A relay at the Lekware Production Station Substation 11 was tested. The test results found that the pick up voltage was 77.5V and pick up current was 10mA for the new settings, which were within acceptable ranges. The drop off voltage was 31.1V and drop off current was 10mA. The test results were found to be satisfactory.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
88 views
DCS Test Report
A relay at the Lekware Production Station Substation 11 was tested. The test results found that the pick up voltage was 77.5V and pick up current was 10mA for the new settings, which were within acceptable ranges. The drop off voltage was 31.1V and drop off current was 10mA. The test results were found to be satisfactory.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 4
SITE TEST REPORT Page: 1/1
INSPECTION AND TESTING OF MVAX SUPERVISION RELAY
General Data;
Station/Location: LEKWARE PRODUCTION
Serial No.1884554/04/06 STATION /SUB STATION-11 Feeder:P3238A -11KV SWITCH GEAR rated auxiliary voltage (DC): 110/125V Model Number:MVAX12R1CA0753A Type:MVAX Make:AREVA Date : 24.04.15 Function No. of Contacts: 2 B Relay Resistance:
1. Operation Checks
Pick up Pick up Drop off Drop off
voltage(V) current(mA) voltage(V) current(mA)
Old 78.31 7.68 32.74 3.22
New 77.5 10 31.1 10
Remarks:Test results found satisfactory
Tested By Witnessed By Approved By
Signature
Name C.A.JKARTHIK Organization POWERTECH STST PDO SITE TEST REPORT Page: 2/1