Ultra Power Acb User Manual
Ultra Power Acb User Manual
POWER
User Manual
Maintenance Instructions of Ultra Power ACB
www.bchindia.com
CAUTION
Ensure that deviations of the mains and control voltages do not exceed the
2. Understanding
2.1
2.2 Exploring
2.3 Racking-out
2.4 Operating
2.5 Technical Data
3. Installing
3.1 Mounting & Door cut-out
3.2 Termination
3.3 Loading in panel
3.4 Control circuit connections
6. Putting
6.1 Reloading in Panel
6.2 Checking ON-OFF operation
6.3 Testing
6.4 Setting P&C unit
6.5 Trip simulation of P&C unit
6.6 System in Connected Position
6.7 Securing
ULTRA
POWER
Section 1
On Receiving
ULTRA
POWER
1.1 Visual Inspection
Before Unpacking,
A) Inspect the carton for any damage. In case of visible damage to the carton, contact nearest
Before proceeding with unpacking, it is important to know the gross weight of the breaker for proper
selection of handling equipment.
Approx. Gross Weight of breaker with packing , adaptors & accessories (kg)
Frame I II III
N S H N S H S H N/S H N S H S H H V H V
Rated Uninterrupted current at 50deg.C In (A) 400-1600 2000 2500 400-2500 3200 4000 400-5000 6300#
Fixed 3P 60 62 69 64 64 69 69 69 76 83 83 83 83 83 83 130 130 138
138
Weight ACB 4P (100%N) 73 76 85 79 79 85 85 85 120 132 132 132 132 132 132 143 143 170 170
kg 3P 87 91 103 94 98 103 103 103 113 125 125 125 125 136 136 198 198 227 227
Drawout
ACB 4P (100%N) 104 109 127 112 115 127 127 127 168 181 181 181 181 195 195 248 248 285 285
50% N
Frame III
H V
Rated Uninterrupted current at 50deg.C In (A) 400 - 5000
Weight Fixed 4P (50% N) 137 137
kg D/O 4P (50% N) 223 223
200% N
Frame I II III
N S N S H N S H S H
Rated Uninterrupted current at 50deg.C In (A) 400 -1250 1600 2000 2000 - 2500
Weight Fixed 4P (200% N) 85 85 132 132 132 132 132 132 123 123
kg D/O 4P (200% N) 127 127 181 181 181 195 195 195 185 185
# 40 deg C
1-1
Step 1: Cut & remove the straps Step 2: Lift the carton and remove any accessories taped to the
breaker or kept loose on the palette.
Step 3: Remove Breaker mounting nuts (8 Nos.) as indicated by arrows from both left and right sides
Step 1: Cut & remove the straps Step 2: Lift the carton and remove any accessories taped to the
breaker or kept loose on the palette.
Step 4: Rack-out the breaker & remove breaker from cradle (Details in Section 2.3)
2
1
b) For Draw-out breakers:
1-3
o
Temperature Range : -40 to 85 C.
Understanding
2.2 Exploring
2.3 Racking-out
2.4 Operating
2.5 Technical Data
ULTRA
POWER
UV Release Closing Release Shunt Release
415~,400V 415~,400V 415~,400V
12
OFF O 29k 4 Pole 100%N 2500 A
12 kV
29b
29c
ON I 29h
Ue
400 / 440 V
500 / 550 V
Ics = Icu
50 kA
42 kA 29g
660 / 690 V 36 kA
2500 A
4 Pole 100%N Icw 50 kA 1.0 s
29j
12 kV
13 400 / 440 V
500 / 550 V
660 / 690 V
42 kA
36 kA
1.0 s
29d
29f
50 kA
Icw 26 kA 3.0 s
CHARGED
29e
29l
BU2-25N
ULTRA
29m
POWER
29a BU2-25N
2-1
2.2 Exploring
(Microswitch)
2-2
CONNECTED
TEST
DISCONNECTED
15
ocations
25 Withdrawal Rails
ation 26 Door Racking Interlock
15 Racking Handle 27 Breaker Pull-out Handle
16 Smart Racking Shutter 34 Guide for
16
2-3
2.3 Racking-out
Breaker is out of the panel or the panel door is open, gently press Racking
Interlock (26) to defeat it.
Insert the racking handle &
Note: Once racking shutter is opened, the breaker can not be closed, even by
rotate anti-clockwise
Take out the handle automatically recloses only in distinct ‘Connected’ / ‘Test’ and
‘Disconnected’ positions (17). Hence, Breaker cannot be closed in
CONNECTED
any Intermediate positions to ensure User safety.
Excessive, forceful Racking-out beyond
DISCONNECTED
CAUTION Disconnected position may lead to Product damage.
2-4
Initially, the Breaker is and Spring is
2-5
Unit
V Ue Upto 690
V Ui 1000
kV Uimp 12
kV Uimp 4
3 & 4 (50, 100, 200% N)
Yes
IP 53 / IP 54*
4
B
-250C to 700C
IK 08 / IK 10*
FRAME I II III
Neutral Unit Symbol
A In 400-1600 2000 2500 400-2500 3200 4000 400-5000 6300**
Versions N S H N S H S H N S H N S H S H H V H V
415/440V ~ 50/60 Hz kA 50 65 80 50 65 80 65 80 50 65 80 50 65 80 65 80 80 100 80 100
500/550V ~ 50/60 Hz kA Icu 42 55 65 42 55 65 55 65 42 55 70 42 55 70 55 70 70 85 70 85
660/690V ~ 50/60 Hz kA 36 50 55 36 50 55 50 55 36 50 55 36 50 55 50 55 65 75 65 75
415/440V ~ 50/60 Hz
500/550V ~ 50/60 Hz kA Ics 100% Icu
660/690V ~ 50/60 Hz
0.5 sec kA 50 65 80 50 65 80 65 80 50 65 80 50 65 80 65 80 80 100 80 100
1.0 sec kA Icw 50 65 80 50 65 80 65 80 50 65 80 50 65 80 65 80 80 100 80 100
3.0 sec kA 26 36 44 26 36 44 36 44 26 44 50 26 44 50 44 50 65 75 65 75
415/440V ~ 50/60 Hz kA 105 143 176 105 143 176 143 176 105 143 176 105 143 176 143 176 176 220 176 220
500/550V ~ 50/60 Hz kA Icm 88 121 143 88 121 143 121 143 88 121 154 88 121 154 121 154 154 187 154 187
Making Capacity
660/690V ~ 50/60 Hz kA 76 105 121 76 105 121 105 121 76 110 121 76 110 121 110 121 143 165 143 165
Break Time 25
ms
Close Time 60
Width - 3P mm W 347 447 647
Width - 4P 100% mm W 447 581 847
ACB Depth mm D 324 324 334
mm H 430
Dimensions
Width - 3P mm W 347 447 647
Width - 4P 100% mm W 447 581 847
ACB Depth mm D 421 421 431
mm H 433
no. of cycles 20000 15000 10000
cycles/hour 60
no. of cycles 10000 5000 5000 5000 2000
cycles/hour 40 20
Pitch I/C - O/G mm 105
Ph-Ph mm 100 133 200
Pitch
Ph-N 100% mm 100 133 200
3P kg 60 62 69 67 64 69 69 69 76 76 83 83 83 83 83 83 130 130 138 138
Weight 4P 100% kg 73 76 85 79 79 85 85 85 120 120 132 132 132 132 132 132 143 143 170 170
3P kg 87 91 103 94 98 103 103 103 113 113 125 125 125 125 136 136 198 198 227 227
4P 100% kg 104 109 127 112 115 127 127 127 168 168 181 181 181 181 195 195 248 248 285 285
2-6
Section 3
Installing
ULTRA
POWER
Mounting in a Panel
General Information:
3-1
Frame 1, 3 Pole Ultra Power ACB System of
- Link layout
- Size of Power cables, etc.
Mounting
400A-2000A N & 400A-2500A S/H Fr.1 3P
Fixed Circuit Breaker
300 min
300 min
VERSION DIM. B
400-2000A N & S 326
400-2000A H 324
2500A S & H 324
142
C
N, S, H 45 70
DISCONNECTED
25.5
421
(250) (47.5)
(62.4)
(280)
3-3
Mounting
300 min
300 min
VERSION DIM. B
N, S, H 45 70
C
DISCONNECTED
25.5
421
(280)
3-4
Mounting
400A-4000A N*/S/H Fr.2 3P
Fixed Circuit Breaker
300 min
300 min
VERSION DIM. B
400-2500A N/S 326
3200-4000A N*/S 324
400-4000A H 324
C
N, S, H 45 70
DISCONNECTED
These 2 supports
are must
(250)
(280)
3-5
Mounting
400A-4000A N*/ S/ H Fr.2 4P (100% N)
Fixed Circuit Breaker
300 min
300 min
VERSION DIM. B
N, S, H 45 70
C
DISCONNECTED
These 3 supports
(250)
(280)
are must
3-6
Mounting
400A-6300A H/V Fr.3 3P
Fixed Circuit Breaker
300 min
300 min
C
C
DIM. C DIM. C*
VERSION (min.)
(min.)
H, V 45 70
DISCONNECTED
35.5
431
(100) (250) (47.5)
(49.5)
(62.4)
These 3 supports
(250)
(280)
are must
3-7
Mounting
300 min
300 min
C
DIM. C DIM. C*
VERSION (min.)
(min.)
H, V 45 70
DISCON-
NECTED
35.5
431
(49.5) (200) (100) (250) (47.5)
(62.4)
These 4 supports
are must
(250)
(280)
3-8
All Dimensions in mm FIXED ACB BEZEL
FIXING DRILLING PLAN
10.5
10.5
Cutout for Main Facia 171 171
181
181
8 HOLES-DIA.5
(Bezel overall Dims W=371XH=391; 25mm around the cutout)
D/O ACB BEZEL
Cutout for door Interlock device FIXING DRILLING PLAN
See Detail `z’
9.2 10.5
171 171
10.5
53.5
208.5
208.5
8 HOLES-DIA.5
(Bezel overall Dims W=371XH=446; 25mm around the cutout)
3 411.8
4 545.8
3 611.8
III 4 811.8
Installation: Fix the sealing (Bezel assy.) frame on the panel door
by provided M4x8mm length Screws at 8 places from the rear side
of panel door.
the facia cutout to Panel door edge for both (RHS & LHS) side hinges .
3-9
Termination on Draw-out Breakers
Terminal Adaptor:
3-10
Draw Out Version
Fr Frame 1 Frame 2 Frame 3
A 400A-2000A 2500A 400A-3200A 4000A 400A-4000**A 5000**A 6300A
termination
recommended
Horizontal
Width : 65mm Width : 98mm Width : 100mm Width : 165mm Width : 165mm
Vertical termination
recommended
BLCA60963OOOO BLCA60964OOOO BL60316OOOO BL60073OOOO BLCA60966OOOO
Vertical
Height : 65mm Height : 98mm Height : 150mm Height : 125mm Height : 125mm Height : 150mm
BLCA60963OOOO BLCA60964OOOO BL60420OOOO BL60128OOOO(1EA) BL60067OOOO(1EA) BL60965OOOO(1EA)
Fixed Version
Fr Frame 1 Frame 2 Frame 3
Ver N/S H S/H N/S N/S/H S/H H/V
A 400A-2000A 400A-2000A 2500A 400A-2500A 400A-3200A 4000A 400A-4000**A 5000**A
Width : 65 mm Width : 65 mm Width : 100 mm Width : 100 mm Width : 165 mm Width : 165 mm
Horizontal
BL60967OOOO BL60968OOOO BL60122OOOO BL60977OOOO BL60373OOOO (1EA) BL60373OOOO (1EA)
Details of Terminal adaptors for Fixed and Draw - out ACBs
Vertical
Height : 65 mm Height : 65 mm Height : 100 mm Height : 100 mm Height : 100 mm Height : 150 mm Height : 125 mm Height : 150 mm
BL60967OOOO BL60968OOOO BL60976OOOO BL60122OOOO BL60977OOOO BL60417OOOO BL60418OOOO (1EA) BL60347OOOO (1EA)
3-11
**Frame-3, 4000A and 5000A, horizontal for bus-coupler ACBs only
X = 100 -150 mm
X
15 max
X
X
X = 100 -150 mm
3-12
Termination - Fixed Breakers
Flat Termination C
32
A
B
M10
105
A
B
32
122
C
41
Bolt length
FRAME 1 A B C D 100 100
400-1600A N 24 50 50 11 347
15
400-1600A S 24 50 65 11
Bolt length for mounting 400-1600A H 30 55 65 9
74
72
40
69
108.8
19
Ø12.9 27
M12 / Equivalent BS bolts to be used for link termination
Tightening torque: 3.2 kgfm 100 100
3-13
Termination - Fixed Breakers
Vertical Terminals
A
BREAKER ADAPTOR 19
BL60967OOOO
65
27
BL60968OOOO
40
BREAKER DIMENSION
A
74
65
72
Ø12.9
117.5
100 100
63
15
M12 / Equivalent BS bolts to be used for link termination 100 100
Tightening torque: 3.2 kgfm
72
2500A S/H Fr.1-3P 19
63
(Adaptor-BL60976OOOO)
27 27
100
45
100
Ø12.9
80.8
100 100
20
100 100
M12 / Equivalent BS bolts to be used for link termination
Tightening torque: 3.2 kgfm
3-14
Termination - Fixed Breakers
Flat Termination Bolt length Bolt length for FRAME 1 A B C D
400A-1600A N/S/H Fr.1-4P mounting link(s) on 24 50 50
24 50 65
to be cumulative
link(s) thickness + 30 55 65 9
15 mm.
C
32
D
B
A
B
M10
105
A
41
122
15
C
Holes (on both sides) for Earthing
connections by M10/Equivalent BS bolt.
100 100 100 73.5
Horizontal Termination
400A-1600A N/S/H Fr.1-4P BREAKER ADAPTOR A
S/H Fr.1-4P 63
15
400-2000A N/S BL60967OOOO
400-2000A H BL60968OOOO
69
BREAKER DIMENSION
A 40
74
72
69
108.8
19
27
Ø12.9 100 100 100
65
27
BREAKER DIMENSION
A
40
74
72
65
Ø12.9
23 27 27
100
45
100
Ø12.9
80.8
20
M12 / Equivalent BS bolts to be used for link termination
Tightening torque: 3.2 kgfm 100 100 100
3-16
Termination - Fixed Breakers
Flat Termination Bolt length for mounting
400A-1600A N/S/H Fr.2-3P Bolt length
to be cumulative link(s)
C thickness + 15 mm.
32
VERSION A B C
24 24 81.2
30 30 98.4
M10
9
55
105
55
122
41
15 133.3 133.3 90
Holes (on both sides) for Earthing
connections by M10 / Equivalent BS bolt 447
20
BL60977OOOO
BL60977OOOO
74
BREAKER DIMENSION
48
A
74
72
72
74
103.8
19
27
20 54
133.3 133.3
3-17
Termination - Fixed Breakers
Vertical Termination
400A-4000A N*/N08/N10/S/H Fr.2-3P
VERSION ADAPTOR
BREAKER DIMENSION
RATING A
400 - 2500A N/S 74
3200-4000A N*/S 72
400-4000A N08/N10/H 72
A
63
19
27
27
150
133.3 133.3
27
27
57
150
150
133.3 133.3 20
25
3-18
Termination - Fixed Breakers
Flat Termination
VERSION A B C
24 24 81.2
9 c 30 30 98.4
32
55
M10
55
105
41
B
15
Holes (on both sides) for Earthing
connections by M10 / Equivalent BS bolts
122
133.3 133.3 133.3
M10 bolts to be used for link termination 581
Tightening torque: 3.0 kgfm
VERSION ADAPTOR
A
BL60122OOOO
63
20
BL60977OOOO
BL60977OOOO
74
BREAKER DIM. A
48
74
72
74
72
103.8
27 27 20
19
Ø12.9 100
133.3 133.3 133.3
3-19
Termination - Fixed Breakers
Vertical Termination
400A-4000A N*/N08/N10/S /H Fr.2-4P (100% N)
VERSION ADAPTOR
BREAKER NO OF
RATING A B C
HOLES
400-2500A N/S 74 100 77.2 3
3200-4000A N*/S 72 100 77.2 3
400-4000A N08/N10/H 72 150 25 5
A
63
19
54
B
20
B
3-20
Termination - Fixed Breakers
Flat Termination
165
Bolt length Bolt length for mounting
link(s) on Flat Terminals
65 to be cumulative link(s)
32 thickness + 15 mm.
M10
30
56
10
105
56
30
122
41
Adaptor No of
Breaker Rating Dim. A Dim. B Holes
Cat. No.
82
Vertical Termination 400-4000A BL60418OOOO 125 61 4
63
400A-5000A H/V Fr.3-3P 5000A BL60347OOOO 150 36 5 19
27 27 27
A
36
A
B
100 100 100 100 100
3-22
Termination - Fixed Breakers
Bolt length for mounting
Bolt length
link(s) on Flat Terminals
to be cumulative link(s)
Flat Termination thickness + 15 mm.
400A-1600A H/V Fr.3-4P (100% N)
65
32
M 10
9
56
30
10
105
56
30
122
41
27 27 27
A
36
A
100 100 100 100 100 100 100
B
20
100 100 100 100 100 100 100
Flat Terminals
400A-1600A, N/S/H
14.5
56.8
10.4
105
36
Ø12.5
36
150
Bolt length
25.5
16 347
Bolt length for mounting link(s) on
M12 bolts to be used for link termination
Thickness + 20 min to 25 max Tightening torque: 3.2 kgfm
36 65
Horizontal Terminals
400A-2000A N/S/H M12
22.5
Adaptor - BLCA60963OOOO
15
105 36
2 HOLES Ø12.9
27 PITCH
45
150
15
100 100
88.5 16 73.5
347
36 65
Vertical Terminals
15
400A - 2000A N/S/H
M12
Adaptor - BLCA60963OOOO
22.5
FOR 2500A REFER PAGE 3-30
27
36
65
Ø12.9 105
45
150
100
15
100
73.5
88.5 16 347
3-25
Termination - Draw-out Breakers
Vertical Terminals
Adapter - BLCA60964OOOO 65 20 36
95.5
70
20 Ø12.9
27 27
36
98
Ø12.9
105
150
15
100 100
16 73.5
347
M12 / Equivalent BS bolts to be used for links termination
Tightening torque: 3.2 kgfm
Vertical Terminals 20 65 36
Adapter - BLCA60964OOOO
95.5
70 Ø 12.9
20
27 27
36
98
105
Ø12.9
150
73.5
16 447
M12 / Equivalent BS bolts to be used for links termination
Tightening torque: 3.2 kgfm All Dimensions in mm
3-26
Termination - Draw-out Breakers
400A-2000A, N/S/H, 4P (100%N)
65
Flat Terminals
400A-1600A, N/S/H
65
56.8
14.5 36
Ø 12.5
105
56.8
36
150
10.4
25.5
Bolt length
16
447
Bolt length for mounting link(s) on Flat M12 bolts to be used for link termination
Tightening torque: 3.2 kgfm
thickness +20 min to 25 max.
Horizontal Terminals 36 65
400A - 2000A N/S/H
Adaptor - BLCA60963OOOO
M12
2 HOLES Ø12.9
27 PITCH
105 36
15
22.5
45
150
88.5
100 100 100
73.5
15
16 447
Vertical Terminals 36
15
65
400A - 2000A N/S/H
Adaptor - BLCA60963OOOO
For 2500A REFER PAGE 3-30 M12
22.5
36
27
65
105
Ø12.9
45
150
88.5
100 100 100
M12 / Equivalent BS bolts
16 73.5
15
Flat Terminals
400A-1600A, N/S/H
M12
77.2
36
105
77.2
36
140
Bolt length
25.5
16 133.3 133.3 90
15
447
Bolt length for mounting link(s) on M12 bolts to be used for link termination
Tightening torque: 3.2 kgfm
thickness+20 min to 25 max
Horizontal Terminals 98
400A-3200A, N/S/H
Adaptor - BLCA60964OOOO 95.5
M12
20
20
45 65
105
3 HOLES Ø12.9
27 PITCH
140
133.3 133.3 90
15
16 447
Vertical Terminals
36 20 20
400A-3200A, N/S/H
Adaptor - BLCA60964OOOO
95.5
20 M12
Ø12.9
27 27
98
36
105
98
36
140
45 36
133.3 133.3 90
447
16
15
3-28
Vertical Terminals
4000A, S/H
Adaptor - BL60420OOOO 20 65
95.5
12.9
45
21 27 27 27 27
165
150
36 36
20
29
58
36
21 27 27 27 27
178.5
150
15
70
16 90.5 133.3 133.3
25.5
447
95.5
3 HOLES 12.9
100
72
32
20
83.8
35
45
36
21 27 27 27 27
179
150
20
M12 / Equivalent BS bolts to be used for links termination.
Tightening torque: 3.2 kgfm 23 27 27
3-29
Termination - Draw-out Breakers
Flat Terminals 65
400A-1600A, N/S/H 36
M12
77.2
36
105
77.2
36
140
25.5
Bolt length
16 90 133.3 133.3 133.3
15
581
Horizontal Terminals
400A-3200A, N/S/H
Adaptor - BLCA60964OOOO 98 36
95.5 N M12
20
20
65
36
45
105
3 HOLES Ø12.9
140
27 PITCH
15
Vertical Terminals
400A-3200A N/S/H 20 36 65
Adaptor - BLCA60964OOOO
95.5
M12
Ø 12.9 20
27 27
98
36
105
98
140
45
90.5
581
M12 / Equivalent BS bolts to be used for links termination.
Tightening torque: 3.2 kgfm
3-30
Vertical Terminals
4000A, S/H
Adaptor - BL60420OOOO 20 65
95.5
12.9
45
21 27 27 27 27
165
36 36
150
20
28
58
36
21 27 27 27 27
178.5
150
70
16 581
25.5
95.5
3 HOLES 12.9
100
72
32
20
35
83.8
45
36
178.5
21 27 27 27 27
150
581
12.9
20
3-31
Termination - Draw-out Breakers
& 6300A, H/V Fr.3-3P
Flat Terminals
400A-1600A H/V
165
36
56
36
ø12.9
105
36
56
179
25.5
100
16 Hole (on both sides)
for Earthing connections 647
Bolt length
by M10 / Equivalent BS bolt
Bolt length for mounting link(s) on M12 bolts to be used for link termination
Flat Terminalsto be cumulative link(s) Tightening torque: 3.2 kgfm
thickness+20 min to 25 max
6 HOLES - Ø12.9
PITCH 27 mm.
36
65
22.5
40
15
183
45
63 35.5
15
16
73.5 100 100 100 100 100
647
6 HOLES - Ø12.9
45
Ø12.9
22 27 27 27
125
134
36
40
22.5
58
36
22 27 27 27
183
Bolt length 35.5
70
16
15
134
36
40
20
58
36
22 27 27 27
183
35.5
70
16
15
Vertical Terminals
6300A H/V
Adaptor - BL60965OOOO 165 20
36 M12
45
Ø12.9
21 27 27 27 27
150
36 36
165
20
28
58
36
21 27 27 27 27
183
35.5
70
15
16
73.5 100 100 100 100 100
M12 / Equivalent BS bolts to be used for links termination. 647
3-33
Termination - Draw-out Breakers Bolt length
56
36
ø12.9
105
36
56
179
25.5
6 HOLES - Ø12.9
PITCH 27 mm.
36
65
22.5
40
15
8
183
45
63
22.5
63 35.5
27 27 27 27 27
16 73.5
BL60073OOOO 847
6 HOLES - Ø12.9
PITCH 27 mm.
36
65
20
40
20
183
45
15
70
70 35.5
20
27 27 27 27 27
100 100 100 100 100 100 100
15
16 73.5
TOP VIEW OF 847
BL60966OOOO
Ø12.9 45
22 27 27 27
134
125
36
22.5
58
40
36
22 27 27 27
183
Bolt length
35.5
70
16
15
Hole (on both sides) 73.5 100 100 100 100 100 100 100
Bolt length for mounting link(s) on for Earthing connections 847
by M10 / Equivalent BS bolt
thickness+20 min to 25 max
165 20
Vertical Terminals 36
M12
5000A H/V
Adaptor -
BL60067OOOO
Ø12.9 45
134
22 27 27 27
125
36
40
20
58
36
22 27 27 27
183
35.5
70
16 73.5 100 100 100 100 100 100 100
15
847
Vertical Terminals
6300A H/V 165 20
Adaptor - 36 M12
BL60965OOOO
Ø12.9 45
21 27 27 27 27
150
36 36
165
20
28
58
36
21 27 27 27 27
183
35.5
70
15
Bolt length
56
36
ø12.9
105
36
56
179
Not applicable for Neutral pole 25.5
Bolt length for mounting link(s) on
15
16 Hole (on both sides) 100 100 100 100 100 100 73.5
thickness+20 min to 25 max for Earthing connections
by M10 / Equivalent BS bolt 747
36
40 65
22.5
15
POLES A 63
183
Phase: R, Y, B 35.5
A
Neutral: N 25.5
16 73.5 100 100 100 100 100 100
15
747
Vertical Terminals
165
400A-4000A H/V 36 M12
15
Adaptor - BL60128OOOO
Ø12.9 45
22 27 27 27
125
134
36
22.5
58
40
36
22 27 27 27
183
POLES A A
Phase: R, Y, B 35.5
70
Neutral: N 25.5 16
15
134
36
20
40
58
36
22 27 27 27
183
POLES A
Phase: R, Y, B 35.5 A
Neutral: N 25.5 70
16 73.5 100 100 100 100 100 100
15
A
B
M10
105
B
A
C
122
41
Bolt length for mounting link(s) on M10 bolts to be used for link termination
thickness + 15 mm. Tightening torque: 3.0 kgfm
15
400-1000A H BL60968OOOO
69
BREAKER DIMENSION
A
74
72 40
69
108.8
19
27
Ø12.9 100 100 100
65
27
BREAKER DIMENSION
A
40
74
65
Ø12.9
117.5
100 100 100
15
100 100 100
M12 / Equivalent BS bolts to be used for link termination
Tightening torque: 3.2 kgfm
Vertical Terminals 72
63
1250A N/S Fr.1-4P (200% N) 19
(Adaptor-BLCA60976OOOO)
23 27 27
100
45
100
Ø12.9
80.8
20
M12 / Equivalent BS bolts to be used for link termination
100 100 100
Tightening torque: 3.2 kgfm
3-38
Termination - Fixed Breakers
400A-1600A N/S/H Fr.2-4P (200% N)
VERSION A B C D E c
32
24 24 81.2 11 50
30 30 98.4 9 55
30 30 98.4 9 55
D
M10
A
E
105
B
E
122
133.3
41
133.3 133.3
15
581
Holes (on both sides) for Earthing
connections by M10 / Equivalent
BS bolts
VERSION ADAPTOR A
63
20
BLCA60122OOOO
BLCA60977OOOO
74
BLCA60977OOOO
VERSION DIMENSION
A
48
74
72
74
72
103.8
27 27 20
19
Ø12.9
100
133.3 133.3 133.3
Vertical Termination
VERSION ADAPTOR
BLCA60122OOOO
BLCA60977OOOO
BLCA60977OOOO
63
Ø 12.9 19
27
100
54
23
20
133.3 133.3 133.3
77.2
3-40
Termination - Fixed Breakers Bolt length
M10
30
56
105
56
30
122
41
15
100 100 100 100 100 73.5
647
Holes (on both sides) for Earthing connections by
M10 / Equivalent BS bolt M10 to be used for links termination
Tightening torque: 3.0 kgfm
82
63
19
27 27 27
A
36
A
100 100 100 100 100 100 100
B
20
100 100 100 100 100 100 100
3-42
Termination - Draw-out Breakers
Flat Terminals
400A-1000A, N/S/H
65
14.5 36
M12
(Ø 12.5)
105
56.8
36
150
10.4
25.5
Bolt length
100 100 100
16 73.5
15
447
Bolt length for mounting link(s) on Flat M12 bolts to be used for link termination
Terminals to be cumulative link(s) Tightening torque: 3.2 kgfm
thickness +20 min to 25 max.
Horizontal Terminals 65 36
400A - 1000A N/S/H
Adaptor - BLCA60963OOOO
M12
2 HOLES Ø12.9
27 PITCH
36
15
105
22.5
45
150
88.5
100 100 100
16 73.5
15
447
Vertical Terminals
15 65 36
400A - 1000A N/S/H
Adaptor - BLCA60963OOOO
M12
22.5
27
65
36
105
Ø12.9
45
150
88.5
100 100 100
M12 / Equivalent BS bolts
16 73.5
15
Ø12.9
77.2
36
105
77.2
36
140
25.5
Bolt length
16
15
Horizontal Terminals
400A-2000A N*/S/H (200% N) 98 36
Adaptor - BLCA60964OOOO
95.5 N M12
20
20
65
36
45
105
3 HOLES-Ø12.9
PITCH-27mm
140
15
Ø 12.9 20
36
27 27
98
105
140
98
45
133.3 133.3 133.3 90.5
581
* Available till 1600A 16
15
56
36
ø12.9
105
36
56
179
Bolt length 25.5
N
15
Hole (on both sides) 100 100 100 100 100 73.5
16
for Earthing connections 647
Bolt length for mounting link(s) on by M10 / Equivalent BS bolt
6 HOLES - Ø12.9
PITCH 27 mm.
36
65
22.5
40
15
8
183
45
63
22.5
63 35.5
27 27 27 27 27
16 73.5
BLCA60073OOOO 847
165 20
36
Adaptor - BLCA60128OOOO M12
45
Ø12.9
22 27 27 27
134
125
36
40
22.5
58
36
22 27 27 27
183
35.5
70
16 73.5
15
3-45
For Earth fault protection and protection of Neutral against overloads, Neutral
CT is required. For 4-Pole breakers, the CT is provided inside the breaker, to be
used on 4 wire system whereas for 3-pole breakers, external CT is available
separately.
65
Frame Size Rating 40
40 13
13
1, 2 & 3 400/630/800
19
19
1, 2 & 3 1000/1250/1600
42
42
(ref. Page 2-6 for Frame size details)
72 19
72
TERMINAL THICKNESS 15 mm.
42
19
19
90
Frame Size Rating
12.5
12.5 40 13
1 2000/2500
19
(ref. Page 2-6 for Frame size
19
45.5
details)
45.5
72
72
TERMINAL THICKNESS 30 mm.
45.5
19
65
19
19
(ref. Page 2-6 for Frame size details)
45.5
45.5
72
72
TERMINAL THICKNESS 30 mm.
45.5
45.5
98.3 19
65
Frame Size Rating
12.5 40 40
40 40
40 13
13
3 5000/6300
19
19
45.5
19
Shutter (16).In case panel door is open, also gently depress Excessive forceful racking-in beyond Connected
the Door Racking Interlock(26).
3-47
3.4 Control Circuit Connections:
SICs & SIC Bridge
Secondary Isolating contacts (8b) facilitate Control
circuit wiring with following features,
1
2
3
4
5
6
7
8
Disconnected Test Connected
3-48
Control Termination:
BU-B
For URM / SRM
only one
can be used
Closing X=111/121
Release X1= 112/122
# X2 = 114/124
5 6m
*
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
}
41
11
21
31
V1
A1
X1
42
43
44
22
23
24
32
D-
33
34
C1
V0
12
A2
X2
N1
13
14
D1
V2
V3
C2
N2
D2
D+
SI1
CN
GI1
SI2
Z-L
AL-
C-H
AS-
131
101
Z-H
GI2
C-L
AS-
132
102
134
104
AL+
C-G
SO1
RR-
EC1
AS+
CH1
GO2
AS+
M-G
TST
GO1
EC2
TCS
CH2
SO2
RR+
DCN
CMN
Legend
Control
circuit
equipment
Ref. No.
The above
# For using electrical accessories with DC Control Supply, it is recommended to connect D1/A1/C1 to +ve and D2/A2/C2 to -ve.
# m indicates micro switch
3-49
* These ZSI Terminals should only be used for BTX 1Gi/1.5Gi Releases.
Connection Details
(BU-BTX 1.0)
41
21
31
11
33
43
A1
D1
13
23
C1
N R Y B
CN
134
TST
RR+
132
122
112
124
104
114
102
CH1
EC1
DCN
TCS
.1
.2
.3
.3
.1
.3
.1
.3
.1
.1
EC AX AX AX AX UR CR SR/SRW RR
CFM PI
.4
.4
.4
.4
.2
.2
BU-B
.2
.2
LOAD
34
44
EC2
D2
CH2
22
12
14
CMN
24
A2
C2
32
42
RR-
111
121
131
101
Main Circuit Protection & Control Unit Electric Spring U/V Closing Shunt Common Ready
U/V Fault Signal Electrical
Charging Charge Release Release Release Fault to /Shunt Trip Signal Position Remote
Reset
Device Indication (only one can
Indication Close Indication
be used)
3-50
Connection Details
(BU-BTX 1G)
41
21
31
11
33
43
A1
D1
13
23
N R Y B
C1
CN
134
TST
RR+
132
122
112
124
104
114
102
CH1
EC1
DCN
TCS
.1
.2
.3
.3
.1
.3
.1
.3
.1
.1
EC AX AX AX AX UR CR SR/SRW RR
CFM PI
.4
.4
.4
.4
.2
.2
.2
.2
BU-B
N1
N2
LOAD
34
44
EC2
D2
22
12
14
CMN
24
A2
C2
32
42
RR-
CH2
111
121
131
101
Main Circuit Protection & Control Unit Electric Spring U/V Closing Shunt Common Ready
U/V Fault Signal Electrical
Charging Charge Release Release Release Fault to /Shunt Trip Signal Position Remote
Reset
Device Indication (only one can
Indication Close Indication
be used)
3-51
Connection Details
(BU-BTX 1.5G)
41
21
31
11
33
43
A1
D1
13
23
N R Y B
C1
CN
134
TST
RR+
132
122
112
124
104
114
102
CH1
EC1
DCN
TCS
.1
.2
.3
.3
.1
.3
.1
.3
.1
.1
EC AX AX AX AX UR CR SR/SRW RR
CFM PI
.4
.4
.4
.4
.2
.2
.2
.2
BU-B
N1
N2
LOAD
34
44
EC2
D2
22
12
14
CMN
24
A2
C2
32
42
RR-
CH2
111
121
131
101
Main Circuit Protection & Control Unit Electric Spring U/V Closing Shunt Common Ready
U/V Fault Signal Electrical
Charging Charge Release Release Release Fault to /Shunt Trip Signal Position Remote
Reset
Device Indication (only one can
Indication Close Indication
be used)
3-52
Connection Details
(BU-BTX 1Gi / 1.5Gi)
N R Y B
134
104
124
13
23
33
43
132
102
122
CN
21
31
41
A1
DCN
D1
C1
CH1
RR+
TCS
TST
EC1
SI1
GI1
AS+
SO1
GO1
ACB STATUS
.1 .2
.3
.3
.3
.3
.1
.1
.1
.1
RR
SR
UR
CR
EC
PI
CFM
BU-BTX 1.0Gi/1.5Gi
.4
.4
.4
.4
AX .2
AX .2
AX .2
AX .2
N1
N2
LOAD
SI2
GI2
AS-
14
24
34
44
12
22
32
42
CMN
D2
C2
A2
CH2
SO2
131
101
121
EC2
GO2
RR-
ACB STATUS
U/V Fault Signal
Electric Spring Common Ready
Auxiliary Contacts U/V Closing Shunt /Shunt Trip Signal Electrical Remote
Main Circuit Protection & Control Unit Charging Charge Fault to Position
4NO + 4 NC Release Release Release Indication (only one can Reset
Device Indication Close Indication
be used)
Ref. No 2 2m 3 4 5 6 1m 7 4m/6m 8e
AS+ : Auxiliary 24 V DC
AS- : Ground
SOUT : ZSI S/C Output
SIN : ZSI S/C Input
GOUT : ZSI E/F Output
GIN : ZSI E/F Input
N1 : External Neutral CT
3-53
N2 : External Neutral CT
Connection Details
(BU-BTX 3.5)
41
N R Y B
21
31
11
33
43
A1
D1
13
23
C1
AS+
Z-H
CN
V3
V1
AL+
C-H
D+
M-G
134
TST
RR+
132
122
112
124
104
114
CH1
102
EC1
DCN
TCS
.1
.2
.3
.3
.1
.3
.1
.3
.1
.1
EC AX AX AX AX UR CR SR/SRW RR
CFM PI
BU-B
.4
.4
.4
.4
.2
.2
.2
.2
N1
N2
LOAD
V2
V0
AL-
AS-
Z-L
34
44
EC2
C-G
D2
C-L
22
12
14
D-
CMN
24
A2
C2
32
42
RR-
CH2
111
121
131
101
Main Circuit Protection & Control Unit Electric Spring U/V Closing Shunt Common Ready
U/V Fault Signal Electrical
Charging Charge Release Release Release Fault to /Shunt Trip Signal Position Remote
Reset
Device Indication (only one can
Indication Close Indication
be used)
3-54
V0,V1,V2,V3 :N ,R,Y,B, VOLTAGE I/P.
Connection Details
(BU-BTX 3.5EC/3.5H)
41
N R Y B
21
31
11
33
43
A1
D1
13
23
C1
AS+
Z-H
CN
V3
V1
AL+
C-H
D+
M-G
134
TST
RR+
132
122
112
124
104
114
102
CH1
EC1
DCN
TCS
.1
.2
.3
.3
.1
.3
.1
.3
.1
.1
EC AX AX AX AX UR CR SR/SRW RR
CFM PI
BU-B
.4
.4
.4
.4
.2
.2
.2
.2
N1
N2
LOAD
V2
V0
AL-
AS-
Z-L
34
44
EC2
C-G
D2
C-L
22
12
14
D-
CMN
24
A2
C2
32
42
RR-
CH2
111
121
131
101
Main Circuit Protection & Control Unit Electric Spring U/V Closing Shunt Common Ready
U/V Fault Signal Electrical
Charging Charge Release Release Release Fault to /Shunt Trip Signal Position Remote
Reset
Device Indication (only one can
Indication Close Indication
be used)
3-55
V0,V1,V2,V3 :N ,R,Y,B, VOLTAGE I/P.
Section 4
ULTRA
POWER
a. Safety Shutter (39):
Tools required: Screw Driver (Blade length 300 mm, Tip width 8 mm)
Tools required: Philip head Screw driver (Tip no.2), Ring spanner
(size 13)
cradle and the other on the panel door. Door interlock is mounted inside Converting Door-interlock for RHS hinge
the side plate of the cradle.
Cut-out for
Door Interlock
Assemble the Interlock as shown. Rest the rear end of the torsion Also assemble panel-door mounted
spring on the SIC bridge, as shown. part of door-interlock.
4-1
c. Mechanical Interlock:
Function: Mechanical Interlock is used for interlocking breakers as per the desired control scheme.
üü ûû
Cable length: 2 meters/3 meters/5 meters
min. radius of cable bend: 70mm
Type of Interlock Typical Circuit Interlocks possible Schematic diagram
G
G
Two Incomers A B
(2 I/C)
G
G
Three Incomers A B C
(3 I/C)
G
Two Incomers &
One Standby
A B C
(2 I/C + 1 S/B)
a. Mounting actuator
(Common for Fixed & Draw-out breakers) 1
3
Remove facia. Provide a cut in the facia Install the actuator on the main shaft & MIL
along the guides shown inside the facia. components as shown.
3
2
For 2I/C+1B/C:
4 i. Adjust the Screw (1) till Actuator link (2) is
1 horizontal and is in lowermost position
4-3
Mounting / Installing Cable Wires
Routing of cable should be with no slip arrangement.
R>70mm
4-4
4.2 Breaker Mounted Accessories
Removing facia
12 OFF O
DISCHARGED
13
Facia can be taken out by removing 2 screws This is true even for higher frame sizes,
(32) on either side of the facia. where side covers need not be removed for
taking out the facia.
After removing the screws on both sides, pull down Take out the facia by tilting it upwards as
the charging handle (14) half-way. shown.
4-5
Auxiliary Contact Undervoltage Closing Shunt
Block (3a) Release (4) Release (5) Release (6)
Common Fault
12 34 5 Indication
6
Several Breaker-mounted accessories are located on the
Undervoltage
release
controller (4c)
Operation
Undervoltage
Counter (10)
Trip Indication
Indication
as shown.
While making connections, refer wiring diagrams on pages 3-38 to 3-
b. Shunt Release - SR :
Function: To trip the breaker from a remote location
Features: Available with the following control voltages,
Type Short-time Power Operating
Consumption Limit
C2
4-6
c. Closing Release - CR :
backwards to lock.
Features: Undervoltage releases are available with the following control voltages,
UV Release
Breakers equipped with Undervoltage release cannot be normally closed unless the
release is energized.
To return the release to normal state, energize the release and then disconnect the
control supply.
4-7
e. Electrical Charging Device - ECD : To avoid possibility of personal injury,
CAUTION ensure that before opening the facia,
Function: To charge the main spring electrically. breaker is OFF and Spring is discharged.
Device.
Align
Installation: On the ECD, turn the output shaft in
anti-clockwise direction till the slot is aligned with
corresponding position of charging shaft.
f. Operation Counter :
Installation:
4-8
g. Common Fault Indication:
Tools required: Screw driver (Tip width 8 mm) or Philip head (Tip No. 2)
Installation:
4 screws as shown
4-9
Accessories (a-e & g-h)
The above accessories (except F) are pre-wired with
positions.
Fixing Cradle SICs
Accessories (a-f)
4-10
j. Locking ‘OFF’ Button (18):
Installation:
Castell
Ronis
Kirk
Profalux
(dia 7mm), at depressed locations Mount the lock using LOPB rivets
4-11
Section 5
ULTRA
POWER
BU-BTX 1.0 BU-BTX 1G
BU - BTX1.0 BU - BTX1G
Power ON LED
BU - BTX1Gi
BU - BTX1.5G BU - BTX1.5Gi
OLED OLED
Display Display
TO ACCESS TEST KIT SOCKET & BREAKER RATING, REMOVE THIS FLAP TO ACCESS TEST KIT SOCKET & BREAKER RATING, REMOVE THIS FLAP TO ACCESS TEST KIT SOCKET & BREAKER RATING, REMOVE THIS FLAP
1 2 3 4 5
1 2 3 4 5 1 2 3 4 5
5-1
BU-BTX 3.5 BU-BTX 3.5EC BU-BTX 3.5H
Communication Module
Metering Module
5-2
2.Feature List
Feature FEATURES/MODULE BU-BTX VERSIONS
no. SUPPORTED 1.0 1G 1Gi 1.5G 1.5Gi 3.5 3.5EC 3.5H
1 Protections LSI LSIGN LSIGN LSIGN LSIGN LSIGN
2 Current Metering
3 Voltage Metering *
4 THD & I-harmonics Metering
5
6 Event records
7 Additional protections
8 Power Metering *
9 Maximum Demand *
10 Reverse Power *
11 * * *
12 Earth Leakage * * *
13 Restricted Earth Fault * * *
14 Digital Input Output * * *
15 Analog Output * * *
16 Relay * * *
17 Zone Selective Interlock * * *
18 * * *
19 Temperature Module * * *
20 Modbus * *
21 * * *
22 Zig-bee * * *
**THD current %
**I1, I2, I3 harmonics Upto 13th harmonic
V1,V2,V3 Phase-Neutral voltage
Max V Maximum voltage per phase
# V12,V23,V31
Max V12,V23,V31
**THD voltage %
**V1, V2, V3 harmonics Upto 13th harmonic
#
Frequency F System Frequency
Power Factor # System Power Factor
W Active Power per phase and total (kW)
#
Power
5-3
5.3 Detailed Overview
5-4
BU-BTX
5-5
BU-BTX3.5 BU-BTX3.5EC BU-BTX3.5H
Supplimentary Module * * * -
Time based set group L L L -
L L L -
AUX supply(24V DC) L L L -
5-6
Protection Characteristics
2
BU-BTX1.0
10000
1000
100
Trip Time (s)
10
Tolerance
10s
0.1
1.2 2 3 4 5 6 7 8 9 10
Current Multiples (x Ir)
5-7
Protection Characteristics
2
BU-BTX
10000
1000
100
Trip Time (s)
30 s
10 24 s
18 s Tolerance
12 s
6s
4s
1
2s
1s
0.5 s
0.1
1 1.2 2 3 4 5 6 7 8 9 10
Current Multiples (x Ir)
5-8
Protection Characteristics
4
BU-B
100000
10000
1000
100
Trip Time (s)
10
30 s
24 s
18 s
12 s
1
6s
4s
2s
Tolerance
1s
0.1 Trip Time: ±20%
0.5 s
0.01
1 1.2 2 3 4 5 6 7 8 9
5-9
Protection Characteristics
BU-B
10000
1000
100
Trip Time (s)
30s
24s
18s
12s
10
6s
4s
2s
Tolerance
Trip Time: ±20%
1
1s
0.5s
0.1
1 1.2 2 3 4 5 6 7 8 9 10
5-10
Protection Characteristics
BU-B
10000
1000
100
30s
24s
10 18s
12s
6s
4s
2s
1 Tolerance
1s
0.5s
0.1
1 1.2 2 3 4 5 6 7 8 9
Current Multiples (x Ir)
5-11
Protection Characteristics
BU-B
2
10000
1000
0.6 12
100
10
Trip Time (s)
0.4
0.3
0.2
0.1
0.1
0.02
0.01
0.01 0.1 1 10 50
Current Multiples (x In)
5-12
Protection Characteristics
BU-B
2
10000
1000
0.6
100 0.6 12
10
Trip Time (s)
0.4
0.3
0.2
0.1 0.1
0.02
0.01
0.1 1 10 50
Current Multiples (x In)
5-13
Protection Characteristics
BU-B
100
10
1.5 15
Trip Time (s)
0.1
0.01
0.01 0.1 1 10
Current Multiples (x In)
5-14
Protection Characteristics
2
BU-B
10000
1000
0.2
0.3
100
0.4
0.5
0.6
0.8 2.4
10
Trip Time (s)
0.4 s
0.1 0.1 s
0.01
0.8 2.4
0.01 0.1 1 10 50
Current Multiples (x In)
5-15
Protection Characteristics
2
BU-B
100
0.2 0.6
10
Trip Time (s)
1
1 0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1 0.1
0.01
0.1 1 10 50
Current Multiples (x In)
5-16
Protection Characteristics
BU-B
2
0.1
0.4 2.4
5-17
Protection Characteristics
BU-B
2
100
0.2 0.6
10
Trip Time (s)
1 1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1 0.1
0.01
0.1 1 10 50
5-18
Section 6
ULTRA
POWER
6.1 Re-loading in panel:
6-1
6.2. Checking ON-OFF Operation:
6-2
(if breaker is equipped with accessories)
• If breaker is equipped with Electrical Charging Device UN-EC (2), main spring
will get charged as soon as breaker reaches ‘Test’ position and Control supply
is switched ON. If breaker is not equipped with Electrical Charging Device,
charge the spring manually.
• If Undervoltage release UN-UR (4) is installed, but not energized, it will not
allow the breaker to Close. However, you can continue the testing by defeating
the Undervoltage release (Ref. Page 4-10)
• Give supply to Closing release UN-CR (5) to close the breaker. In case not
equipped with closing release, manually close the breaker by pushing the ON
equipped with shunt release, manually trip the breaker by pushing the OFF
button.
release, if it is energized.
ULTRA-POWER
breakers / electrical devices in the scheme.
6-3
BU-B
BU-BTX1.0/1G/1Gi/1.5G/1.5Gi
BU-B
BU-B
ZSI ZSI
Protection To activate ZSI E/F and ZSI S/C , set the ZSI E/F and ZSI S/C
E/F S/C
BU-B
6-4
BU-B
1. System Settings
Setting Breaker Rating (BU-BTX-3.5/3.5EC):
Save Settings ?
Rest of the parameters under System settings should be set in same manner.
After programming the settings, press key to escape from menu and
Yes No
Note: To apply any parameter change in System settings in P&C unit , reset the power supply
once settings are saved.
6-5
2. Unit Settings
Unit settings can be programmed following menu navigation Sequence given below
Date & Time :Current date & time to be entered. Helpful for fault history time stamping.
Communication :Total 126 Device Ids are provided along with Parity option, Baud Type,
Baud rate with wide range up to 19.2kbps.
Event Recorder :To capture an event viz alarm, pick-up, trip ,module connect/disconnect
and maintenance.
Max Demand :Maximum demand of energy integration and refreshing interval can be
selected.
Command password :The factory default command password is “0000”. This password is valid for
following commands enlisted in “Restore settings” menu, namely
Maint.operation ,Clear MD ,Set Group ,Factory Setting, Clear Max I, Clear
time based set groups. Active set group will switch over to dormant set group
after the set time elapsed.
Day Light Saving :Day light saving can be programmed through this option. Enable the
Day light saving option, using “DST Mode” Enable and set the Start
and End DST dates and the time which is required to add.
6-6
3. Protection
Set the protection settings as per the following menu navigation Sequence.
Press “SEL” key in the Select “Settings” by Enter the password “0000”
overlay SEL key (Factory Set: default)
Set Group 1
requirements in plant.
I Protection Set group 1 is Default active Set group. Time based set group can be programmed
V Protection through “AUTO SET GRP”.
Freq Protection
Overload :It’s a protection against over current. The characteristics provided are It, It4
2
LI, SI, VI with Thermal memory. Thermal memory help to reduce the trip time of the
unit in case of recursions of overload.
Directional SC :The protection is a short circuit protection with the ability to recognize the direction of the
phases current during the fault period. The current direction makes it possible to determine
distribution systems, this makes it possible to identify and disconnect the distribution
feeder where the fault has occurred, whilst keeping the rest of the system running.
Instantaneous :This protection works as short circuit protection with no intentional time delay
which means release operates in 20milliseconds as soon as the fault current
exceeds the set pick-up.
Note: Refer BU-BTX Release manual for the programming of further protections in detail.
6-7
3. Protection....continued
the distribution system. This feature provides protection against earth fault current.
Neutral Overload :This provides protection against neutral overload at 50%, 100% & 200% of rated
current. It follows overload characteristics.
Restricted EF :It works in the restricted zone of source side. It functions similar to normal earth
fault protection
occurrence of fault signal to the main release is being done by an earth leakage module.
Under current :Decrease in any phase current below threshold leads to under current.
Current Unbalance :It provides protection against any unbalance in phase currents .
Save Settings ? After programming the settings, press key to escape from menu and
Yes No Set Group by pressing the escape key . “Save in Progress” message
Note: Refer BU-BTX Release manual for the programming of further protections in detail.
6-8
Protections under V- protection:
Under voltage :When the voltage in one of the phases reduces than threshold, this
protection gets activated.
Over voltage :When the voltage in one of the phases increases above threshold, this
protection gets activated.
Voltage unbalance :Voltage unbalance creates damage to the distribution system. This protection
checks voltage unbalance in all three phases.
Residual voltage :Gives protection against the residual voltage present in the system.
Under frequency
Over frequency
} applicable for both control frequencies 50Hz & 60Hz.
Reverse power : When the direction of the total active power reverses to that of
the set direction, this protection gets activated. The direction of power depends on
Leading PF : It checks whether the power factor is increasing beyond the set value when load is
capacitive.
Lagging PF : When the power factor for inductive load goes below the set value, this protection
gets activated. It’s important for any plant to maintain the power factor to unity.
MD active
MD reactive
MD apparent
} When max. demand of active, reactive & apparent power exceeds the set
value, then this protection gets activated.
Phase sequence :Mostly used for motor applications where phase reversal can be seen.
Breaker failure : In case if the breaker fails to open under fault condition (mechanism jam,
FSD malfunctions etc.) release issues one more trip command to FSD to operate
the breaker as per the set delay through this protection.
Note: Refer BU-BTX Release manual for the programming of further protections in detail.
6-9
The Salient Features:
“Click”
5 6 “Click”
CONNECTED
TEST
c DISCONNECTED
b
a
Ultra-Power
LED
BU-BTX
mode*.
6-11
6.7 Securing your Breaker:
ACB offers several security features to prevent unauthorized access and inadvertent operation.
breaker remains locked in OFF position. For switching the breaker ‘ON’,
reinsert the key & turn to release OFF button.
6-12
Section 7
ULTRA
POWER
7.1 Maintenance Schedule & Operations:
Regular maintenance of Ultra - Power Series of breaker will help ensure proper operation, reliable
protection and enhanced product life.
• Ensure that main and control supply is disconnected, before commencing any work on the
device.
CAUTION • Failure to meet the above precautions can lead to electrocution and result in serious injury /
death to personnel.
• It is recommended to call Authorised Service Centre for servicing the breaker.
• After maintenance, in P&C unit (BU-BTX3.5/3.5EC) give “Yes”command to the
“Maintenance” in “Restore Settings” .
Nature of
Schedule/Frequency Actions Reference
Maintenance
If ‘POWER ON’ LED is Blinking Green, it implies that the P&C unit is
healthy and is protecting your circuit. POWER ON
If ‘ POWER ON’ LED is OFF when there is no/minimal current in the LED
main circuit.
Remove cover of P&C unit and press ‘T’ button. Enter the Command
password (Default factory set password is “0000”).Unit issues trip in
EF and trip, E/F LED glows.
To reset the LEDs, again press the “T” button once the breaker is
7-1
Door Racking Interlock defeat (26):
Tools required: None
Door Racking interlock prevents opening of smart racking
shutter (16) and thus, racking in/out of the breaker when
panel door is open.
If it is necessary to rack-out the breaker with panel door open,
racking interlock must be defeated. For opening racking shutter
Up to 690V AC
Rear Side of
Once Arc chutes are opened, contacts are visible and can be inspected for erosion.
This feature is only for indication purposes and contacts should be replaced
after cleaning major fault/on completion of electrical life indicated.
moving contact
7.1h Greasing of Mechanism:
Non-adherence to greasing schedule
earlier. Grease to be used in Mechanism - Parts 1 to 6: Red
Grease(MobilithSHC-100 of Mobill); Parts 10 & 11 (plastic parts) on right may lead to malfunction.
hand side of Mechanism: White Grease (MOLYKOTE 33 MEDIUM)
CAUTION Ensure that ACB is OFF and Spring is
Grease to be used on parts 1 to 9 of Cradle: Red Grease (MobilithSHC-100 Discharged, before commencing
of Mobill) greasing operation.
The following components can be greased, without dismantling any
accessory or component, using a brush. 1 : Racking Screw
2 : Racking Cam & Drop Pin joint
1 : Pole shaft bearing (all) 3 : Base Plate
2 : Bearings (both sides of mechanism) 4 : Rail Sliding surface on Side plate
5 : Racking Cam & Service Latch follower
10
5
11 4
8
2
1
7
3
6
7-4
Fault diagnosis in BU-BTX1.0/1.0+ Units
P&C unit stores 5 Trip Records and 10 Event records which can be read
when auxiliary supply(24 dc) is present. Trip Record contains current, voltage
frequency levels of the system when the fault occured. Event Record records
the events like pick-up,alarm and trip.
220V.
240V~,
Moving part of the pole can now
be removed
Jaws can be replaced without using any tool. Slightly rotate the jaw
left or right to remove it.
Tools required: Screw Driver (Blade - Length 300 mm & Dia 8 mm,
Tip width 8 mm)
B A B
Remove screws ‘A’ and loosen screws Pull out the cradle terminal Now you can replace the cradle
‘B’. As a result, Removing of Safety Shutter, assembly using projections terminals & Jaw Cluster assemblies.
jaws and Terminal support clamp will drop down. on the terminal support.
7-7
Sr. Component Cat No. Units per Units per
No. Cat No. ACB*
1 Electrical AC 110 V BLECD90360OOOO
Charging 50/60Hz 220 V BLECD90364OOOO
Device 240 V BLECD90359OOOO
(ECD) 415 V BLECD90361OOOO
DC 24/30 V BLECD90362OOOO 1 1
48/60 V BLECD90363OOOO
110/125 V BLECD90360OOOO
200 V BLECD90364OOOO
240V~, 220-250V __
---
250 V BLECD90359OOOO
400 V BLECD90361OOOO
2 Shunt Release AC 110 V BLSH90816OAOO
(SR) 50/60 Hz 220 V BLSH90816OBOO
Shunt Release
240 V BLSH90816OBOO
415 V BLSH90816ODOO
240V~, 220V.
DC 24 V BLSH90816O4OO
30 V BLSH90816O4OO 1 1
Shunt Release
48 V BLSH90816O5OO
60 V BLSH90816O5OO
240V~, 220V.
110 V BLSH90816OAOO
125/127 V BLSH90816O1OO
220 V BLSH90816OBOO
250 V BLSH90816OBOO
SRW AC 240 V BL90823OBOO
(Wide band 10-130%) 50 Hz 415 V BL90823ODOO
3 Undervoltage Release AC 110 V BLUV90818AOOO
(With/Without Delay -UVR) 50/60Hz 240 V BLUV90818BOOO
415 V BLUV90818DOOO
24/30 V BLUV908184OOO 1 1
UV Release
415V-, 415V~.
DC 48 V BLUV908185OOO
110 V BLUV90818AOOO
220 V BLUV90818BOOO
4 Closing Release AC 110 V BLCR90817AOOO
(CR) 50/60Hz 220 V BLCR90817BOOO
240 V BLCR90817BOOO
415 V BLCR90817DOOO
DC 24 V BLCR908174OOO 1 1
30 V BLCR908174OOO
48 V BLCR908175OOO
Closing Release
240V~, 220V.
60 V BLCR908175OOO
110 V BLCR90817AOOO
125/127 V BLCR908171OOO
220 V BLCR90817BOOO
250 V BLCR90817BOOO
7-8
Component Cat No. Units per Units per
No. Cat No. ACB
#
BL90010OOOO
10 Racking handle 1 1
BL90290OOOO
# Quantities for all 4-pole ACBs pertain to 100% N rating
## Horizontal for bus-coupler application of ACBs only
* Available upto 3200A
7-9
Component Cat No. Units per Units per
No. Cat No. ACB*
7-10
23 2 Incomers (2m) BL90810OOOO
3 Incomers (2m) BL90811OOOO
1 set 1 set per scheme
2 Incomers & 1 Standby (2m) BL90812OOOO
2 Incomers & 1 Buscoupler (2m) BL90813OOOO
2 Incomers (3m) BL90659OOOO
3 Incomers (3m) BL90660OOOO
1 set 1 set per scheme
2 Incomers & 1 Standby (3m) BL90661OOOO
2 Incomers & 1 Buscoupler (3m) BL90662OOOO
2 Incomers (5m) BL90663OOOO
3 Incomers (5m) BL90664OOOO
1 set 1 set per scheme
2 Incomers & 1 Standby (5m) BL90665OOOO
2 Incomers & 1 Buscoupler (5m) BL90666OOOO
24
Frame 1 N/S/H BL91153OOOO
7-11
29 Locking Arrangement for all Position for Castell Lock BLCLC90981OOOO
for Ronis Lock BLCLR90927OOOO 1 or 2 as
1
for Kirk Lock BL90868OOOO required
for Profalux Lock BL90869OOOO
30 C.T. Wire Harness for Matrix Frame 1-3P BL00687OOOO
Frame 1-4P BL00688OOOO
Frame 2-3P BL00689OOOO
Frame 2-4P BL00690OOOO 1 1
Frame 3-3P BL00691OOOO
Frame 3-4P BL00692OOOO
Frame 3-4P, 50% N BL00693OOOO
31 400/630/800A BLEN00700OOOO
(Internal) Frame 1 1000/1250/1600A BLEN00701OOOO
2000/2500A BLEN00702OOOO
3 for 3 pole
400/630/800A BLEN00725OOOO
4 for 4 pole
1000/1250/1600A BLEN00703OOOO
Frame 2
2000A/2500A/
BLEN00704OOOO 1
3200/4000A
400/630/800A BLNC00726OOOO
1000/1250/1600A BLNC00727OOOO
6 for 3 pole
Frame 3 2000A/2500A/
BLNCL00705OOOO 8 for 4 pole
3200A/4000A
5000A/6300A BLNC00706OOOO
32 400/630/800A BLEN00717OOOO
Frame 1,2,3
External Neutral 1000/1250/1600A BLEN00718OOOO
Frame 1 2000/2500A BLEN00719OOOO
1 1
2000A/2500A/
Frame 2,3 BLNC00720OOOO
3200A/4000A
Frame 3 5000A/6300A BLNC00721OOOO
33 Trip Indication for Undervoltage release BLUM90947OOOO 1 1
Shunt release BLSM90951OOOO 1 1
Common fault indication BLCM90949OOOO 1 1
Ready-to-Close indication BLRCM90953OOOO 1 1
7-12
Section 8
Useful Hints
ULTRA
POWER
Useful Hints
Smart Racking Shutter is open Close the Smart Racking Shutter (Insert
Racking Handle once & pull back)
close
the breaker
Smart Racking Shutter does not Breaker is in-between Rack-in or out the
re-close automatically after Connected/Test/Disconnected breaker to any of the
racking handle is pulled out position. Position Indicator distinct positions
is not aligned with any of
the positions
8-1
Useful Hints
75 - 2 runs 75 - 2 runs
800 800 75 - 2 runs - - - - - -
50 - 3 runs 50 - 3 runs
bus-bar sizes (in terms of thickness & width) can also be used to achieve bus-bar cross section recommended by IS & IEC.
De-rating of switchgear depends upon various factors such as cross section area, orientation and material of bus bar,
healthiness of bus-bar joints, panel construction, and ventilation, etc.
#
4000 7200* - - 100 - 6 runs - - 150 - 4 runs
bus-bar sizes (in terms of thickness & width) can also be used to achieve bus-bar cross section recommended by IS & IEC.
De-rating of switchgear depends upon various factors such as cross section area, orientation and material of bus bar,
healthiness of bus-bar joints, panel construction, and ventilation, etc.
8-2
Useful Hints
Termination - Draw-out Breakers
Aluminium cross
Frame Rating
section as per
Size (A)
IS/IEC (in sq. mm)
6 mm 10 mm 12 mm 6 mm 10 mm 12 mm
4000 7200* - 150 - 5 runs 150 - 4 runs - 125 - 6 runs 125 - 5 runs
bus-bar sizes (in terms of thickness & width) can also be used to achieve bus-bar cross section recommended by IS & IEC.
De-rating of switchgear depends upon various factors such as cross section area, orientation and material of bus bar,
healthiness of bus-bar joints, panel construction, and ventilation, etc.
Copper cross
Frame Rating
section as per IEC Flat
Size (A)
(in sq. mm)
6 mm 10 mm 12 mm 6 mm 10 mm 12 mm 6 mm 10 mm 12 mm
50 -1 run 50 -1 run
800 500 - 60 - 1 run - - - - -
60 - 1 run 60 - 1 run
bus- bar sizes (in terms of thickness & width) can also be used to achieve bus-bar cross section recommended by IS & IEC.
De-rating of switchgear depends upon various factors such as cross section area, orientation and material of bus bar,
healthiness of bus-bar joints, panel construction, and ventilation, etc.
8-3
Useful Hints
Termination - Draw-out Breakers
Frame-2 : 400 - 3200A N/S/H & 4000A S/H
Copper cross
Frame Rating
section as per IEC
Size (A)
(in sq. mm)
6 mm 10 mm 12 mm 6 mm 10 mm 12 mm
However other bus-bar sizes (in terms of thickness & width) can also be used to achieve bus-
Bar cross section recommended by IS & IEC. De-rating of switchgear depends upon various factors
Such as cross section area, orientation and material of bus bar, healthiness of bus-bar joints,
panel construction, and ventilation, etc.
However other bus-bar sizes (in terms of thickness & width) can also be used to achieve bus-bar
Cross section recommended by IS & IEC. De-rating of switchgear depends upon various factors
Such as cross section area, orientation and material of bus bar, healthiness of bus-bar joints,
panel construction, and ventilation, etc.
8-4
Useful Hints
Current carrying capacity with copper bus-bars with orientation: Top - Vertical & Bottom - Vertical with adaptors
Note: The values indicated in the above tables are for general guideline for product selection. These values have been extrapolated from test
data and theoretical calculations. They cannot replace practical industrial application or a temperature rise test. However de-rating of
switchgear depends on others factors such as cross section area, orientation and material of bus-bar, healthiness of bus-bar joints, panel
construction, and ventilation, etc.
8-5
Useful Hints
Ultra-Power ACB’s
Watt loss value
Overall dimension, rated current carrying capacity of Bus-bar and watt loss of apparatus attach
8-6
ULTRA
POWER
ULTRA
POWER Range of Air Circuit Breakers
BU1-08 BU1-10 BU1-12 BU1-16 BU1-20 BU2-25 BU2-32 BU2-40 BU3-50 BU3-63
Frame-1 Frame-2 Frame-3
8-7
ULTRA
POWER ACB ordering information:
ULTRA
POWER ACBs are offered with following standard features:
Draw-out Version: Ultra power ACBs with BU-BTX release will have inbuilt
Current Metering (BTX 1.5G/1.5Gi/3.5/3.5H/4.5), Common Fault Indication microswitch, 4NO+4NC Aux.
contacts, Smart-racking, Shutter, Safety shutter assembly, Racking handle, Door sealing frame, Pad-locking
arrangement for ON/OFF button, Rating Error Preventer, Arc shield.
A) For ratings upto 1600A, one side vertical terminal adaptors (Bottom) for Frames 1.
B) For ratings 2000A & above, both side vertical terminal adaptors (Top & Bottom) for Frames 1, 2 & 3.
C) For rating 4000A and above operation counter inbuilt for Frames 2 & 3 both.
Fixed Version: Ultra power ACBs with BU-BTX release will have inbuilt-
Current Metering (1.5G/1.5Gi/3.5/3.5H/4.5), Common Fault Indication microswitch, 4NO+4NC Aux. contacts,
Door sealing frame & Pad-locking arrangement for ON/OFF push but
A) For ratings upto 1600A, one side vertical terminal adaptors (Bottom) for Frame 1, 2 & 3.
B) For ratings 2000A & above, both side vertical terminal adaptors (Top & Bottom) for Frames 1, 2 & 3.
C) For rating 4000A and above operation counter inbuilt for Frames 2 & 3 both.
Electrically operated ACB includes ECD (240V AC), CR (240V AC) & SR (240V AC OR 24V DC).
8-8
Power Control Products
Industrial Enclosures
Industrial Products
Customised Solution
Automation
www.bchindia.com
Visit us at : www.bchindia.com
Corporate Office : 1105, New Delhi House, 27, Barakhamba Road, New Delhi - 110 001 Tel. : 91-11- 43673100 BCH 1800-103-9262
CIN : U31103WB1965PLC026427, Customercare No. 1800-103-9262, E-mail : [email protected] [email protected]
Registered Office : Block 1E, 216, Acharya Jagadish Chandra Bose Road, Kolkata - 700 017 Customer Care
Works 1 : 20/4, Mathura Road, Faridabad - 121 006 (Haryana) Tel. : 0129-4063000/4293000 Fax : 0129-2304016
Works 2 : 64-68, Sector-7, IIE, Pant Nagar, Rudrapur, Udham Singh Nagar - 263 153 (Uttrakhand) Tel. : 05944-250214/16 Fax : 05944-250215
Sales Offices :
Ahmedabad Bangalore Bhubaneswar Chandigarh (Panchkula) Chennai Coimbatore
401, Shilp Zeveri,, 2nd Floor, 130/5, Mallick Commercial SCO -129, 2nd Floor, Flat No. 3A, 3rd Floor, 87, Dr. Nanjappa Road,
Beside Shyamal Iconic, K.H. Road (Double road), Complex Plot No.: A/69, unit - 3 MDC, Sector-5 Panchkula, Sree Apartments, Coimbatore - 641 018
Above Westside, Bangalore - 560 027 Bhubaneswar - 751 001 Haryana-134 114 No.508, TTK Road, Tel. : 0422-2305311 / 2302599
Shyamal Cross Road, Tel. : 080-41144879 / 22236759 Tel.: 0674-2380988 Tel.: 0172-5078957 / 5049905 Alwarpet, Chennai 600 018 E-mail : [email protected]
Ellis bridge, Ahmedabad - 380015 E-mail : [email protected] E-mail.: [email protected] E-mail.: [email protected] Tel.: 044-24337046, 24337047
E-mail.: [email protected] E-mail : [email protected]