0% found this document useful (0 votes)
393 views

Boq Dec Civil Finishes Boq For Quotation

This document provides a summary of civil and finishes works for Delhi Eye Care Hospital in Patel Nagar, New Delhi. It includes brickwork, flooring work using wooden laminate and stone, and woodwork including door and window frames of sal wood and red mirandi wood. Flush doors are specified for various sizes with and without vision panels using laminate and veneer. Sliding doors are also included made of laminate and veneer. The total estimated cost is ₹108,000 for brickwork, ₹68,880 for flooring work, and ₹347,308 for woodwork and doors.

Uploaded by

Hasan Jamal
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
393 views

Boq Dec Civil Finishes Boq For Quotation

This document provides a summary of civil and finishes works for Delhi Eye Care Hospital in Patel Nagar, New Delhi. It includes brickwork, flooring work using wooden laminate and stone, and woodwork including door and window frames of sal wood and red mirandi wood. Flush doors are specified for various sizes with and without vision panels using laminate and veneer. Sliding doors are also included made of laminate and veneer. The total estimated cost is ₹108,000 for brickwork, ₹68,880 for flooring work, and ₹347,308 for woodwork and doors.

Uploaded by

Hasan Jamal
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 12

DELHI EYE CARE HOSPITAL, PATEL NAGAR, NEW DELHI

9/22/2022 DAC ARCHITECTS

CIVIL AND FINISHES WORKS

SL NO DESCRIPTION UNIT QTY RATE AMOUNT LOCATION


1.0 BRICK WORKS
ORDINARY FLYASH BRICK WORK

1.1 Providing & Laying brick work in cement mortar 1:6 (1 cement : 6 coarse sand) using fly
ash bricks of class designation 7.5 in super structure all complete upto all height and level. Cum 0.5 7000 3,500 FHC DOOR AREA

1.2 Providing & Laying half brick work in cement mortar 1:4 of flyash bricks of class SHAFT ENCLOSURE WALL,
designation 7.5 in superstructure including using 2 Nos - 6mm dia hoop iron after every Sqm 110 950 104,500 OT FLOOR &
third coarse. INVESTIGATION FLOOR

TOTAL TO SUMMARY 108,000

2.0 FLOORING WORK LOCATION


The scope of work of Flooring work includes the supply, laying, jointing, (grinding
and polishing) of all types of floorings inside the building. Protection of Flooring after
execution is part of the item.

2.1 WOODEN LAMINATED FLOORING

Providing and Laying 8mm thick laminated wooden floor with surface guard on top of the
substrate specially developed core of plank size 1200mmx197mm having offset joint with
dock lock tongue and groove construction to secure long lasting joints fixed directly over WAITING AREA OF OPD
2.1.1 Sqm 32.00 1350 43,200
existing vitrified tile flooring . Providing and Laying of accessories for above floor of same FLOOR
shade as per the manufacturers specification. including high resistance matt melamine
polish, edge beading etc.

2.1.2 Skirting board RM 7.20 300 2,160

2.2 STONE FLOORING


Stone Counters with jet black Granite : Providing and laying 20 mm thick mirror
polished stone to counter top and front splash/facia in single long pieces with length upto
1000mm as shown with machine cut edges, installed in position as shown fixing with
araldite adhesive above the storage counter made of marine ply as called for and any other
suitable fixtures as shown and/or as directed with all accessories, ie cutting for ALL WASH BASINS, OFFICE
2.2.1 Sqm 4.90 4800 23,520
undercounter wash basin, all incidental work like cutting chase in wall for fixing and SPACE TABLE
making good with cement mortar and polishing etc. complete.
(Over all area shall be measured and no deductions of holes from single piece and inside
cutting shall be made). Cost to include polishing of all the cut edges,and cutting holes etc
exposed to view. Basic Rate-160 Rs/SFT

TOTAL TO SUMMARY 68,880

3.0 WOODWORK LOCATION

DOOR AND WINDOW FRAMES

Door/window frames:
Providing and fixing wood work in frames / transoms of doors, windows, clerestory
windows, glazed partitions and other frames with 1st class wood, wrought framed & fixed
in position, 125 x 50mm / 125 x 60mm cut to shape as per drawings, made to size and
shape as shown in the drawings including applying black Japan paint / wood preservator to
3.1 0 ALL ROOMS
unexposed surfaces, with mitred joints including fixing to rough grounds supports with
threaded expansion bolts as called for providing grooves, architrave's, rebates for locks
hinges etc. the frames shall be finished melamine polish (matt finish) of approved shade
applied evenly and finished to approved texture including preparation of surface with
approved primer and undercoat.

3.1.1 Same as above in Sal wood Cum 0.70 210000 147,000


3.1.2 Same as above in Red Mirandi wood Cum RO 196000 0

FLUSH DOOR LAMINATE/ LAMINATE with or without vision panel of 250mm x


1000mm :
Providing and fixing 35mm thick solid core homogeneous flush door shutter Interior WWR
grade-IGSB, with ISI mark as defined by IS:12406-1988 & BS:1142:1989 IGSB finished
3.2 ALL ENTRY DOORS
with 1.5 mm laminate , suede matt finish of approved shade and colour on both faces of
shutters, including 4 nos. 100mm size heavy type SS ball bearing hinges, edges to be with
hard wood beading , complete as specified to the entire satisfaction of Engg incharge/
Architect.Total Thickness 38mm

D1 (Size 1025 mm x 2200mm ) with a clear vision panel of size 250mm width & 1000 mm
3.2.1 Sqm 16.00 7300 116,800
high made of 6mm thick glass

D2 (Size 950 mm x 2200mm ) with a clear vision panel of size 250mm width & 1000 mm
3.2.2 Sqm 9.00 7300 65,700
high made of 6mm thick glass
D4 (Size 1025 mm x 2200mm ) with a clear vision panel of size 250mm width & 1000 mm
3.2.3 Sqm 2.26 7300 16,498
high made of 6mm thick glass

3.2.4 D3 (Size 765 mm x 2200mm ) without vision panel Sqm 3.40 6950 23,630

3.2.5 D5 (Size 1050 mm x 2200mm ) without vision panel Sqm 2.40 6950 16,680

SHAFT DOOR- FLUSH DOOR LAMINATE/PAINT


Providing and fixing 35mm thick solid core homogeneous flush door shutter Interior WWR
grade-IGSB, with ISI mark as defined by IS:12406-1988 & BS:1142:1989 IGSB finished
3.3 with 1.5 mm laminate , suede matt finish of approved shade and colour on front faces of Sqm 3.00 6500 19,500 SHAFT ACCESS DOORS
shutter and paint on the other side, including 4 nos. 100mm size heavy type SS ball bearing
hinges, complete as specified to the entire satisfaction of Engg incharge/ Architect.Total
Thickness 36.7mm (TD size .65m x 2.2m)

SLIDING DOOR- FLUSH DOOR VENEER/VENEER : Providing and fixing 35mm


thick solid core homogeneous flush door shutter Interior WWR grade-IGSB, with ISI mark
as defined by IS:12406-1988 & BS:1142:1989 IGSB finished with 4 mm veneer , of
3.4 Sqm 6.00 12500 75,000 MAIN OT DOOR
approved shade and colour on front faces of shutter and paint on the other side, including
the aluminium rail for sliding & rollers, complete as specified to the entire satisfaction of
Engg incharge/ Architect. Total Thickness 45 mm (Maximum door size 1.4m x 2.2m)

SLIDING DOOR- FLUSH DOOR LAMINATE/LAMINATE : Providing and fixing


35mm thick solid core homogeneous flush door shutter Interior WWR grade-IGSB, with
ISI mark as defined by IS:12406-1988 & BS:1142:1989 IGSB finished with 1.5 mm
3.5 laminate , suede matt finish of approved shade and colour on front faces of shutter and Sqm 8.00 8500 68,000 TOILETS
paint on the other side, including the aluminium rail for sliding & rollers, complete as
specified to the entire satisfaction of Engg incharge/ Architect. Total Thickness 37 mm
(Maximum door size .85m x 2.2m)

3.6 COST OF HARDWARE 0


Fixing door closers from dorset Nos 20.00 0 ALL DOORS
Fixing SS pull handles with cylindrical lock from dorset Nos 40.00 0 ALL DOORS
Fixing door stoppers from dorset Nos 20.00 0 ALL DOORS

Providing and fixing 6mm thick mirror with 12mm thick waterproof ply backing, 4 to 6
3.7 mm foam, edge polishing of glass on all sides, fixed with SS studs 1” dia complete in all Sqm 10.00 4800 48,000 ALL WASHBASINS AREA
respect as per detail drawing/design and as directed by architects / project managers.

TOTAL TO SUMMARY 596,808

4.0 METAL DOORS LOCATION


FIRE DOORS (2 HRS RATING)
Providing and fixing of Hollow metal fire rated doors for stability and integrity. Pressed
Galvanized steel with the following specification. Recommended fire door shall have doors
tested for maximum rating of 2hrs with vision panel. Test certificates should be available
for circular vision panels of 360mm diameter as part of the fire door assembly. Independent
4.1 glass test certificates will not be accepted. Manufacturer test certificate shall cover doors
both single and double leaf and all doors supplied should be within the tested specimen,
deviation in specification and sheet thickness other than what is mentioned in the test
certificates are not allowed. Proper label confirming the type of door and the hourly rating
is mandatory.

Door frame of section 110X70mm with one side inbuilt architrave 20X14mm & inbuilt
groove to receive the gasket/smoke seal, made out of 1.6 mm (16 gauge) minimum thick
galvanized steel sheet. Frames shall be Mitered and field assembled with self tabs. All
provision should be mortised, drilled and tapped for receiving appropriate hardware.
Rubber door silencers should be provided on the striking jamb. Frames should be provided
with 50 mm wide back plate bracket and anchor fasteners for installation on a finished
plastered masonry / RCC wall opening. The fastner opening should be covered with similar
colour cap.

Door leaf shall be 46mm thick fully flush double skin door with or without vision lite. Door
leaf shall be manufactured from 1.2mm (18guage) minimum thick galvanised steel sheet.
The internal construction of the door should be rigid reinforcement pads for receiving
appropriate hardware. The infill material shall be resin bonded honeycomb core. All doors
shall be factory prepped for receiving appropriate hardware and provided with necessary
reinforcement for hinges, locks, and door closers. The edges should be interlocked with a
bending radius of 1.4mm. For pair of doors astragals has to be provided on the meeting stile
for both active and inactive leaf. circular vision panels of 360mm diameter wherever
applicable should be provided as per manufacturers recommendation with a beeding and
screws from inside. The glass and glazing should be in lined with relevant test certificate as
approved by the consultants. The glass should be 6mm clear borosilicate fire rated glass of
the door.

All doors and frames shall be finished with polyurethane aliphatic grade paint / Powder
Coated (60-80 Micron) ( both outer and inner face of frames should properly powder
coated) of approved colour . The door leaf and frame shall have passed minimum 250 hours
of salt sprey test. Rate should include supply and installation of
windows and glass as per schedule.
2 Hrs Fire Rated Steel double door leaf (with circular vision panel 1
nos-360 mm dia) of size 2.20x1.5 m)
FD1 - (active shutter 1200mm) - with single door closer / 1 vision panel (Thickness
Sqm 2.64 0
Frame/Shutter -1.6/1.2 mm)

Hardware

SS-304 Ball Bearing Butt Hinges ( 101 x 75 x 3mm ) - 8 Nos


One side key & inside thumb turn operation cylinder
SS lever Handle 19 mm set D type
1 Circular vision panel fire rated 360 mm on single leaf door only
Door Closer for single leaf
Gasket/smoke seal
FIRE HOSE CABINET DOORS

Providing of metal door at all levels from ISO 9001-2000 certified Manufacturer. Pressed
Galvanized steel Double leaf with 1 no of vision panel on each shutter to required sizes of
4.2
approved make which consists of frame, shutter, infill and finish as detailed below and
conforming to IS 277.

Door frame of size 101X58 mm shall be of Single inbuilt architrave frame made out of
1.60mm thick galvanized steel sheet . Frames should be Mitered and field assembled with
self tabs. Frames should be provided with back plate bracket and anchor fasteners for
installation on a finished plastered masonry / RCC wall opening. Once frame installed
should be grouted with cement slurry if recommended on the clear masonry opening.
approved make shakti hormann or approved equivalent.

Door leaf shall be 46mm thick fully flush double skin door. Door leaf shall be
manufactured from 1.35mm (18guage) minimum thick galvanised steel sheet. The internal
construction of the door should be rigid reinforcement pads for receiving appropriate
hardware. The infill material shall be resin bonded honeycomb core. All doors shall be
factory prepped for receiving appropriate hardware and provided with necessary
reinforcement for hinges, locks, and . The edges should be interlocked with a bending
radius of 1.4mm. Rectangular vision panels of 318mm x 1715mm each to be provided as
per manufacturers recommendation with a beeding and screws from inside. The glass
should be 6mm clear.

All doors and frames shall be finished with polyurethane aliphatic grade paint / Powder
Coated (60-80 Micron) of approved colour. The door leaf and frame shall have passed
minimum 250 hours of salt spray test.
Rate should include supply and installation of door and hardware set as mentioned in the
door and hardware schedule.

FHC door - Size W-1.35mX H-2.17m Sqm 8.79

Hardware-GEZE or Dorset make


SS 304 grade ball bearing butt hinges (101x75x3 mm)-4 nos

Rubber door silencer should be provided on the jamb-inbuilt groove to receive the gasket
Mortise dead lock with alan key
With SS-304 recessed handle
2 nos vision panel of 318mm X1715 MM in each shutter panel

TOTAL TO SUMMARY 0

5.0 FALSE CEILING


The scope of work of suspended ceiling work includes the supply, laying and
finishing of all types of types of false ceilings used in the building

5.1 METAL FALSE CEILINGS

Aluminium baffle False Ceiling: Supply & Installation of Metalium Type G.I. Powder
Coated Baffle Size 50*70 (Centre to Centre 100MM & Clear Gap 50mm) with accessories:
U Shaped Panel 50mm wide x 70mm height x 3600mm length center to center 100mm &
0.50mm TCT thick G.I. Powder coated Profile. The U Profile shall be powder coated on
extension surface only. When two panels are to be joined, they shall be joined together by OPD FLOOR WAITING
5.1.1 means of panel coupler suitable for U shaped Screen Panel. Edge profile shall be L- shaped, Sqm 33.07 6500 214,934 LOBBY, INVESTIGATION
roll formed out of 0.50 Sheet with powder coated in standard colors .Hanging rod fixed to FLOOR LOBBY
RCC slabs with 50x6mm SS hilti dash fastners, and profiles needed to support the baffles
suited as per site and as specified in drawings incl. cutting holes for ceiling lights, exhaust
diffusers, wastage , scaffolding etc complete. (colour-RAL Metallic color) Note : Cutting of
the ceiling for AC's etc to be included.

5.1.2 Same as above to be fixed on wall without the handing rods Sqm 10.22 7000 71,516

5.2 GYPSUM BOARDS FALSE CEILING


Providing and laying gypsum ceiling with 1 layers of Standard gypsum Boards
manufactured by Lafarge Boral Gypsum India Pvt Ltd/Hilux at all heights and levels.
Standard board size and thickness 12.5mm, standard board to be laid on metal sections, to
be fixed as per manufacturer's specifications metal section comprising of Universal
Channel (web 45mm and Flange 27mm Base Metal Thickness (BMT) 0.55m and Length
3660mm to be use as “Main Channel” as well as Ceiling Channel, connecting clips,
Perimeter channel (Size- Web 28mm, Flange 18/30mm and Length 3660mm length, BMT
0.55mm ) and "L" angle (Length 3050mm BMT 0.55mm) with Finally the boards are to be
jointed and finished so as to have a flush look which includes filling and finishing the
tapered and square edges of the boards with Joint Gypsum based jointing compound, paper
tape.

The rate should include fixing SS dash fasteners in RCC/sheet decking 50 mm long 6mm
dia as per manufacturer spacing recommendation, providing and laying two or more coats
of oil bound distemper to give neat and even finish including preparing the base with
primer and scaffolding etc. complete in all respects.etc. Note : No extra charge shall be
given for layout and providing cutouts/coves for light fittings, grill diffusers, slits, or
providing coves in ceilings , for making any grooves if required in horizontal / Vertical/
Inclined surfaces. False ceiling As laid area of ceiling shall be measured for billing

5.2.1 Horizontal / Vertical/ Inclined surfaces false ceiling with 12.5mm thk plain Gypsumboard.
Sqm 235.00 1350 317,250 ALL AREAS
5.2.2 Curved surfaces false ceiling with 12.5mm thk plain Gypboard. Sqm 1 1470 1,470
5.2.3 With moisture resistant plasterboard Sqm 1 1750 1,750 PROVISION
5.3 WOODEN FALSE CEILING 0
Providing and fixing 2400 mm by 1200 mm 12 mm thick ply board including providing
and fixing of framework made of special sections power pressed from MS sheet and zinc
coating. P/F Aluminum U/C-section shadow angle groove/band on wall including all
accessories, of the taping of all the joints between boards and fixing element and any
5.3.1 incidentals may required to properly secure on wall/ceiling and to accomplish the job in all Sqm 7 8500 59,500
respect as per detail drawings, including providing and sticking with glue 4 mm thick
veneer to the ply and give final melamine polish design and as directed and approved by
architect.

TOTAL TO SUMMARY 666,419

6.0 PARTITION AND PANELLING WORK


PARTITION
6.1 GYPSUM BOARD PARTITION
Providing and fixing dry partition system (RCP 042) Non Fire Rated Acoustic- Rw- 42dB
for vertical height upto 3.0 m maximum : consists of 1X12.5mm thick Standard Board on
one side and 1x12.5mm thick standard board from other side with screwed fixed using
“typeS”25mm corrosion resistant screws spaced at 200mm maximum centers on all joints
and 300mm maximum centers in the field of the board to either side of 50mm x 0.55 mm
BMT (Base metal thickness). The metal Studs are to be installed perpendicularly at 600mm
max centers and located directly opposite of each other within parallel 50mm x 0.55 bmt
top and bottom tracks. The tracks are to be fastened to floor slab and soffit using 6mm
expansion bolts at 600mm centers, with the first and the last fixing points a max. 50 mm
6.1.1 Sqm 170 2120 360,400 ALL PARTITIONS
from either end i/c making provision for conduits & gang box etc. The cavity is to be filled
with 50mm thick 40kg/m3 Rockwool or mineral fiber wool i/c wire mesh. Contact line
between gupsum board and steel column to be made of U shape aluminium channel of
12.5X12.5mm , 1 mm thick of the approved color by the architect. Item to be included in
the partition work. All opening and penetrations are to be sealed with acoustic sealant.
Jointing & Finishing: Finally the face layer of the boards are to be jointed and finished so
as to have a flush look which includes filling and finishing with Joint gypsum based
jointing compound and joint paper tape.(As per recommended practice of Lafarge Boral
Gypsum India pvt ltd-universal section to be used)

6.2 WOODEN BOARD PARTITION


Providing and fixing dry partition system (RCP 042) Non Fire Rated Acoustic- Rw- 42dB
for vertical height upto 3.0 m maximum : consists of 1X12.5 mm standard gypsum board
on one side and 1X12 mm thick marine ply board on the other side, the ply will be fully
covered with 4mm thick veneer i/c arrangemnt for fixing ply to stud, melamine polish of
the same,with screwed fixed using “typeS”25mm corrosion resistant screws spaced at
200mm maximum centers on all joints and 300mm maximum centers in the field of the
board to either side of 50mm x 0.55 mm BMT (Base metal thickness). The metal Studs are
to be installed perpendicularly at 600mm max centers and located directly opposite of each
other within parallel 50mm x 0.55 bmt top and bottom tracks. The tracks are to be fastened
to floor slab and soffit using 6mm expansion bolts at 600mm centers, with the first and the
last fixing points a max. 50 mm from either end i/c making provision for conduits & gang
box etc. The cavity is to be filled with 50mm thick 40kg/m3 Rockwool or mineral fiber
wool
All opening and penetrations are to be sealed with Fire rated and acoustic sealant.
6.2.1 Jointing & Finishing: Sqm 10 5400 54,000 WAITING LOUNGES
Finally the face layer of the veneers are to be groove jointed and finished so as to have a
flush surface, as directed by the architect

6.2.2 Same as above with only 12mm thk ply on specific locationto hold the storages, putting
sqm 5 2800 14,000 WAITING LOUNGES
extra GI channels wherever required.
6.2.2 Same as above with 1.5 laminate instead of natural wood veneer. sqm RO 4500 0
6.3 PANELLING
The scope of work of Wood work includes the supply, cutting, jointing, grinding and
polishing of all types of woodworks and paneling inside the building. All lead and lift
shall be included
WOODEN PANELLING
Providing and fixing Architrave and wooden paneling 23 mm with 19 mm marine ply with
4 mm teak veneer with architrave in solid teak only framed and fixed in position made to
size and shape as shown in drawings including polishing/wood preservator including fixing
to RCC/ brick walls with ss threaded expansion bolts 6mm dia and 50mm long. Finishing
and all hardware inclusive. The panels to be melamine polished (matt finish) of approved WAITING LOBBY &
6.3.1 SQM 22 4200 92,400
shade applied evenly and finished to approved texture including preparation of surface with LOUNGES
approved primer and undercoat. The item includes the architrave of 60X30 in solid teak
wood

TOTAL TO SUMMARY 520,800


7.0 METAL WORK
MS Hollow Section: Providing,fabricating and fixing of MS Hollow Section as per drawing
complete including 2 or more coat of PU paint over 2 coats of anti-corrosive steel primer
of approved make complete.
Providing and fixing MS Powder coated Tubular sections 100x100MM, 4mm thick, @ 11.5
Kg/RM with end plates 200X200 6mm thick with 4 holes and 4 75mm long, 8mm dia
7.1.1 SS304 dashfastener in RCC slabs top and bottom. Top Plate to be welded to steel when Kg 50 250 12,500 PROVISION
meeting a steel beam.

TOTAL TO SUMMARY 12,500

8.0 FINISHES

Providing and applying 12-15mm thick internal wall plaster in CM 1:4 (1 cement : 4 sand
using 25% coarse sand and 75% fine sand) at all heights and levels including making
8.1.1 coving/chamfering in plaster as per drawing, scaffolding, drip course curing etc. complete. Sqm 250 470 117,500 ALL BRICKWORK

Providing & applying 10mm thick plaster in CM 1:3 (1 cement : 3 coarse sand using 25%
coarse sand and 75% fine sand) on ceiling including hacking the surface, scaffolding,
8.1.2 curing & making drip course/ coving/chamfering etc. at all levels and heights etc. all Sqm RO 530 0
complete.
Providing and laying 5 to 10mm - Birla White Cement putty from Birla or equivalent in
two layers on outside brick wall surface including racking joints, curing, drip course
8.1.3 scoffolding etc complete as per drawing,specifications and as directed by Engineer-in- Sqm 250 80 20,000 ALL BRICKWORK
charge.
Anti-Bacterial Plastic Emulsion Paint : Providing and applying 3 or more coats of
washable plastic emulsion paint of approved manufacturer and shade to walls/ ceilings and
other similar areas at all levels applied evenly to produce uniform even surface to approved
finish including grinding,reparing with cement mortar & finishing of wall & slab joints
8.1.4 etc,cleaning and smoothening and preparing the surface and applying birla white Sqm 590 360 212,400 ALL WALLS
cementesious putty of 2mm thickness as per manufacturers specifications, applying coat
of approved cement primer including scaffolding etc complete all level.

8.2 TILE CLADDING


TILES CLADING
Providing and laying in position glazed Ceramic tiles with tapering edge profile fixed
with tile Adhesive on marine ply surface etc finished neat with 4 mm spacers and groove to
be filled with 4 mm Epoxy grout admixed with AD1 and GT1 respectively (
grout/adhesive Bal Endura/Laticrite as per specifications & instruction from EIC
complete.
WASH BASIN AREA OF THE
2.a Ceramic glazed tiles 100X100 mm, 6 mm thick (basic price of tile Rs.45/Sft) Sqm 5 2400 12,000
CABINS
TOTAL TO SUMMARY 361,900

9.0 ALUMINIUM COMPOSITE PANELS


Providing and fixing 4mm thick Aluminium Composite Panels (ACP) of exterior grade for
Alstrong / Eurobond or approved equivalent make cladding in combination of solid /
9.1.1 Metallic colours, including all necessary frame work and complete weather sealing silicon Sqm RO 4500 0 PROVISIONAL
etc complete.

TOTAL TO SUMMARY

10.0 ROOFING WATERPROOING & INSULATION


10.1 THERMAL INSULATION
UNDERDECK INSULATION: Providing and fixing 50mm thick rock wool under deck
insulation having a density of 32 Kg./cum with one layer of reinforced aluminium facing
and fixed with washer & fastner i/c supporting annealed wire etc complete , fixed to roof UNDER ROOF AND
10.1.1 sqm 60 900 54,000
aluminum deck sheeting complete in all respect. TERRACES

Providing and fixing 50 mm thick XPS board under deck insulation having density
32kg/cumwith PVC fastner 100 mm long and 50 dia cap. The baord or be painted with 2
10.1.2 coat of black japan paint.(to be fixed to metal deck sheet) sqm RO 1700 0

TOTAL TO SUMMARY 54,000

11.0 DISMANTLING WORK


Carefully dismantling of existing brick work of all thickness including cement plaster on
one or both faces, any finish on wall including stacking the serviceable material and
disposal of unserviceable material away from site within local municipal yard as directed TOILET WALLS FOR
11.1 Cum 1 3000 3,000
by the Engineer-in-Charge. The rate should also include cost of scaffolding if any. SLIDING DOORS
(measured wall thickness only)
Dismantling of PCC including removal of loose concrete in surroundig if any , stacking of
serviceable material within campus and disposal of unserviceable material outside the
11.2 premises area within Local municipal yard as directed by the Engineer-in-Charge. Cum 1 3000 3,000

Dismantling of RCC including plaster/ guniting in beams, columns, slabs etc. including
removal of loose concrete in surroundig if any , stacking of serviceable material within
11.3 campus and disposal of unserviceable material outside the premises area within Local Cum RO 4500 0
municipal yard as directed by the Engineer-in-Charge.

TOTAL TO SUMMARY 6,000


12.0 MISCELLENIOUS WORK
12.1 Core Cuts : 150mm dia core cuts to fix the floor traps for the wash basins Nos 5 800 4,000
wooden hand rail: Providing and fixing in position 40X80 mm r section of teak wood ,
rounded and sanded as per instruction of the architect for handrail in staricases, including
12.2 MS support made of 20mm dia pipes and plate of 75 mm dia, 5mm thick at 900 CtC with 4 Rm 10 3500 35,000
SS 304 Dashfastener of 6mm dia, 50 mm long.

RCC Lintel : Pre cast RCC lintels of sizes 115mmx200mm high x 1m - 1.6m in length as
per site conditions to be placed for door openings in the brick walls, 8mm dia rods to be
12.3 used for the lintels, sizes as per architect's dwg. Rm 10 750 7,500

PU Sealant - Providing & Forming Vertical/Horizontal groove of size from surface as per
12.4 approved pattern using paper tape, Backer Rod & PU Sealant inc primer, scaffolding etc
complete at all levels.
12.4.1 20mm x 15mm Rmt 10 980 9,800
12.4.2 25mm x 15mm Rmt 10 1020 10,200

TOTAL TO SUMMARY 66,500

GRAND TOTAL CIVIL AND FINISHES WORK 2,461,807