Understanding Short Circuit Protection
Understanding Short Circuit Protection
A Guide to Understanding:
Short-Circuit Protection Devices,
Overload Protection Devices, and
Coordinated Protection
Table of Contents
Code Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Short-Circuit Protection Devices . . . . . . . . . . . . . . . . . . 3
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Type 2 Coordination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Motor Overload Protection . . . . . . . . . . . . . . . . . . . . . . 15
Eutectic alloy overload relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Bimetallic alloy overload relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Solid-state overload relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Advanced Motor Protection . . . . . . . . . . . . . . . . . . . . . 20
Coordinated Motor Circuit Protection . . . . . . . . . . . . . . 22
Life of a Typical Motor Installation . . . . . . . . . . . . . . . . 26
Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
1
“COORDINATED” MOTOR CIRCUIT PROTECTION
CODE REQUIREMENTS
Whether you are designing motor circuits for use in North America,
Europe, or any other part of the world, several basic requirement are
typically specified for a motor circuit. In the U.S., the National Electrical
Code (NEC) is followed as the basis for most electrical installations. In
Canada, the Canadian Electrical Code (CEC) is followed, and in Europe,
each country has it’s own electrical code requirements that must be met. Due
to time and space limitations, we will address code issues in reference to the
NEC unless otherwise stated.
Article 430 of the NEC describes the requirements for installations
involving motors, motor circuits, and controllers. In Article 430, the
requirements for motor branch circuit short-circuit, and ground fault
protection and motor overload protection are specified. Figure 1 identifies
the control and protection components required for a motor branch circuit.
Figure 1
NEC Article 430 – Motor Branch Circuit Requirements
Supply
Disconnecting
Means
Short-Circuit Fuses
Protection Device or
(SCPD) Circuit Breaker
Motor Controller
Motor
FUSES
Fuses are over-current protective devices that are placed in an
electrical circuit to protect the control components, wiring, insulation, and
motor from damage caused by excessive current and associated heat.
Overcurrents are considered any increase in continuous current above the
normal operating current level.
In motor circuits, overcurrents are classified in two different
categories. Motor overloads are any overcurrents up to or slightly above
locked rotor current (6-8 times FLA). This range of overcurrent is protected
by overload relay protection devices which will be discussed in more detail
later. Short-circuit overcurrents are those produced by short-circuit or ground
fault conditions with fault current levels in excess of 8 times FLA. In todays
industrial facilities, short-circuit overcurrents can easily reach 50,000A. If
the short-circuit overcurrents are not interrupted within fractions of a second,
severe damage to the electrical installation can occur including motor
damage, conductor and controller damage or even fires. In motor circuits,
fuses best provide protection from damage caused by short–circuit currents.
Throughout the world, many different types of fuses are used for
short-circuit protection in motor circuits. In North America, UL and CSA
fuses are most commonly used. In other parts of the world, DIN (German)
and BS88 (British) fuses are dominant. Even though the construction and
fastening means are quite different (See Figure 2), all these fuses still
perform the same essential function of short-circuit protection.
3
“COORDINATED” MOTOR CIRCUIT PROTECTION
Figure 2
The World of Fuses
BS88 Fuses
• IEC fuse type: Fuse-link for bolted connection
• Voltage rating: 660V AC
• Interrupting rating: 80,000A
• Standard cartridge sizes: A1, A2, A3, A4, B1, B2,
B3, and B4
• Typical ampere ratings: 2–400A
• Construction: Blade type for bolted connection
• Where commonly used: United Kingdom, Australia,
New Zealand, Asia, and Middle East
DIN Fuses
• IEC fuse type: Fuse-link with blade contacts
• Voltage rating: 660V AC
• Interrupting rating: 100,000A
• Standard cartridge sizes: 00, 0, 1, and 2
• Typical ampere ratings: 2–400A
• Construction: Blade type
• Where commonly used: Europe, South America,
Middle East, and India
UL/CSA Fuses
• Operation: Time-delay; Current-limiting
• UL fuse type: Class CC
• CSA fuse type: HRCI-MISC
• Voltage rating: 600V AC
• Interrupting rating: 200,000A
• Standard cartridge sizes: 30A
• Typical ampere ratings: 1–30A
• Construction: Ferrule type
• Where commonly used: North America
4
“COORDINATED” MOTOR CIRCUIT PROTECTION
5
“COORDINATED” MOTOR CIRCUIT PROTECTION
CSA Fuses
• CSA fuse type: HRCII-C
• Voltage rating: 600V AC
• Interrupting rating: 200,000A
• Standard cartridge sizes: 30A, 60A, 100A,
200A, and 400A
• Typical ampere ratings: 1–400A
• Construction: Blade type for bolted connection
• Where commonly used: Canada
Fuses are designed to meet specific standard performance
requirements. In the case of UL and CSA fuses, specific characteristics such
as current ratings, voltage rating, fuse dimensions, rejection features,
withstand ratings, maximum I2T and Ip current let-through limits, trip time
parameters (time-delay) and more are specified in the standards.
Table A compares the performance requirements of various UL and
CSA fuse classes. As you can see, different class fuses with similar current
ratings can have significantly different results on I2T and Ip let-through
values.
Table A
Fuse Performance Requirements
UL Fuse Performance Requirements
per UL 198, 600 Volts, 100kA ➊
Ampere Max I2t 103 Max. Ip 103
UL Fuse Class
Rating (A) (A2-Sec.) (A)
K5, RK5 50 11
K1, RK1 10 10
30 J 7.0 7.5
T 7.0 7.5
CC 7.0 7.5
K5, RK5 200 21
K1, RK1 40 12
60
J 30 10
T 30 10
CSA Fuse Performance Requirements
per CSA C22.2 No. 106 ➊
Ampere Max I2t 103 Max. Ip 103
CSA Fuse Class
Rating (A) (A2-Sec.) (A)
HRCII-C 50 14
HRCI-R 50 14
30
HRCI-J 7 12
HRCI-T 7 12
HRCII-C 200 26
HRCI-R 200 26
60
HRCI-J 30 16
HRCI-T 30 16
➊ Fuses are tested on circuits with available fault currents between the threshold current of the fuse and 100,000
RMS symmetrical amperes.
6
“COORDINATED” MOTOR CIRCUIT PROTECTION
FUSE MECHANICS
Figure 3 illustrates the typical operation of a dual element-time delay
fuse. As its name indicates, “dual element” means that the fuse incorporates
two separate current sensing elements arranged in a series configuration (A).
The overload element opens when continuous overcurrent conditions exist
(B). During an instantaneous short-circuit condition, the short-circuit
element will open in multiple locations (C), interrupting the short-circuit an
limiting the let-through I2T and Ip within the limits specified by the fuse
standard requirements.
Figure 3
Dual Element Time Delay Fuse
Short–circuit Element
7
“COORDINATED” MOTOR CIRCUIT PROTECTION
CIRCUIT BREAKERS
An increasingly popular method of providing short-circuit protection
in motor circuits is with the use of circuit breakers. Circuit breakers have
become very popular due to the fact that following a fault condition, circuit
breakers can be easily reset once proper troubleshooting and maintenance
procedures are completed. The ability to reset a circuit breaker following a
fault condition, allows the manufacturing process to begin operation with
minimal downtime.
There are many different types of circuit breakers on the market. In
discussing the world of circuit breakers, we will concentrate on two groups
of products. The first group will be UL/NEMA type molded case circuit
breakers which are very popular in North America, and IEC type circuit
breakers (motor circuit protectors) that are commonly used as short-circuit
protection devices outside North America.
8
“COORDINATED” MOTOR CIRCUIT PROTECTION
Figure 5
IEC Type Circuit Breakers
10
“COORDINATED” MOTOR CIRCUIT PROTECTION
Figure 6
North American “Group Motor Installation”
Disconnect
Switch Circuit
Breaker
OR
Fuses
Bulletin 140
Bul. Bul. Bul. Bul. Manual Starter
140 140 140 140 and Protector
Contactor
for Remote
Operation
M1 M2 M3 M4
Figure 7
Motor Installations Outside North America
Disconnect
Switch
Bulletin 140
Bul. Bul. Bul. Bul. Manual Starter
140 140 140 140 and Protector
Contactor
for Remote
Operation
M1 M2 M3 M4
TYPE 2 COORDINATION
Type 2 Coordination is a term used to describe a level of protection
that can be achieved by properly “coordinating” the selection of the
short-circuit protection device with the withstand capability of the motor
controller and overload protection device in the circuit. The concept of Type
2 Coordination originated from the IEC (International Electrotechnical
Commission) standard 947-4-1. In this standard, two levels of short-circuit
coordination are identified.
Type 1 Coordination is defined as follows:
“Under short-circuit conditions, the contactor or starter shall cause no
danger to persons or installation and may not be suitable for further
service without repair and replacement of parts.”
In other words, contact welding is allowed in the contactor and
overload burnout is acceptable. In either case, replacement of the control
components are required.
Type 2 Coordination on the other hand, limits the effect of a
short-circuit on the control components. Type 2 Coordination is defined as
follows:
“Under short-circuit conditions, the contactor or starter shall cause no
danger to persons or installation and shall be suitable for further use.
The risk of contact welding is recognized, in which case the manufacturer
shall indicate the measures to be taken in regard to the maintenance of
the equipment.”
Figure 8 illustrates the results of a short-circuit if a motor branch
circuit was protected by current limiting device vs. a circuit without a current
limiting device. In circuits using a current limiting device, the let-through
energy is limited to less than 1/2 cycle. This limited level of let-through
energy allows the control components to survive a short-circuit and continue
operation with little or no maintenance required.
In general, fuses have had much better current limiting capabilities
than do circuit breakers, although some current limiting circuit breakers can
provide Type 2 Coordination results. It is best to consult the control
manufacturer for recommended short-circuit protection devices required to
achieve Type 2 Coordination. Control manufacturers can provide component
selection data (see Table B) that has already been proven during Type 2
testing programs. By following the manufacturers guidelines, you can be
assured of achieving Type 2 Coordination in your motor branch circuit
installation.
Benefits of Type 2 coordination include:
• Increased productivity and less down time
• Reduced component replacement costs
• Simple selection of SCPDs and motor circuit components with
manufacturer supplied data
12
“COORDINATED” MOTOR CIRCUIT PROTECTION
Figure 8
Let-through Heat and Current
Current
Peak available current (lp)
without current limiting fuse
NOT CURRENT-LIMITED
Normal
Load
Current Heat Energy
Time
Point
of Fault
Current
Peak available current (lp)
without current limiting fuse
CURRENT-LIMITED
Normal
Load
Current Heat Energy
Time
Point
of Fault
At the inception of a fault, a branch circuit can reach peak available current (lp) without a
current-limiting protector. The heat produced reaches temperatures that melt conductors as well
as insulation, and the magnetic forces bend conductors and supports. When protected with a
current-limiting fuse, however, the let-through current is only a fraction of lp, usually opening the
fuse in less than one-half cycle. Type 2 Coordination assures that no harm to people or damage
to equipment results from short-circuit currents.
13
“COORDINATED” MOTOR CIRCUIT PROTECTION
Table B
Manufacturer Fuse Recommendation for Type 2 Coordination
UL Listed Time-delay
Overload
Motor Horsepower Contactor Class J
Relay
(CSA HRCI-J) Fuse
Single Fuse
Three-phase Cat. No.
Phase Max.
Basic Amp. Gould-
115V 230V 200V 230V 460V 575V Rating Bussman Littlefuse
Cat. No. Cat. No. Shawmut
— — — — 1/2 3/4 100-A09 193-BSB16 2 LPJ-2 AJT2 JTD2
— — — — 3/4 1 100-A09 193-BSB16 2 LPJ-2 AJT2 JTD2
— 1/10 — 1/2 1 — 100-A09 193-BSB22 3 LPJ-3 AJT3 JTD3
— 1/8 — — — — 100-A09 193-BSB22 3 LPJ-3 AJT3 JTD3
— 1/6 1/2 — 1-1/2 1-1/2 100-A09 193-BSB30 6 LPJ-6 AJT6 JTD6
— — — — — 2 100-A09 193-BSB30 6 LPJ-6 AJT6 JTD6
1/10 1/4 3/4 3/4 2 — 100-A09 193-BSB42 6 LPJ-6 AJT6 JTD6
— 1/3 — 1 — — 100-A09 193-BSB42 6 LPJ-6 AJT6 JTD6
1/8 — — — — 3 100-A09 193-BSB50 6 LPJ-6 AJT6 JTD6
1/6 1/2 1 1-1/2 3 — 100-A09 193-BSB60 10 LPJ-10 AJT10 JTD10
1/4 3/4 1-1/2 2 5 5 100-A09 193-BSB80 10 LPJ-10 AJT10 JTD10
1/3 — — — — — 100-A09 193-BSB80 10 LPJ-10 AJT10 JTD10
— 1 2 — — 7-1/2 100-A09 193-BSC10 15 LPJ-15 AJT15 JTD15
— — — 3 — — 100-A12 193-BSC10 15 LPJ-15 AJT15 JTD15
1/2 1-1/2 3 — 7-1/2 10 100-A12 193-BSC15 20 LPJ-20 AJT20 JTD20
— 2 — — — — 100-A12 193-BSC15 20 LPJ-20 AJT20 JTD20
3/4 — — 5 10 — 100-A18 193-BSC15 20 LPJ-20 AJT20 JTD20
1 3 5 — — 15 100-A18 193-BSC24 30 LPJ-30 AJT30 JTD30
1-1/2 — — 7-1/2 15 20 100-A24 193-BSC24 30 LPJ-30 AJT30 JTD30
2 — — — — — 100-A24 193-BSC24 30 LPJ-30 AJT30 JTD30
14
“COORDINATED” MOTOR CIRCUIT PROTECTION
15
“COORDINATED” MOTOR CIRCUIT PROTECTION
Figure 9
NEMA Type Eutectic Alloy Overload Relay
Eutectic Alloy
Heater
L1 T1
Ratchet
Pawl
To
Starter
Coil
16
“COORDINATED” MOTOR CIRCUIT PROTECTION
Figure 10
NEMA Type Bimetal Overload Relay
Trip Bar Contacts
Heater
Element
Power Bimetal To
Circuit Strip Starter
Coil
17
“COORDINATED” MOTOR CIRCUIT PROTECTION
Figure 11
IEC Type Bimetal Overload Relay
L1
L2
L3
Heater
Bimetal
Strip To
Starter
Coil
Trip Bar
18
“COORDINATED” MOTOR CIRCUIT PROTECTION
Figure 14
Advanced Overload Protection Devices
Table C
Advanced Solid-state vs. Traditional OLRs
Advanced Protection Feature Solid-state OLRs Traditional OLRs
D Jam/Stall protection selectable D Trips within .5 sec. at D Relays on overload trip
– I/O selectable 400% of FLA setting curve response
D Ground (earth) fault protection D Monitors phase vector D None – rely on SCPD
selectable angles
– I/O selectable Trips at lower level prior to
fault level
D Single-phase “protection” D Trips within two sec. on D “Sensitive” to single-
fully loaded motor phase conditions
Trips in 40 sec. or longer
D Trip setting accuracy D Dip switch setting D Potentiometer or heater
increased accuracy ±2.5% elements: ±10%
D Repeat accuracy of trip setting D Increased accuracy ±1% D ±5–10%
D LED trip indication D Fault cause indication D None
– Jam/Stall
– Ground earth fault
– Improper setting
– Communication loss
– Test
– Phase loss
– Overload
D Wide current adjustment range D 3.2:1 and 5:1 D 1.6:1 and 1.1:1
D Low power requirement and D 150mW per device D 6W or greater per device
low heat dissipation
D Trip classes 10, 15, 20, 30 D Selectable by DIP switch D Dedicated components per
setting trip class
D Network communications D Control, data acquisition D None
and fault cause indication
D Control
– Start/stop
– Reset
– Restart limit
D Data acquisition
– % thermal capacity
used (trip warning)
– Trip frequency
– Phase unbalance
– FLA trip setting
– Average current
D Fault cause indication
(see above)
21
“COORDINATED” MOTOR CIRCUIT PROTECTION
Figure 15
Overload Response Curve
Time in
Seconds
1 2 3 4 5 6 7 8 9 10
Multiples of FLC
22
“COORDINATED” MOTOR CIRCUIT PROTECTION
Figure 16
Short-circuit Protective Device Responsive Curve
Time in
Seconds
1 2 3 4 5 6 7 8 9 10
Multiples of FLC
23
“COORDINATED” MOTOR CIRCUIT PROTECTION
Figure 17
Coordinated Motor Circuit Protection
Short-circuit
Protective Devices
Overload
Relay
COORDINATION
Time in POINT
Seconds
1 2 3 4 5 6 7 8 9 10
Multiples of FLC
24
“COORDINATED” MOTOR CIRCUIT PROTECTION
If, however, these curves do not intersect, or intersect well above the
motor locked rotor current, the overload protective device will react to
short-circuit currents in the gap between the overload range and short-circuit
protection, and probably be damaged.
Figure 18
Protection Not Coordinated (Curves Do Not Intersect)
Overload Short-circuit
Relay Protective Devices
Time in
Seconds
1 2 3 4 5 6 7 8 9 10
Multiples of FLC
If the curves intersect in the overload range below the locked rotor
current, the short-circuit protective device will nuisance trip on motor
start-up.
Figure 19
Protection Not Coordinated (Curves intersect at less than locked rotor current)
Overload
Time in Relay
Seconds
Short-circuit
Protective Devices
1 2 3 4 5 6 7 8 9 10
Multiples of FLC
25
“COORDINATED” MOTOR CIRCUIT PROTECTION
26
“COORDINATED” MOTOR CIRCUIT PROTECTION
Figure 20
Life of a 40 HP Motor
Crusher Application
40 HP Motor (50A FLC)
Ie
100,000
50,000
10,000
5,000
1,000
500
100 WARNING!
Motor 100%
FLA 50
2 Sec. 40 Sec. 1/2 Sec. 15 Sec.
0 Time
Short- Ground/
Fault Type Circuit Earth Overload Phase Loss Jam/Stall Impending Trip
Fuses
or
Circuit Breakers
“Coordinated“
Motor Circuit
Protection Point
27
“COORDINATED” MOTOR CIRCUIT PROTECTION
TERMINOLOGY
To help understand Coordinated Motor Circuit Protection, it is
necessary to be familiar with the characteristics and definitions related to
fuses, circuit breakers, overload relays, short-circuit, and overload protection.
• Ampere Rating – The continuous current carrying capability of a fuse or
circuit breaker.
• Ampere-squared Seconds (I 2t) – An expression related to the thermal
energy associated with current flow.
• Available Fault Current – The maximum possible short-circuit current
that can flow in an unprotected circuit.
• BS88 Fuse Designations – British Standards Institute has defined basic
physical specifications (size, mounting dimensions, labeling) and
guidelines to fuse manufacturers for providing maximum let-through
current and energy for fuses (in a standard format). Fuse designed to
British Standards are described by their dimension (e.g., Al, A2, A3, A4,
B1, etc.) and continuous current rating.
• Circuit Breaker – A device designed to open and close a circuit by
non-automatic means and to open the circuit automatically on a
predetermined overload current.
• Clearing Time – The total time measured from the beginning of the fault
to the interruption of the circuit.
• Current Limiting Circuit Breaker – A circuit breaker that does not
employ a fusible element and that when operating within its current
limiting range, limits the let-through I2t to a value less than the I2t of a 1/2
cycle wave of the symmetrical prospective current.
• Current Limiting Fuse – A fuse which will limit both the magnitude and
duration of current flow under short-circuit conditions. The available
fault currents a fuse will clear in less than 1/2 cycle, thus limiting the
actual magnitude of current flow.
• DIN Fuse Designations – DIN/VDE Standards specify physical
specifications as well as classes of operation for fuses. The class of
operation is identified by two or three letters (e.g., gL, aM, gTr). The gL
fuse is a general purpose fuse with characteristics that are well suited for
the protection of starters and associated wiring. These fuses are described
by their dimension (e.g., 00, 0, 1, 2, 3 and 4) and continuous current
rating.
28
“COORDINATED” MOTOR CIRCUIT PROTECTION
29
“COORDINATED” MOTOR CIRCUIT PROTECTION
30
Allen–Bradley is committed to supporting you throughout
each phase of the Automation Investment Life Cycle.
Allen–Bradley offers a wide range of motor protection products that
will help extend the life of your motor. These products are an integral
part of the automation process and the life cycle.
Justify. If your application requires motor protection, choose any
one of our solutions for increased productivity. These product lines
offers many protective features such as detection of overload, short
circuit and ground fault conditions. Analyze the complete line of mo-
tor protection products through customer training seminars, product
demonstrations and literature.
Apply. Any one of the motor protection devices may be applied
based upon your application and requirements. Many of these prod-
ucts work together to provide increased functionality.
Install. Integrate our products with new systems as well as existing
systems. Traditional and solid–state protection is available. Our pan-
el system solution reduces wiring and installation costs.
Operate. Striving for optimum productivity and monitoring motor
faults constitute pro–active approaches to this phase.
Maintain. By protecting the motor from damage, our products help
reduce downtime. Product features such as diagnostics and commu-
nications capability also reduce system maintenance.
Improve. Extending the life of your motor is the main benefit of our
product line. As your needs change, we change with you by increas-
ing the effectiveness of our products and monitoring market demands.
Staying focused on product line improvements results in advanced
product offerings such as the SMPTM Overload Relays and the Smart
Motor Manager.
The Automation Investment Life Cycle graphic and SMP are trademarks of the
Allen–Bradley Company.