61800-3 Emc For Power Drive Systems
61800-3 Emc For Power Drive Systems
REO UK LTD
REO (UK) LTD, Units 2 - 4 Callow Hill Road, Craven Arms
Business Park, Craven Arms Shropshire SY7 8NT
Tel: 01588 673411 Fax: 01588 672718
Email: [email protected] Website: www.reo.co.uk
1
Contents
1. Introduction 2
2. What is not covered in this Guide 7
3. Cost implications 9
4. Emissions 17
5. Immunity 54
6. EMC suppression products from REO 56
7. References and further reading 57
B(T), V(v)
-10
-1.0
-20 The same waveform
-1.5 when measured
0 5 10 15 (ms) 20 -30 with a spectrum analyser
4HE MEASURED MOTOR CURRENT -40
IS A REASONABLE
QUALITY SINEWAVE
AT THE DESIRED FREQUENCY -50
etc...
Fundamental (16kHz)
5th Harmonic of 16kHz
-60
kHz
20 50 100 200 500 1,000 2,000
Figure 10:
6 Example of frequency content of a 16kHz squarewave PWM with
! 2μs rise and fall times
Rectifier Chopper
Mains DC AC
6-Pulse type also called switcher
Supply Link Motor
shown here or inverter
Figure 13:
Example of intermodulation increasing the interharmonic levels in a VFD
The remainder of this Guide will Thyristors and triacs switch much
focus on VFDs and VSDs that use more slowly than PowerFETS and
CM noise from rectifier and chopper
PWM, because these are the worst IGBTs, and their switching rate is no that also flows through the DC Link This symbol indicates intentional and/or stray
capacitances to thesite’s earth/ground structure
for creating high-frequency noise higher than the mains frequency. As (whether external cases/frames are earthed/grounded for safety reasons or not) from internal components, heatsinks, windings etc.
Figure 18:
Suppression with mains inductors and filters, and screened motor cables
Figure 17:
Examples of suppressing mains noises
32 33
takes the loop that presents the least problems, is to make the motor
overall impedance. cable very short indeed – less than 50kW VSD
one-tenth of the wavelength at the Chopper
To achieve the low impedance
highest significant chopper harmonic
necessary to control the motor
frequency (e.g. 1m for 30MHz, 10m
output’s CM currents:
for 3MHz, 100m for 300kHz). The
At the chopper end, the motor very best is to combine the BDM with
cable screen must be RF- the motor, with their metal frames
bonded to the chopper’s metal multi-point RF-bonded together,
enclosure, chassis or frame. or combined in a common casting,
At the motor end, the motor so there is no external motor cable
cable screen must be RF- at all. This technique has been
bonded to the motor’s metal very successfully used by some
terminal box, which in turn must manufacturers, including Danfoss.
be RF-bonded to the motor’s All VFD and VSD manufacturers
enclosure or frame (e.g. by should provide detailed EMC
seam-welding or multiple spot or instructions for their products. I do not Braid-screened motor cable’s screen
tack welds). recommend using any manufacturer termination at chopper
who does not (or will not) provide Uses a metal saddleclamp that bonds
Note: Figure 18 does not show an them. They will often be different for to a wide flange extending from the
earth/ground cable between the motor different models and ratings of drives, chassis of the chopper’s electronics
body and the chopper, although one and for example, higher rated drives
will almost certainly be required. This will generally require different filter
is because some VFD manufacturers specifications. Figure 19:
require it to be contained within the Detail of the motor cable connection to the chopper in Figure 16
screen of a screened motor cable, Cable screen RF-bonding is
whereas other manufacturers require sometimes called 360° termination
or 360° bonding, because it should Figure 19 shows an amplified detail
it to be routed outside the screen (but of Figure 16, where the motor cable
still close to the motor cable along ideally make electrical connection all
around the circumference or periphery connects to the 50kW VFD’s chopper
its route). These requirements come unit. It shows that the cable’s braid is
from the electronic design of the of the braid screen. Alternatives, such
as multi-point bonding, may be used clamped to a flange protruding from
VFD, so it is important to obtain the the chopper’s chassis, using a metal
manufacturer’s EMC instructions for providing the bonding points surround
the cable. saddleclamp.
the exact model of motor drive, and
follow them.
A good way to prevent noise from
the chopper which is causing EMC
34 35
Figure 20 shows the other end of the types of EMC gland, the top left-hand
motor cable in the system driven by one being the preferred type. Where
the VFD in Figure 16. Here the motor connectors are used instead, they
cable’s braid uses an “EMC Gland” should terminate the cable screen in
to 360° bond to the motor’s terminal 360° just like an EMC gland.
box. Figure 21 shows a variety of
A high quality cable gland from
KEC
(uses an iris spring to make an
excellent RF-bond
Figure 20:
Detail of the cable connection to the motor driven by the VFD of Figure 16
36 37
Figure 23:
Example of a suitable 360° bond for solid conduit
Figure 22:
Examples of screened flexible conduit and overbraid
Figures 15 and 18 show the DM and associated with a VSD are installed
CM currents flowing entirely within ([37] records some difficulties with
Where it is difficult to source high- for a motor cable, but the usual the VSD assembly, which includes this). So, in practice, the electrical
current cables with good quality “banjo” washers are useless for any mains chokes or filters, and any installation of a VSD and/or its
screens, or when suppressing the suppression purposes because they output filters and/or motor cable associated components (chokes,
noise from a legacy system that rely on lengths of wire to bond them to screen bonds (at the chopper end). filters, isolating transformers, motor
used an unscreened motor cable, an earth/ground terminal, and so have However, electrical installers often cable screen bonds, etc.) might not
overbraids or shielded flexible conduit too high an impedance at RF. Figure seem to be of the opinion that all be compact, and its earth/ground
can be used, as shown in Figure 22. 23 shows one manufacturer’s solution earths or grounds are equivalent, and conductors may connect all over the
When choosing either, make sure that – a conduit nut that makes a multi- also that it does not matter exactly place.
appropriate 360° glands or connectors point 360° bond between the solid where the various components
are available for it. conduit and a metal enclosure at the
point of penetration of the enclosure.
Solid conduit makes the best screen
38 39
It is however very important indeed engineers involved will be blamed for structure, using very short 4.4. More details on
that the following two general getting it wrong, when the problem is electrical bonds. Follow all the suppressing PDS emissions
installation rules are followed: incorrect installation. necessary safety codes taking
the earth/ground leakage A little Guide like this cannot be a
a) All of the component parts of I strongly recommend to all EMC textbook and provide everything one
current from each into account
a VSD, plus its associated engineers associated with such might need to know, but at least it can
(could be several amps, due to
suppression components projects, that they write down provide the basics, and this has been
the mains filtering).
(chokes, filters, isolating mandatory requirements for the done above. This section provides
transformers, motor cable installation of their suppression a few additional notes, and many
screen bonds, etc.) must be in devices, using as much detail as references, on suppressing PDS
very close proximity, ideally needed to communicate with the emissions.
all contained within one metal electrical installers in terms that they
enclosure. will clearly understand – and insisting
4.4.1. Obtain manufacturer’s
that the contract with the customer
b) All of the earth/ground EMC instructions and follow
includes an item covering their
conductors associated with them
inspection and approval of the final
the component parts in a)
electrical installation. VFD and VSD manufacturers EMC
above must connect to one
point, ideally the chassis, Some readers might contrast point b) design/installation guides should
frame, backplate or surface above with other REO Guides, books always be obtained, and their advice
of the metal cabinet they are and articles I have written (e.g. [19] followed accurately. However, they
all contained within. This one [26]) in which the virtues of meshed may not aim to achieve the degree of
point must then connect to common-bonding networks (MESH- noise suppression that is needed (for
the site’s or vessel’s safety CBNs) are extolled at length. Note example when installing many PDSs
earth/ground structure via one that these also allow the possibility in one system, such as the example of
conductor – following all the of combining single-point bonded Figure 3).
necessary safety codes taking systems with mesh-bonded ones, There are many general guides and
the earth/ground leakage so there is no conflict. However, if a textbooks on suppressing emissions
current into account (it could MESH-CBN or MESH-IBN (see [19] or from motor drives, including [31], [32],
be several amps, due to the [26] for definitions) that can control up [33], [34], [35] and [36], and these
mains filtering). to 30MHz, at least, exists in the area might provide sufficient information
where the VSD and its suppression to overcome any shortcomings in the
I make no apology for repeating some
components are located, then b) can drive manufacturer’s EMC installation
of the points already emphasised in
be modified to read as follows: instructions. If even more information
the earlier text. Electrical installers
must be controlled very carefully to b*) All of the earth/ground is required, see the following
ensure that these rules are met in conductors associated with subsections.
full – otherwise all the time and cost the component parts in a)
of determining how to suppress the above must connect to their
drives will be wasted, and the EMC local meshed CBN or IBN
40 41
4.4.2. Filtering Where RF interference is suspected phase CM choke components can be filters on their own, so great care
from a mains or output cable, it will connected in series. should be taken when a VFD is fitted
The specifications for the filters usually be the CM currents that are with an internal mains filter, but its
should be obtained from the VFD or When trying to specify your own
to blame. Clamping a ferrite toroid performance is not enough and you
VSD manufacturer’s detailed EMC mains filter in the absence of guidance
around all of the phase and neutral are tempted to add another filter in
instructions for exactly the model of from the drive manufacturer (or when
conductors in the cable or bundle, with series with it.
drive being used. When not using an that information proves inadequate)
or without including their associated
output filter, longer motor cables – or it is important to understand that, However, multi-stage filters are
protective earthing (safety grounding)
screened or armoured motor cables in real life, mains filters operate available that have excellent
conductor, can sometimes be enough
– will have more stray capacitance, with “mismatched” input and output performance, although the more
to stop the interference, and is
causing an increase in the magnitude impedances – i.e. they are not both stages they have, the larger, heavier
especially effective at frequencies
of the chopper’s CM currents, and 50Ω, or even both the same. All and more costly they tend to be. But
above 30MHz. At frequencies below
may therefore need to use higher- mains filters resonate and provide the author knows custom-engineering
30MHz two or more ferrite toroids may
specification mains filters for the same gain rather than attenuation at their control cubicle manufacturers who
be needed in series on the cable.
level of emissions (all else being the resonant frequencies, and especially automatically fit a 100A 3-phase
same). Distributors stock many suitable so when operated mismatched 5-stage mains filter to the incoming
ferrite toroids, and the split versions – as they always are in real-life. But supply of their cabinets. Although
So the mains filter specifications in a are better for retrofitting (all EMC attenuation data from most distributers over-specified in most cases, they
properly documented EMC installation engineers carry many kilograms of and some manufacturers do not show reckon that it saves them time and
guide should show how the filter various types of ferrite when visiting this, because they only show the cost overall, by avoiding the need
specifications depend on the length of a site to try to solve a problem). It results of “matched” tests (i.e. 50Ω to spend time choosing and proving
the motor cable, and in some cases is important to ensure that all of input and output). which is the most cost-effective filter
on the type of cable too (e.g. screened the power conductors associated for each cabinet.
cable, or cable routed in conduit, will How to deal with the problems of filter
with a mains supply or motor load
have higher stray capacitance than resonance is discussed in detail in Most standard mains filters sold as
pass through the ferrite toroid, and
the same length of unscreened). section 5.10.1 of [19], 4.7.1 of [20] ‘EMC filters’ will not provide much
it may be necessary to wind those
and Chapter 8.1.3.1 of [26]. These attenuation for the VSD’s emissions
For more information on EMC filtering, conductors two or even three times on
all basically recommend getting below 150kHz (see the case study in
and how to assemble it in cabinets, the toroid. Always check that – when
all the CM and DM, matched and 3.4). Filters suitable for VSDs must
systems and installations to get maxi- installed on a cable – the ferrites do
mismatched test data from the filter provide good attenuation down to the
mum benefits, see section 5.10 of not get too hot to hold your hand on
supplier (6 curves in all), drawing the chopper’s fundamental frequency (i.e.
[19], 4.7 of [20] and Chapter 8 of [26]. for several minutes, when the drive
worst case of all of the attenuation switching frequency) for both the DM
is running at full power. Ideally, they
Mains harmonics can be filtered, curves, and assuming that a filter’s and CM noise emissions. The CM
would hardly get warm at all, and if
instead of simply reduced by line real-life performance will be no better attenuation is especially important.
they do it usually means that a much
inductors. However, because of their than that.
larger ferrite is required. CM + DM output filters convert the
low frequencies special passive and/ Cascading mains filters is generally PWM output into a relatively “clean”
or active filtering techniques are used, For even better performance from a
a bad idea. Resonances can occur DC or AC waveform, that can be sent
and these are discussed in pages 51 ferrite CM filter at low frequencies,
that make the attenuation of the significant distances, over perfectly
through 55 of [29]. wound single-phase and three-
combination worse than any of the ordinary cables to the motor, without
42 43
causing interference problems – able to tell you which VFDs or VSDs Ships and other vessels generally or when it is “corner-grounded” (one
incidentally improving cable and motor they are suitable for. use mains supplies that do not have phase connected to earth/ground,
life as mentioned earlier. But because their neutral directly bonded to their rather than the neutral), all capacitors
In between low-cost ferrite toroids
they are costly, such output filters earth/ground structure [35], and some connected to the earth/ground (e.g.
and expensive CM + DM motor output
will probably not even be mentioned land-based installations also use this in a filter) should be safety-rated for
filters, there are various medium-cost
in most drive manufacturers’ EMC practice. This situation is discussed in the full phase-to-phase voltage, rather
alternatives. So-called dV/dt filters
instructions. Section 4.5. than phase-to-neutral.
“round off” the edges of the motor
Where using screened motor cables output PWM waveforms, which – in
is impractical for some reason, the frequency domain – attenuates 4.4.3. Safety issues with 4.4.4. Benefits of isolating
CM+, DM filters like REO’s Sinus ++ the higher frequency noise spectrum. filtering transformers
series may be the only solution. The Figure 24 shows the effect of applying Filters contain capacitors from the Where a BDM is not powered from
manufacturers of the filters should be a REO dV/dt output filter to a VFD. phase conductors (mains or motor) a co-located dedicated step-down
to the earth/ground, and these isolating mains transformer, and
The same VFD output increase the current in the protective where the mains power supply that
Rising edge of PWM output earthing conductor (the green/yellow feeds it is shared with other electronic
waveform from a VFD waveform with a REO
striped wire in the mains supply). equipment (which may include other
CNW 811 “dV/dt filter” fitted
Safety standards and electrical BDMs) that are not co-located with
wiring codes set quite low limits on the BDM concerned – then a number
this current, to help prevent electric of EMC issues arise that may be
shock hazards, but they will allow best dealt with by fitting the BDM
any amount of earth/ground leakage with a dedicated co-located isolating
current when high-integrity earthing/ transformer.
grounding systems are used with a
Isolating transformers are large and
fixed VSD installation (i.e. one that
costly components, especially for
does not have a flexible mains lead or
high-power BDMs, but omitting them
mains plug, sometimes called “non-
or trying to use less costly alternatives
pluggable” equipment.).
can prove to be more costly overall
The high earth/ground leakage (see section 3).
currents caused by filters can also
6OLTAGE RISE
K6 S 6OLTAGE RISE
K6 S In situations where a mains power
make it impossible to use residual-
-EASURED WITH M OF MOTOR CABLE -EASURED WITH M OF MOTOR CABLE supply feeds two or more items of
current circuit breakers (RCCBs),
equipment spread over a site or
earth leakage circuit breakers
vessel, the DM impedances of the
Figure 24: (ELCBs) or ground-fault interrupters
“Rounding off” the PWM waveform with a dV/dt filter
phases can become different from
(GFIs).
each other due to unequal loading,
Where the mains system is isolated and the CM impedance between the
from the safety earth/ground (see 4.5), phases and the earth/ground can
44 45
become quite low due to the stray mains filter. But all chokes cause However, there are techniques 4.4.5. More detail on
capacitances of the long cables and some voltage drop and so this might available for decreasing the stray
RF-bonding techniques
the CM filters in other equipment. cause an increased rate of tripping primary-secondary interwinding
These impedance effects negatively due to sags or dips in the supply. capacitance, and for adding Figure 25 shows the basics of the
affect the performance of a BDM’s Another possibility is to fit an earth/ interwinding screens. These can ideal method of RF-bonding two
mains filter (see [36]). Fitting an ground choke to the BDM, which of be used to provide better isolation metal items together (e.g. RF-bonding
isolating transformer restores the course will only work if it is fitted to performance and higher CM source the metal bodies of the mains filter,
balance to the DM impedances, and the single conductor that connects impedance, from DC to radio rectifier and chopper to the backplate
also restores a high CM impedance, the BDM’s earth/ground to the earth/ frequencies, which may be needed on in Figure 16).
helping the mains filter achieve its ground structure of the site or vessel occasion, for example when a mains But there are many more details
designed potential. (see item b in Section 4.3). filter is not fitted at all. that could be important, and in
Earlier, I discussed how a BDM’s But an isolating transformer dedicated some cases alternatives might be
CM return currents were ‘steered’ by to the BDM and co-located with it appropriate, so the information in
capacitors in its input and/or output (see item a in section 4.3) will provide
filters and their low-impedance much better control of CM currents Any insulating finishes Anti-vibration device,
bonding to the BDM’s chassis/frame, than any chokes. removed from entire e.g. Anti-vibration washer
bonding area or other method
so that they flowed mostly in the But never use chemical
A mains isolating transformer might (e.g. paint, anodising,
BDM’s assembly. But when the CM polymer passivation) ‘thread-lock’
also prove to be sufficient, on its own
impedance of the mains supply
without a mains filter, for preventing
is low the ratio between the path Note: this RF-bond
the CM noise from a BDM’s mains is shown partially
impedances provided by the mains
input from circulating widely. It would disassembled
filter and that provided by the mains
do little or nothing for the BDM’s DM
supply might not be as high as we
noise emissions, or the resulting
would like. For example, where there
waveform distortion, but this is often
are two or more equipments fitted with
not as much of a problem as the CM
mains filters connected to a mains
noise emissions anyway.
supply, their low CM impedances
Metal components to
encourage the CM currents of each Where a BDM is fitted with a mains be RF-bonded
item of equipment to flow in the filter that deals with CM noise as Conductive gaskets
could be inserted here
other’s mains filter – encouraging CM well as DM, the majority of problems
currents to flow widely, which is not with widely-circulating CM currents Do not rely on screw
what we want. occur at lower frequencies, below Reliable RF-bonds re created by pressing
threads of any type to
together highly-conductive metal surfaces
150kHz. In this case experience make the RF-bonds
Where a BDM’s mains filter does not Materials should be chosen to prevent
seems to show that the normal oxidation or corrosion over the lifecycle,
include a CM choke on the supply taking the real-life environment into account
type of construction for an isolating
side of its CM capacitors, this problem
transformer is adequate for controlling
can be reduced by fitting a CM choke
CM currents in this frequency range.
in that position, co-located with the Figure 25: RF-bonding two metal surfaces
46 47
section 5.7 of [19], 2.2 through 2.5 the DIY screen-bonding technique of 4.4.7. Screened (shielded) but is now EN/IEC 61000-6-4). Each
of [20] and Chapter 5 of [26] may be Figure 26. enclosures VFD complied on its own, but when all
useful. the drives in the cabinet were running,
However, where a screened enclosure EN/IEC 61800-3 is rather dismissive their aggregate emissions were
4.4.6. More detail on cable (e.g. cabinet, room, etc.) is used (see of the potential of PDSs to interfere significantly above the limit line.
screening (shielding) 4.4.5), “proper” glands like the top with radio reception through
left-hand side on in Figure 21 should radiated emissions. However, VFDs As PowerFETs and IGBTs develop,
techniques always be used (or connectors with they are designed to switch faster
– especially low-power ones switching
This will be found in sections 5.7.6 similar screened braid terminations). at over 20kHz – have been known to to reduce heat losses and increase
through 5.7.10 and 5.11 of [19], 3.7 of interfere with radiocommunications, efficiency, so the prospects for
[20] and Chapter 7.2 of [26]. as some items in [15] show (e.g. No. radiated interference can only worsen.
24). And as mentioned in section 3, more
Screen bonding need not be costly, radiocommunications are being used
especially where there are number As long ago as the early 1990s I everywhere, which also increases the
of cables screens to be bonded (e.g. have had to improve the shielding potential for radiated interference from
to a cabinet backplate) as shown by of industrial control cabinets that PDSs.
contained several VFDs, to pass the
Metal clamping plate radiated emission tests to the generic Designing and/or installing shielded
Cable screens exposed emissions standard for the industrial enclosures requires a lot of attention
to make good contact environment (which was EN 50082-1, to detail, but the basic principles are
Screened cables entering/leaving the BDM with the gaskets
(Strain relief and environmental sealing not shown) outlined in Figure 27, which shows
Filters
Figure 27:
The basic principles of employing a screened enclosure
Figure 26:
A low-cost way to RF-bond multiple cable screens
48 49
that no conductor of any type (even A great deal of detail on the whines and whistles if routed too close 4.4.10. Mains harmonics and
a mechanical push-rod or metal pipe) design and installation of shielded to cables associated with a drive, and interharmonics
can enter/exit a screened enclosure enclosures, of all sizes from just large are a matter of some concern to EN/
without either: enough for one small VFD, up to IEC 61800-3 (see 6.2.5 in [1]). For a These are typically suppressed by
screening an entire room or even a real-life example of serious telephone using a “3% inductor” in series with
a) Being RF-bonded to the the rectifier, as shown in Figures 15
building, will be found in the following: interference from a high-power drive,
enclosure’s metal wall at the point of and 16. The 3% refers to the fact that
section 5.12 of [19], section 5 of [20] see Item 1 in [15].
entry/exit, or when carrying its full rated current, its
and Chapter 6 of [26].
Cable classification and segregation internal impedance reduces the mains
b) Being filtered to an appropriate
is covered in section 4.8 of [19] (4.4 voltage by 3%. This is considered
specification, with the filter RF-bonded 4.4.8. Other EMC techniques is also important); 3.3 of [20] and to be a cost-effective compromise,
to the enclosure’s metal wall at the
The above discussion has not Chapter 7.4 of [26]. but sometimes it is necessary to go
point of entry/exit, or
addressed all the EMC techniques as high as a 4% inductor. Increasing
c) Being a screened cable with an that will probably be required, for 4.4.9. Commutation notches the impedance even further is not
appropriate specification, the screen which read [31] [32] [33] [34] [36] and advised, so if series inductors have
being RF-bonded (i.e. 360° bonded) Voltage “notching” is an emission
[19] [20] and [26]. not managed to reduce the harmonic
to the enclosure’s metal wall at the problem caused by naturally
For example, most (if not all) VFD commutated thyristors/triacs in DC and interharmonic emissions by
point of entry/exit. enough, other techniques must be
manufacturer’s EMC installation drives. The cross-conduction when
No alternatives are ever permitted, for instructions, as well as [33] [34] and one thyristor or triac turns on before used instead of, or as well as, series
any reason. I am often asked to solve [36] will include the requirement to another has finished turning off, inductors.
real-life problems in which expensive classify the cables associated with momentarily shorts-out their phases Single-phase VSDs and VFDs
shielded cabinets are found to be a PDS according to some rules, and causing a dip with a depth of 100%. suffer from emitting all of the odd-
“leaking”, and the usual problem is then to route these “cable classes” numbered mains harmonics, including
that some conductor assumed to Although this is a low-frequency
separately from each other, with triplens as mentioned earlier. On
be insignificant (e.g. hydraulic pipe, noise, it is very severe and can
certain minimum spacings to be four wire systems (i.e. 3 phase + N)
mouse cable, etc.) has been allowed interfere with other equipment that
maintained between cable classes the triplens add arithmetically in the
to enter/exit the enclosure without is using those phases. However,
where they are routed in parallel. neutral conductor causing significant
one of the above three methods being a “3% inductor” such as is often
This acknowledges the fact that no fitted to reduce emissions of mains problems with localised power quality
applied. and equipment operation. However,
cable screens or filters are perfect, harmonics and interharmonics (see
However, sometimes the problem has so it helps to reduce the crosstalk 4.4.8), will generally provide adequate three-phase (6 pulse) drives running
been that the system integrator has between the cables, especially from suppression. from reasonably low-distortion mains
simply cut a large hole in the wall or the motor output to the mains supply supplies have very low levels of
door of the screened enclosure, to [1] calls this series inductor a “triplen” harmonics, of which the most
or control cables. It also helps ensure
mount their human-machine interface, “decoupling reactance” and requires important are the 3rd and 9th. Losing
low crosstalk to cables that are not
destroying the screening effectiveness that its size be specified. the 3rd makes it easier to use series
associated with the drive, such as
in the process. telephone cables, which can suffer inductors to get good levels of mains
dramatically from audio-frequency harmonic reduction.
50 51
Phase-shifting mains transformers ships and vessels often use special is really a chopper that is controlled filters up to almost 3,000kW for both
can be used to create six-phase harmonic suppression techniques that to source or sink mains currents in AC and DC drives. Being passive
(often called 12-pulse) rectifiers, are not commonly used in land-based antiphase to those that are causing and linear, they do not cause EMI
which has the effect of causing the 5th installations, see [35] for details. problems, and – despite its name – is emissions.
and 7th harmonics to be substantially not a filtering technique at all. Passive
A reasonably new design technique, Cost-effectiveness calculations may
cancelled out in the rectifier’s circuits, and active harmonic filters are often
at the time of writing, is the “active show that it costs less to allow all
so that its first significant mains used where it is desired to deal with
front end” (AFE), which uses IGBTs the PDSs on a site or in a vessel to
harmonic is the 13th. Increasing the harmonics of all the equipment
instead of plain old rectifiers. These emit their harmonics, and to clean
multiples of three phases (or six on one floor of a building, or even an
are switched at a high rate, just like them up with a single filter (passive or
pulses) attenuates even higher-order entire building, site or vessel, instead
a chopper that drives PWM into a active) so that they do not cause too
harmonics, but the specification on of dealing with them at the level of
motor, but control software arranges much distortion of the mains voltage
the purity of the mains supply’s sine individual items of equipment.
the sequencing and timing so that, waveform.
waveform and equipment and phase
after passing through a series inductor Active filters, introduced some 10
shift transformer quality (internal These and other “installation level”
to average out the PWM, the result is years ago, are expensive but widely
imbalance tolerance levels) must techniques are discussed in pages
a rectifier that appears to the mains used. These electronic ‘filters’ provide
increase with the number of phases 42-62 of [29], and [35].
supply as a substantially linear (i.e. a very low impedance source (<1%)
for this to be effective. However,
resistive) load, which as a direct for the harmonic currents. Therefore,
using large or multiple-phase-shift 4.4.11. Mains voltage
consequence is claimed to achieve if rated correctly, the load(s) draw the
transformers, as is typical of oil fluctuations
low emissions of mains harmonics harmonic currents from the active
production platforms, can still reduce
(<5% Ithd). filter whilst the source provides only [1] sets limits for the generation of
this excessive voltage distortion,
the fundamental current. Depending mains voltage fluctuations, for which
especially at higher order where they However, AFEs achieve this at the
on the type, active filters can reduce there are only a few installation-
are both most problematic and difficult cost of significant harmonic currents
harmonic emissions to below 5%. level mitigation techniques, such as
to treat. in the supply at the switching
Active filters are parallel devices, Dynamic Voltage Restorers (DVRs)
frequency of the AFE bridge, higher
Ships and other vessels often have and so only need to be rated for the see pages 36-49 of [30].
EMI emissions between 10kHz and
very distorted mains supplies because harmonic current.
100kHz, and other a number of other At the level of the motor drive, the
their electricity generators have much
issues. AFE rectifiers, being series The other type of harmonic filter major benefit comes from using “soft-
higher (about 3 times) the source
devices, have to be dimensioned which is very popular is worldwide starting”, especially for AC motors
impedance of a landlubber’s HV
for the total load. This, of course, is the passive “wide spectrum filter”. because they can draw very large
transformer of the same VA rating, and
a matter of drive selection, and is These are multi-limbed reactors magnetising currents when switched
also because of the increased use of
not otherwise under the control of a wound on a common core, fitted Direct-On-Line (DOL) near the
powerful VFDs in “electric thrusters”
system integrator or installer. with a small capacitor bank (not like zero-crossings of the mains voltage.
and even electrical propulsion. For
traditional passive filters). They are Using VFDs solves this problem
this reason, 6-phase and higher Filtering was mentioned earlier
connected in series with the load(s) automatically.
(12-pulse and higher) rectifiers are as a means of suppressing mains
and – depending on manufacturer
often unsuitable for ships, because harmonics, using passive filters such Where high-powered drives have a
– can also reduce the Ithd to around
they rely on low-distortion mains for as resonant traps. Another technique rapidly fluctuating load, the fluctuating
5%. One manufacturer supplies these
their harmonic improvements. So is the so-called “active filter”, which
52 53
motor currents can also give rise to in a steel mill, often the only solutions necessary) either filtered or screened. from ground, and says that in
significant mains voltage fluctuations. are either to make sure that sensitive When filtering techniques are used, such situations the only mitigation
This may be able to be cured by equipment is located far enough away filters may be needed at both ends, possible is to ensure that all the other
adding inertial energy storage (e.g. a not to be effected, use equipment because the DC-Link carries noises equipment on the site is immune
larger flywheel) or by installing a DVR that is not sensitive (e.g. use plasma generated by both the rectifier and the enough to the noise emitted by the
with an adequate rating, see 5.3.9 on or LCD computer screens instead of chopper. PDS. But this ignores the possibility of
page 48 of [30]. cathode ray tube (CRT) types), or fit interference with equipment off-site,
localised screening to the affected 4.4.14. Neutral shift can and with radio receivers, so is not a
4.4.12. Radiated EM items of equipment. stress motor insulation complete solution.
disturbances – low frequency Screening for very low frequencies Section 4-12 of [36] discusses the However, if filters are fitted to
H-fields can be passive (e.g. using problems of increasing neutral- individual BDMs as recommended
MuMetalTM); or active, in which metal earth/ground voltage caused by in this Guide, all that is necessary
These are suppressed by the filtering
frameworks are driven with currents VSDs with Wye-connected inputs. It is to “float” the chassis, frame or
and cable screening methods
to create magnetic fields that “cancel also discusses solutions that can be enclosure of the BDM. Since the
discussed earlier, and by ensuring
out” the local ambient magnetic field. used when a Delta connected mains mains and output filters (if used) will
that all conductors carrying DM loops
input cannot be used. These include be RF-bonded directly to the BDM’s
are in close proximity, preferably Where there are powerful currents
using an isolation transformer at the chassis, frame or enclosure they will
twisted together, along their entire there is always the possibility that
mains input and floating the neutral not increase the leakage current into
route, see section 4.4 of [19]. human exposure to the resulting
connection to the VSD. the earth/ground. Of course, this will
magnetic fields could be too high, see
Where cables carry currents that are mean protecting the BDM from being
[10] and [11] for limits, and methods
too large to permit them to be twisted touched, to prevent personnel from
for testing and calculation. 4.5. Insulated Neutral,
or placed close together, because suffering electric shocks if there is
of the physical damage that would “floating” mains power a phase-to-earth/ground fault in the
occur to their insulation due to the 4.4.13. Emissions from the systems system.
electro-motive forces acting on their DC-Link
Ships and other vessels generally use When using cable screens and/or
conductors, it may be possible to DC-Link conductors can carry as mains supplies that do not have the armour instead of output filters, a
arrange for external shielding around much noise as the output cables. neutral of their mains power supply capacitive RF-bond could be used at
the bundle of conductors to protect Figure 14 shows that there is some directly bonded to their earth/ground one end of the motor cable, either at
nearby equipment from the magnetic stray capacitance to earth/ground structure [35], and some land-based the BDM or in the motor’s terminal
fields (see 5.12 in [19]). from the DC-Link conductors, so the installations also use this practice. box. This will not be as effective as
But shielding can be very costly, noise voltages and currents on the This is known as an IT power network a proper 360° RF-bond, but may be
especially in the case of very low DC-Link can couple noise into other (nothing to do with Information good enough if their lead lengths
frequencies – say below 1kHz – equipment and radio receivers by Technology!). are kept very short. For safety, such
where it can also be very difficult to do induction or radiation. screen-bonding capacitors should
EN/IEC 61800-3 [1] assumes
at all. Where problems arise with low- The DC-Link should therefore be (D.1.2.2 and D.2.2) that filtering is be safety-rated for the full phase-to-
frequency magnetic field emissions, treated like a motor cable: made an unsuitable technique where the phase voltage, and of course their
for instance in a ±8kA DC drive I saw as short as practicable, and then (if mains power network is isolated effect on the amount of earth/ground
54 55
leakage current must be taken into 5. Immunity 5.1. Power quality issues high frequencies.
account.
As well as dealing with emissions, Section 5 of [30] is the most relevant A technique that attenuates an
Another technique for reducing the EN/IEC 61800-3 [1] specifies test reference for installation-level equipment’s emissions of a particular
earth/ground leakage of filters and methods and test levels for immunity. methods for dealing with poor power electromagnetic disturbance,
cable screen/armour bonds, is to fit The issues it is concerned with are: quality, and 4.2 of [19] will also be generally provides a similar level
a co-located isolating transformer useful. of attenuation when protecting
to the PDS so that it can be bonded Power quality issues, including: equipment from interference by that
directly to the earth/ground without Distorted mains supplies Part 6.5 of [21] describes a number same type of disturbance.
compromising the rest of the system. (including harmonic distortion of ways of designing equipment to
Of course, if the PDS is powered from and commutation notches) improve its immunity to power quality
issues, and some of those techniques
5.3. Surge transients
a dedicated and co-located step- Supply voltage deviations,
down isolating mains transformer, can also be applied “stand-alone” to a Series inductors used for suppressing
variations, changes, fluctuations, PDS, system or installation.
a separate isolating transformer is emissions of harmonics or
dips, dropouts and short
not required – its EMI suppression commutation notches also help
interruptions And the techniques for dealing with
function is provided by the step-down increase a drive’s immunity to surge
commutation notching and other
transformer. Three-phase voltage unbalance transients. Other techniques are
low-frequency emissions such as
galvanic isolation and surge protection
Mains frequency variations harmonics and interharmonics
devices (SPDs), which are discussed
described in section 4 above, may
Magnetic fields in sections 4.3 and 5.13 of [19],
also be able to be used to improve
Conducted continuous EM respectively.
immunity to those electromagnetic
disturbances (150kHz to 80MHz) disturbances. These techniques can be used
Fast transients individually, or together in any
Radiated continuous EM 5.2. Magnetic fields, combination.
disturbances (80MHz to 1GHz)
conducted/radiated
Surge transients 5.4. Electrostatic discharge
disturbances, fast transients
Electrostatic discharge (ESD)
Most of these are best dealt with Where a PDS has problems
by the design of the equipment, as complying with the tests for immunity ESD techniques for equipment are
described in [21] and [22], and so not to magnetic fields; conducted covered in part 6.1 of [21], and they
in the scope of this Guide. continuous EM disturbances can be applied to a complete BDM
(150kHz to 80MHz); fast transients, by enclosing it in either a plastic
To discuss what can be done to and/or radiated continuous EM enclosure (to prevent ESD from
improve the immunity of a PDS by disturbances (80MHz to 1GHz) occurring at all) or in a shielded
using installation techniques, the – the usual solutions are to use the enclosure (to divert ESD disturbances
immunity problems can be broken filtering and screening techniques away from the BDM’s electronics
down into four groups, see below. discussed in section 4 above for within).
suppressing emissions of low and Plastic enclosures do not protect
56 57
from the radiated fields of a nearby 6. EMC suppression 7. References Conformity, March 2008, pages
discharge, so it may turn out that a products from REO and further reading 12-22, http://www.conformity.
shielding solution is better. This is com/PDFs/0803/0803_F1.pdf.
then just a matter of applying the Figure 28 shows the range of products [1] EN 61800-3:2004, “Adjustable Also published in a slightly
shielding techniques briefly introduced that REO provides for suppressing Speed Electrical Power Drive amended form in Conformity’s
in 4.4.5 above, usually aiming for the and/or protecting motor drives. Systems – Part 3: EMC 2009 Annual Reference Guide.
upper frequency to be controlled to be requirements and specific test
methods”. Identical to IEC [4] Seventeen EMC Guides on EM
at least 1GHz, ideally 3GHz.
61800-3:2004. phenomena, legal compliance
To suppress ESD within an installation and EMC testing have been
means preventing it from happening [2] European Union Directive written by Keith Armstrong
by using static control measures: 2004/108/EC (as amended) on and published by REO (UK)
dissipative flooring and other surfaces, Electromagnetic Compatibility Ltd. They are very readable
dissipative clothing, ionising blowers, (2nd Edition) in English: http:// and practical, and can be
control of relative humidity etc., all eur-lex.europa.eu/LexUriServ/ downloaded from www.reo.co.uk/
very familiar to anyone who has site/en/oj/2004/l_390/l_ knowledgebase.
worked in semiconductor manufacture 39020041231en00240037.pdf
They are also available from
or light electronic assembly. – in any EU language: http:// REO (UK) Ltd and Cherry
DC Converter PWM Inverter ec.europa.eu/enterprise/electr_ Clough Consultants as a CD-
equipment/emc/directiv/dir2004_ ROM that contains all 17 of them
108.htm plus two other REO EMC Guides
The Directive’s official and a great deal of other useful
L1
L2
M
EU homepage includes a information on EMC.
L3
3
downloadable version of the [5] “On-Site EMC Test Methods”,
Line Inductor Input Filter Output Filter current EMC Directive and its Keith Armstrong, EMC Test Labs
successor; a table of all the Association (www.emctla.co.uk)
dV/dt EN standards listed under
Filter
Technical Guidance Note No.
Braking Resistor
the Directive; a guidance TGN 49, also available from the
document on how to apply the “Publications and Downloads”
Directive; lists of appointed EMC pages at www.cherryclough.com.
Motor
Inductor
Competent Bodies; etc., all
DC Link Choke at: http://europa.eu.int/comm/ [6] The EC’s official Guide to
enterprise/electr_equipment/ 2004/108/EC can be downloaded
emc/index.htm. from: http://ec.europa.eu/
Combined Filter Inductor
Sinusoidal
enterprise/electr_equipment/
Filter [3] Keith Armstrong, “Complying emc/directiv/dir2004_108.
with the EMC Directive htm#guide
Figure 28: REO’s motor drive products
(2004/108/EC), Second Edition”,
58 59
[7] The EMC Regulations 2006, [12] 2004/40/EC, “On the minimum More “Banana Skins” are [19] REO Guide on “Good EMC
United Kingdom Statutory health and safety requirements published 6 times a year in “The Engineering Practices in the
Instrument 2006 No. 3418: http:// regarding the exposure of EMC Journal”, available free at Design and Construction
www.opsi.gov.uk/si/si2006/uksi_ workers to the risks arising from www.theemcjournal.com or www. of Fixed Installations”, free
20063418_en.pdf, implementing physical agents (electromagnetic compliance-club.com. download from: www.reo.co.uk/
2004/108/EC in UK law. fields) (18th individual Directive knowledgebase
[16] IEC TS 61000-1-2, basic safety
within the meaning of Article
[8] The official guide to the UK’s publication, draft second edition, [20] REO Guide on “Good EMC
16(1) of Directive 89/391/EEC)”,
2006 EMC Regulations is posted January 2008, “Electromagnetic Engineering Practices in the
dated 29 April 2004. From:
under “Related Documents” Compatibility (EMC) – Part 1-2: Design and Construction
http://www.hse.gov.uk/radiation/
at: http://www.berr.gov.uk/dius/ General – Methodology for the of Industrial Cabinets”,
nonionising/l184emf.pdf
innovation/regulations/ecdirect/ achievement of the functional available from www.reo.co.uk/
page12469.html [13] EN/IEC 61800-5-2, “Adjustable safety of electrical and electronic knowledgebase
speed electrical power drive equipment with regard to
[9] The consolidated version of the [21] Keith Armstrong, “Design
systems – Part 5-2: Safety electromagnetic phenomena.”
Low Voltage Directive, 2006/95/ Techniques for EMC” in six
requirements – Functional”
EC, replaces 73/23/EEC and its [17] The IET, “Guide on EMC for parts, The EMC Journal, Issue
amendment by 93/68/EEC, http:// [14] IEC 61508: “Functional Safety Functional Safety”, August 2008, 62 through Issue 77 (January
europa.eu.int/comm/enterprise/ of Electrical, Electronic and ISBN 978-0-9555118-2-0 2006 through July 2008), www.
electr_equipment/lv/index.htm Programmable Electronic theemcjournal.com, (search by
Cost £27 plus p&p from http://
Systems” (seven parts) “Keith Armstrong”)
[10] 1999/519/EC, “Council www.emcacademy.org/books.
recommendation 1999/519/EC [15] The First 500 “Banana Skins”, asp or free download from www. [22] Keith Armstrong, “EMC for
on the limitation of exposure Nutwood UK, 2007, 500 reports theiet.org/factfiles/emc/index. Printed Circuit Boards – Basic
of the general public to and anecdotes concerning cfm. and Advanced Design and
electromagnetic fields (0 Hz electromagnetic interference Layout Techniques”, Nutwood/
[18] The “Machinery Safety Directive”:
to 300 GHz)”, from: http:// (EMI). Read it at www. Armstrong, February 2007, £47
“Directive 98/37/EC of the
ec.europa.eu/enterprise/electr_ theemcjournal.com, or buy plus p&p.
European Parliament and of
equipment/lv/emf.htm from [email protected]
the Council of 22 June 1998 on Perfect bound (with titled spine):
(approximately £10) or via http://
[11] EN 62311:2008, “Generic the approximation of the laws of ISBN 978-0-9555118-1-3
www.emcacademy.org/books.
standard to demonstrate the Member States relating to
asp. Spiral bound (lays flat):
the compliance of electronic machinery”
ISBN 978-0-9555118-0-6
and electrical apparatus Numbers: 1, 18, 50, 101, 162,
The new Machinery Safety
with the basic restrictions 168, 233, 274, 278, 279, 282, Order via http://www.
Directive: “Directive 2006/42/EC
related to human exposure to 324, 433, 438, 455, 469, 483 emcacademy.org/books.asp
of the European Parliament and
electromagnetic fields (0 Hz - concern incidents associated
of the Council of 17 May 2006 [23] Keith Armstrong, “BOM Cost and
300 GHz)” (a modified version of with switch-mode power
on machinery, and amending Profitability”, The EMC Journal,
IEC 62311:2007, it replaces EN conversion, including variable
Directive 95/16/EC (recast)” Issue 82, May 2009, pages 32-
50392:2004). speed motor drives.
34, www.theemecjournal.com
60 61
[24] Keith Armstrong, “Getting What [32] “Variable Speed Drives – A Guide International EMC Symposium,
You Want”, The EMC Journal, to Supply Harmonics and Other Austin Texas, USA, 17-22 August
Issue 77, July 2008, pages 19- Low-Frequency Disturbances”, 2009, ISBN: 978-1-4244-4285-0
21, www.theemcjournal.com Emerson Industrial Automation,
free download from: www.
[25] Keith Armstrong, “Absence of
controltechniques.com/guides EN and IEC standards may be
Proof is Not Proof of Absence
purchased from British Standards
(and the “proven in use” fallacy)”, [33] “A Guide to Electromagnetic
Institution (BSI) at: orders@bsi-global.
The EMC Journal, Issue 78, Compatibility (EMC) for
com. To enquire about a product or
September 2008, pages 16-20, Variable Speed Drives”,
service call BSI Customer Services
www.theemcjournal.com Emerson Industrial Automation,
on +44 (0)20 8996 9001 or e-mail
free download from: www.
[26] Tim Williams and Keith them at [email protected].
controltechniques.com/guides
Armstrong, “EMC for Systems IEC standards can also be purchased
and Installations”, Newnes, [34] “Control Techniques Drives and with a credit card, in English and
2000, ISBN: 0-7506-4167- Controls Handbook, 2nd Edition”, many other languages, from http://
3, www.bh.com/newnes, RS Bill Drury, IET publishers, 2009, [email protected].
Components 16/No. 377-6463, ISBN 978-1-84919-013-8, www.
(approximately £47, paperback) theiet.org/publishing/books/
pow-en/control-techniques-2nd-
[27] Keith Armstrong, “The Truth Acknowledgement
ed.cfm
of Murphy’s Law”, The EMC
Journal, Issue 79, November [35] American Bureau of Shipping, Many thanks to Ian Evans of Harmonic Solutions Co.UK, for reviewing this text
2008, pages 16-18, www. “Guidance Notes on Control of and making many very useful suggestions.
theemcjournal.com Harmonics in Electrical Power
Systems”, May 2006, free
[28] Pulse-Width Modulation (PWM),
download from: www.eagle.
see: http://en.wikipedia.org/wiki/
org/absdownloads/getpub.
Pulse-width_modulation
cfm?pub=150
[29] REO (UK) Ltd Guide on
[36] EPRI, “Trouble-Shooting Guide
“Harmonics”, available from
for Low-Voltage ASD/Motor
www.reo.co.uk/knowledgebase.
Systems”, TR-11097, final report
[30] REO Guide on “Power Quality”, November 1998, free download:
available from www.reo.co.uk/ http://mydocs.epri.com/docs/
knowledgebase. public/TR-111097.pdf
[31] REO Guide on “Power Quality [37] K O Phipps, P F Keebler and
for Variable Speed Drives”, free R F Arritt, “Real World ASD
download from: www.reo.co.uk/ Interference Case Study with
knowledgebase Modeled Solutions”, IEEE 2009
62
and has written and presented a
great many papers and articles on
EMC. He is a past chairman of the
IEE’s Professional Group (E2) on
Electromagnetic Compatibility, is a
member of the IEEE’s EMC Society,
the EMC Test Labs Association [59],
the EMC Industries Association
(www.emcia.org), and chairs the
IEE’s Working Group on ‘EMC and
Functional Safety’.
Contact: Keith Armstrong by email at
[email protected]
or visit the Cherry Clough website
www.cherryclough.com.