Dold Siemens Voltage Relay

The document describes an undervoltage relay called the VARIMETER BA 9043 and AA 9943. It measures the arithmetic mean voltage of a 3-phase system between 100-690V and can detect undervoltage conditions. It has adjustable operate and release values, LED indicators, and operates on a 3-phase 3-wire or 4-wire system. It is insensitive to harmonics and has a frequency range up to 400Hz.

Uploaded by

hammad129
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
108 views4 pages

Dold Siemens Voltage Relay

The document describes an undervoltage relay called the VARIMETER BA 9043 and AA 9943. It measures the arithmetic mean voltage of a 3-phase system between 100-690V and can detect undervoltage conditions. It has adjustable operate and release values, LED indicators, and operates on a 3-phase 3-wire or 4-wire system. It is insensitive to harmonics and has a frequency range up to 400Hz.

Uploaded by

hammad129
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Monitoring Technique

VARIMETER
Undervoltage Relay
BA 9043, AA 9943

• According to EC/EN 60255-1


• 3-phase
• For nominal voltage of 3 AC 100 / 57 to 690 / 400 V
• Measures arithmetic mean value
0221539

• Adjustable operate and release value


• For 3p3w or 3p4w systems
• BA 9043 with optionally adjustable time delay
• De-energized on trip operation
• LED indicator for operation and state of contact
• Insensitive to harmonics
• Frequency up to 400 Hz
• Width 45 mm

BA 9043 AA 9943

Function Diagram Approvals and Markings


*)
U

A025518 see variants


*)

operate value
0,4-0,6UN
Application
hysteresis
3 phases L1, L2, L3 • Undervoltage detection in 3 phase systems
t • For industrial and railway applications

BA9043
Indicators
11-14
BA9043/001
AA9943 11-12 upper LED (only BA 9043): on, when voltage connected

lower LED: on, when output contact activated


BA9043/002 11-14
BA9043/003
11-12 Notes
M6864_a tv
tv For determination of the arithmetic mean value of the voltage the 3
phases are measured against N.
The variants without N ( /001 and /003) measure L1 and L2 against L3.
delay the delay is only active at U ≥ 0,6 UN . At < 0.4 UN the relay switches
off without delay.

Circuit Diagrams Technical Data

Input
L1 L2 L3 11 21 L1 L2 L3 11 21

Nominal voltage UN
L1 L1
11 21 11 21 BA 9043, BA 9043/002
N L2
AA 9943: 3/N AC 100/57 V; 220/127 V; 400/230 V
L2 415/240 V; 440/254 V; 500/290 V
L3 12 14 22 24 12 14 22 24 BA 9043, BA9043/002: 3/N AC 690/400 V
L3
BA 9043/001, BA 9043/003,
12 14 22 24 N 12 14 22 24 AA 9943/001: 3 AC 100 V; 220 V; 400 V; 415 V, 440 V;
M7520 M7521
500 V
BA 9043, BA 9043/002 BA 9043/001, BA 9043/003 BA 9043/001, BA 9043/003: 3 AC 690 V
AA 9943 AA 9943/001 Max. overload
BA 9043: 1.2 UN continuously
AA 9943: 1.1 UN continuously
Nominal consumption: AC 4 VA
Nominal frequency: 50 ... 400 Hz
Frequency range: ±5%
Temperature influence: < 0.05 % / K

Setting Ranges

Response value: 0.85 ... 1.05 UN, infinite variable with


upper potentiometer
Hysteresis: 0.75 ... 0.95 of operate value
Setting accuracy: ≤ ± 10 %
Switching delay tM: see diagram switching delay
Time delay tv: infinite variable from 0.5 ... 10 sec for
BA 9043/002, BA 9043/003
Between 0.4 and 0.6 UN the contacts
fall back according to the diagram
without additional delay

All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time. 1 25.07.16 en / 742
Technical Data CCC-Data
Output Thermal current Ith: 5A

Contacts Switching capacity


BA 9043: 2 changeover contacts to AC 15: 2 A / AC 230 V IEC/EN 60 947-5-1
AA 9943.11: 1 changeover contact to DC 13: 1 A / DC 24 V IEC/EN 60 947-5-1
AA 9943.12: 2 changeover contacts
Thermal current Ith: 6 A; see diagramm Technical data that is not stated in the CCC-Data, can be found
Continuous current limit curve in the technical data section.
Switching capacity nfo
to AC 15
NO contact: 3 A / AC 230 V IEC/EN 60 947-5-1
NC contact: 1 A / AC 230 V IEC/EN 60 947-5-1 Classification to DIN EN 50155 for BA 9043
to DC 13
Vibration and
NO contact: 1 A / DC 24 V IEC/EN 60 947-5-1
NC contact: 1 A / DC 24 V IEC/EN 60 947-5-1 shock resistance: Category 1, Class B IEC/EN 61 373
Electrical life IEC/EN 60 947-5-1 Ambient temperature: T1 compliant
to AC 15 at 3 A, AC 230 V: 3 x 105 switching cycles T2, T3 and TX with operational limitations
Short circuit strength Protective coating of the PCB: No
max. fuse rating: 4 A gL IEC/EN 60 947-5-1
Mechanical life: > 30 x 106 switching cycles Standard Type

General Data BA 9043 3/N AC 400 / 230 V 50 ... 400 Hz


Article number: 0039676
Operating mode: Continuous operation • for 3p4w systems
Temperature range • Nominal voltage UN: 3/N AC 400 / 230 V
Operation: - 20 ... + 60°C • Output: 2 changeover contacts
Storage: - 25 ... + 60°C • Width: 45 mm
Altitude: < 2.000 m
Clearance and creepage
Variants
distances
rated impulse voltage / AA 9943/001: without neutral
pollution degree: 4 kV / 2 IEC 60 664-1 AA 9943/175: for nuclear power plants
EMC BA 9043/001: without neutral
Electrostatic discharge: 8 kV (air) IEC/EN 61 000-4-2 BA 9043/002: with neutral, adjustable time delay
HF irradiation tv = 0.5 ... 10 sec
80 MHz ... 1 GHz: 10 V/m IEC/EN 61 000-4-3 BA 9043/003: without neutral, adjustable time delay
1 GHz ... 2.5 GHz: 3 V/m IEC/EN 61 000-4-3 tv = 0.5 ... 10 sec
2.5 GHz ... 2.7 GHz: 3 V/m IEC/EN 61 000-4-3 BA 9043: with CCC-approval on request
Fast transients: 2 kV IEC/EN 61 000-4-4
Surge voltages
Ordering example for variants
between
wires for power supply: 1 kV IEC/EN 61 000-4-5
between wire and ground: 2 kV IEC/EN 61 000-4-5 BA 9043 /_ _ _ 3/N AC 400/230 V 50 ... 400 Hz
HF wire guided: 10 V IEC/EN 61 000-4-6
Interference suppression: Limit value class B EN 55 011 Nominal frequency
Degree of protection Nominal voltage
Housing: IP 40 IEC/EN 60 529 Variant, if required
Terminals: IP 20 IEC/EN 60 529 Type
Housing: Thermoplastic with V0 behaviour
according to UL subject 94 AA 9943 .11 /_ _ _ 3/N AC 400/230 V 50 ... 400 Hz
Vibration resistance: Amplitude 0.35 mm IEC/EN 60 068-2-6
frequency 10 ... 55 Hz Nominal frequency
Climate resistance: 20 / 060 / 04 IEC/EN 60 068-1 Nominal voltage
Terminal designation: DIN EN 50 005 Variant, if required
Wire connection: 2 x 2.5 mm2 solid or Contact
2 x 1.5 mm2 stranded wire with sleeve Type
DIN 46 228-1/-2/-3/-4
Wire fixing: Flat terminals with self-lifting
clamping piece IEC/EN 60 999-1 Accessories
Fixing torque: 0.8 Nm
AA 9943:
Mounting: DIN rail IEC/EN 60 715
Weight K 70-34 Cover
BA 9043: 310 g Article number: 0011790
AA 9943: 300 g

Dimensions

Width x height x depth


BA 9043: 45 x 73 x 132 mm
AA 9943: 45 x 77 x 127 mm

2 25.07.16 en / 742
Characteristics

I (A)
A
contact current
6

5 B

-20 0 20 40 60 T (°C)
M6865_a ambient temperature

Continuous current limit curve

A = Devices mounted with 2 cm distance


B = Devices mounted without distance
F
x off
2,0
1,8
x on
1,6
1,4
1,2
1,0
0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2
t [s]
M6866_a

Diagram switching delay

Switching delay tM:

When the voltage changes fast on the measuring input, the arithmetic mean
value can only adjust after a short delay.

Example:
U applied 240 V
F = F= = 1.26
U setting 190 V

U setting = 190 V
U applied = 240 V

according to diagram:
tMon = approx. 800 ms
tMoff = approx. 100 ms

3 25.07.16 en / 742