MSR127 Minotaur Monitoring Safety Relays: Installation Instructions
MSR127 Minotaur Monitoring Safety Relays: Installation Instructions
Original Instructions
Topic Page
Rockwell Automation cannot accept responsibility for failure of this device if the
procedures given in these instructions are not followed or if it is used outside the
Summary of Changes 1
recommended specifications in these instructions.
Safety 1
Repair 1
Functional Description 1
IMPORTANT The safety inputs of these products are described as
normally closed (N.C.), that is, with the guard closed, the
Specifications 2 actuator in place (where relevant) and the machine able to
Diagnostics 2 be started. Exposure to shock and/or vibration in excess
of what is stated in IEC 60068 part: 2-6/7 must be avoided.
Safety Input 2 Adherence to the recommended inspection and
Reset 2 maintenance instructions forms part of the warranty.
Installation 3
Wiring Examples 3
Circuit Diagram 3
Repair
Approximate Dimensions 3
Safety Specifications 4
ATTENTION: MSR127 safety relays are not repairable.
Declaration of Conformity 4
If there is any malfunction or damage, do not attempt to repair. The unit must be
Summary of Changes replaced before machine operation is allowed.
This publication contains the following new or updated information. This list
includes substantive updates only and is not intended to reflect all changes.
Functional Description
Topic Page The unit is enabled once the supply is powered up and the safety circuits are
Updated Declaration of Conformity 4 closed. The PWR status indicator is on.
A valid reset operation activates the safety outputs. The CH1 and CH2 status
Safety indicators of the output illuminate. At the demand of the safety function and if any
This device is intended to be part of the safety-related control system of a fault occurs, the safety outputs de-energize within the specified response time.
machine.
Fault Detection
Safety Notes If a fault occurs, the internal relay circuit forces the safety outputs off. One or both
Before installation, perform a risk assessment to determine whether the output status indicators can be off. The PWR status indicator can flash. Remove
specifications of this device are suitable for all foreseeable operational and the fault and cycle the safety input to re-enable the device. Cycling power to the
environmental characteristics of the machine to which it is to be fitted. At regular safety relay can also clear the fault condition.
intervals during the life of the machine, check whether the characteristics
foreseen remain valid.
Attribute Value
According to ISO 13849-1:
• PLe, Cat. 4
• MTTFd [a]: 378
• DC average: 99%
S11 S52 S12 S11 S52 S12
According to IEC 62061 and IEC 61508:
• SIL CL 3 S21 S22 S21 S22
Functional safety data • PFH [1/h]: 1.94E-09
• HFT: 1
• DC: 99% Max PLc: single-channel; N.C. Max PLd: dual-channel; 3-wire connection
• TM (PTI) [a]: 20
• dop [d]/hop [h] (1): 365/24
• tcycle [h]/[s] (2): 8/28,800
24V AC/DC, 115V AC, 230V AC
Power supply
0.85…1.1 x rated voltage 50/60 Hz A1
24V
Power consumption 2W DC
A2
Safety inputs 1 N.C., 2 N.C., 2 PNP light curtain
S11 S52 S12
Input simultaneity Infinite
S11 S52 S12 S21 S22
Allowable input resistance, max 110 Ω
Reset Manual monitored and automatic/manual S21 S22
MSR127RP/TP 3 N.O. safety, 1 N.C. auxiliary
Outputs Max PLe: dual-channel; 24V DC Max PLe: dual-channel; 4-wire connection,
MSR127.1T 2 N.O. safety, 2 N.O. auxiliary
signal cross faults require fault reset
• UL: B300
5 A/240V AC
Output rating
• AC-15: 5 A/250V AC
• DC-13: 3 A/24V DC Reset
Fuses output (external) 6 A slow blow or 10 A quick blow
• Reset modes — The unit is available with automatic/manual start
Switched current/voltage, min 10 mA/10 V
(MSR127T/TP safety relay) and manual monitored reset (MSR127R/RP
Contact material AgSnO2 + 0.5µAu
safety relay).
• 100,000 (220V AC/4 A/880VA cosφ = 0.35)
Electrical life (operations) • 500,000 (220V AC/1.7 A/375VA cosφ = 0.6)
• 1,000,000 (30V DC/2 A/60 W) A valid start/reset can only be operated if the feedback circuit is closed.
• 2,000,000 (10V DC/0.01 A/0.1 W) Feedback contacts of controlled actuators are connected in series with
Mechanical life 10,000,000 cycles the start/reset circuit (S12-S34).
Power on delay 1s
• T - Automatic/manual Start
Response time 15 ms
Recovery time 100 ms
Impulse withstand voltage 2500V
In Automatic/Manual Start mode, the reset circuit S12-S34 is not
Pollution degree 2
monitored against signal changes (no edge detection). The reset circuit
Installation group Overvoltage category III, VDE 0110-1
can close before or after the safety inputs are closed. The unit is active
Operating temperature -5…+55 °C (23…131 °F)
once the safety inputs close and the reset circuit are closed. If the
Relative humidity 90%
safety inputs and reset circuit are concurrently closed during power-up,
Enclosure protection IP40 (NEMA 1)
the unit activates immediately.
Terminal protection IP20
Wiring Use copper that withstands 60/75 °C (140/167 °F) MSR127 MSR127.1
Conductor size 0.2…2.5 mm² (24…12 AWG)
Torque settings - terminal screws 0.6…0.8 N•m (5…7 lb•in) S11 S52 S12 K1 K1
S11 S52 S10
Case material Polyamide PA 6.6 S21 S22 S34 S21 S22 S33
K2 K2
Mounting 35 mm (1.4 in.) DIN rail in an enclosure with a minimum
rating of IP54
• 24V AC/DC: 210 g (0.463 lb) • R - Manual Monitored Reset
Weight
• 115V AC or 230V AC: 260 g (0.573 lb)
Vibration 10…55 Hz, 0.35 mm (0.01 in.) In Manual Monitored Reset mode, a signal change of the reset circuit
(1) Operation time (day, hour) (S33-S34) is required and monitored. A reset fault occurs if the safety
(2) Cycle time (hour, sec) inputs remain open while the reset circuit is closed.
- Positive edge:
Diagnostics
Unit is active once the safety inputs are closed and then the reset
Auxiliary (N.C.) outputs 41…42 monitor the safety output state.
circuit is closed.
K1
Wiring Examples
A2 S21 S22 14 24 34 42 14 24 34 44
Figure 1 - Dual-channel Safety Gates, Monitored Manual Reset,
Monitored Output
MSR127/(MSR127.1) MSR127.1
L1 Reset
Table 1 - Connections
L1L2L3
A1 S11 S52 S12 13 23 33 41 Terminal Description
A1, A2 Power
Open S11, S12 (S10), S52, S21, S22 Safety input (N.C.)
K1
MSR 127RP S34 (S33) Monitoring feedback loop with Reset button
MSR127R, MSR127T, MSR127RP, MSR127TP
K2 13, 14, 23, 24, 33, 34 Safety output (N.O.)
Closed S21 S22 S34 A2 14 24 34 42 41, 42 Auxiliary output (N.C.)
MSR127.1T
K1 K2 M 13, 14, 23, 24 Safety output (N.O.)
N Max PLe, SIL 3 33, 34, 43, 44 Auxiliary output (N.O.)
Figure 2 - Dual-channel Safety Gates, Auto Reset, Monitored Output
+24V
Approximate Dimensions
L1L2L3
A1 S11 S52 S10 13 23 33 43
Figure 3 - Dimensions [mm (in.)]
22.5 114.5 (4.5)
Open (0.88)
K1 13 23 33 41
MSR127.1T (43)
A1 S11 S52 S12
(S10)
K2 PWR
Closed S21 S22 S33 A2 14 24 34 44
CH1 99
K1 K2 CH2 (3.89)
M
Max PLe, SIL 3
(S33)
S21 S22 S34 A2
(44)
14 24 34 42
At the end of life, this equipment should be collected separately from any unsorted municipal waste.
Rockwell Automation maintains current product environmental information on its website at rok.auto/pec.
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback.
For technical support, visit rok.auto/support.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenkÖy, İstanbul, Tel: +90 (216) 5698400 EEE YÖnetmeliğine Uygundur
Allen-Bradley, expanding human possibility, Guardmaster, Minotaur, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 440R-IN079D-EN-P - July 2022 | Supersedes Publication 440R-IN079C-EN-P- May 2020 PN-387541