- 54
3.2.8 Regeneration resistance- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 54

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 34/N

3.2 Control box

The manual mainly introduces content about IRIS NV elevator maintenance


work only. Therefore, the manual does not include detailed technology details,
please refer to STEP control box manual.

Notice

 When check the control box, cut off the power supply; after
performing Lock Out /Tag Out, conduct work.
 Please determine whether plastic cap is covered on the terminal.
If cap is not covered on its top, please make cap cover the top.
 If power supply is 200V or 400V, please affix marking label to
make others take care.
 If PCB is applied, it should be avoided that PCB is scratched by
protruded pin at back.
 If INV elevator type is applied, after cutting off power supply,
smoothing condenser is still in charging state; therefore, please
determine whether DC voltage on capacitor two ends conduct
working after discharging completely.

3.2.1 Daily inspection items and standards


Inspection
Part Inspection item Tool State/standard
circle

Ambient temperature:
Naked eyes, lower than 40℃,
Ambient temperature, moisture, vibration,
Operating thermometer, accord with moisture 1 month
dust, corrosive gas, oil, dust, dribbles etc.
environment hygrometer etc. environment
requirements
Whether danger exists around the assembly Naked eyes No dangerous item 1 month
LCD
Whether LCD indicating is normal Naked eyes Indicating is normal 1 month
indicating
Connector Bolts relaxation is not allowed. Naked eyes, No abnormal condition
1 month
terminal Connector relaxation is not allowed. screwdriver Assemble is stable
Bolts and tail Determine whether protective layer cracks Naked eyes No abnormal condition 1 month
cord or discolors

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 35/N

Determine whether earthing panel deforms.

Electromagne Whether there is vibration noise in working Naked eyes, None


tic contactor, acoustic Noise occurs at
Contact attraction state of contact point 1 month
relay sensation contacting point
Determine liquid leakage, discolor, crack, Naked eyes No abnormal condition
Electrolytic case expansion conditions 1 month
capacitor Determine whether safety liquid flows out,
and whether case expanses
Capacitor Determine whether there is dust Naked eyes, No abnormal condition 1 month
cooling fan hands
Determine whether the fan conduct air Naked eyes
exchanging and determine its fixing state
Control box, Whether there is abnormal noise Acoustic Normal rotation 1 month
cooling fan (after cutting off the power supply, conduct sensation,
determination by rotating fan vane naked eyes,
manually) hands

Whether there is abnormal vibration Naked eyes No abnormal condition 1 month


Whether discoloring condition occurs for Naked eyes,
over-high temperature. smell
Connector Determine connecting state between control Naked eyes No abnormal condition 1 month
box and connector, and state of dust &
foreign adhesive matter
PCB PCB discoloring and abnormal odor Naked eyes, No abnormal condition 1 month
PCB crack, damage, deformation smell

(1) Num of electric wire connected on a terminal is 2 strands, and num of both sides is less
than 4 strands. And it is not allowed that the current is higher than maximum permissible
current of the terminal.
(2) Slightly draw the electric wire to determine fastening state and connecting state of jack.
(3) Leave electric wire long enough for conditions of contact moving, or cover opening for
fault handle or inspecting etc..
(4) Figure 2-1 is outline drawing of control box (for function description, please refer to STEP
control box manual).

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 36/N

Figure 2-1. Outline drawing of control box

Function of each Part

No. Section Part Name Function


1 Part1 RR resistance Consume regenerated electric power
2 DZ1 Brake resistance
Part2 Main board & Hall communication wire power supply [input
3 SMPS
220V, output 24V]
Buttons used for low-speed operation [Up, Com, Down,
4 Part3 ERO
NOR/INS, E.STOP]
5 FU1 Fuse [110V safety chain, capacity:2A]
6 FU2 Fuse [Brake voltage, capacity:4A]
7 FU3 Fuse [Door & car door power supply, capacity:2A]
8 FSK2 Break [hoistway lighting switch]
9 CP1 Break [SMPS power supply input terminal]
Part4 Safety chain[landing door, KAD contactor will be “on” when
10 KAD
landing door is closed]
Fire Return contactor [contactor will be “on” when hall switch is
11 FR
on]
The 2nd fire-fighting operation contactor [the contactor will be on
13 FIRE2
when the 2nd fire-fighting switch is on]
2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 37/N

14 ERO ERO switch


Part5
15 DZL Door Zone Lamp[used for rescue operation]
16 BY Brake relay [it will be “on” when starts]
Part6 Similar with relay C1ST, it could be started in opening state
17 KMZ
only]
18 UCM1 Door-opening car-departure [in normal: on, when start: off]
19 UCM2 Door-opening car-departure [in normal: on, when start: off]
20 FIRE1 Relay for the 1st fire-fighting operation
Speed governor relay [it is on when speed governor safety
21 GOV
chain is enabled]
Terminals used for wire connecting of external apparatus of
22 Part7 Field panel
control box
23 Part8 TB Terminal block[used for wire connecting of control box]
Transformer [used for supply power for control box (single
phase), input power supply is 380V, output power supply is
24 Part9 Trans
110V
Supply for [FU1], 123V[FU2], 220V[FU3]
25 OCB Break of main power supply [380V]
Contactor [similar with C1SW, could be started under the state
26 SW
Part10 of being enabled only]
27 FSK1 Break used for lighting power supply
28 APD EMI filter
29 TB Terminal block
30 Main board Drive board
31 Part11 PG Card Rotary Encoder
Integrated
32 IPM
driver

(5) When connect 2 strands of electric wire end terminal to another, keep maximum contact
face between terminals. Please not make wire connecting angle become higher than 60˚.

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 38/N

60˚

Figure 2-2. Connecting method of connecting terminal

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 39/N

3.2.2 Control box MCCB (OCB)


Inspection
Part Inspection item Tool State/standard
circle
Voltage regulation [V] -15 ~+10% 1 month
Voltmeter
Unparallel voltage [V] ±10% 1 month
Control box Surface
Apparatus surface heats up 1 month
MCCB thermometer
Terminal is screw up and conduct
Screwdriver 1 month
wiring

(1) If fault is related to input power supply, please inspect following content.
1) The 1st side: ⓐ R-S, ⓑ R-T, ⓒ S-T
nd
2) The 2 side: ⓓ R1-S1, ⓔ R1-T1, ⓕ S1-T1
If measured voltage (ⓐ) of the 1st side and measured voltage (ⓓ) of the 2nd side are
higher than 2% of service voltage, cut off MCCB of building distributor box, and measure
resistance between R-R1 after opening control box MCCB, measuring result should be
0[Ω] or near to 0[Ω].
(2) Measure rest S, T phase with method same with the one for R mentioned above. If there
is abnormal condition, please conduct accurate inspection and takes measures
(replacing) according to inspection results.
(3) Measure peak (p.m. 3~4 o’clock, 8~9 o’clock) voltage in each summer and ordinary (a.m.)
voltage, and record measuring results on the daily inspection record.
(4) After cutting off the power supply and implementing Lock Out / Tag Out, inspect whether
MCCB surface discolors; and determine whether its temperature is normal after
measuring the temperature.
(5) Please determine whether there is abnormal noise or vibration inside MCCB.
3.2.3 Determine voltage and fuse

Inspection
Part Inspection item Tool State/standard
circle

Measure Each control/signal wire Voltmeter Refer to field drawing 1 month


voltage and Rated capacity and contact state Naked Refer to field drawing 1 month
confirm fuse eyes

(1) Confirm voltage and fuse capacity of each control/signal wire.


(2) Confirm fuse connecting state and fastening state of terminals with hands.

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 40/N

3.2.4 Insulation measuring and earthing


Inspection
Part Inspection item Tool State/standard
circle
nd
The 2 side face of control box Insulation 1㏁
Insulation resistance 12 months
Each control/signal wire 0.5 ㏁
meter
Fastening state of terminals on
Earthing Screwdriver Fastening 1 month
specified position

(1) Working overview


Resistance property of insulator is insulation. Measure property of this insulation to
prevent electric shock accident and defective insulation to protect apparatus and avoid
safety accident coursed by abnormal action of elevator.
(2) Electric shock preventing
1) DC voltage straightly through main circuit of frequency converter, even though the
MCCB is turned off, voltage charged by the capacitor can not be discharged
completely at once. Thus, please pay much attention to safety issue. And capacitor
(AL electrolytic capacitor) connects with main circuit, even though the MCCB is
turned off, voltage charged by the capacitor can not be discharged completely and
immediately. Therefore, please adopt tester to determine whether DC voltage is
0~10VDC before working.
2) Please must implement insulation test before measuring the insulation to prevent
PCB from being damaged.
There are semiconductor elements used in the circuit, therefore, elements will be
damaged if integrated circuit is earthed. Thus, please adopt insulation resistance
tester (generation voltage 15V) or digital integrated electricity meter to conduct
insulation test on all connector terminal in the control box.
(3) Please determine connecting control box earthing.
(4) For detailed insulation measuring methods, please refer to “Sigma Elevator Test-Run
Adjust Manual”.
(5) Regulated value of insulation resistance
Circuit name Measured part Regulated
value

Main circuit Power supply terminal (TERM1) between ~ Higher


Frame than1.0[㏁]

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 41/N

Motor circuit Motor terminal (TERM2) between ~ Frame


Control circuit The 2nd contact point of MCCB used for lighting Higher than
between ~ Frame 0.5[㏁]
The 2nd main contact point of main contactor
between ~ Frame
(6) Connect earthing wire on one side of building to specific position. If connect the earthing
wire to other position, control part may be can not be protected for interference from
external reasons.
3.2.5 Electronic contactor
Inspection
Part Inspection item Tool State/standard
circle
Contactor Excess space for fixing and wiring, Naked eyes, 1 month
fasten the terminal screwdriver
Abnormal abrasion, dusting, electric Naked eyes, 1 month
arc, changeable tension force of multimeter
contact point

(1) Please determine whether electric wire used for wiring has excess part.
(2) Please determine whether changeable tension device could be started smoothly.
(3) Please determine whether there is serious arc trace occurs for abnormal abrasion
(irregular abrasion) of contact point.
(4) Please determine ON / OFF action of electronic contactor.

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 42/N

3.2.6 PCB base board


Inspection
Part Inspection item Tool State/standard
circle
PCB Board Fixing state, jack connecting state Naked eyes, 1 month
hands

(1) Precautions for treatment and cleaning


1) Please pack PCB to prevent it from being impacted in moving. Please do not keep it
in humid place for a long term.
2) After cutting of power supply and implementing Lock Out / Tag Out, please pay
attention to static electricity, and conduct cleaning.
(2) Main PCB
1) Outline.

도면 3.18 제어电路端子

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 43/N

Figure 3.18 Terminal of control circuit

No Mic name Function Remark


Low-voltage optical coupling
1 JP1-JP5
input
2 JP6 Power supply input interface
3 JP7-JP9 CAN communication interface
4 JP10 Used for emergency condition
5 JP11 Modem supervising interface
6 JP12 Portable governor interface
7 JP13-JP16 Relay output interface
High-voltage optical coupling
8 JP17
input
Drawing 3.18 Terminal of control circuit

2) Switch function

Switch
No. State Function Remark
name
On ARM Program start Setup state: OFF
1 ARM Normal working Note: when start
Off program, start CPLD
state
firstly → and set
SW1 On DSP Program start SW1 to be ON→
DSP program start→
2 DSP Normal working ARM program start
Off
state (start window is
different)
SW2 CAN Terminal SW2 assembly state:
On OFF
SW3 resistance setup
SW3/SW4
SW4 CAN Terminal
Off assembly state: ON
resistance invalid
RS485 Terminal
On
resistance setup
SW5 assembly state: ON
RS485 Terminal
Off
resistance invalid

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 44/N

3) MIC name and function description.

Mic Connected
Name Function Default
name Wire num
1 X0 Auto/Inspection input signal default
2 X1 X0 and X1 all input→automatic default
JP1
3 X2 Up signal default
4 X3 DN signal, default
1 X4 2LS(SDS1U) close
2 X5 1LS(SDS1D) close
3 X6 4LS(SDS2U) close
4 X7 3LS(SDS2D) close
GOV CTT contact point input
5 X8 open
JP2 signal
KMZ CTT contact point input
6 X9 open
signal
FR CTT contact point input
7 X10 open
signal
8 X11 open
1 X12 UL(up limit switch) close
2 X13 DL(down limit switch) close
3 X14 2LV(level switch signal) open
JP3
4 X15 1LV(level switch signal) open
5 X16 close
6 X17 open
1 x18 Fireman(fire-hazard reset switch) open
2 x19 Fireman Service fireman switch open
3 x20 SW CTT contact point input open
4 x21 signal open
JP4
5 x22 BY CTT input signal open
6 x23 BS1 switch signal (left) open
7 x24 BS2 switch signal (right) open
8 x25 MTH signal input open

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 45/N

9 x26 Earthquake signal input (EQS) open


ARD signal(emergency level for
10 x27 open
power failure)input

Mic Connected
Name Function Default
name Wire num
1 x28 UCM1,2 CTT contact point input open
2 x29 KAD CTT contact point input open
FIRE1 CTT contact point input
3 x30 open
(the 1st fire-fighting)
JP5
FIRE2 CTT contact point
4 x31 nd open
input(the 2 fire-fighting)
X0~X31 input signal common
5 COM
terminal
0VDC power input terminal
1 GND
(used for CTT input circuit)
24VDC power input terminal
2 24V
(used for CTT input circuit)
JP6
0VDC power input
3 GND
(used for CTT output circuit)
24VDC power input
4 24V
(used for CTT output circuit)
1
2
JP7 3 CAN1H Tandem communication signal
(TXA1+)/(TXA1-)
4 CAN1L
(Car & Hall CAN communication)
1 +24V
2 0V
JP8
3 CAN2H Parallel or group-control tandem
4 CAN2L signal (TXA2+) (TXA2-)
1 +24V
JP9 2 0V
3 CAN3H
2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 46/N

4 CAN3L
JP10 1
MODEM telemonitoring
JP11 1 interface; ARM tandem guiding
window
Could be connected with RS232
JP12 1 interface portable governor; DSP
tandem guiding window

Mic Connected
Name Function Default
name Wire num
1 Y14B Output
2 Y14A Output
3 COM6 Output
JP13 4 Y15B Fire-fighting reset indicating Output
5 Y15A Fire-fighting reset indicating Output
Fire-fighting reset output relay
6 COM7 Output
Y15 common terminals
1 Y8 FIRE1 CTT output terminal Output
2 Y9 FIRE2 CTT output terminal Output
3 Y10 UCM1,2 CTT output terminal Output
4 Y11 DZI Lamp output terminal Output
JP14 Output relay Y8-Y11 common
5 COM4
terminals
6 Y12 Output
7 Y13 Output
8 COM5
1 Y4 FR CTT output terminal Output
2 Y5 Output
Output relay Y4-Y5 common
JP15 3 COM2
terminals
4 Y6 Output
5 Y7 Output

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 47/N

6 COM3
1 Y0 BY CTT output Output
2 Y1 KMZ CTT output Output
3 Y2 Output
JP16
4 Y3 SW CTT output Output
Output relay Y0-Y3 common
5 COM1
terminals
Used for inspecting abnormal
1 X32 In-put
conditions of safety circuit
Used for inspecting abnormal
2 X33 In-put
conditions of landing door circuit
JP17 Used for inspecting abnormal
3 X34 In-put
conditions of CAR door circuit
4 X35 In-put
X32-X35 input signal common
5 COM
terminal 0V
JP25 CPLD program JTAG guiding window

(3) Synchromotor PG card


Input function of processing encoder
1) Outline

Control box interface

PG card frequency resolution


output interface

UVW encoder signal input


interface

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 48/N

2) Terminal function description

Terminal No. Terminal function description


Name

Frequency Frequency resolution signal start


Resolution Collecting electrode output A,B
signal

Collecting electrode output of transistor open-


circuit (max. output frequency 50kHz)

Specification

Terminal No. Terminal function description Specification


Name
A phase signal

B phase signal Encoder differential signal input


Encoder Z phase signal interface, maximum frequency
input signal U phase signal 50kHz
V phase signal

W phase signal

Shield earthing Shielding field


Encoder +5V or+5.3V
power Maximum 200mA output
supply Encoder GND Select S1 bridging

(4) SM.02/1 PCB(TOC Controller Board)


Assembled on tool box, signal for output door driving and input CLS/OLS,PTM.Chime, Safety
Shoe etc. signals
1) Outline

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 49/N

JP3 JP4 JP JP6 JP7


5

JP JP1 SW1,2 JP9 JP8


2
2) Switch function and description
MIC name Function Remark
Used for CAN communication terminal
resistance setup
SW1 (1,2 simultaneously) 2P
(ON: terminal resistance setup, OFF: release
terminal resistance)
Used for program start setup (1,2
simultaneously)
SW2 2P
(On: program start, OFF: normal operation
state)

3) Terminal function and description


MIC name Function Remark

CAN communication and power supply


JP1 4P
(1:24V,2:GND,3:CANH,4:CANL)
For adding Board connecting(connecting for ex
JP2 14P
pansion)
JP3 Ring for floor arrival 5P

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 50/N

JP4 For door drive signal output 8P

JP5 For Safety Shoe signal input 3P

JP6 For 20%, 80%, 110% Micro S/W signal input 4P

JP7 For parallel interface communication 10P

JP8 For relay output of Light/Fan driving 2P

JP9 Used for inspect load(PTM) 4P

DB1 Used for program start 9P

(5) SM.02/G PCB


Assembled on operation panel, through main board input communication, open/close button and
input ATT part signal.
1) Outline

JP1
JP5

SW1

SW3

JP3
JP2

JP7
DB1
JP6

SW2 JP4

2) Switch function and description

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 51/N

MIC name Function Remark


Used for CAN communication terminal resistance
setup
SW1 (1,2 simultaneously) 2P
(ON: terminal resistance setup, OFF: release
terminal resistance)
Used for program start setup (1,2 simultaneously)
SW2 2P
(On: program start, OFF: normal operation state)
1 2 3 4 Operation panel type 4P

On Off Off Off Main operation panel

Off On Off Off Back operation panel


SW3
Off Off On Off Operation panel for the
disable
Off Off Off On Server operation panel

3) Terminal function and description

MIC name Function Remark

CAN communication and power supply


JP1 4P
(1:24V, 2:GND, 3:CANH, 4:CANL)

For adding Board connecting(connecting


JP2 14P
for command)

For adding Board connecting(connecting


JP3 14P
for expansion)

JP4

JP5 For ATT part switch signal input 5P

JP6 For connecting Open Button 4P

JP7 Used for Close Button 4P

DB1 For connecting program start 9P

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 52/N

(6) SM-03 PCB(Car Call Board)


Assembled on COP and connected to SM-02/G PCB, floor button input and Lamp output.
1) Outline

-connecting method of floor button and lamp

The 1st and 2nd pins are connected to lamp


power supply [-] and [+] terminals
respectively.
The 3rd and 4th pins are connected command
button terminals
2) MIC name and description

Remark
Used for button connecting of F Used for button connecting of F Used for button connecting of F
1 car floor 9 car floor 57 car floor

Used for button connecting of F Used for button connecting of F Used for button connecting of F
2 car floor 10 car floor 58 car floor

Used for button connecting of F Used for button connecting of F Used for button connecting of F
3 car floor 11 car floor 59 car floor

Used for button connecting of F Used for button connecting of F Used for button connecting of F
4 car floor 12 car floor 60 car floor

Used for button connecting of F Used for button connecting of F Used for button connecting of F
5 car floor 13 car floor 61 car floor

Used for button connecting of F Used for button connecting of F Used for button connecting of F
6 car floor 14 car floor 62 car floor

Used for button connecting of F Used for button connecting of F Used for button connecting of F
7car floor 15 car floor 63 car floor

Used for button connecting of F Used for button connecting of F Used for button connecting of F
8 car floor 16 car floor 64car floor

Connector used for expansion

(7) SM.04V 12/A (Call & Display Control Board)


Assembled at hoistway of each floor, landing door calling logging and output IND signal
1) Outline

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 53/N

2) MIC name and signal

MIC name Function Remark


Power and CAN
JP1 4P
communication
JP2 1: Output 4P

JP3 2: 24V 4P
3:GND
JP4 4P
4: Input
JP5 4P

JP6 Used for SPI communication 4P

Used for PCB fix position


S1 2P
selecting
Used for CAN communication
SW1 2P
terminal resistance setup

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 54/N

(8) SM.04V 12/A (Call & Display Control Board)


1) Outline

2) MIC name and description

MIC name Function Remark

JP1 Power and CAN communication 4P

JP2 Used for SPI communication 4P


Used for CAN communication te
SW1 rminal resistance setup 2P

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 55/N

(9) BST Door Controller


Assembled on upper part of car and connected to operation panel SM.02/I PCB,
implement door opening/closing.
1) Outline

2) MIC name and description


Function Function Function

Input power
Earthing
Signal output

Signal output
Function
Signal output

Signal
Drive power

Earthing

3) Switch function and description

Switch name Function


Open Speed - Door Open Speed for adjust
Switch name Function
Close - Door Close Speed for adjust 1 ON RIGHT
HOLD - HOLD Torque for adjust OFF LEFT
2 TEST MODE ENABLE
OBSTruction - OBSTruction Torque for adjust
3 AUTO TUNE Mode
Torque 4 Communication Choice

2005.12.27. Approval
Name IRIS NV Elevator Maintenance Rev. Date 2011.02.25
SIGMA Code OEMS-P1-111-000 Rev. No. 0
Standard Application Service Business Dept. Page 56/N

4) Function description of Push Button and LED


Push Button Function LED Function

TEST Used for confirming door action OPENED Used for confirming Open

state finish(OLS)

(Push to Check The Door) CLOSED Used for confirming Close finish,

AUTO (Push to Calibrate The not used(CLS)

ADJUSTMENT Door/Auto Tune Motor) OBSTRUCTION

READ/ERROR Two-side Shoe,used for CUT

3.2.7 Transformer
Inspection
Part Inspection item Tool State/standard
circle
Terminal/terminal relaxation, noise, he Naked eye 6 months
ating s
Transformer
Wire connecting of earthing wire, cap Naked eye 6 months
s

One side of the 1st and 2nd transformer is electrified, therefore, please conduct inspe
ction after cutting off power supply and implementing Lock Out /Tag Out.
(1) Please determine whether abnormal odor or over-heating state occurs.
(2) Please determine whether there is abnormal noise.
(3) Please determine whether Transformer bears over-load.
(4) Please determine whether there is dust or carbon powder between terminals, adopt
cleaning cloth or brush to clean up.
3.2.8 Regeneration resistance
Inspection
Part Inspection item Tool State/standard
circle
Naked No relaxation is
Fixing state of connecting part 6 months
Regeneration eyes allowed
resistance Heating and assembly state of cap Naked No relaxation is
3 months
(partition) eyes allowed

(1) Please determine whether electric wire connected on regeneration resistance is relax.
(2) Please determine whether over-heat condition occurs on regeneration resistance.

2005.12.27. Approval