Base Control
Base Control
base control
for screw compressors
Operating instructions
base control
for screw compressors
BOGE KOMPRESSOREN
Otto Boge GmbH & Co. KG
Postfach 10 07 13
33507 Bielefeld
Otto-Boge-Straße 1-7
33739 Bielefeld
Issue: 08 / 2017
No. 596.1495.18
Nominal price: € 5,00
Index
1.3 Operation......................................................................................... 6
General base control is an integrated control and monitoring concept, having two ob-
jectives:
– Energy savings and thus reduction of ongoing costs.
– Prolonging the service life of the compressor due to wear which is as low
as possible.
All programmed data is stored in a memory module (EEPROM). Thus the
stored information is even available following a power failure.
Control The BOGE control concept dynamically adapts to the respective operating
conditions. The control assumes the following three tasks:
1. Automatic selection of the most economical operating mode
In order to save operating costs, it always strives for the most economical
intermittent operation.
2. Automatic optimization of the motor switching cycles
3. Automatic display of the maintenance intervals
The control monitors the maintenance intervals.
Ease of servicing Rapid replacement of the controls in the event of failures increases the avail-
ability of the compressor. This eliminates time consuming and costly trouble
shooting by specialists.
1 LC display
2 Indicator lamp – Fault (red)
3 Indicator lamp – Ready (green)
4 Info key
5 Enter key
6 On key
7 Off key
Position of the Depending on the compressor type the Emergency Stop button is either
Emergency Stop button mounted on the side (1) or front (2) of the switch cabinet.
Fig. 1.2: Possible positions of the Emergency Stop button: side (1) / front (2)
Emergency Stop button on the side (1): Shutting down the – Press the Emergency Stop button.
compressor in an emer- The Emergency Stop button engages and interrupts
gency the control voltage. All displays are cut off from the
power.
After rectifying the fault, unlock the Emergency Stop but-
ton:
– Turn the Emergency Stop button a quarter turn clock-
wise.
Emergency Stop button on the front (2): – Quit the display element test by pressing the Off key
.
– The compressor is ready for operation again.
Attention!
Always switch the compressor off with the
Off key .
Only use the Emergency Stop button in
case of an emergency!
Power disconnecting device Disconnect compressor – Turn switch of the power disconnecting device to the
(with Emergency Off function) (3) from the power supply / left to the position ‚0‘. The supply voltage is discon-
switch off in case of an nected. All displays are cut off from the power.
emergency Once the fault has been rectified, turn switch of the power
disconnecting device into position ‚1‘:
– Quit display element test by pressing the Off key .
– The compressor is ready for operation again.
Attention!
Always switch the compressor off with the
Off key .
Only for C LF N series Only use power disconnecting device
with power disconnecting device with Emergency Off function in case of
an emergency!
Off key To switch the Compressor may continue to run in idling mode
compressor off (factory setting 30 seconds).
Enter key For confirmation during – see section „Parameterization of the control“ on
parameterisation / for page 11.
acknowledging warning
and fault messages
Indicator lamp – Ready (green) Ready indicator The green lamp indicates that the machine is ready.
Indicator lamp – Fault (red) Fault indicator The red lamp indicates the existence of a fault.
3-digit 7-segment display Display: Shown in psi with a decimal point between the second
P: Pressure and third digit.
psi
°F
Anti-freeze idling
Thermometer
1.3 Operation
Switching off the com- Press Off key → Compressor Off → the
pressor pressure control function is deactivated and the
display shows the idling symbol .for up to
30 seconds. During this time the green indicator
blinks. The symbol O then appears and the
green indicator lamp goes out.
Motor servicing interval Press Info key a fourth time → and the
display shows the operating time until the next
Motor servicing and the symbols O (stands for
motor) running time and servicing (spanner).
Check wearing parts Press Info key a fifth time → and the
display shows the 1000-output cycle servicing
counter with the single exponent 103 (x 1000),
the load speed symbol, the circle (here for the
receiver) and the servicing symbol (spanner),
meaning the number of possible output cycles
until the next wearing parts inspection (suction
means: 20 x 103 = 20000 load cycles until next regulator).
receiver servicing.
Lower target pressure Press INFO key a ninth time → and the
value segment display shows the Lower target pres-
sure and an underscore at the bottom right next
to it.
Display element test Press INFO key a tenth time → and the
display shows all symbols and segments
together with the two indicator lamps.
15 Suction control 1)
General The control unit calculates from the current operating data the respective best
operating mode and automatically selects it.The parameters are adjustable.
In order to prevent unintentional changes to pre-set parameters, these param-
eters are code-protected.
Caution!
Never change the value of a parameter if you do not know what it means!
This may cause incorrect behaviour of the control unit!
Do not experiment with parameter settings!
Always call BOGE-Service if you are unsure or have any doubts.
Parameterization From the main display the first step in parameterization is performed by re-
peated pressing of the Info key , until the display the software-no., and then
proceeding as follows:
1. Press Enter key → and the parameterization symbol is shown on
the left, followed by three zeros, the left of which blinks.
2. Press Info key to change the first digit.
3. Press Enter key → and now the middle zero blinks.
4. Press Info key to change the second digit.
5. Press Enter key → and now the right zero blinks.
6. Press Info key to change the third digit.
7. Press Enter key → the display will now branch off depending on the
set number – if the value is invalid the main display will reappear.
Set the compressor To make changes easier, the respective setting is changed in large steps.
servicing interval and 1. Enter Code 111, as described under parameterization (see page 12) →
zero the counter and the display shows, as already described, the compressor servicing
interval in blinking digits.
2. Press Info key to change the value.
3. Press Enter key to overwrite the non-volatile EEPROM with the blink-
ing value, and the main display reappears.
Set the motor servicing To make changes easier, the respective setting is changed in large steps.
interval and zero the 1. Enter Code 222, as described under parameterization (see page 12) →
counter and the display shows, as already described, the motor servicing interval
in blinking digits.
2. Press Info key to change the value.
3. Press Enter key to overwrite the non-volatile EEPROM with the blink-
ing value, and the main display reappears.
Set receiver inspection To make changes easier, the respective setting is changed in large steps.
load cycles and restart 1. Enter Code 333, as described under parameterization (see page 12) →
and the display shows, as already described, the receiver inspection inter-
val in blinking digits.
2. Press the Info key to change the value.
3. Press Enter key to overwrite the non-volatile EEPROM with the blink-
ing value, and the main display reappears.
Start leakage measure- This function serves to determine the energy loss resulting from any potential
ment leaks in your compressed air network.
To this purpose, the control unit measures the duration of the operating loads
in time periods during which, under normal circumstances, no production of
compressed air takes place, as for example over night or during operation
downtimes.
This, however, is conditioned on the fact that operational compressed air pro-
duction be discontinued for a protracted period of time and that the compres-
sor be set into the "ready" mode by means of the control system. In case of a
potential pressure reduction below the preset minimum pressure value result-
ing from leaks in the compressed air network, this compressor automatically
switches into the operating mode in order to recover the set pressure range.
The leakage measurement serves to record the duration of the operating load
times and to extrapolate them for the whole year. This allows you to quantify
any leakages and to easily determine their portion of additional costs due to
any energy losses.
A potential leakage is either measured by a single (LE) or continuous (Lc /
LC) value measurement:
In case of single leakage measurement a single measurement operation
over six hours serves to determine the hourly operating load times per year
due to leakage.
If, during measurement, the compressor is put out of operation the number
9990 will be displayed, i.e. the compressor is switched off and the energy loss
due to leakage could not be properly determined during said measurement. In
this case, too, the measurement process should be repeated at a later stage
while making sure that the compressor be switched off during measurement.
Change pressure target If changes are made to these target values, the value of Pmin is automatically
values (pmax and pmin) held or brought outside any applicable minimum hysteresis range.
1. Enter Code 360, as described under parameterization (see page 12) →
and the display shows, as already described, the upper target pressure
value, but blinking.
2. Press Info key to change the value.
3. Press Enter key to overwrite the non-volatile EEPROM with the blink-
ing value, and the lower target pressure value appears (blinking).
4. This value can now be changed by pressing the Info key .
5. Press Enter key to overwrite the non-volatile EEPROM with the blink-
ing value, and the main display reappears.
6. It is not permissible to set the bottom pressure target value below the
stipulated pmin value. In case this should be necessary please contact
BOGE-Service beforehand.
Note!
If the compressor is set for an output release device, the bottom of the main
display shows the appropriate symbol . The following always applies,
even with external output release: if the upper target pressure value in the
compressor is exceeded, the output will be shut off.
Change after-running
time
The after-running time determines the time interval for which the compressor
remains in idling after having reached the parameterised switch-off pressure.
1. Enter Code 019, as described under parameterization (see page 12) →
and the display shows the figure on the left.
The number 30 blinks. The quotation mark symbol here stands for sec-
onds. A run-out curve is indicated on the two right positions.
2. Press Info key to change the value.
(Setting range between 8 and 655 seconds).
3. Press Enter key to overwrite the non-volatile EEPROM with the blink-
ing value, and the main display reappears.
Set continuous
operation
If pressure drops in relatively small receiver / pressure network volumes must
be avoided at any price, continuous operation can be set as follows:
1. Enter Code 733, as described under parameterization (see page 12) →
and the display shows illustration left.
The shading of the left arrow blinks. This means: automatic power econ-
omy operating mode selection.
2. Press Info key to change to illustration (press again to toggle
back...).
The shading of the right arrow blinks. This means: continuous operation.
3. Press Enter key to overwrite the non-volatile EEPROM with the blink-
ing symbol, and the main display with the selected symbol appears.
Enable network
independent ON-OFF
memory (Auto-Restart)
Caution!
With activated automatic restart (Auto-Restart) the compressor restarts
automatically after a power failure.
Condition: the network pressure is lower than the set switch-on pressure and
it was switched on beforehand.
Using energy independent memory for remembering ON-OFF:
Normally a compressor always assumes an OFF status directly after an elec-
trical power failure.
Anti-freeze idling The compressor is set to automatically start an idling phase from standby
(only in mode: when the temperature drops to below +40 °F, and to remain idling until reach-
ing +68 °F final compression temperature.
Ready for operation)
Motor switching Motor switching limitation is only activated when the air requirement makes
limitation it necessary.
Then a switching from intermittent to limited continuous operation – syn-
chronous DB control, is effected. The control unit calculates the cycle time
so that on the one hand the maximum allowed number of cycles per 12 min-
utes can not be exceeded, and on the other hand unnecessary idling times
can be avoided.
Star phase time control The star time is fixed in the control unit according to the type of compressor.
Pre-acknowledgement
If a service message is acknowledged, the cause of which has not (yet) been
attended to, the spanner symbol continues to appear (but no longer blinking).
1.5 Faults
General The tables on the following pages give information on the possible causes of
operating faults and measures for their rectification.
Caution!
Ensure that any work required to rectify faults is only carried out by trained
personnel or specialists. Ensure that components which have a safety func-
tion are only set, repaired or exchanged by BOGE Service!
Please contact the Technical Support at the following telephone numbers, if
you have any questions.
Telephone: +1-770-874-1570
Telephone: +49 5206 601-140
Acknowledgement of messages
Display the message – e.g. by pressing the Info key . Press Enter key
to cancel the display and acknowledge the message. The main display ap-
pears, if the cause for the fault was rectified.
1 Final compression
temperature too high
Ambient temperature too
high
Employ suitable measures to improve the air inlet and venti-
lation in the installation room
Insufficient cooling air Keep air inlet opening to the compressor clean;
quantity check to ensure that any existing cooling air duct systems are
adequatly dimensioned
Temperature sensor defec- Replace temperature sensor or repair the wire break
tive or wire breakage
Excessive network pressure Reduce net pressure to prevent compressor from building up
a pressure exceeding the permissible max. pressure
PTC resistor defective or Overhaul motor
aged
13 Frequency converter /
motor
Motor overload!
Power input too high caused
Ensure correct voltage conditions:
Constant voltage in accordance with IEC 38
by undervoltage
b) Fan motor overloaded Have fan motor checked by BOGE service personnel
Overcurrent fan motor
25 Reconciliation error
Control unit EEPROM
Error loading software.
Control unit defective
Reload software or have control replaced by BOGE-Service
personnel
Warning messages
of the control
10 Motor servicing due Servicing intervals see operating instructions for servicing
11 Compressor servicing
due
Servicing intervals see operating instructions for servicing
18 Fault of an external
control
Higher level (Master) control
faulty
Check supply voltage of master control. Parameterization
of external output release.
Otherwise have control repaired or replaced by BOGE-
Service personnel.
20 Continuous contact of
an external control
Higher level (Master) control
faulty
Check supply voltage of master control. Parameterization
of external output release.
Otherwise have control repaired or replaced by BOGE-
Service personnel.