0% found this document useful (0 votes)
106 views2 pages

4114 Universal Transmitter Data Sheet

The universal transmitter can accept inputs from RTDs, thermocouples, ohms, potentiometers, and mA/V signals. It provides galvanic isolation and has programmable current and voltage outputs. It is FM-approved for hazardous locations and can be programmed using a detachable display for applications like temperature measurement, signal conversion, and process control.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
106 views2 pages

4114 Universal Transmitter Data Sheet

The universal transmitter can accept inputs from RTDs, thermocouples, ohms, potentiometers, and mA/V signals. It provides galvanic isolation and has programmable current and voltage outputs. It is FM-approved for hazardous locations and can be programmed using a detachable display for applications like temperature measurement, signal conversion, and process control.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Universal transmitter

4114
– Input for RTD, TC, Ohm, potentiometer, mA and V
– 2-wire supply > 16 V
– FM-approved for installation in Div. 2
– Output for current and voltage
– Universal AC or DC supply

Advanced features
Applications
• Programmable by way of detachable display front (4501),
process calibration, signal simulation, password protection,
error diagnostics and help text available in several languages.

Application
• Linearized, electronic temperature measurement with RTD or
TC sensor.
• Conversion of linear resistance variation to a standard analog
current / voltage signal, i.e. from solenoids and butterfly
valves or linear movements with attached potentiometer.
• Power supply and signal isolator for 2-wire transmitters.
• Process control with standard analog output.
• Galvanic separation of analog signals and measurement of
floating signals.
• The 4114 is designed according to strict safety requirements
and is therefore suitable for application in SIL 2 installations.

Technical characteristics
• When 4114 is used with the 4501 display / programming front,
all operational parameters can be modified to suit any
application. As the 4114 is designed with electronic hardware
switches, it is not necessary to open the device for setting of
DIP-switches.
• A green / red front LED indicates normal operation and
malfunction.
• Continuous check of vital stored data for safety reasons.
• 3-port 2.3 kVAC galvanic isolation.

This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions Cold junction compensation
(CJC) via ext. sensor in
Operating temperature................................... -20°C to +60°C 5910............................................................... 20...28°C ≤ ±1°C, -20...20°C /
Storage temperature...................................... -20°C to +85°C 28...70°C ≤ 2°C
Calibration temperature................................. 20...28°C CJC via int. mounted sensor.......................... ±(2.0°C + 0.4°C * Δt)
Relative humidity............................................ < 95% RH (non-cond.) Δt =................................................................. Internal temp.-ambient temp.
Protection degree........................................... IP20 Sensor error detection................................... Yes
Sensor error current: When
Mechanical specifications detecting / else............................................... Nom. 2 μA / 0 μA
Dimensions (HxWxD)..................................... 109 x 23.5 x 104 mm Current input
Dimensions (HxWxD) w/ 4501/4511.............. 109 x 23.5 x 116 / 131 mm Measurement range....................................... 0...20 mA
Weight approx................................................ 155 g Programmable measurement ranges............ 0...20 and 4...20 mA
Weight incl. 4501 / 4511 (approx.)................. 170 g / 185 g Input resistance.............................................. Nom. 20 Ω + PTC 50 Ω
Wire size........................................................ 1 x 2.5 mm2 stranded wire Sensor error detection: Loop
Screw terminal torque.................................... 0.5 Nm break 4...20 mA.............................................. Yes
Vibration......................................................... IEC 60068-2-6
2...13.2 Hz...................................................... ±1 mm Voltage input
13.2...100 Hz.................................................. ±0.7 g Measurement range....................................... 0...12 VDC
Programmable measurement ranges............ 0/0.2...1, 0/1...5, 0/2...10 VDC
Common specifications Input resistance.............................................. Nom. 10 MΩ

Supply Output specifications


Supply voltage, universal............................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC Current output
Fuse............................................................... 400 mA SB / 250 VAC Signal range................................................... 0...20 mA
Max. required power...................................... ≤ 2.0 W Programmable signal ranges......................... 0...20/4...20/20...0/20...4 mA
Load (@ current output)................................. ≤ 800 Ω
Isolation voltage Load stability.................................................. ≤ 0.01% of span / 100 Ω
Isolation voltage, test / Sensor error indication................................... 0 / 3.5 / 23 mA / none
working........................................................... 2.3 kVAC / 250 VAC NAMUR NE43 Upscale/Downscale............... 23 mA / 3.5 mA
Output limitation, on 4...20
Response time and 20...4 mA signals.................................... 3.8...20.5 mA
Temperature input (0...90%, Output limitation, on 0...20
100...10%)...................................................... ≤ 1 s and 20...0 mA signals.................................... 0...20.5 mA
mA / V input (0...90%, 100...10%).................. ≤ 400 ms Current limit.................................................... ≤ 28 mA
Auxiliary supplies Voltage output
2-w. supply (term. 44...43)............................. 25...16 VDC / 0...20 mA Signal range................................................... 0...10 VDC
Programming................................................. PR 45xx Programmable signal ranges......................... 0/0.2...1; 0/1...5 ; 0/2...10;
Signal / noise ratio......................................... Min. 60 dB (0...100 kHz) 1...0.2/0; 5...1/0; 10...2/0 V
Accuracy........................................................ Better than 0.1% of sel. range Load (@ voltage output)................................ ≥ 500 kΩ
EMC immunity influence................................ < ±0.5% of span of span........................................................... = of the currently selected
Extended EMC immunity: NAMUR measurement range
NE21, A criterion, burst.................................. < ±1% of span
Observed authority requirements
Input specifications EMC............................................................... 2014/30/EU
RTD input LVD................................................................ 2014/35/EU
RTD type........................................................ Pt10/20/50/100/200/250; EAC................................................................ TR-CU 020/2011
Pt300/400/500/1000;
Ni50/100/120/1000;
Cu10/20/50/100 Approvals
Cable resistance per wire.............................. 50 Ω (max.) FM.................................................................. 3025177
Sensor current............................................... Nom. 0.2 mA UL................................................................... UL 508 / C22.2 no. 14
Effect of sensor cable resistance DNV-GL Marine............................................. Stand. f. Certific. No. 2.4
(3-/4-wire)....................................................... < 0.002 Ω / Ω EU RO Mutual Recognition Type
Sensor error detection................................... Yes Approval......................................................... MRA000000Z
Short circuit detection.................................... < 15 Ω SIL.................................................................. Hardware assessed for use in
SIL applications
Linear resistance input
Linear resistance min....max.......................... 0 Ω...10000 Ω

Potentiometer input
Potentiometer min....max............................... 10 Ω...100 kΩ

TC input
4114-100419

Thermocouple type........................................ B, E, J, K, L, N, R, S, T, U,
W3, W5, LR