FG100 Tech Manual v2
FG100 Tech Manual v2
FG-100
ADVANCED
GENSET
CONTROLLER
DESCRIPTION COMMUNICATIONS
The FG-100 series are next generation genset • USB Device
control units combining multi-functionality and wide • J1939-CANBUS (optional)
communication possibilities together with a reliable • RS-485 Modbus (optional)
and low cost design. • GSM Modem 2G or 3G (optional)
The unit complies and mostly exceeds world’s • Ethernet 10/100 Mb (optional)
tightest safety, EMC, vibration and environmental • Free PC software: Rainbow Plus
standards for the industrial category. • Modbus RTU through USB
• Ready Rainbow Scada central monitoring
Software features are complete with easy firmware
service
upgrade process through USB port.
The Windows based PC software allows monitoring
and programming through USB, serial and GPRS.
The PC based Rainbow Scada software allows
monitoring and control of an unlimited number of TOPOLOGIES
gensets from a single central location.
3 phases 4 wires, star
3 phases 3 wires, 3 CTs, delta
FUNCTIONALITIES 3 phases 3 wires, 2 CTs (L1-L2)
3 phases 3 wires, 2 CTs (L1-L3)
Remote start controller 2 phases 3 wires, L1-L2
Manual start controller 3 phases 4 wires, delta
Engine controller 1 phase 2 wires
FG-100 User Manual Firmware V-5.8
COPYRIGHT NOTICE
Any unauthorized use or copying of the contents or any part of this document is prohibited.
This applies in particular to trademarks, model denominations, part numbers and drawings.
This document describes minimum requirements and necessary steps for the successful installation of
the FG-100 family units.
Follow carefully advices given in the document. These are often good practices for the installation of
genset control units which reduce future issues.
QUERRIES
If additional information to this manual is required, please contact FG Wilson technical helpdesk
RELATED DOCUMENTS
FILENAME DESCRIPTION
Rainbow Installation Rainbow Plus Installation Guide
Rainbow Usage Rainbow Plus Usage Guide
GSM Configuration GSM Configuration Guide
Firmware Update Firmware Update Guide for FG-100
MODBUS Modbus Application Manual
Rainbow Scada Installation Rainbow Scada Installation Guide
Rainbow Scada Usage Rainbow Scada Usage Guide
-2-
FG-100 User Manual Firmware V-5.8
REVISION HISTORY
TERMINOLOGY
-3-
FG-100 User Manual Firmware V-5.8
ORDERING CODES
The FG-xxx family units are available in various options and peripheral features. Please use below
information for ordering the correct version:
FG100 -J -G -T -00
Variant
00: standard unit
Family Code 01...99: customer
specific products
SPARE PARTS
Sealing Gasket
-4-
FG-100 User Manual Firmware V-5.8
SAFETY NOTICE
Failure to follow below instructions
will result in death or serious injury
-5-
FG-100 User Manual Firmware V-5.8
TABLE OF CONTENTS
1. INSTALLATION INSTRUCTIONS
2. MOUNTING
2.1 DIMENSIONS
2.2 SEALING, GASKET
2.3 ELECTRICAL INSTALLATION
3. TERMINAL DESCRIPTIONS
3.1. BATTERY VOLTAGE INPUT
3.2. AC VOLTAGE INPUTS
3.3. AC CURRENT INPUTS
3.4. DIGITAL INPUTS
3.5. ANALOG SENDER INPUTS, SENDER GROUND AND SENDER SUPPLY
3.6. CHARGE INPUT TERMINAL
3.7. DIGITAL OUTPUTS
3.8. J1939-CANBUS PORT (OPTIONAL)
3.9. USB DEVICE PORT
3.10. GSM MODEM (OPTIONAL)
3.11. RS-485 PORT (OPTIONAL)
3.12. ETHERNET PORT (OPTIONAL)
4. TOPOLOGIES
4.1. SELECTING THE TOPOLOGY
4.2. 3 PHASE, 4 WIRE, STAR
4.3. 3 PHASE, 3 WIRE, DELTA
4.4. 3 PHASE, 4 WIRE, DELTA
4.5. 3 PHASE, 3 WIRE, DELTA, 2 CT (L1-L2)
4.6. 3 PHASE, 3 WIRE, DELTA, 2 CT (L1-L3)
4.7. 2 PHASE, 3 WIRE, DELTA, 2 CTs (L1-L2)
4.8. 2 PHASE, 3 WIRE, DELTA, 2 CTs (L1-L3)
4.9. 1 PHASE, 2 WIRE
5. FUNCTIONALITIES
5.1. REMOTE START FUNCTIONALITY
5.2 ENGINE CONTROLLER FUNCTIONALITY
6. CONNECTION DIAGRAMS
6.1. REMOTE START FUNCTIONALITY
6.2. ENGINE CONTROL FUNCTIONALITY
-6-
FG-100 User Manual Firmware V-5.8
7. TERMINAL DESCRIPTION
8. TECHNICAL SPECIFICATIONS
9. DESCRIPTION OF CONTROLS
9.1. FRONT PANEL FUNCTIONALITY
9.2. PUSHBUTTON FUNCTIONS
9.3. DISPLAY SCREEN ORGANIZATION
9.4. MEASURED PARAMETERS
9.5. LED LAMPS
10. DISPLAYING EVENT LOGS
11. STATISTICAL COUNTERS
11.1. FUEL CONSUMPTION MONITORING
12. OPERATION OF THE UNIT
13.1. QUICK START GUIDE
13.2. STOP MODE
13.3. AUTO MODE
13.4. RUN MODE, MANUAL CONTROL
13.5. TEST MODE
13. PROTECTIONS AND ALARMS
13.1. DISABLING ALL PROTECTIONS
13.2. SERVICE REQUEST ALARM
13.3. LIST OF ALARMS
13.4. NON-VISUAL WARNINGS
14. PROGRAMMING
14.1. RESETTING TO FACTORY DEFAULTS
14.2. ENTERING THE PROGRAMMING MODE
14.3. NAVIGATING BETWEEN MENUS
14.4. MODIFYING PARAMETER VALUE
14.5. PROGRAMMING MODE EXIT
15. PROGRAM PARAMETER LIST
16. CRANK CUTTING
17. OVERCURRENT PROTECTION (IDMT)
18. MOTORIZED CIRCUIT BREAKER CONTROL
19. J1939 CANBUS ENGINE SUPPORT
20. SMS COMMANDS
-7-
FG-100 User Manual Firmware V-5.8
-8-
FG-100 User Manual Firmware V-5.8
1. INSTALLATION INSTRUCTIONS
Before installation:
Read the user manual carefully, determine the correct connection diagram.
Remove all connectors and mounting brackets from the unit, then pass the unit through the
mounting opening.
Put mounting brackets and tighten. Do not tighten too much, this can brake the enclosure.
Make electrical connections with plugs removed from sockets, then place plugs to their sockets.
Be sure that adequate cooling is provided.
Be sure that the temperature of the environment will not exceed the maximum operating
temperature in any case.
-9-
FG-100 User Manual Firmware V-5.8
2. MOUNTING
2.1. DIMENSIONS
- 10 -
FG-100 User Manual Firmware V-5.8
Mount the unit on a flat, vertical surface. Before mounting, remove the mounting brackets and connectors
from the unit, then pass the unit through the mounting opening.
87mm
117mm
Panel Cutout
WALL
- 11 -
FG-100 User Manual Firmware V-5.8
- 12 -
FG-100 User Manual Firmware V-5.8
Panel
Gasket
Module
The rubber gasket provides a watertight means of mounting the module to the genset panel. Together
with the gasket, IEC 60529-IP65 protection can be reached from the front panel. A short definition of IP
protection levels is given below.
- 13 -
FG-100 User Manual Firmware V-5.8
Fuses must be connected to the power supply and phase voltage inputs, in
close proximity of the unit.
For current transformer inputs, use at least 1.5mm2 section (AWG15) cable.
The current transformer cable length should not exceed 1.5 meters. If
longer cable is used, increase the cable section proportionally.
- 14 -
FG-100 User Manual Firmware V-5.8
3. TERMINAL DESCRIPTIONS
Cranking dropouts: Survives 0VDC during 100ms. The voltage before surge should be
8VDC minimum
Overvoltage protection: Withstands 150VDC continuously.
Reverse voltage: -33VDC continuous
Maximum operating 200mA @ 12VDC. (All options included, digital outputs open.)
current: 100mA @ 24VDC. (All options included, digital outputs open.)
Typical operating current: 100mA @ 12VDC. (all options passive, digital outputs open)
50mA @ 24VDC. (all options passive, digital outputs open)
Measurement range: 0 to 36VDC
Display resolution: 0.1VDC
Accuracy: 0.5% + 1 digit @ 24VDC
- 15 -
FG-100 User Manual Firmware V-5.8
- 16 -
FG-100 User Manual Firmware V-5.8
- 17 -
FG-100 User Manual Firmware V-5.8
CONNECTING CTs:
Be sure of connecting each CT to the related phase input with the correct polarity. Mixing CTs between
phases will cause faulty power and pf readings.
Many combinations of incorrect CTs connections are possible, so check both order of CTs and their
polarity. Reactive power measurement is affected by incorrect CTs connection in similar way as active
power measurement.
CORRECT CT CONNECTIONS
Let’s suppose that the genset is loaded with 100 kW on each phase. The load Power Factor (PF) is 1.
Measured values are as follows:
kW kVAr kVA pf
Phase L1 100.0 0.0 100 1.00
Phase L2 100.0 0.0 100 1.00
Phase L3 100.0 0.0 100 1.00
Total 300.0 0.0 300 1.00
- 18 -
FG-100 User Manual Firmware V-5.8
The generator is still loaded with 100 kW On each phase. The load Power Factor (PF) is 1.
PF in phase L2 will show -1,00 due to reverse CT polarity. The result is that total generator power
displayed by the controller is 100 kW.
Measured values are as follows:
kW kVAr kVA pf
Phase L1 100.0 0.0 100 1.00
Phase L2 -100.0 0.0 100 -1.00
Phase L3 100.0 0.0 100 1.00
Total 100.0 0.0 300 0.33
The generator is still loaded with 100 kW on each phase. The load Power Factor (PF) is 1.
PF in phases L2 and L3 will show -0,50 due to phase shift between voltages and currents which is
caused by CT swapping. The result is that total generator power displayed by controller is 0 kW.
Measured values are as follows:
kW kVAr kVA pf
Phase L1 100.0 0.0 100 1.00
Phase L2 -50.0 86.6 100 -0.50
Phase L3 -50.0 -86.6 100 -0.50
Total 0.0 0.0 300 0.0
- 19 -
FG-100 User Manual Firmware V-5.8
Type of inputs: all configurable, additional sender ground input and sender supply
output (+5VDC)
Function selection: from list
Sender supply: 5.0VDC, 20mA max.
Structure: Sender_1: analog voltage input (0-5V)
Senders_2-3: 667 ohms resistor polarizing to 3.3VDC
Measurement: Sender_1: analog voltage measurement
Senders_2-3: Analog resistor measurement.
Open circuit voltage: Sender_1: 0VDC
Senders_2-3: +3.3VDC
Short circuit current: 5mA (senders 2-3)
Measurement range: 0 to 5000 ohms. (senders 2-3)
Open circuit threshold: 5000 ohms. (senders 2-3)
Resolution: 1 ohms @ 300 ohms or lower (senders 2-3)
Accuracy: 2 %+1 ohm (±7 ohms @300 ohms) (senders 2-3)
Common mode voltage ± 3VDC (senders 2-3)
range:
Noise filtering: yes
- 20 -
FG-100 User Manual Firmware V-5.8
The sender ground signal should be connected to the engine body, close to senders for the best
measurement accuracy. It can be left open if preferred.
The +5V supply output provides a maximum of 50mA for active sender types. It is protected by an internal
electronic fuse and resets automatically after an overload or short circuit condition.
- 21 -
FG-100 User Manual Firmware V-5.8
USB Device
Connector
USB A to B
Cable
The USB-Device port is designed to connect the module to a PC. Using the RainbowPlus software,
programming, control of the genset and monitoring of measured parameters are achieved.
The RainbowPlus software can be downloaded from PowerUp 2 website.
The connector on the module is of USB-B type. Thus A to B type USB cable should be used. This is the
same cable used for USB printers.
For more details about programming, control and monitoring please refer to RainbowPlus user manual.
- 22 -
FG-100 User Manual Firmware V-5.8
The optional plug-in GSM modem offers the advantage of being internally powered and is fully compatible
with the unit. It does not require any special setup.
2G and 4G modem options are available.
The 1800/1900 MHz magnetic antenna together with its 2 meter cable is supplied with the modem. The
antenna is intended to be placed outside of the genset panel for the best signal reception.
The module requires a GPRS enabled SIM card for full functionality. Voice-only type SIM cards will
usually not function properly.
Please refer to GSM Modem Configuration Guide for more details.
Antenna connector
Magnetic antenna
- 23 -
FG-100 User Manual Firmware V-5.8
- 24 -
FG-100 User Manual Firmware V-5.8
The RS-485 port features MODBUS-RTU protocol. Multiple modules (up to 128) can be paralleled on the
same RS-485 bus for data transfer to automation or building management systems.
The RS-485 port provides also a good solution for distant PC connection where RainbowPlus program
will enable programming, control and monitoring.
- 25 -
FG-100 User Manual Firmware V-5.8
Data Flow
led
Link
Established
Ethernet
led
Connector
LED FUNCTIONS:
GREEN: This led turns on when the ethernet link is established (connector inserted)
YELLOW: This led blinks when data transfer occurs inwards or outwards. Periodic blinking will witness
data flow.
- 26 -
FG-100 User Manual Firmware V-5.8
4. TOPOLOGIES
Generator
Parameters
s
Topology
Selection
- 27 -
FG-100 User Manual Firmware V-5.8
- 28 -
FG-100 User Manual Firmware V-5.8
- 29 -
FG-100 User Manual Firmware V-5.8
- 30 -
FG-100 User Manual Firmware V-5.8
- 31 -
FG-100 User Manual Firmware V-5.8
5. FUNCTIONALITIES
The same unit provides different functionalities through parameter setting. Thus, a single stock item will
fulfill various duties, minimizing stock cost.
When the Remote Start functionality is selected, the unit will wait for a Remote Start signal from external
controller. Upon reception of this signal, it will run the engine, and provide engine and alternator
instrumentation and fault monitoring.
The unit features both MPU and J1939 CANBUS input options. Thus, both mechanical and electronic
engines are supported.
When the Engine Controller functionality is selected, genset electrical measurements and protections will
be disabled. The unit is supposed to control an engine without alternator.
When the Engine Control Mode is activated:
-the unit will not display genset AC parameters (volts, amps, kW and pf).
-genset voltage and frequency protections are disabled. However engine rpm protections will be
active.
The unit features both MPU and J1939 CANBUS inputs. Thus both mechanical and electronic engines
are supported.
- 32 -
FG-100 User Manual Firmware V-5.8
6. CONNECTION DIAGRAMS
- 33 -
FG-100 User Manual Firmware V-5.8
- 34 -
FG-100 User Manual Firmware V-5.8
7. TERMINAL DESCRIPTION
- 35 -
FG-100 User Manual Firmware V-5.8
- 36 -
FG-100 User Manual Firmware V-5.8
8. TECHNICAL SPECIFICATIONS
EU Directives Conformity
-2014/35/EC (low voltage)
-2014/30/EC (electro-magnetic compatibility)
Norms of reference:
EN 61010 (safety requirements)
EN 61326 (EMC requirements)
- 37 -
FG-100 User Manual Firmware V-5.8
9. DESCRIPTION OF CONTROLS
Graphic LCD
screen
Next screen
Fault condition
group.
indicators
LAMP TEST if
held pressed
Mimic Diagram
(sysem status) Next screen in
the same group.
ALARM Mute
When the engine hours OR the time limit is over, the SERVICE REQUEST led (red) will start to flash and the
service request output function will be active. The service request can also create a fault condition of any
level following parameter setting.
The service request output function may be assigned to any digital output using Relay Definition
program parameters.
To turn off the SERVICE REQUEST led, and reset the service
period, press together the OFF and LAMP TEST keys for 5
seconds.
- 38 -
FG-100 User Manual Firmware V-5.8
BUTTON FUNCTION
Selects RUN mode. The genset runs off-load.
If held pressed for 5 seconds, selects TEST mode. In TEST mode the
genset runs and takes the load.
Selects AUTO mode. The genset runs on REMOTE START signal status.
When held pressed for 5 seconds, resets service request counters. Please
review chapter SERVICE REQUEST ALARM for more details.
- 39 -
FG-100 User Manual Firmware V-5.8
Each depression of the button will cause the display to switch to the next group of parameters. After
the last group the display will switch to the first group.
Each depression of the button will cause the display to switch to the next parameter in the same
group. After the last parameter the display will switch to the first parameter.
Below is a basic list of parameter groups:
Genset Parameters: Genset voltages, currents, kW, kVA, kVAr, pf etc...
Engine Parameters: Analog sender readings, rpm, battery voltage, engine hours, etc...
J1939 Parameters: Opens only if the J1939 port is enabled. The unit is able to display a long list of
parameters, under the condition that the engine sends this information. A complete list of available
readings is found at chapter J1939 CANBUS ENGINE SUPPORT.
Alarm Display: This group displays all existing alarms, one screen per alarm. When there is no more
alarm to display it will show “END OF ALARM LIST”.
GSM Modem Parameters: Signal strength, counters, communication status, IP addresses etc...
Ethernet Parameters: Ethernet connection status, counters, IP addresses etc...
Status & Counters Groups: This group includes various parameters like genset status, service
counters, firmware version etc...
- 40 -
FG-100 User Manual Firmware V-5.8
The unit features 3 analog senders, fully configurable for the name and function.
Below is a typical list of analog senders, capable of changing following configuration:
Coolant temperature
Oil pressure (bar, kPa)
Fuel level (%, lt)
- 41 -
FG-100 User Manual Firmware V-5.8
Alarm indicator
Warning indicator
Service request
indicator
FLASH: Genset
running
ON: Genset
Contactor on
STATUS LEDS:
ALARM: Turns on when a shutdown fault condition exists.
WARNING: Turns on when a warning fault condition exists.
SERVICE REQUEST: Turns on when at least one of the service counters has expired.
GENSET: Flashes when all genset phase voltages and the genset frequency are within limits. If
enabled, the genset phase rotation order must be also right. Turns on when the GENSET
CONTACTOR is activated.
MODE LEDS: Each led turns on when the related mode is selected, either locally or remotely.
- 42 -
FG-100 User Manual Firmware V-5.8
The unit features more than 400 event logs with date-time stamp and full snapshot of measured values at
the moment that the event has occurred.
Stored values in an event record are listed below:
-event number
-event type / fault definition (see below for various event sources)
-engine hours
-operation mode
-operation status (on-load, on-mains, cranking, etc...)
-engine hours run
-genset phase voltages: L1-L2-L3
-genset phase currents: L1-L2-L3
-genset frequency
-genset total active power (kW)
-genset total power factor
-oil pressure
-engine temperature
-fuel level
-oil temperature
-canopy temperature
-ambient temperature
-engine rpm
-battery voltage
-charge voltage
Possible event sources are various. Every source can be individually enabled or disabled:
Event enable
selection tab
Program mode entrance event: recorded with the password level when program mode is entered.
Mode change event: recorded when the operation mode is changed.
Shutdown/loaddump/warning events: recorded when the related fault condition occurs.
Remote Start/Remote Stop events: recorded when mains status is changed
Engine started/stopped events: recorded when engine status is changed
Genset on_load/off_load events: recorded when the genset loading status is changed
- 43 -
FG-100 User Manual Firmware V-5.8
Event logs are also displayed within the main screen. Press button to find event record screen.
When displaying event logs, button will display the next event.
Alarms are displayed with their numbers and engine hour on event log screen.
Press to navigate
between screens.
- 44 -
FG-100 User Manual Firmware V-5.8
These counters are kept in a non-volatile memory and are not affected from power failures.
The unit is capable to display the actual fuel consumption of the engine through J1939 fuel consumption
information
If the engine is sending the fuel rate through J1939 messaging, then the unit will directly display the fuel
consumption information coming from the ECU.
Related parameters are:
Required Description
Parameter Definition Unit Min Max
Value
Fuel Counter Unit Lt/gal - - any This is the unit for the fuel counter
- 45 -
FG-100 User Manual Firmware V-5.8
LOAD TEST: Hold pressed RUN button for 5 seconds. The genset will run and take the load.
- 46 -
FG-100 User Manual Firmware V-5.8
When REMOTE START signal arrives then an engine start sequence begins:
The unit waits during Engine Start Delay for skipping short mains failures. If the mains is restored
before the end of this timer, the genset will not start.
The unit turns on the fuel and preheat glow plugs (if any) and waits for preheat timer.
The engine will be cranked for programmed times during crank timer. When the engine fires, the
crank relay will be immediately deactivated. See section Crank Cutting for more details.
The engine will run at idle speed during Idle Speed Timer.
The engine will run unloaded during engine heating timer.
If alternator phase voltages, frequency and phase order are correct, the unit will wait for the
generator contactor period and the generator contactor will be energized.
When REMOTE START signal goes off then an engine stop sequence begins:
The engine will continue to run for the mains waiting period to allow mains voltages to stabilize.
Then the generator contactor is deactivated and the mains contactor will be energized after mains
contactor timer.
If a cooldown period is given, the generator will continue to run during the cooldown period.
Before the end of cooldown, the unit will reduce the engine speed to idle speed.
At the end of cooldown, the fuel solenoid will be de-energized, the stop solenoid will be energized for
Stop Solenoid timer and the diesel will stop.
The unit will be ready for the next mains failure.
- 47 -
FG-100 User Manual Firmware V-5.8
In order to stop the engine press button or select another mode of operation.
The TEST mode is entered by holding pressed the button for 5 seconds.
The TEST mode is used in order to test the genset under load.
Once this mode is selected, the engine will run as described in the RUN mode, regardless of the REMOTE
START signal and the load will be transferred to the genset.
The genset will feed the load indefinitely unless another mode is selected.
- 48 -
FG-100 User Manual Firmware V-5.8
The unit provides 3 different protection levels, being warnings, loaddumps and shutdown alarms.
1- SHUTDOWN ALARMS: These are the most important fault conditions and cause:
- The ALARM led to turn on steadily,
- The genset contactor to be released immediately,
- The engine to be stopped immediately,
- The Alarm digital output to operate.
2- LOAD_DUMPS: These fault conditions come from electrical trips and cause:
- The ALARM led to turn on steadily,
- The genset contactor to be released immediately,
- The engine to be stopped after Cooldown period,
- The Alarm digital output to operate.
3- WARNINGS: These conditions cause:
- The WARNING led to turn on steadily,
- The Alarm digital output to operate.
Most of the alarms have programmable trip levels. See the programming chapter for adjustable alarm limits.
- 49 -
FG-100 User Manual Firmware V-5.8
To turn off the SERVICE REQUEST led, and reset the service
period, press together the STOP and LAMP TEST keys for 5
seconds.
The remaining engine hours and the remaining time limits are kept stored in a non-volatile memory and are
not affected from power supply failures.
The time and engine hours to service are displayed in the GENSET STATUS menu group.
- 50 -
FG-100 User Manual Firmware V-5.8
Alarms are displayed with their numbers. Thus, a reference list is necessary to decrypt the alarm details.
The unit has 256 shutdown alarms, 256 loaddump alarms and 256 warnings. Thus, a total of 768 different
alarms may be displayed.
• Warnings are displayed with (!e) prefix.
• Shutdowns and loaddumps are displayed with (Xe) prefix.
A sample Alarm: !e0569 = High Engine Temperature Warning
- 51 -
FG-100 User Manual Firmware V-5.8
- 52 -
FG-100 User Manual Firmware V-5.8
- 53 -
FG-100 User Manual Firmware V-5.8
- 54 -
FG-100 User Manual Firmware V-5.8
- 55 -
FG-100 User Manual Firmware V-5.8
14. PROGRAMMING
Hold
Pressed
For 5
seconds
Hold pressed
The program mode is used to adjust timers, operational limits and the configuration of the unit.
Although a free PC program is provided for programming, every parameter may be modified through the front
panel, regardless of the operating mode.
When modified, program parameters are automatically recorded into a non-erasable memory and take effect
immediately.
The program mode will not affect the operation of the unit. Thus programs may be modified anytime, even
while the genset is running.
- 56 -
FG-100 User Manual Firmware V-5.8
Press 2 buttons
for 5 seconds
The buttons modify the value of the current digit. The buttons navigate between digits.
The unit supports 3 password levels. The level_1 is designed for field adjustable parameters. The level_2
is designed for factory adjustable parameters. The level_3 is reserved. It allows recalibration of the unit.
The password level-1 is factory set to ‘1234’ and the password level-2 is factory set to ‘9876’.
If a wrong password is entered, the unit will still allow access to the program parameters, but in read-only
mode.
If password “0000” is entered, only EVENT LOG file will be available.
Increase
parameter
value
Previous
parameter
Decrease
parameter
Long Press:
value
Return to the
upper menu
Next
parameter
- 57 -
FG-100 User Manual Firmware V-5.8
To exit the program mode press STOP button. If no button is pressed during 2 minutes the program
mode will be cancelled automatically.
Press STOP
button to exit
PROGRAM
mode
- 58 -
FG-100 User Manual Firmware V-5.8
Factory Description
Parameter Definition Unit Min Max
Set
This parameter is used to set LCD
001-LCD Contrast - 30 50 31 contrast. Adjust for the best viewing
angle.
This parameter defines the delay after
002-Fault Holdoff Timer sec 0 120 12 the engine runs and before the fault
monitoring is enabled.
This is the period during which the
ALARM relay is active. If the period is
003-Alarm Relay Timer sec 0 120 60
set to 0, this will mean that the period is
unlimited.
0: In RUN mode, the load will not be
transferred to the genset even if the
004-Emergency Backup mains fails.
- 0 1 0
Operation 1: In RUN mode, the load will be
transferred to the genset if the mains
fails.
005-Exercise Enable -
0: exercise once per week
1: exercise once per month
006-Exercise Period - 0 1 0 The exact exerciser day and time is
adjusted within the EXERCISE
SCHEDULE section.
007-Exercise Off/On 0: Exercise at RUN mode
- 0 1 1
Load 1: Exercise at TEST mode
008-Delayed Simulate 0: delayed simulate mains disabled
- 0 1 0
Mains 1: delayed simulate mains enabled
0: SMS messages disabled
009-SMS Enable - 0 1 0
1: SMS messages enabled
010-GPRS Connection 0: GPRS disabled
- 0 1 0
Enable 1: GPRS enabled
011-Rainbow Scada The unit will update the distant
sec 0 65535 5
Refresh Rate monitoring terminal with this rate.
012-Rainbow Scada This is the port number of the first
- 0 65535 0
Address-1 Port monitoring terminal address.
013-Rainbow Scada This is the port number of the second
- 0 65535 0
Address-2 Port monitoring terminal address.
This is the modbus controller identity
014-Modbus Address - 0 240 1
used in Modbus communication.
0: crank cut is performed through oil
pressure switch and oil pressure sender
015-Oil Pressure Switch
- 0 1 0 reading
Priority
1: crank cut is performed only through
oil pressure switch
Delayed Simulate Mains Operation:
max genset running time after Simulate
016-Flashing Relay ON
min 0 1200 0 Mains signal disappears.
Timer
Dual Genset Systems: flashing relay
ON state duration timer.
017-Flashing Relay OFF Dual Genset Systems: flashing relay
min 0 1200 0
Timer OFF state duration.
- 59 -
FG-100 User Manual Firmware V-5.8
Factory Description
Parameter Definition Unit Min Max
Set
This parameter provides the mains and
genset voltage limits with a hysteresis
feature in order to prevent faulty
decisions.
For example, when the mains are
018-Hysteresis Voltage V-AC 0 30 8
present, the mains voltage low limit will
be used as the programmed low limit.
When the mains fail, the low limit will be
incremented by this value. It is advised
to set this value to 8 volts.
0: Genset control
019-Engine Control Only - 0 1 0
1: Engine control (no alternator)
This parameter is used for frequency to
rpm conversion. For a 1500/1800 rpm
020-Alternator Pole Pairs - 1 8 2
engine select 2. For a 3000/3600 rpm
engine select 1.
This parameter controls SMS sending
when mains voltages status is changed.
021-SMS on Mains
- 0 1 0 No warnings generated.
Change
0: no SMS on mains failed or restored
1: SMS sent on mains failed or restored
This parameter controls SMS sending
when IP address of GPRS connection is
022-SMS on IP Change - 0 1 0 changed. No warnings generated.
0: no SMS on IP change
1: SMS sent on IP change
If the fuel level measured from the
sender input falls below this level, then
023-Fuel Pump Low Limit % 0 100 20
the FUEL PUMP function will become
active.
If the fuel level measured from the
024-Fuel Pump High sender input goes above this level, then
% 0 100 80
Limit the FUEL PUMP function will become
passive.
This parameter controls the activation of
the ALARM output during “Engine Start
025-Warning Before Start - 0 1 1 Delay” timer before engine run.
0: no warning before start
1: warning before start
0: warnings are latching/non-latching on
parameter control
026-Latch all Warnings - 0 1 0 1: all warnings are latched. Even if the
fault source is removed, warnings will
persist until manually reset.
This parameter controls remote control
of the unit through Rainbow, Modbus
027-Remote Control
- 0 1 1 and Modbus TCP/IP.
Enable
0: remote control disabled
1: remote control enabled
This parameter is useful to invert all CT
028-Reverse CT polarities at the same time.
- 0 1 0
Direction 0: normal CT polarity assumed.
1: reverse CT polarity assumed.
029-Change Level-1 Level-1 password may be modified with
- 0000 9999 1234
Password this parameter
030-Change Level-2 Level-2 password may be modified with
- 0000 9999 9876
Password this parameter
- 60 -
FG-100 User Manual Firmware V-5.8
Factory Description
Parameter Definition Unit Min Max
Set
If no button is pressed during this
031-LCD Backlight period, then the unit will reduce the LCD
min 0 1440 60
Dimming Delay screen backlight intensity in for
economy.
After activation of the fuel pump
function, if the Fuel Pump High Limit
level is not reached, then the fuel pump
032-Fuel Filling Timer sec 0 36000 0
will stop for safety.
If this parameter is set to zero, then the
timer is unlimited.
0: The unit powers up in STOP mode
033-Open with Last
- 0 1 0 1: The unit powers up in the same
Mode
operating mode before power down.
If this parameter is not zero, the unit will
activate the Wait Before Transfer output
function during this timer, before
034-Pre-Transfer Delay sec 0 60 0 initiating a load transfer.
This function is designed for elevator
systems, in order to bring the cabin to a
floor and open doors before transfer.
035-Enable Auto not 0: Auto not Ready Warning disabled
- 0 1 0
Ready Warning 1: Auto not Ready Warning enabled
This parameter controls SMS sending
when the engine runs or stops. No
036-SMS on Engine
- 0 1 0 warnings generated.
Run/Stop
0: no SMS on engine run/stop
1: SMS sent on engine run/stop
037-Dual Genset Equal 0: Equal aging not enabled
- 0 1 0
Aging Enabled 1: Equal aging enabled
038-CT Secondary 0: xxx/5A
- 0 1 0
Rating 1: xxx/1A
If enabled, the unit will generate a non-
visual warning when maintenance
counters are reset. In consequence,
039-Maintenance Done SMS and e-mails will be sent, the
- 0 1 0
Warning Enable warning will be visible on the central
monitoring system.
0: maintenance warning disabled
1: maintenance warning enabled
This parameter adjusts the time zone of
the controller, in order to allow internal
040-Time Zone min -720 +720 0
real time clock to be synchronized to
the UTC time.
0: no location information from GSM
041-GSM Location
- 0 1 0 1: location information read from GSM
Information
system.
0: When Loaddump alarm occurs,
genset contactor opens and genset
runs until the end of the cooldown
042-Disable STOP at
- 0 1 0 period.
Loaddump
1: When Loaddump alarm occurs,
genset contactor opens but the genset
continues running without timeout.
This is the primary/secondary ratio of
043-Current Transformer
- 1 1000 100 current transformers. All transformers
Ratio
must have the same ratio.
- 61 -
FG-100 User Manual Firmware V-5.8
Factory Description
Parameter Definition Unit Min Max
Set
This is the voltage transformer ratio.
044-Voltage Transformer This value will multiply all voltage and
- 0 5000 1.0
Ratio power readings. If transformers are not
used, the ratio should be set to 1.0
The nominal value of genset and mains
V-
045-Nominal Voltage 0 300 230 voltages. Voltage limits are defined by
AC
reference to this value.
The nominal value of genset and mains
046-Nominal Frequency Hz 0 500 50 frequency. Frequency limits are defined
by reference to this value.
When secondary voltage is selected,
V- this is the nominal value of genset and
047-Nominal Voltage-2 0 300 120
AC mains voltages. Voltage limits are
defined by reference to this value.
When secondary frequency is selected,
this is nominal value of genset and
048-Nominal Frequency-2 Hz 0 500 60
mains frequency. Frequency limits are
defined by reference to this value.
When tertiary voltage is selected, this is
V- the nominal value of genset and mains
049-Nominal Voltage-3 0 300 120
AC voltages. Voltage limits are defined by
reference to this value.
When tertiary frequency is selected, this
is nominal value of genset and mains
050-Nominal Frequency-3 Hz 0 500 60
frequency. Frequency limits are defined
by reference to this value.
If one of the genset phase voltages goes
051-Genset Low Voltage under this limit when feeding the load,
% V-100 V+100 V-15%
Warning Limit this will generate a GENSET LOW
VOLTAGE warning.
If one of the genset phase voltages goes
under this limit when feeding the load,
052-Genset Low Voltage
% V-100 V+100 V-20% this will generate a GENSET LOW
Shutdown Limit
VOLTAGE shutdown alarm and the
engine will stop.
If one of the genset phase voltages goes
053-Genset High Voltage over this limit when feeding the load, this
% V-100 V+100 V+15%
Warning Limit will generate a GENSET HIGH
VOLTAGE warning.
If one of the genset phase voltages goes
over this limit when feeding the load, this
054-Genset High Voltage
% V-100 V+100 V+20% will generate a GENSET HIGH
Shutdown Limit
VOLTAGE shutdown alarm and the
engine will stop.
If at least one of the genset phase
055-Genset Voltage Fail voltages goes outside of the limits
sec 0 10 1
Timer during this timer, a genset voltage fault
will occur.
If the genset frequency goes under this
056-Genset Low limit when feeding the load, this will
% F-100 F+100 V-15%
Frequency Warning Limit generate a GENSET LOW
FREQUENCY warning.
If the genset frequency goes under this
limit when feeding the load, this will
057-Genset Low
% F-100 F+100 F-20% generate a GENSET LOW
Frequency Shutdown Limit
FREQUENCY shutdown alarm and the
engine will stop.
- 62 -
FG-100 User Manual Firmware V-5.8
Factory Description
Parameter Definition Unit Min Max
Set
If the genset frequency goes over this
058-Genset High limit when feeding the load, this will
% F-100 F+100 F+15%
Frequency Warning Limit generate a GENSET HIGH
FREQUENCY warning.
If the genset frequency goes over this
059-Genset High limit when feeding the load, this will
Frequency Shutdown % F-100 F+100 F+20% generate a GENSET HIGH
Limit FREQUENCY shutdown alarm and the
engine will stop.
If the genset frequency goes outside of
060-Genset Frequency
sec 0 10 1 the limits during this timer, a genset
Fail Timer
frequency fault will occur.
If the battery voltage falls below this
061-Low Battery Voltage
V-DC 5.0 35.0 12.0 limit, this will generate a LOW
Warning Limit
BATTERY warning.
If the battery voltage falls below this
062-Low Battery Voltage limit, this will generate a LOW
V-DC 5.0 35.0 9.0
Shutdown Limit BATTERY shutdown alarm and the
engine will stop.
f the battery voltage goes over this limit,
063-High Battery Voltage
V-DC 5.0 35.0 29.0 this will generate a HIGH BATTERY
Warning Limit
warning.
If the battery voltage goes over this
064-High Battery Voltage limit, this will generate a HIGH
V-DC 5.0 35.0 30.0
Shutdown Limit BATTERY shutdown alarm and the
engine will stop.
If the battery voltage goes outside of the
065-Battery Voltage Fail
sec 0 10 3 limits during this timer, a battery voltage
Timer
fault will occur.
If any genset phase voltage differs from
the average more than this limit, it will
generate a Voltage Unbalance fault
066-Genset Voltage
% 0 100 0.0 condition. The action taken upon fault
Unbalance Limit
condition is programmable.
If this parameter is set to 0.0 then
voltage unbalance is not monitored
0: no action
067-Genset Voltage 1: shutdown alarm
- 0 3 0
Unbalance Action 2: loaddump alarm
3: warning
If any genset phase current differs from
the average more than this limit, it will
generate a Current Unbalance fault
068-Genset Current
% 0 100 0.0 condition. The action taken upon fault
Unbalance Limit
condition is programmable.
If this parameter is set to 0.0 then
voltage unbalance is not monitored
0: no action
069-Genset Current 1: shutdown alarm
- 0 3 0
Unbalance Action 2: loaddump alarm
3: warning
If the genset power is negative and
goes above this limit then a
070-Genset Reverse REVERSE POWER warning will be
kW 0 50000 0
Power Warning Limit generated. If this parameter is set to
0 then reverse power fault is not
monitored.
- 63 -
FG-100 User Manual Firmware V-5.8
Factory Description
Parameter Definition Unit Min Max
Set
If the genset power is negative and
071-Genset Reverse
kW 0 50000 0 goes above this limit then a REVERSE
Power Loaddump Limit
POWER loaddump will be generated.
If the genset power is negative and over
072-Genset Reverse
sec 0 120 5 limits during this timer, a reverse power
Power Fail Timer
fault will occur.
If one of the genset phase currents goes
over this limit when feeding the load, this
will generate a genset overcurrent fault
073-Genset Overcurrent
Amp 0 50000 0 condition. The action taken upon fault
Limit
condition is programmable. If this
parameter is set to 0 then overcurrent
fault is not monitored.
When secondary voltage is selected, if
one of the genset phase currents goes
over this limit when feeding the load, this
074-Genset Overcurrent will generate a genset overcurrent fault
Amp 0 50000 0
Limit-2 condition. The action taken upon fault
condition is programmable. If this
parameter is set to 0 then overcurrent
fault is not monitored.
When tertiary voltage is selected, if one
of the genset phase currents goes over
this limit when feeding the load, this will
075-Genset Overcurrent generate a genset overcurrent fault
Amp 0 50000 0
Limit-3 condition. The action taken upon fault
condition is programmable. If this
parameter is set to 0 then overcurrent
fault is not monitored.
076-Genset Overcurrent 0: shutdown alarm
- 0 3 0
Action 1: loaddump alarm
This parameter defines the reaction
speed of the overcurrent detector. A
077-Overcurrent Time
0 1 64 16 higher number means higher sensitivity.
Multiplier
Detailed explanation is given at chapter:
“Overcurrent Protection”
If the total genset active power goes over
this limit when feeding the load, this will
078-Genset Overload
kW 0 50000 0 generate a genset overload loaddump
Limit
alarm. If this parameter is set to 0 then
overload fault is not monitored.
If the genset active power is over the
079-Genset Overload
sec 0 120 3 limit during this timer, an overload fault
Fail Timer
will occur.
If the genset power goes below this limit
080-Load Shedding Low then the load shedding relay will be
kW 0 50000 0
Limit deactivated. Review chapter “Load
Shedding” for more details.
If the genset power goes above this
081-Load Shedding High limit then the load shedding relay will be
kW 0 50000 0
Limit activated. Review chapter “Load
Shedding” for more details.
This is the minimum delay between 2
082-Load Add Delay sec 0 240 0 load_add pulses. Review chapter “Load
Shedding” for more details.
- 64 -
FG-100 User Manual Firmware V-5.8
Factory Description
Parameter Definition Unit Min Max
Set
This is the minimum delay required for a
083-Load Subtract-Add load_add pulse after a load_substract
min 0 120 0
Delay pulse. Review chapter “Load Shedding”
for more details.
This is the connection topology of
genset voltages and CTs. Detailed
explanations are given in the chapter:
TOPOLOGIES.
0: 2 phase, 3 wire L1-L2
084-Genset Connection 1: 2 phase, 3 wire L1-L3
- 0 7 5
Topology 2: 3 phase, 3 wire
3: 3 phase, 3 wire, 2CTs L1-L2
4: 3 phase, 3 wire, 2CTs L1-L3
5: 3 phase, 4 wire star
6: 3 phase, 4 wire delta
7: single phase, 2 wire
This is the period after the mains
085-Genset Contactor contactor has been deactivated and
sec 0 600 0.5
Timer before the genset contactor has been
activated.
After the genset MCB_undervoltage coil
is energized and genset
MCB_undervoltage coil timer is
086-Genset MCB Close
sec 0 10 0.5 elapsed, the genset MCB_close relay
Pulse
will be activated during this period.
Review chapter “Motorized Circuit
Breaker Control” for more details.
The genset MCB_open relay will be
087-Genset MCB Open activated during this period.
sec 0 10 0.5
Pulse Review chapter “Motorized Circuit
Breaker Control” for more details.
The genset MCB_undervoltage coil is
energized during this period before the
088-Genset MCB Under
sec 0 10 0.5 genset MCB_close relay is activated.
Voltage Coil Timer
Review chapter “Motorized Circuit
Breaker Control” for more details.
0: shutdown alarm
089-GCB Alarm Level - 0 1 0
1: loaddump alarm
If a genset MCB feedback input is
090-Genset MCB Fail defined and if the genset MCB fails to
sec 0 600 2.0
Timer change position before the expiration of
this timer, then a fault condition occurs.
0: genset phase order checking
disabled
091-Genset Phase Order
- 0 1 0 1: if genset phase order is faulty, then a
Check Enable
genset phase order fail loaddump alarm
is given.
When the genset active power goes
092-Multi Load Subtract over this limit, the controller will start
kW 0 65000 0
Power Level subtracting load as described in chapter
Five Step Load Management.
When the genset active power goes
093-Multi Load Add below this limit, the controller will start
kW 0 65000 0
Power Level adding load as described in chapter
Five Step Load Management.
- 65 -
FG-100 User Manual Firmware V-5.8
Factory Description
Parameter Definition Unit Min Max
Set
If the load stays over the Multi Load
094-Multi Load Subtract Subtract Power Level parameter
sec 0 36000 0
Start Delay during this timer, then 1 step of load is
subtracted.
095-Multi Load Subtract This is the minimum period between
sec 0 36000 0
Wait Delay two load subtract operations.
If the load stays below the Multi Load
096-Multi Load Add Start
sec 0 36000 0 Add Power Level parameter during
Delay
this timer, then 1 step of load is added.
097-Multi Load Add Wait This is the minimum period between
sec 0 36000 0
Delay two load add operations.
If the genset active power goes above
098-Excess power
kW 0 50000 0 this limit then the controller will give an
Warning Limit
Excess Power Warning.
The nominal value of engine rpm. Low-
099-Nominal RPM rpm 0 50000 1500 high rpm limits are defined by
reference to this value.
When secondary frequency is selected,
this is the nominal value of engine rpm.
100-Nominal RPM-2 rpm 0 50000 1800
Low-high rpm limits are defined by
reference to this value.
When tertiary frequency is selected,
this is the nominal value of engine rpm.
101-Nominal RPM-3 rpm 0 50000 1800
Low-high rpm limits are defined by
reference to this value.
If the engine rpm goes under this limit
102-Low RPM Warning
% R-100 R+100 R-10% when feeding the load, this will generate
Limit
a GENSET LOW RPM warning.
If the engine rpm goes under this limit
103-Low RPM Shutdown when feeding the load, this will generate
% R-100 R+100 R-15%
Limit a GENSET LOW RPM shutdown alarm
and the engine will stop.
If the engine rpm goes over this limit
104-High RPM Warning
% R-100 R+100 R+10% when feeding the load, this will generate
Limit
a GENSET HIGH RPM warning.
If the engine rpm goes over this limit
105-High RPM when feeding the load, this will generate
% R-100 R+100 R+15%
Shutdown Limit a GENSET HIGH RPM shutdown alarm
and the engine will stop.
If the engine rpm goes outside of the
106-RPM Fail Timer sec 0 10 3 limits during this timer, an engine
speed fault will occur.
If the engine rpm goes over the “High
RPM Shutdown Limit” by this quantity,
107-Overspeed HRSL HRSL HRSL
% this will generate immediately a
Overshoot Limit -100 +100 +10%
GENSET HIGH RPM shutdown alarm
and the engine will stop.
If the charge alternator voltage goes
108-Low Charge Voltage
V-DC 0 40 6.0 under this limit, a charge alternator
Warning Limit
voltage warning will occur.
If the charge alternator voltage goes
109-Low Charge Voltage under this limit, a charge alternator
V-DC 0 40 4.0
Shutdown Limit voltage shutdown will occur and the
engine will stop.
110-Charge Voltage Fail If the charge alternator voltage goes
Timer under limits during this timer, a charge
sec 0 120 1
alternator voltage fault will occur.
- 66 -
FG-100 User Manual Firmware V-5.8
Factory Description
Parameter Definition Unit Min Max
Set
If it is requested that the engine runs
111-Engine Heating without load until reaching a certain
°C 0 80 0
Temperature temperature, this parameter defines
the temperature.
This is the time between the mains fails
and the fuel solenoid turns on before
112-Engine Start Delay min 0 720 1 starting the genset. It prevents
unwanted genset operation in battery
backed-up loads.
This is the time after the fuel solenoid
is energized and before the genset is
113-Preheat Timer sec 0 30 0 started. During this period the
PREHEAT relay output is energized (if
assigned by Relay Definitions)
This is the maximum start period.
114-Crank Timer sec 1 15 6 Starting will be automatically cancelled
if the genset fires before the timer.
This is the waiting period between two
115-Wait Between Starts sec 1 240 10
start attempts.
116-Engine Heating This is the period used for engine
sec 0 240 4
Timer heating before load transfer.
The genset will not take the load before
engine heating is completed.
0: engine is heated during Engine
117-Engine Heating Heating Timer.
- 0 1 0
Method 1: engine is heated until the coolant
temperature reaches the Engine
Heating Temperature and at least
during the Engine Heating Timer.
This is the period that the generator
118-Cooldown Timer sec 0 600 120 runs for cooling purpose after the load
is transferred to mains.
This is the maximum time duration for
the engine to stop. During this period
the STOP relay output is energized (if
119-Stop Solenoid Timer sec 0 90 10 assigned by Relay Definitions). If the
genset has not stopped after this
period, a FAIL TO STOP warning
occurs.
120-Number of Starts - 1 6 3 Number of Start attempts
This is the control delay of CHOKE
output.
The choke output is activated together
121-Choke Timer sec 0 240 5
with the crank output. It is released
after this delay or when engine runs
(whichever occurs first).
When the engine runs, the Idle output
relay function will be active during this
122-Idle Speed (Run)
sec 0 240 0 timer. While the IDLE output is active,
Timer
low voltage, low frequency and low rpm
checks are disabled.
Before the engine stops, the Idle output
relay function will be active during this
123-Idle Speed (Stop)
sec 0 240 0 timer. While the IDLE output is active,
Timer
low voltage, low frequency and low rpm
checks are disabled.
- 67 -
FG-100 User Manual Firmware V-5.8
Factory Description
Parameter Definition Unit Min Max
Set
While the IDLE period is over, low
voltage, low frequency and low speed
124-Idle Holdoff Timer sec 0 30 10
checks are enabled after the expiration
of this timer.
The gas solenoid of the gas engine (if
125-Gas Solenoid Delay sec 0 240 5 assigned by Relay Definitions) will be
opened after this delay during cranking.
The crank relay output is deenergized
126-Crank Cut Voltage V-AC 0 65000 100 when the genset phase L1 voltage
reaches this limit.
The crank relay output is deenergized
127-Crank Cut
Hz 0 100 10 when the genset frequency reaches this
Frequency
limit.
The crank relay output is deenergized
128-Crank Cut RPM rpm 0 65000 500
when the engine rpm reaches this limit.
The crank relay output is deenergized
129-Crank Cut Charge
V-DC 0 40 6 when the charge alternator voltage
Voltage
reaches this limit.
0: no crank cut with oil pressure
130-Crank Cut with Oil 1: cranking is cut when oil pressure
- 0 1 0
Pressure switch is open or the oil pressure
measured is above shutdown limit.
If crank cutting with oil pressure is
enabled, cranking is cut after this delay
131-Crank Cut with Oil
sec 0 30 2 when oil pressure switch is open or the
Pressure Delay
oil pressure measured is above
shutdown limit.
0: Crank cutting with charge input
132-Charge Input disabled
- 0 1 0
Connected 1: Crank cutting with charge input
enabled
The full capacity of the fuel tank. If this
133-Fuel Tank Capacity Lt 0 65000 0 parameter is zero, the fuel quantity in
the tank is not displayed.
This parameter is the threshold for
sending FUEL THEFT and FUELLING
sms messages.
If this parameter is set to 0, then no
134-Fuel Consumption
% 0 100 0.0 Fuel Theft and Fuelling sms messages
per Hour
will be sent.
If SMS is required, set this parameter to
a value above the hourly fuel
consumption of the genset.
If the coolant temp is above this limit
135-Coolant Cooler On °C 0 250 90 then the cooler relay function will
become active.
If the coolant temp is below this limit
136-Coolant Cooler Off °C 0 250 80 then the cooler relay function will
become inactive.
If the coolant temp is below this limit
137-Coolant Heater On °C 0 250 50 then the heater relay function will
become active.
If the coolant temp is above this limit
138-Coolant Heater Off °C 0 250 60 then the heater relay function will
become inactive.
- 68 -
FG-100 User Manual Firmware V-5.8
Factory Description
Parameter Definition Unit Min Max
Set
The cooler relay will stay active during
139-Fan Overrun Timer sec 0 240 0 this timer after the coolant temp is below
“Coolant Cooler Off” limit.
The SERVICE REQUEST led indicator
will turn on after this quantity of engine
140-Service-1 Engine hours from the last service. If the period
hours 0 5000 250
Hours is set to ‘0’ no SERVICE REQUEST will
be generated depending on service-1
engine hours.
The SERVICE REQUEST led indicator
will turn on after this amount of time
from the last service. If the period is set
141-Service-1 Period month 0 24 6
to ‘0’ no SERVICE REQUEST will be
indicated depending on Service-1
Period.
0: no action
142-Service-1 Alarm 1: shutdown alarm
- 0 3 3
Level 2: loaddump alarm
3: warning
The SERVICE REQUEST led indicator
will turn on after this quantity of engine
143-Service-2 Engine hours from the last service. If the period
hours 0 5000 250
Hours is set to ‘0’ no SERVICE REQUEST will
be generated depending on service-2
engine hours.
The SERVICE REQUEST led indicator
will turn on after this amount of time
from the last service. If the period is set
144-Service-2 Period month 0 24 6
to ‘0’ no SERVICE REQUEST will be
indicated depending on Service-2
Period.
0: no action
145-Service-2 Alarm 1: shutdown alarm
- 0 3 0
Level 2: loaddump alarm
3: warning
The SERVICE REQUEST led indicator
will turn on after this quantity of engine
146-Service-3 Engine hours from the last service. If the period
hours 0 5000 250
Hours is set to ‘0’ no SERVICE REQUEST will
be generated depending on service-3
engine hours.
The SERVICE REQUEST led indicator
will turn on after this amount of time
from the last service. If the period is set
147-Service-3 Period month 0 24 6
to ‘0’ no SERVICE REQUEST will be
indicated depending on Service-3
Period.
0: no action
148-Service-3 Alarm 1: shutdown alarm
- 0 3 0
Level 2: loaddump alarm
3: warning
0: The J1939 port is inoperative.
1: The analog measurements (oil, temp,
149-J1939 Enable - 0 1 0 and rpm) are picked up from the ECU. If
the ECU communication is lost, then the
engine will be stopped.
- 69 -
FG-100 User Manual Firmware V-5.8
Factory Description
Parameter Definition Unit Min Max
Set
0: GENERIC
1: CUMMINS
2: DETROIT DIESEL
3: DEUTZ
4: JOHN DEERE
5: PERKINS
150-J1939 Engine Brand - 0 15 0 6: VOLVO
7: CATERPILLAR
8: SCANIA
9: IVECO
10: MTU-MDEC
11: BOSCH
Other values: Reserved. Do not use.
GENERIC ENGINE BRAND
0: Generic
CUMMINS ENGINE
0: CM850
1: CM570
DETROIT DIESEL ENGINE
0: Generic
DEUTZ ENGINE
0: Generic
1: EMR2
2: EMR3
JOHN DEERE ENGINE
0: Generic
PERKINS ENGINE
0: Generic
1: ADEM3
2: ADEM 1.3
VOLVO ENGINE
0: Generic
1: without CIU unit
151-J1939 ECU Type - 0 7 0 2: EDC4
CATERPILLAR ENGINE
0: Generic
SCANIA ENGINE
0: Generic
1: S6 (Single Speed)
2: S8 (All Speed)
IVECO ENGINE
0: Generic
1: Vector
2: NEF/CURSOR
MTU-MDEC ENGINE
0: MDEC 302
1: MDEC 201
2: MDEC 303
3: MDEC 304
4: MDEC 506
BOSCH INJECTION SYSTEM
0: Generic
1: EDC 731
2: EDC 9.3
This parameter adjusts the speed of an
152-J1939 Speed Adjust % -100 +100 0.0
ECU controlled engine by +/- 8%.
- 70 -
FG-100 User Manual Firmware V-5.8
Factory Description
Parameter Definition Unit Min Max
Set
If the battery voltage goes below this
153-Battery Charge Run limit the engine will be automatically
V-DC 0 35.0 0
Voltage started in order to charge the battery
using the charge alternator.
If the battery voltage goes below the
Battery Charge Run Voltage limit, the
154-Battery Charge Run
min 0 1200 0 engine will be automatically run during
Timer
this period in order to charge the battery
using the charge alternator.
After a crank start, messages coming
155-J1939 Message
sec 0 240 3 from the ECU are ignored during this
Suspand Timer
timer.
If no message is received from the ECU
156-J1939 Message
sec 0 240 3 during this timer, then an ECU Fail
Absence Timer
Alarm is generated.
The oil pump is activated prior to the
crank cycle and stopped when this
157-Oil Pump Stop
bars 0 20 0 pressure level is reached.
Pressure
If this value is set to zero, then the oil
pump is not activated.
0: Engine speeed checking is
performed with the RPM information
158-Disable ECU speed coming from the engine ECU unit.
- 0 1 0
control 1: the RPM information coming from the
engine ECU unit is not used for engine
speed checking.
The SPN number written to this
159-J1939 SPN Mask - 0 65535 0 parameter is excuded from engine ECU
alarm list.
The FMI number written to this
160-J1939 FMI Mask - 0 65535 0 parameter is excuded from engine ECU
alarm list
For Volvo engines, when this parameter
is set to 1, then the speed of the engine
161-J1939 Speed toggle - 0 1 0
is switched between 1500 and 1800
rpm.
162-RTC Date - 01 31 Current day of the month.
163-RTC Month - 01 12 Current month.
164-RTC Year - 00 99 Last two digits of the current year.
165-RTC Hours - 00 23 Current hour of the day.
166-RTC Minutes - 00 59 Current minute of the hour.
167-RTC Seconds - 00 59 Current second of the minute.
- 71 -
FG-100 User Manual Firmware V-5.8
In order to insure fast and reliable crank cutting, the unit uses various resources for engine running
condition detection.
Cranking is stopped when at least one of below conditions is met:
- Crank timer expired:
The crank timer is adjusted through Engine Parameters > Crank Timer. The maximum allowed
timer is 15 seconds.
- Genset AC voltage over threshold:
If the genset phase L1 AC voltage reaches Engine Parameters > Crank Cut Voltage, then
cranking is immediately stopped.
- Genset frequency over threshold:
If the genset phase L1 frequency reaches Engine Parameters > Crank Cut Frequency, then
cranking is immediately stopped.
- Genset rpm over threshold:
If the genset rpm reaches Engine Parameters > Crank Cut RPM, then cranking is immediately
stopped.
- Charge alternator voltage over threshold
Following setting is necessary: Engine Parameters > Charge Input Connected = 1
If the charge alternator voltage reaches Engine Parameters > Crank Cut Charge Voltage, then
cranking is immediately stopped.
- Oil pressure above threshold
Following setting is necessary: Engine Parameters > Crank Cut with Oil Pressure = 1
The crank cutting with oil pressure offers a programmable delay through Engine Parameters >
Crank Cut with Oil Pressure Delay. The parameter is factory set to 2 seconds.
Both low oil pressure switch and oil pressure sender readings may be used for crank cutting. The
oil pressure switch is always used. The sender may be disabled through Controller
Configuration > Oil Pressure Switch Priority parameter.
If enabled, when oil pressure is detected, cranking is stopped after adjustable timer delay.
- 72 -
FG-100 User Manual Firmware V-5.8
The unit offers a programmable IDMT protection function in order to protect the alternator against
excessive currents.
The IDMT (Inverse Definite Minimum Time) protection function has such tripping characteristics that the
tripping time varies inversely with the value of current. Beyond a certain current limit the tripping time
becomes constant (definite) and causes tripping in minimum time.
The tripping formula is defined as below:
Where:
TMS is the IDMT time multiplier setting. This is also the tripping time at 100% overload.
I is the current of the most loaded phase
Iset is the programmed overcurrent limit
t is the tripping time in seconds
Currents below the overcurrent limit are allowed to flow for unlimited time. Currents above the limit will
cause the IDMT protection to trigger with a delay depending on the strength of the overcurrent. Higher the
current, faster the protection will trip.
When a non-tripping overcurrent condition occurs, the unit will keep trace of it. In case of a consecutive
overcurrent, the controller will take into account the residual heat caused by the previous overcurrent and
will trip faster than usual.
The IDMT multiplier adjusts the sensitivity of the IDMT detector. When the multiplier is low, then tripping
will be faster for the same current.
The unit provides separate Overcurrent limits for primary, secondary and tertiary volt/speed/amp settings.
Switching from primary volt/freq/amps to secondary or tertiary values will also switch the IDMT detector to
the secondary/tertiary setting.
The action of the tripping may be selected as a Loaddump (stop after cooldown) or shutdown alarm
(immediate stop).
- 73 -
FG-100 User Manual Firmware V-5.8
Below is a table showing the tripping delay in function of the percent load level (with TMS=36):
100% unlimited 170% 73s 240% 18s
110% 3600s 180% 56s 250% 16s
120% 900s 190% 44s 260% 14s
130% 400s 200% 36s 270% 12s
140% 225s 210% 30s 280% 11s
150% 144s 220% 25s 290% 10s
160% 100s 230% 21s 300% 9s
Below is the tripping delay curve in function of the load level (with TMS=36):
- 74 -
FG-100 User Manual Firmware V-5.8
The unit offers full control for any brand and model of motorized circuit breakers (MCB).
The MCB control is performed through 3 digital output functions, namely Open, Close and Undervoltage
coil controls. Only 2 of these outputs are used in a single application.
Any digital output can be assigned to MCB control signals through programming menu.
- 75 -
FG-100 User Manual Firmware V-5.8
MCB modules can be operated by 2 different ways. The unit supports both configurations.
Below is the terminology used:
M: gear motor
PF: ready to close contact
XF: close coil
MX: open coil
MN: undervoltage trip (release)
AUX: auxiliary contacts
- 76 -
FG-100 User Manual Firmware V-5.8
The unit offers a special J1939 port in order to communicate with electronic engines controlled by an ECU
(electronic control unit). The J1939 port consists of 2 terminals which are J1939+ and J1939-.
The connection between the unit and the engine should be made with an appropriate balanced 120 ohms
low capacitance coaxial cable. The external conductor should be grounded at one end only.
A 120 ohms termination resistor is installed inside the unit. Please do not connect external resistor.
The J1939 port is activated by setting the program parameter J1939 Enable to 1. The J1939 Engine
Type parameter should be set accordingly. The list of available engines is given at the programming
section.
If the J1939 port is enabled then the oil pressure, coolant temperature and the engine rpm information
are picked up from the ECU unit. If connected, the MPU unit and related analog senders are discarded.
The controller is able to read and display all below parameters, under condition that the engine sends
these information. Most engines send only some of them. If the engine does not send a parameter, the
unit will simply skip it. Thus only available information are displayed.
The complete list of J1939 display parameters is below:
PGN 65253 / SPN 247 Engine Total Hours of Operation
PGN 65257 / SPN 250 Engine Total Fuel Used
PGN 65262 / SPN 110 Engine Coolant Temperature
/ SPN 174 Engine Fuel Temperature 1
/ SPN 175 Engine Oil Temperature 1
PGN 65263 / SPN 100 Engine Oil Pressure
/ SPN 94 Engine Fuel Delivery Pressure
/ SPN 98 Engine Oil Level
/ SPN 101 Engine Crankcase Pressure
/ SPN 109 Engine Coolant Pressure
/ SPN 111 Engine Coolant Level
PGN 65266 / SPN 183 Engine Fuel Rate
/ SPN 184 Engine Instantaneous Fuel Economy
/ SPN 185 Engine Average Fuel Economy
PGN 65269 / SPN 108 Barometric Pressure
/ SPN 171 Ambient Air Temperature
/ SPN 172 Engine Air Inlet Temperature
PGN 65270 / SPN 102 Engine Turbocharger Boost Pressure
/ SPN 105 Engine Intake Manifold 1 Temperature
/ SPN 106 Engine Air Inlet Pressure
/ SPN 107 Engine Air Filter 1 Differential Pressure
/ SPN 173 Engine Exhaust Gas Temperature
PGN 65271 / SPN 158
PGN 61443 / SPN 92 Engine Percent Load At Current Speed
/ SPN 91 Accelerator Pedal Position 1
PGN 61444 / SPN 190 Engine Speed
/ SPN 513 Actual Engine - Percent Torque
/ SPN 512 Driver's Demand Engine - Percent Torque
The J1939 measurements are also available for Modbus operation. Please check chapter Modbus
Communications for more details.
When the fuel output is active, if no information is received from the ECU during last 3 seconds, then the
unit will give a ECU FAIL alarm and stop the engine. This feature prevents uncontrolled engine operation.
The fault conditions of an electronic engine are considered by the unit as warnings and do not cause
engine stop. The engine is supposed protected by the ECU which will stop it when necessary.
- 77 -
FG-100 User Manual Firmware V-5.8
The electronic engine fault codes are displayed in text within the alarm list table, together with their
SPN-FMI codes. The complete list of fault codes is given in the engine manufacturer’s user manual.
Below is a basic list of fault conditions (x denotes any FMI)
- 78 -
FG-100 User Manual Firmware V-5.8
- 79 -
FG-100 User Manual Firmware V-5.8
Please be aware that these codes may differ slightly depending on the engine brand and model.
FMI DESCRIPTION
0 Value too high” Valid data, but above the normal working range
1 “Value too low” Valid data, but below the normal working range
2 “Faulty data” Intermittent or faulty data or
Short circuit to battery voltage, injector high voltage side
3 “Electrical fault” Abnormally high voltage or short circuit to battery
voltage, injector low voltage side
4 “Electrical fault” Abnormally low voltage or short circuit to battery
negative, injector low voltage or high voltage side
5 “Electrical fault” Abnormally low current or open circuit
6 “Electrical fault” Abnormally high current or short circuit to battery
negative
7 “Mechanical fault” Faulty response from mechanical system
8 “Mechanical or electrical fault” Abnormal frequency
9 “Communication fault” Abnormal updating rate or
Open circuit in injector circuit
10 “Mechanical or electrical fault” Abnormally large variations
11 “Unknown fault” Unidentified fault
12 “Component fault” Faulty unit or component
13 “Faulty calibration” Calibration values outside the limits
14 “Unknown fault” Special instructions
15 Data valid but above normal operating range - least severe level
16 Data valid but above normal operating range - moderately severe level
17 Data valid but below normal operating range - least severe level
18 Data valid but below normal operating range - moderately severe level
19 Received network data in error
20 not used (reserved)
21 not used (reserved)
22 not used (reserved)
23 not used (reserved)
24 not used (reserved)
25 not used (reserved)
26 not used (reserved)
27 not used (reserved)
28 not used (reserved)
29 not used (reserved)
30 not used (reserved)
31 Condition exist
- 80 -
FG-100 User Manual Firmware V-5.8
t1: the load goes below the Load Shedding Low Limit, thus the Load Shedding output becomes inactive.
t2: the load goes above the Load Shedding High Limit, thus the Load Shedding output becomes active.
t3: the load goes below the Load Shedding Low Limit, thus the Load Shedding output becomes inactive.
- 81 -
FG-100 User Manual Firmware V-5.8
The parameters used in Load Shedding feature are in the Electrical Parameters Group:
Load Shedding Low Limit: If the genset power goes below this limit then the load_add relay will be
active.
Load Shedding High Limit: If the genset power goes above this limit then the load_substract relay will
be active.
Load Add Delay: This is the minimum delay between 2 load_add pulses. This is also the minimum delay
between 2 load_substract pulses.
Load Subtract-Add Delay: This is the minimum delay between load_add and load_substract pulses.
t1: the load goes below the Load Shedding Low Limit, thus the Load Add output becomes active.
t2: the load goes above the Load Shedding Low Limit, thus the Load Add output becomes inactive.
t3: the load goes above the Load Shedding High Limit, thus the Load subtract output becomes active.
t4: the load goes below the Load Shedding High Limit, thus the Load subtract output becomes inactive.
t5: the load goes below the Load Shedding Low Limit, but the Load subtract-Add delay is not expired. The
controller waits until expiration of the timer.
t6: the timer is expired and the load is still below the Load Shedding Low Limit, the Load Add output
becomes active.
t7: the load goes above the Load Shedding Low Limit, thus the Load Add output becomes inactive.
- 82 -
FG-100 User Manual Firmware V-5.8
t1: the load goes below the Multi Load Add Power Level.
t2: after Multi Load Add Start Delay the load is still below Multi Load Add Power Level, the Load_Add_1
sends a pulse.
t3: after Multi Load Add Start Delay and Multi Load Add Wait Delay, the load is still below Multi Load Add
Power Level, thus Load_Add_2 output sends a pulse.
t4: the load goes above the Multi Load Subtract Power Level.
t5: after Multi Load Subtract Start Delay, the load is still above Multi Load Subtract Power Level, thus the
Load_Substract_2 sends a pulse.
t6: the load goes above the Multi Load Subtract Power Level.
t7: Multi Load Subtract Wait Delay is already expired. After Multi Load Subtract Start Delay, the load is still
above Multi Load Subtract Power Level, thus the Load_Subtract_1 output sends a pulse.
- 83 -
FG-100 User Manual Firmware V-5.8
- 84 -
FG-100 User Manual Firmware V-5.8
- 85 -
FG-100 User Manual Firmware V-5.8
- 86 -
FG-100 User Manual Firmware V-5.8
If switching is done with digital input signal, one of digital inputs has to be defined as “2nd Volt-Freq
Select” using “INPUT FUNCTION SELECT“program group.
If third set is used, the one of digital inputs has to be defined as “3 rd Volt-Freq Select” using “INPUT
FUNCTION SELECT“program group.
Below parameters are available for second voltage-frequency selection:
Nominal Voltage
Nominal Frequency
Nominal RPM
Genset Overcurrent Limit
- 87 -
FG-100 User Manual Firmware V-5.8
- 88 -
FG-100 User Manual Firmware V-5.8
- 89 -
FG-100 User Manual Firmware V-5.8
- 90 -
FG-100 User Manual Firmware V-5.8
CONTROLLER
SUPPLY OUTx
BAT+
The controller wakes-up on applying the power through the “wake-up” pushbutton. Then it will
immediately activate the zero power output which will cause the zero power relay to feed the controller.
If the engine is not run, or if the engine stops, a timer of 5 minutes will be counted. At the expiration of the
counter, the controller will deenergize the zero power relay which will cut the power supply. The controller
will wait in a zero-power state until the wake-up pushbutton is depressed again.
- 91 -
FG-100 User Manual Firmware V-5.8
The CE mark indicates that this product complies with the European requirements for safety,
health environmental and customer protection.
23. MAINTENANCE
Wipe the unit, if necessary with a soft damp cloth. Do not use chemical agents
The European ROHS directive restricts and prohibits the use of some chemical materials in electronic
devices.
Following the “DIRECTIVE 2011/65/EU OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of
8 June 2011 on the restriction of the use of certain hazardous substances in electrical and
electronic equipment”, this product is listed in annex-I under category: “Monitoring and control
instruments including industrial monitoring and control instruments” and exempted from ROHS
directive.
- 92 -
FG-100 User Manual Firmware V-5.8
KW and cosΦ readings are faulty although the Amp readings are correct:
-Current transformers are not connected to the correct inputs or some of the CTs are connected with
reverse polarity. Determine the correct connections of each individual CT in order to obtain correct KW
and cosΦ for the related phase, and then connect all CTs. Please review chapter “AC CURRENT
INPUTS”
When the REMOTE START signal arrivess fails the unit energizes the fuel solenoid, but does not
start and OIL PRESSURE EXISTS ! message is displayed:
The unit is not supplied with battery (-) voltage at the oil pressure input.
-Oil pressure switch not connected.
-Oil pressure switch connection wire cut.
-Oil pressure switch faulty.
-Oil pressure switch closes too lately. If oil pressure switch closes, the unit will start. Optionally oil
pressure switch may be replaced.
The engine does not run after the first start attempt, then the unit does not start again and OIL
PRESSURE EXISTS ! message is displayed:
-The oil pressure switch closes very lately. As the unit senses an oil pressure, it does not start. When oil
pressure switch closes the unit will start. Optionally the oil pressure switch may be replaced.
- 93 -
FG-100 User Manual Firmware V-5.8
When the AC mains fails, the engine starts to run but the unit gives START FAIL alarm and then
the engine stops:
-The generator phase voltages are not connected to the unit. Measure the AC voltage between
terminals GEN L1-L2-L3 and Generator Neutral at the rear of the unit while the engine is running. A
fuse protecting the generator phases may be failed. A misconnection may be occurred. If everything is
OK, turn all the fuses off, and then turn all the fuses on, starting from the DC supply fuse. Then test the
unit again.
-The generator voltage rises lately. Also the generator remnant voltage is below 15 volts. The unit
removes starting with the generator frequency, and needs at least 15 volts to measure the frequency.
-The unit is also able to cut cranking from charge alternator voltage and oil pressure input. Please read
chapter “CRANK CUTTING”
Measure the DC-supply voltage between terminals BAT+ and BAT- at the rear of the unit. If OK, turn all
fuses off, then turn all the fuses on, starting from the DC supply fuse. Then test the unit again.
The program lock input disables programming mode entry. Disconnect the program lock input from
battery negative before modification. Do not forget to make this connection again to prevent
unauthorized program modifications.
These parameters are reserved for factory setting and cannot be modified.
AUTO led flashes and the genset does not run when mains fail:
The unit is in Weekly Schedule OFF time. Please check date and time setting of the unit. Please check
also Weekly Schedule program parameters.
Check that the genset Yellow led is on steadily. Adjust genset voltage and frequency limits if necessary.
Check that the digital output-8 is configured as “Genset Contactor”
Check “Genset Contactor Timer” program parameter.
Check that a Genset Loading Inhibit input signal is not active. Check input functions. If an input is
configured as “Genset Loading Inhibit” then check the signal is not present at this input.
- 94 -