ACS6000 SD
Medium Voltage Drives

Troubleshooting Manual
Software Version: LSCI6570
Release Date: 11/18/2020

3BHS826621 E65, Rev. A

© ABB Switzerland Ltd. All Rights Reserved.


 

2/89 Version LSCI6570 Troubleshooting Manual




ABB reserves all rights to this document. Misuse, in particular duplication


and forwarding to third parties, is not permitted.
This document has been checked with due care and attention. However,
should the user find any errors, these should be reported to ABB.
ABB aims to maintain the most modern standard, therefore, entries in this
manual may differ from the actual product.
This product is designed to be connected to and to communicate
information and data via a network interface. It is Customer's sole
responsibility to provide and continuously ensure a secure connection
between the product and Customer network or any other network (as the
case may be). Customer shall establish and maintain any appropriate
measures (such as but not limited to the installation of firewalls,
application of authentication measures, encryption of data, installation of
anti-virus programs, etc) to protect the product, the network, its system
and the interface against any kind of security breaches, unauthorized
access, interference, intrusion, leakage and/or theft of data or information.
ABB and its affiliates are not liable for damages and/or losses related to
such security breaches, any unauthorized access, interference, intrusion,
leakage and/or theft of data or information.

LSCI6570 ACS6000 SD 3/89


 

Table of Contents
Table of Contents .................................................................................................................... 4

Troubleshooting Manual ........................................................................................................ 5


Faults .......................................................................................................................................... 7
Alarms ....................................................................................................................................... 77

4/89 Version LSCI6570 Troubleshooting Manual



Troubleshooting Manual
If information is required beyond the instructions in this manual, contact
ABB as follows:

ABB Switzerland Ltd


Medium Voltage Drives
CH-5300 Turgi, Switzerland

Phone:+41 844 845 845


Fax:+41 58 589 2984
[email protected]

LSCI6570 ACS6000 SD 5/89


 

6/89 Version LSCI6570 Troubleshooting Manual



Faults

Panel Text AMC: Fault Class 1


Description Class 1 Fault detected in motor control software. Fault reaction is pulse removal (stop motor),
opening of MCB and discharging of DC-link
Causes Reasons for Class 1 Faults are mainly faults concerning DC-circuit e.g. DC overvoltage and NP-
overvoltage.
Rectification Check for other related faults in the fault buffer. Each faults results in two records in fault buffer:
fault class (this one) and fault message (other fault texts in this file)
FaultClass INU FC1
FaultClass ARU Not Appl
Fault Word 183.32: FW Generic Faults Bit B00
Related Parameters Related IO

Panel Text AMC: Fault Class 2


Description Class 2 Fault detected in motor control software. Fault reaction is pulse removal (stop motor), if
drive was already energized MCB stays closed and DC-link charged
Causes Reasons for Class 2 Faults are mainly faults that do not concern the DC circuit e.g. overspeed,
overcurrent, speed measurements
Rectification Check for other related faults in the fault buffer. Each faults results in two records in fault buffer:
fault class (this one) and fault message (other fault texts in this file)
FaultClass INU FC2
FaultClass ARU Not Appl
Fault Word 183.32: FW Generic Faults Bit B01
Related Parameters Related IO

Panel Text Autorest OnBitReset


Description ON bit reset during AutoRestart.
Causes ON bit was cleared during AutoReset state of AutoRestart.
Rectification Check ON bit state.
FaultClass INU FC2
FaultClass ARU
Fault Word 183.33: FW1 Generic Faults Bit B03
Related Parameters Related IO

Panel Text Autorestart Loop


Description Trips the drive if the maximum number od auto-restart attempts is exceeded
Causes - Wrong parameter setting
- Depends on the fault that started the auto-restart sequence
Rectification - Check related parameter
FaultClass INU FC2
FaultClass ARU Not Appl.
Fault Word 183.33: FW1 Generic Faults Bit B01
Related Parameters Related IO

Panel Text Autorestart Timeout


Description Trips the drive if an auto-restart sequence takes too long
Causes - Wrong parameter setting
- Depends on the fault that started the auto-restart sequence
Rectification - Check parameter
FaultClass INU FC2
FaultClass ARU Not Appl.
Fault Word 183.33: FW1 Generic Faults Bit B00
Related Parameters Related IO

LSCI6570 ACS6000 SD 7/89


 
Panel Text CBU Short Circuit
Description Short circuit in DC link
Causes A short circuit has been detected in the DC link with MCB in status CLOSED
Rectification Check MCB status
Check IGCT\'s and Diodes finding a short circuit
Contact ABB Service organisation
FaultClass INU FT
FaultClass ARU FT
Fault Word 183.20: FW Short Circuit Bit B00
Related Parameters Related IO

Panel Text CCB Communication


Description CCB excitation unit has detected a communication error.
Causes CCB board wrong node address
Faulty fiber optic connection between AMC and CCB boards
Can happen at the initialization after a power cycle
Rectification Check node address of CCB board.
Check Fiber Optic between AMC and CCB.
Check auxiliary power on CCB.
FaultClass INU FC2
FaultClass ARU
Fault Word 183.02: FW Communication Bit B11
Related Parameters Related IO

Panel Text DC Overvoltage


Description DC link voltage exceeds the trip level.
Causes Mains supply too high
Internal parameter settings
Defective circuit board
Communication faulty
Rectification Check if mains supply voltage is within limits.
Verify ARU parameters (if present).
Verify maximum braking power settings.
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.12: FW DC LinkVolt Bit B00
Related Parameters 186.02 186.03 186.04 Related IO

Panel Text DC Overvoltage FT


Description Firing through active, one of the half DC-link voltage reached the
overvoltage “firing through” limit.
Causes Overvoltage in the DC link
Rectification Check data logger off all units
Check all fault logger
Check if mains supply voltage is within limits
FaultClass INU FT
FaultClass ARU Not Appl.
Fault Word 183.13: FW1 DC LinkVolt Bit B02
Related Parameters 186.02 186.03 186.04 Related IO

Panel Text DC Overvoltage FT 1


Description Firing through active, one of the half DC-link voltage reached the
overvoltage “firing through” limit.
Causes Overvoltage in the DC link
Rectification Check data logger off all units
Check all fault logger
Check if mains supply voltage is within limits
FaultClass INU FT
FaultClass ARU ND
Fault Word 183.13: FW1 DC LinkVolt Bit B12
Related Parameters 186.02 186.03 186.04 Related IO

8/89 Version LSCI6570 Troubleshooting Manual



Panel Text DC OvervoltageMCB
Description anyone of the half DC link voltages exceeds the trip level
Causes - mains supply voltage high
- parameter settings
- defective circuit board
- communication disturbed
Rectification - check value of the supply voltage
- check the situation of the network and monitor signals at the same situation, also for a longer
time
- check parameter 186.04
FaultClass INU FC1
FaultClass ARU Not Appl.
Fault Word 183.12: FW DC LinkVolt Bit B01
Related Parameters 186.02 186.03 186.04 Related IO

Panel Text DC Undervoltage


Description DC bus voltage went below the trip level.
Causes Mains supply low.
Internal parameter settings.
Defective circuit board.
Communication faulty.
Rectification Check if mains supply voltage is within limits.
Check for other related faults.
Check actual DC Voltage compared with the trip limit.
Check parmeter settings
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.12: FW DC LinkVolt Bit B02
Related Parameters 186.05 Related IO

Panel Text DCS Aux Undervolt


Description Auxiliary undervoltage fault from DCF excitation unit
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.10: FW3 CntrlHardware Bit b04
Related Parameters Related IO

Panel Text DCS CH0 DDCS COM


Description Communication fault in channel 0 between AMC board and DCS EXU.
Causes Fiber optic link or connected boards faulty
DCS wrong node address
Auxiliary power issue in EXU unit
Rectification Check fiber optic cables and connections
Check DCS node address
Check DCS auxiliary power
FaultClass INU FC2
FaultClass ARU
Fault Word 183.03: FW1 Communication Bit B06
Related Parameters Related IO

LSCI6570 ACS6000 SD 9/89


 
Panel Text DCS Cur Ripple
Description Too high current ripple in DCS excitation unit detected.
Causes Broken fuse or broken thyristor
Too big gain of the current controller
Broken current transformer
Rectification Check EXU parameter settings
Check EXU hardware
FaultClass INU FC2
FaultClass ARU Not Appl.
Fault Word 183.18: FW2 Current Bit B06
Related Parameters Related IO

Panel Text DCS Earth Fault


Description Earth fault in DCS excitation unit detected.
Causes
Rectification Check EXU parameter settings
Check EXU hardware
FaultClass INU
FaultClass ARU
Fault Word 183.18: FW2 Current Bit B05
Related Parameters Related IO

Panel Text DCS Ext Fault


Description DCS excitation unit has detected an external fault via digital input.
Causes Various, see DCS settings
Rectification Check the fault list in the EXU
Check corresponding digital input signal
FaultClass INU FC2
FaultClass ARU Not Appl.
Fault Word 183.36: FW1 Other Bit B14
Related Parameters Related IO

Panel Text DCS MCB Acknowleg


Description MCB of DCS excitation unit does not show correct position feedback
status.
Causes Broken wiring to EXU MCB
Broken EXU MCB
Rectification Check EXU connections
Check EXU MCB
FaultClass INU FC2
FaultClass ARU Not Appl.
Fault Word 183.10: FW3 CntrlHardware Bit B07
Related Parameters Related IO

Panel Text DCS No Fan Acknowlg


Description Fan contactor in DCS excitation unit does not show correct feedback
status.
Causes Broken wiring to fan contactor
Broken fan contactor
Rectification Check EXU connections
Check EXU fan
FaultClass INU FC2
FaultClass ARU
Fault Word 183.10: FW3 CntrlHardware Bit B06
Related Parameters Related IO

10/89 Version LSCI6570 Troubleshooting Manual



Panel Text DCS Overcurrent
Description DC-overcurrent in DCS excitation unit detected.
Causes Wrong EXU settings
Broken fuse or broken thyristor
Too big gain of the current controller
Broken current transformer
Rectification Check EXU parameter settings
Check EXU hardware
FaultClass INU FC2
FaultClass ARU Not Appl.
Fault Word 183.18: FW2 Current Bit B04
Related Parameters 131.01 Related IO

Panel Text DCS Overtemperature


Description Overtemperature fault from DCS excitation unit.
Causes Air flow in DCS EXU not sufficient
Rectification Check whether air-circulation is possible
Check whether fan is running
FaultClass INU FC2
FaultClass ARU
Fault Word 183.10: FW3 CntrlHardware Bit B05
Related Parameters Related IO

Panel Text DCS: Mains Overv


Description DCS excitation unit has detected an overvoltage in the mains supply.
Causes Wrong EXU parameter settings.
Too high supply EXU supply mains voltage
Rectification Check EXU parameter settings
Check EXU supply mains
FaultClass INU FC2
FaultClass ARU
Fault Word 183.26: FW Network Bit B12
Related Parameters Related IO

Panel Text DCS: Mains Underv


Description DCS excitation unit detected undervoltage in mains supply
Causes Wrong parameter setting in DCF EXU
Lost mains supply of EXU
Rectification Check EXU parameter settings
Check EXU hardware
FaultClass INU FC2
FaultClass ARU
Fault Word 183.26: FW Network Bit B11
Related Parameters Related IO

Panel Text DCS: Not Sync


Description DCS EXU lost synchronization with the supplying network
Causes Wrong EXU parameter settings
Issue with EXU mains voltage
Rectification Check EXU parameter settings
Check EXU mains voltage
FaultClass INU FC2
FaultClass ARU
Fault Word 183.26: FW Network Bit B13
Related Parameters Related IO

LSCI6570 ACS6000 SD 11/89


 
Panel Text Delayed PSU AuxPwr
Description At least one PSU aux power failure is pending for more than 1 minute
Causes PSU auxiliary power issue
Fiber optic between PSU and INT boards faulty
Rectification Check auxiliary power supply and fuses
Check auxiliary power supply wiring
Check fiber optic cables and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.07: FW CntrlHardware Bit B00
Related Parameters Related IO

Panel Text Encoder Mismatch


Description Difference between measured speed (NTAC-02) and calculated speed
(LD-GRB01) is above trip limit.
Causes Speed measurement chain is defective: NTAC-02 or pulse encoder device.
Position measuremt chain is defective: LD-GRB01 or gray encoder device is defect, not correctly
positoned or not correctly fixed.
Rectification Check cabling and connections between position encoder and GRB module
Check if cables are twisted pair cables and shielded cables. Check if modules are grounded and
shielding are connected (follow users manual)
Check calibration offset of gray encoder.
Check if modules are correctly fixed on motor shaft and have correct potential connection.
Check the actual values for speed (165.28/166.26/160.18) and compare them with the trip levels
(186.19/186.20)
Check the pulses of the encoder with oscilloscope
FaultClass INU FC2
FaultClass ARU
Fault Word 183.29: FW SpeedPosition Bit B03
Related Parameters Related IO

Panel Text EXTERNAL MODULATION


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.04: FW2 Communication Bit b12
Related Parameters Related IO

Panel Text EXU Current Minimum


Description EXU current minimum trip level was reached.
Causes EXU current reference minimum lower than EXU current minimum trip level.
Actual EXU current too small.
Wrong tuning of EXU PI controller.
Rectification Check EXU current reference minimum to be higher than EXU current minimum trip level.
Check actual EXU current.
Check tuning of PI controller of EXU.
FaultClass INU FC2
FaultClass ARU
Fault Word 183.41: FW2 Other Bit B05
Related Parameters Related IO

12/89 Version LSCI6570 Troubleshooting Manual



Panel Text EXU PHS CHG NOT RDY
Description EXU is not ready during Brushless Bidirectional Operation (phase change).
Causes Output switches not connected.
No feedback from output switches.
Wrong excitation type.
Dataset in DCS EXU not set.
Rectification Check cabling of output switches.
Check communication of EXU.
Set valid exitation type (only Brushless / Brushless bidirectional).
Check dataset configuration in DCS, especially for digital input.
FaultClass INU FC2
FaultClass ARU
Fault Word 183.41: FW2 Other Bit B03
Related Parameters Related IO

Panel Text EXU: Alpha Min Flt


Description EXCITATION BRIDGE ALPHA MIN LIMIT FAULT
Causes Firing angle alpha is in minimum limit
Rectification Check parameters settings
With brushless EXUs, verify also 146.14 par. 159.9 (ALPHA_COND) <= par. 154.11
(ALPHA_MIN) during par. 182.15 (alpha_lim_time)
FaultClass INU FC2
FaultClass ARU
Fault Word 183.17: FW1 Current Bit B04
Related Parameters Related IO

Panel Text EXU: BCO Fault


Description Bridge Change Over fault i.e. timeout for current zero has occured
Causes Too much current in the bridge due to low network voltage. Timeout settings too short.
Rectification Check Network voltage
FaultClass INU FC2
FaultClass ARU
Fault Word 183.35: FW Other Bit B07
Related Parameters Related IO

Panel Text EXU: BOD Activation


Description Direct EXU: Excitation bridge overvoltage BOD is active.
Causes Overvoltage protection activated (PAI IO)
Rectification Check Uf
Check operating points:
e.g. high speed => check Ie, could be very low and the effect of the stator current is to big from
CCB: par. 145.3/Bit9 Status word or par. 169.6/Bit11 PAIIOOUT
FaultClass INU FC2
FaultClass ARU
Fault Word 183.13: FW1 DC LinkVolt Bit B01
Related Parameters Related IO

Panel Text EXU: Communication


Description EXU communication error detected.
Causes EXU wrong node address
Faulty fiber optic connection between AMC and EXU boards
Can happen at the initialization after a power cycle.
Rectification Check EXU board node address
Check fiber optic connection between AMC and EXU
Check EXU auxiliary power
FaultClass INU
FaultClass ARU
Fault Word 183.02: FW Communication Bit B12
Related Parameters Related IO

LSCI6570 ACS6000 SD 13/89


 
Panel Text EXU: Control HW
Description EXU: General hardware fault on EXU control boards.
Causes EXU faulty auxiliary power or defective boards
Rectification Check auxiliary power on the EXU boards
FaultClass INU FC2
FaultClass ARU
Fault Word 183.07: FW CntrlHardware Bit B02
Related Parameters Related IO

Panel Text EXU: CSM1 Timeout


Description EXU: CSM1 Timeout, Current too high for a too long time.
Causes
Rectification
FaultClass INU FC2
FaultClass ARU
Fault Word 183.35: FW Other Bit B06
Related Parameters Related IO

Panel Text EXU: Fault Class 1


Description Class 1 Fault detected in EXU software. Fault reaction is Block Pulses, Trip MCB
Causes EXU fault
Rectification Check for EXU related faults in the fault logger.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.32: FW Generic Faults Bit B07
Related Parameters Related IO

Panel Text EXU: Fault Class 2


Description Class 2 Fault detected in EXU software.
Causes EXU fault
Rectification Check for EXU related faults in the fault logger.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.32: FW Generic Faults Bit B08
Related Parameters Related IO

Panel Text EXU: Fault Class 3


Description Class 3 Fault detected in EXU software.
Causes EXU fault
Rectification Check for EXU related faults in the fault logger.
FaultClass INU FC2
FaultClass ARU
Fault Word 183.32: FW Generic Faults Bit B09
Related Parameters Related IO

Panel Text EXU: Fuse/TmpSwitch


Description EXU: Excitation bridge fuse failure.
Causes Fuse failure
or PAI IO indication fault
Rectification Replace fuse if defective
FaultClass INU FC2
FaultClass ARU
Fault Word 183.09: FW2 CntrlHardware Bit B03
Related Parameters Related IO

14/89 Version LSCI6570 Troubleshooting Manual



Panel Text EXU: Illegal Fault
Description EXU: Illegal Fault. DSP fault due to EMC problems.
Causes Disturbances
Rectification Verify EXU EMC sealings and openings
FaultClass INU FC2
FaultClass ARU
Fault Word 183.35: FW Other Bit B05
Related Parameters Related IO

Panel Text EXU: No Sync


Description Error indicating that CCB phase Locked loop is no longer synchron
Causes Synchronisation voltage is missing or out of limit
Rectification Check supply voltage
Check measurements of sync voltage and connection
FaultClass INU FC2
FaultClass ARU
Fault Word 183.26: FW Network Bit B09
Related Parameters Related IO

Panel Text EXU: OperatingSys


Description EXU: Operating system software not running, due to time level overflow.
Causes Software operating system issue
Rectification Perform power cycle on EXU board
Redownload the EXU board software
Change EXU board
FaultClass INU FC2
FaultClass ARU
Fault Word 183.35: FW Other Bit B04
Related Parameters Related IO

Panel Text EXU: Overcurrent


Description EXU: DC-overcurrent in CCB excitation unit detected.
Causes Actual current is too big or max limit is set too low.
Rectification Measure actual EXU current
Check EXU tuning
FaultClass INU FC2
FaultClass ARU
Fault Word 183.17: FW1 Current Bit B03
Related Parameters 131.01 Related IO

Panel Text EXU: PAI Communica


Description Communication error between PAI and CCB detected.
Causes Fibre optic links
Broken PAI
Aux power on PAI missing
Broken CCB receiver
Rectification Check fiber optic cables between between CCB AND PAI boards located in the EXU cabinet.
Check Aux power on PAI by checking the LED 7(green = Aux power ok)
Check PAI node address, check CCB node address.
LED 1 on PAI is red => PAI not ok.
FaultClass INU FC2
FaultClass ARU
Fault Word 183.02: FW Communication Bit B13
Related Parameters Related IO

LSCI6570 ACS6000 SD 15/89


 
Panel Text EXU: SupplyFreq
Description Network frequency deviation in CCB excitation unit detected.
Causes Network frequency is not within the specified range
Measurement device defective
PLL not correctly tuned
Rectification Check system voltage and frequency
Check measurement
check tuning of PLL according to SW commissioning manual
Check system voltage and frequency
Check measurement
check tuning of PLL according to SW commissioning manual ceck in exu par 182.13 =
omega1_limit
par 121.18 = line_freq
FaultClass INU FC2
FaultClass ARU
Fault Word 183.26: FW Network Bit B10
Related Parameters Related IO

Panel Text EXU: Undervoltage


Description Supply undervoltage in CCB excitation unit detected.
Causes Loss of supply voltage for EXU
Variation of supply voltage down to 60% (voltage Dip)
Measurement Unit Interface MUI-board is defect or connection is wrong.
Rectification Check supply voltage magnitude and variations
Check EXU measurement boards
FaultClass INU FC2
FaultClass ARU
Fault Word 183.26: FW Network Bit B08
Related Parameters Related IO

Panel Text FLASH START FAULT


Description Flash start for resynchronization was not successful because the algorithm did not get enough
current response from the machine when applying short circuits.
Causes Machine is not rotating
Machine flux is too small
Rectification Check whether the interval during which the machine has no supply is too long
FaultClass INU FC2
FaultClass ARU
Fault Word 183.41: FW2 Other Bit B09
Related Parameters Related IO

Panel Text GRAY Missing


Description Error detected in primary position measurement device (GRAY).
Causes GRB module defective
Position encoder defective
Cabling or connections between position encoder and GRB module
Internal parameter setting
Rectification Check cabling and connections between position encoder and GRB module
Follow standard procedure.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.02: FW Communication Bit B09
Related Parameters Related IO

16/89 Version LSCI6570 Troubleshooting Manual



Panel Text Ground Overcurrent
Description Sine filter ground current is exceeding trip limit.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.17: FW1 Current Bit b14
Related Parameters Related IO

Panel Text IGCT Overtemp


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.24: FW1 Switching Bit b06
Related Parameters Related IO

Panel Text IGCT Supervision


Description IGCT (semiconductor) supervision active.
Causes
Rectification
FaultClass INU FC2
FaultClass ARU
Fault Word 183.09: FW2 CntrlHardware Bit B13
Related Parameters Related IO

Panel Text INT: Fault Class 1


Description INT: Fault class 1 fault pending in one of the INT boards.
Causes Any fault INT fault pending
Rectification Check fault buffer for related INT faults
FaultClass INU FC1
FaultClass ARU
Fault Word 183.32: FW Generic Faults Bit B02
Related Parameters Related IO

Panel Text INT: Fault Class 2


Description INT: Fault class 2 fault pending on an INT board.
Causes Any fault class 2 pending on an INT board.
Rectification Check fault buffer for related INT faults
FaultClass INU FC2
FaultClass ARU
Fault Word 183.32: FW Generic Faults Bit B03
Related Parameters Related IO

Panel Text INT: MCB Trip Req


Description INT: MCB open command via INT – board.
Causes Application or Control has requested to open the MCB via INT
Rectification This is not a fault but only information as consequence of another fault
FaultClass INU FC1
FaultClass ARU
Fault Word 183.32: FW Generic Faults Bit B11
Related Parameters Related IO

LSCI6570 ACS6000 SD 17/89


 
Panel Text INT0 1STFL:ASYMCUR
Description First fault of INT:
Sum of current is exceeding the limits (27% of CVMI maximum measurable current)
Causes Earth fault
Communication faulty
Rectification Check the main circuit isolation
FaultClass INU FC1
FaultClass ARU
Fault Word 183.37: EPLD0 First Fault Bit B22
Related Parameters Related IO

Panel Text INT0 1STFL:COMER A


Description First fault of INT: Communication error in PPCC link A
Causes PPCC link A between AMC or PUB and INT is faulty
Rectification Verify the optical fiber connection between AMC or PUB and INT.
Verify the overall cleaness of the cabinet.
Dust can create trouble in optical connections
Verify that optical fiber are not bended or broken
Dust can create trouble in optical connections
Verify that optical fiber are not bended or broken
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.37: EPLD0 First Fault Bit B01
Related Parameters Related IO

Panel Text INT0 1STFL:COMER B


Description First fault of INT: Communication error in PPCC link B
Causes PPCC link B between AMC or PUB and INT is faulty
Rectification Verify the optical fiber connection between AMC or PUB and INT.
Verify the overall cleaness of the cabinet.
Dust can create trouble in optical connections
Verify that optical fiber are not bended or broken
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.37: EPLD0 First Fault Bit B02
Related Parameters Related IO

Panel Text INT0 1STFL:COMER C


Description First fault of INT: Communication error in PPCC link C
Causes PPCC link C between AMC or PUB and INT is faulty
Rectification Verify the optical fiber connection between AMC or PUB and INT.
Verify the overall cleaness of the cabinet.
Dust can create trouble in optical connections
Verify that optical fiber are not bended or broken
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.37: EPLD0 First Fault Bit B03
Related Parameters Related IO

Panel Text INT0 1STFL:COMER D


Description First fault of INT: Communication error in PPCC link D
Causes PPCC link D between AMC or PUB and INT is faulty
Rectification Verify the optical fiber connection between AMC or PUB and INT.
Verify the overall cleaness of the cabinet.
Dust can create trouble in optical connections
Verify that optical fiber are not bended or broken
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.37: EPLD0 First Fault Bit B04
Related Parameters Related IO

18/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT0 1STFL:COMER FT
Description First fault of INT: Communication error in Firing Through link
Causes - Fibre optic connected to FT receiver is damaged
- Transmitting INT or PINT are disturbed by EMC
Rectification Ceck fiber optic, change if damaged.
Verify the EMC protection sealings are all installed properly
FaultClass INU FT
FaultClass ARU FT
Fault Word 183.37: EPLD0 First Fault Bit B05
Related Parameters Related IO

Panel Text INT0 1STFL:CTRVLU L


Description First fault of INT:
Control fault in lower VLU
Causes - Damaged VLSCD in VLU
- Damaged fibre optic between VLU and INT
Rectification - Check the part of the VLU which is conected to the DC- in respect of fibre optic connections
and damages
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.37: EPLD0 First Fault Bit B23
Related Parameters Related IO

Panel Text INT0 1STFL:CTRVLU U


Description First fault of INT:
Control fault in upper VLU
Causes - Damaged VLSCD in VLU
- Damaged fibre optic between VLU and INT
Rectification - Check the part of the VLU which is conected to the DC+ in respect of fibre optic connections
and damages
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.37: EPLD0 First Fault Bit B24
Related Parameters Related IO

Panel Text INT0 1STFL:EX TRIP


Description First fault of INT:
Stop modulation command received via INT to INT link
Causes External fault generated by another component (ARU or INU)
Rectification Check fault on other units, because this fault is generated external.
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.37: EPLD0 First Fault Bit B39
Related Parameters Related IO

Panel Text INT0 1STFL:EX TRIP FT


Description First fault of INT:
Firing Through command received vie INT to INT link
Causes External fault generated by another component (ARU or INU)
Rectification Check fault on other units, because this fault is generated external.
FaultClass INU FT
FaultClass ARU FT
Fault Word 183.37: EPLD0 First Fault Bit B37
Related Parameters Related IO

LSCI6570 ACS6000 SD 19/89


 
Panel Text INT0 1STFL:EX TRIPMCB
Description First fault of INT:
Command to open MCB via INT to INT link received
Causes External fault generated by another component (ARU or INU)
Rectification Check fault on other units, because this fault is generated external.
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.37: EPLD0 First Fault Bit B38
Related Parameters Related IO

Panel Text INT0 1STFL:FT OC


Description First fault of INT:
Firing Through due to overcurrent
Causes Main component as IGCT or Diode in short circuit.
Short on tha power circuit
Rectification - Check fault logger of all units, in case of an short circuit also other units could be damaged
- Check IGCT and Diodes in respect of a short circuit
- Check LED on IGCT\'s
FaultClass INU FT
FaultClass ARU FT
Fault Word 183.37: EPLD0 First Fault Bit B33
Related Parameters 186.01 Related IO

Panel Text INT0 1STFL:FT OV DC


Description First fault of INT:
Firing Through due to overvoltage
Causes To high voltage on the DC bus
exceeding the Overvoltage Firing Trough limit
Rectification - Check fault logger of all units
- Check the operating point e.g. braking (160.18/161.02)
- Check DC link values (160.11/160.13/160.09) and compare them to the trip limits (186.02)
- Check network values (161.04)
FaultClass INU FT
FaultClass ARU FT
Fault Word 183.37: EPLD0 First Fault Bit B32
Related Parameters 186.02 Related IO

Panel Text INT0 1STFL:FTC FT


Description First fault of INT:
INT has received Firing Through command via FT Link
Causes - Short circuit detected by another INT or PINT
- FT started by Control
Rectification Check fault on other units, because this fault is generated external.
FaultClass INU FT
FaultClass ARU FT
Fault Word 183.37: EPLD0 First Fault Bit B06
Related Parameters Related IO

Panel Text INT0 1STFL:INT-INT


Description First fault of INT:
Communication error in INT to INT link
Causes - Damaged fibre optics
Rectification - Check the connection of the fibre optic
- Check the fibre optic in respect of bending and damages
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.37: EPLD0 First Fault Bit B27
Related Parameters Related IO

20/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT0 1STFL:LSU DIO1
Description First fault of INT:
LSU diode failure
Causes Broken diode in LSU
Rectification - Check diodes in LSU regarding short circuit
- Check also in other UNIT\'s the semiconductors
FaultClass INU FT
FaultClass ARU FT
Fault Word 183.37: EPLD0 First Fault Bit B13
Related Parameters Related IO

Panel Text INT0 1STFL:LSU DIO2


Description First fault of INT:
LSU diode failure
Causes Broken diode in LSU
Rectification - Check diodes in LSU regarding short circuit
- Check also in other UNIT\'s the semiconductors
FaultClass INU FT
FaultClass ARU FT
Fault Word 183.37: EPLD0 First Fault Bit B14
Related Parameters Related IO

Panel Text INT0 1STFL:OV DC L


Description First fault of INT:
Overvoltage in lower DC link half
Causes - Overvoltage in DC circuit
- Fiber optic link from CVMII to INT faulty
- Defective circuit board
Rectification - Check fault logger of all units
- Check the operating point e.g. braking (160.18/161.02)
- Check DC link values (160.11/160.13/160.09) and compare them to the trip limits (186.02)
- Check network values (161.04)
FaultClass INU FC1
FaultClass ARU
Fault Word 183.37: EPLD0 First Fault Bit B19
Related Parameters 186.02 186.03 186.04 Related IO

Panel Text INT0 1STFL:OV DC U


Description First fault of INT:
Overvoltage in upper DC link half
Causes - Overvoltage in DC circuit
- Fiber optic link from CVMII to INT faulty
- Defective circuit board
Rectification - Check fault logger of all units
- Check the operating point e.g. braking (160.18/161.02)
- Check DC link values (160.11/160.13/160.09) and compare them to the trip limits (186.02)
- Check network values (161.04)
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.37: EPLD0 First Fault Bit B20
Related Parameters 186.01 186.02 186.03 186.04 Related IO

LSCI6570 ACS6000 SD 21/89


 
Panel Text INT0 1STFL:OVERCURR
Description First fault of INT:
Overcurrent
Causes - Overcurrent in a phase
- Poor cable grounding or shielding between LEM and CVMI
- CVMI failure
- Current scaling print (SCA on CVMI) failure
Rectification - Check IGCT\'s and Diodes in respect of short circuit
- Check current (160.07) compared to the trip value (186.01)
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.37: EPLD0 First Fault Bit B21
Related Parameters 186.01 Related IO

Panel Text INT0 1STFL:PF CVMI


Description First fault of INT:
Auxiliary power failure on CVMI
Causes - Damaged CVMI
- Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.37: EPLD0 First Fault Bit B08
Related Parameters Related IO

Panel Text INT0 1STFL:PF INT


Description First fault of INT:
Auxiliary power failure on INT
Causes - Damaged INT
- Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.37: EPLD0 First Fault Bit B07
Related Parameters Related IO

Panel Text INT0 1STFL:PF VLU


Description First fault of INT: VLU GUSP power failure
Causes - Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.37: EPLD0 First Fault Bit B12
Related Parameters Related IO

Panel Text INT0 1STFL:PHA PSU 1


Description First fault of INT:
GUSP power failure
Causes - Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.37: EPLD0 First Fault Bit B09
Related Parameters Related IO

22/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT0 1STFL:PHA PSU 2
Description First fault of INT:
GUSP power failure
Causes - Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.37: EPLD0 First Fault Bit B10
Related Parameters Related IO

Panel Text INT0 1STFL:PHA PSU 3


Description First fault of INT:
GUSP power failure
Causes - Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.37: EPLD0 First Fault Bit B11
Related Parameters Related IO

Panel Text INT0 1STFL:SC EXT L


Description First fault of INT:
Short circuit detected by di/dt measurement device (FSCD or VLSCD) in lower commutation
group
Causes - Converter short circuit on another unit (ARU or INU)
- Defective circuit board
Rectification - Check fault logger of other units because the fault is external. So one other unit should have a
fault which is detected by his own.
- Check diodes and IGCT\'s respecting short circuit.
- Concentrate on the parts which are connected to the DC- but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.37: EPLD0 First Fault Bit B17
Related Parameters 186.01 191.08 Related IO

Panel Text INT0 1STFL:SC EXT U


Description First fault of INT:
Short circuit detected by di/dt measurement device (FSCD or VLSCD) in upper commutation
group
Causes - Converter short circuit on another unit (ARU or INU)
- Defective circuit board
Rectification - Check fault logger of other units because the fault is external. So one other unit should have a
fault which is detected by his own.
- Check diodes and IGCT\'s respecting short circuit.
- Concentrate on the parts which are connected to the DC+ but ceck also the others
FaultClass INU
FaultClass ARU
Fault Word 183.37: EPLD0 First Fault Bit B18
Related Parameters 186.01 191.08 Related IO

LSCI6570 ACS6000 SD 23/89


 
Panel Text INT0 1STFL:SC INU L
Description First fault of INT:
Short circuit detected by di/dt measurement device (FSCD or VLSCD) in lower commutation
group
Causes - Converter short circuit
- Defective circuit board
Rectification - Check diodes and IGCT\'s in respect of short circuit in this unit
- Concentrate on the parts which are connected to the DC- but check also the others.
FaultClass INU FT
FaultClass ARU
Fault Word 183.37: EPLD0 First Fault Bit B15
Related Parameters 186.01 191.08 Related IO

Panel Text INT0 1STFL:SC INU U


Description First fault of INT:
For discharge units with IGCTs:
Short-circuit detected by di/dt measurement device (FSCD or VLSCD) in upper VLU/DIU/BCU
system.
For discharge units with relay:
Short-circuit detected by di/dt measurement device (FSCD or VLSCD) in discharge relay (DIU)
system.
Causes - Converter short circuit
- Defective circuit board
Rectification - Check diodes and IGCTs in respect of short circuit in this unit
- Concentrate on the parts which are connected to the DC+ but check also the others.
FaultClass INU FT
FaultClass ARU
Fault Word 183.37: EPLD0 First Fault Bit B16
Related Parameters 186.01 191.08 Related IO

Panel Text INT0 AuxiliaryPower


Description Auxiliary voltage supply malfunction (SYN, CVMI or INT boards)
Causes Aux power failure
Fiber optic link faulty
Defective SYN, CVMI or INT board
GUSP failure
Rectification Check auxiliary supply and fuses
Check auxiliary supply wiring
Check fiber optic cables and connections
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.07: FW CntrlHardware Bit B01
Related Parameters Related IO

Panel Text INT0 Block Modulati


Description INT0 Modulation stopped, firing through in other drive.
Causes Reason should be a FT in other drive. See firing through, additionally malfunction of the INT-INT
link.
Rectification Check if other drive did a FT.
See firing through and INT-INT link.
FaultClass INU FC2
FaultClass ARU
Fault Word 183.35: FW Other Bit B08
Related Parameters Related IO

24/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT0 Curr Asym High
Description Sum of motor three phase current exceeds 27% of the maximum measurable CVMI current.
Causes Earth fault
Defective circuit board
Communication faulty
Firing-through
Rectification Check for other related faults
Check main circuit
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.16: FW Current Bit B04
Related Parameters 186.12 Related IO

Panel Text INT0 DI/DT SuperVi


Description Di/dt measurement malfunction (FSCF or VLSCD)
Causes - Fiber optic link from FSCD- to INT-board faulty
- FSCD- or INT-board failure
- Internal parameter setting
Rectification Check fiber optic cables and connections to FSCD-board
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.20: FW Short Circuit Bit B07
Related Parameters 186.01 191.08 Related IO

Panel Text INT0 Firing-Through


Description Fault with Firing-Through occured.
Causes Firing-through via FT Link (Other INU/ARU), Overvoltage, Overcurrent, Phase module short-
circuit , VLU short-circuit, LSU short-circuit, Arcguard firing-through, or CBU (DC-Link).
Rectification Find firing-through root-cause.
Acknowledge firing-through fault through parameter 16.24
FaultClass INU FC1
FaultClass ARU
Fault Word 183.85: Other 1 Bit B08
Related Parameters Related IO

Panel Text INT0 FT Link


Description Firing through (FT) link communication failure
Causes - Fiber optic link between INT-boards of two power stages faulty
- INT-board failure
Rectification Check fiber optic cables and connections status
Ceck int board HW status.
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.02: FW Communication Bit B03
Related Parameters Related IO

Panel Text INT0 INT2INT FT


Description INT 0 has been tripped with FT command because of fault in the other INT.
Causes 1) Other INT tripped.
2) Link malfunction.
3) INT malfunction.
Rectification 1) Check if other drive had a fault.
2) See INT-INT link.
3) Check INT board and fibre optic link.
FaultClass INU FT
FaultClass ARU ND
Fault Word 183.36: FW1 Other Bit B08
Related Parameters Related IO

LSCI6570 ACS6000 SD 25/89


 
Panel Text INT0 INT2INT MCB
Description INT0 tripped opened MCB, due to trip in another INT
Causes Other INT tripped.
Link malfunction.
INT malfunction.
Rectification Check if other drive had a fault.
See INT-INT link.
Check INT board and fibre optic link.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.36: FW1 Other Bit B04
Related Parameters Related IO

Panel Text INT0 INT2INT Trip


Description INT0 has tripped due to trip in another INT.
Causes Other INT tripped.
Link malfunction.
INT malfunction.
Rectification Check if other drive had a fault.
See INT-INT link.
Check INT board and fibre optic link.
FaultClass INU FC2
FaultClass ARU
Fault Word 183.36: FW1 Other Bit B00
Related Parameters Related IO

Panel Text INT0 INTtoINT Link


Description Fault in communication between INT0 and INT1
Causes Fiber optic from INT1 to INT0
Rectification Check fiber optic cables between INT0 and INT1
FaultClass INU FC2
FaultClass ARU
Fault Word 183.03: FW1 Communication Bit B00
Related Parameters Related IO

Panel Text INT0 Link C Lost


Description Communication fault in link C between interface board and ADCVI
Causes Ensure that the ADCVI board and the INT board in the communication link each have their
power and the PPCS fiber optic cables are secure. The ADCVI board converts the analogue
measurement signals of current and voltage into digital signals. The digital signals are
transmitted via fiber optic cables (PPCS) to the INT board. The ADCVI board may be the cause
of the fault. The INT board is used as a measurement interface between the ADCVI board. The
INT board receives the intermediate link DC voltage and the inverter, sine filter and ground
current signals from the ADCVI board. The communication between the INT board and the
ADCVI board is made with fiber optic cables. The logic circuit called EPLD on the INT board is
dealing with all protection signals and SW control signals. The INT board may be the cause of
the fault.
Rectification The communication link should work properly if all the settings and connectors are secure. To
first test if the ADCVI board is the cause of the fault, temporarily connect a replacement ADCVI
board to the unit. Ensure the SVA and SCA subprints are compatible with the ACS converter
type. If the fault is not removed, test if the INT board is the cause of the fault, temporarily connect
a replacement INT board to the unit. Ensure the INT board is identical to the board being
replaced and check the compatibility of the EPLD memory.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.03: FW1 Communication Bit B07
Related Parameters Related IO

26/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT0 Link D Lost
Description Communication fault in link D between interface board and ADCVI
Causes Ensure that the ADCVI board and the INT board in the communication link each have their
power and the PPCS fiber optic cables are secure. The ADCVI board converts the analogue
measurement signals of current and voltage into digital signals. The digital signals are
transmitted via fiber optic cables (PPCS) to the INT board. The ADCVI board may be the cause
of the fault. The INT board is used as a measurement interface between the ADCVI board. The
INT board receives the intermediate link DC voltage and the inverter, sine filter and ground
current signals from the ADCVI board. The communication between the INT board and the
ADCVI board is made with fiber optic cables. The logic circuit called EPLD on the INT board is
dealing with all protection signals and SW control signals. The INT board may be the cause of
the fault.
Rectification Check the connectors of the VLSCD2 board are secure. The communication link should work
properly if all the connectors are secure. Test if the VLSCD2 board is the cause of the fault,
temporarily connect a replacement VLSCD2 board to the unit. Test if the INT board is the cause
of the fault, temporarily connect a replacement INT board to the unit. Ensure the INT board is
identical to the board being replaced and check the compatibility of the EPLD memory.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.03: FW1 Communication Bit B08
Related Parameters Related IO

Panel Text INT0 Link E Lost


Description Communication fault in link E between interface board and ADCVI
Causes Ensure that the ADCVI board and the INT board in the communication link each have their
power and the PPCS fiber optic cables are secure. The ADCVI board converts the analogue
measurement signals of current and voltage into digital signals. The digital signals are
transmitted via fiber optic cables (PPCS) to the INT board. The ADCVI board may be the cause
of the fault. The INT board is used as a measurement interface between the ADCVI board. The
INT board receives the intermediate link DC voltage and the inverter, sine filter and ground
current signals from the ADCVI board. The communication between the INT board and the
ADCVI board is made with fiber optic cables. The logic circuit called EPLD on the INT board is
dealing with all protection signals and SW control signals. The INT board may be the cause of
the fault.
Rectification The communication link should work properly if all the settings and connectors are secure. To
first test if the ADCVI board is the cause of the fault, temporarily connect a replacement ADCVI
board to the unit. Ensure the SVA and SCA subprints are compatible with the ACS1000
converter type. If the fault is not removed, test if the INT board is the cause of the fault,
temporarily connect a replacement INT board to the unit. Ensure the INT board is identical to the
board being replaced and check the compatibility of the EPLD memory.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.03: FW1 Communication Bit B09
Related Parameters Related IO

Panel Text INT0 LSU DiodeFault


Description EAF board installed in LSU has detected a danage in the LSU
Causes Broken LSU diode
Rectification Check LSU hardware by measuring the diodes with a multimeter.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.07: FW CntrlHardware Bit B05
Related Parameters Related IO

LSCI6570 ACS6000 SD 27/89


 
Panel Text INT0 MF I2I Link
Description Communication fault in INT to INT link between Master and Follower detected on INT0
Causes Only on ACS6000 FRD
Fibre optics or connected boards faulty
Rectification Check fiber optic cables and connections
FaultClass INU FC2
FaultClass ARU
Fault Word 183.03: FW1 Communication Bit B10
Related Parameters Related IO

Panel Text INT0 Overcurrent


Description Overcurrent detected by CVMI.
Causes Overcurrent in a phase
Poor cable grounding or shielding between LEM and CVMI
CVMI failure
Current scaling ptint (SCA on CVMI) failure
Rectification Use datalogger to check if there was too high current
Check wires between CVMI and LEM
Check LEM
Check current scaling print on CVMI
Check for other related faults
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.16: FW Current Bit B05
Related Parameters 186.01 Related IO

Panel Text INT0 Overcurrent FT


Description Firing through active, too high current detected by INT0, 1st Inverter.
Causes Overcurrent in a phase
Current measurement problem
Unstable control
Saturated transformer
Rectification Use datalogger to check if current was too high
Check current measurement chain
FaultClass INU FT
FaultClass ARU
Fault Word 183.18: FW2 Current Bit B00
Related Parameters 186.01 Related IO

Panel Text INT0 Overcurrent FT


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.18: FW2 Current Bit 0
Related Parameters Related IO

28/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT0 Overvoltage
Description DC Overvoltage detected by INT0 board, 1st Inverter.
Causes Overvoltage in DC circuit
Fiber optic link from ADCVI to INT faulty
Defective circuit board
Rectification Check if mains supply voltage is within the limits
Is ARU modulating
Check the situation (e.g. braking)
Check for other related faults
Check parameter 186.02
Check value 160.09
Check parmeter settings respecting braking equipment (Grp.192)
Use datalogger to check if there was too high voltage
Check IOV fiber between CVMI and INT
Check CVMI
Check voltage scaling print (SVA)
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.12: FW DC LinkVolt Bit B05
Related Parameters 186.02 186.03 186.04 Related IO

Panel Text INT0 Overvoltage FT


Description Firing Through because of too high DC link voltage detected by CVMI
Causes Overvoltage in DC link
Fiber optic failure (IOV)
CVMI board failure
Voltage scaling board (SVA on CVMI) failure
Rectification Check if mains supply voltage is within the limits
Is ARU modulating
Check the situation (e.g. braking)
Check for other related faults
Check parameter 186.02
Check value 160.09
Check parmeter settings respecting braking equipment (Grp.192)
Use datalogger to check if there was too high voltage
Check IOV fiber between CVMI and INT
Check CVMI
Check voltage scaling print (SVA)
FaultClass INU FT
FaultClass ARU
Fault Word 183.13: FW1 DC LinkVolt Bit B08
Related Parameters 186.02 186.03 186.04 Related IO

Panel Text INT0 PHA PSU AuxPwr


Description INT0: PSU auxiliary voltage supply malfunction in one inverter phase.
Causes Aux power failure
Fiber optic link faulty
GUSP failure
Rectification Check auxiliary supply and fuses
Check auxiliary supply wiring
Check fiber optic cables and connections
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.07: FW CntrlHardware Bit B02
Related Parameters Related IO

LSCI6570 ACS6000 SD 29/89


 
Panel Text INT0 PPCS Link
Description INT has detected a problem in at least one of the PPCS communication links
Causes - Fiber optic link from CVMI, AMC3, PUBPFF or SYN to INT faulty
- No Aux power on CVMI, or SYN
- Defect CVMI or SYN
Rectification Check fiber optic cables and connections clean eventual dust on it.
Change CVMI or SYN board
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.02: FW Communication Bit B02
Related Parameters Related IO

Panel Text INT0 PSU1


Description PSU1 failure
Causes Power supply coming from the auxiliary power supply into the PSU board is faulty.
Faulty INTerface board may cause the fault.
Rectification Check the output voltage of the auxiliary power supply supplying the Gate Unit Power Supply
GUSP. Check that the input voltage of the GUSP is OK. The Gate Unit Power Supply indicates a
fault either when its supply voltage drops below 21.5V or when its internal chopper transformer is
making switchings only in one of the two primary windings. Check the INTerface board.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.07: FW CntrlHardware Bit B08
Related Parameters Related IO

Panel Text INT0 PSU2


Description PSU 2 failure
Causes Power supply coming from the auxiliary power supply into the GUSP board is faulty.
Faulty INTerface board may cause the fault.
Rectification Check the output voltage of the auxiliary power supply supplying the Gate Unit Power Supply
GUSP. Check that the input voltage of the GUSP is OK. The Gate Unit Power Supply indicates a
fault either when its supply voltage drops below 21.5V or when its internal chopper transformer is
making switchings only in one of the two primary windings. Check the INTerface board.
FaultClass INU
FaultClass ARU
Fault Word 183.07: FW CntrlHardware Bit B09
Related Parameters Related IO

Panel Text INT0 ShortCircuit


Description Short circuit detected by di/dt measurement device (FSCD or VLSCD), or firing-through.
Causes Converter short circuit
Defective circuit board
Rectification Check diodes and IGCTs to locate short circuit in this unit
Check also the other units
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.20: FW Short Circuit Bit B01
Related Parameters 191.08 Related IO

Panel Text INT0 ShortRecDiod


Description Detected a shortend rectifier diode (from INT0)
Causes Broken rectifier diode
Rectification - Measure rectifier diodes. And substitute the shorted one
- Contact ABB service organization
FaultClass INU FC1
FaultClass ARU Not Appl.
Fault Word 183.20: FW Short Circuit Bit B14
Related Parameters 191.08 Related IO

30/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT0 VLU Control
Description INT0: VLU of INT0 was switched on but no feedback was received.
Causes Fibre optic link to VLU IGCT interrupted
Broken VLU Gate unit
Broken VLU VLSCD board
Rectification Check IGCT status Leds
Check VLSCD Board connections
FaultClass INU FC2
FaultClass ARU
Fault Word 183.07: FW CntrlHardware Bit B04
Related Parameters Related IO

Panel Text INT0 VLU ShortCirc


Description Short circuit in DIU/VLU/BCU circuit
(DIU/VLU/BCU feedback is not matching the control signal)
Causes - Short circuit inside the DIU/VLU/BCU circuit
- Wrong DIU/VLU/BCU feedback signal connected
Rectification - Verify discharge circuit diodes and igcts, or discharge relay (DIU)
- Verify also other units
FaultClass INU FT
FaultClass ARU
Fault Word 183.20: FW Short Circuit Bit B02
Related Parameters Related IO

Panel Text INT1 1STFL:ASYMCUR


Description First fault of INT:
Sum of current is exceeding the limits
Causes - Earth fault
- Communication faulty
Rectification - Verify the main circuit Isolation
- Verify the current transducer
- Verify the CVMI boad HW connections and status
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B22
Related Parameters Related IO

Panel Text INT1 1STFL:COMER A


Description First fault of INT: Communication error in PPCC link A
Causes PPCC link A between AMC or PUB and INT is faulty
Rectification Verify the optical fiber connection between AMC or PUB and INT.
Verify the overall cleaness of the cabinet.
Dust can create trouble in optical connections
Verify that optical fiber are not bended or broken
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B01
Related Parameters Related IO

Panel Text INT1 1STFL:COMER B


Description First fault of INT: Communication error in PPCC link B
Causes PPCC link B between AMC or PUB and INT is faulty
Rectification Verify the optical fiber connection between AMC or PUB and INT.
Verify the overall cleaness of the cabinet.
Dust can create trouble in optical connections
Verify that optical fiber are not bended or broken
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B02
Related Parameters Related IO

LSCI6570 ACS6000 SD 31/89


 
Panel Text INT1 1STFL:COMER C
Description First fault of INT: Communication error in PPCC link C
Causes PPCC link C between INT and CVMI is faulty
Rectification Verify the optical fiber connection between AMC or PUB and INT.
Verify the overall cleaness of the cabinet.
Dust can create trouble in optical connections
Verify that optical fiber are not bended or broken
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B03
Related Parameters Related IO

Panel Text INT1 1STFL:COMER D


Description First fault of INT: Communication error in PPCC link D
Causes PPCC link D between INT and CVMI is faulty
Rectification Verify the optical fiber connection between AMC or PUB and INT.
Verify the overall cleaness of the cabinet.
Dust can create trouble in optical connections
Verify that optical fiber are not bended or broken
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B04
Related Parameters Related IO

Panel Text INT1 1STFL:COMER FT


Description First fault of INT: Communication error in Firing Through link
Causes - Fibre optic connected to FT receiver is damaged
- Transmitting INT or PINT are disturbed by EMC
Rectification Ceck fiber optic, change if damaged.
Verify the EMC protection sealings are all installed properly
FaultClass INU FT
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B05
Related Parameters Related IO

Panel Text INT1 1STFL:CTRVLU L


Description First fault of INT:
Control fault in lower VLU
Causes - Damaged VLSCD in VLU
- Damaged fibre optic between VLU and INT
Rectification - Check tha part of the VLU which is conected to the DC- respecting to the fibre optic and
damages
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B23
Related Parameters Related IO

Panel Text INT1 1STFL:CTRVLU U


Description First fault of INT:
Control fault in upper VLU
Causes - Damaged VLSCD in VLU
- Damaged fibre optic between VLU and INT
Rectification - Check tha part of the VLU which is conected to the DC+ respecting to the fibre optic and
damages
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B24
Related Parameters Related IO

32/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT1 1STFL:EX TRIP
Description First fault of INT:
Stop modulation command received via INT to INT link
Causes External fault generated by another component (ARU or INU)
Rectification Check fault on other units, because this fault is generated external.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B39
Related Parameters Related IO

Panel Text INT1 1STFL:EX TRIP FT


Description First fault of INT:
Firing Through command received vie INT to INT link
Causes External fault generated by another component (ARU or INU)
Rectification Check fault on other units, because this fault is generated external.
FaultClass INU FT
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B37
Related Parameters Related IO

Panel Text INT1 1STFL:EX TRIPMCB


Description First fault of INT:
Command to open MCB via INT to INT link received
Causes External fault generated by another component (ARU or INU)
Rectification Check fault on other units, because this fault is generated external.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B38
Related Parameters Related IO

Panel Text INT1 1STFL:FT OC


Description First fault of INT:
Firing Through due to overcurrent
Causes Main component as IGCT or Diode in short circuit.
Short on the power circuit
Rectification - Check fault logger of all units, in case of an short circuit also other units could be damaged
- Check IGCT and Diodes in respect of a short circuit
- Check LED on IGCT\'s
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B33
Related Parameters 186.01 Related IO

Panel Text INT1 1STFL:FT OV DC


Description First fault of INT:
Firing Through due to overvoltage
Causes To high voltage on the DC bus
exceeding the Overvoltage Firing Trough limit
Rectification - Check fault logger of all units
- Check the operating point e.g. braking (160.18/161.02)
- Check DC link values (160.11/160.13/160.09) and compare them to the trip limits (186.02)
- Check network values (161.04)
FaultClass INU FT
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B32
Related Parameters 186.02 186.03 186.04 Related IO

LSCI6570 ACS6000 SD 33/89


 
Panel Text INT1 1STFL:FTC FT
Description First fault of INT:
INT has received Firing Through command via FT Link
Causes - Short circuit detected by another INT or PINT
- FT started by Control
Rectification Check fault on other units, because this fault is generated external.
FaultClass INU FT
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B06
Related Parameters Related IO

Panel Text INT1 1STFL:INT-INT


Description First fault of INT:
Communication error in INT to INT link
Causes - Damaged fibre optics
Rectification - Check the connection of the fibre optic
- Check the fibre optic in respect of bending and damages
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B27
Related Parameters Related IO

Panel Text INT1 1STFL:LSU DIO1


Description First fault of INT:
LSU diode failure
Causes Broken diode in LSU
Rectification - Check diodes in LSU regarding short circuit
- Check also in other UNIT\'s the semiconductors
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B13
Related Parameters Related IO

Panel Text INT1 1STFL:LSU DIO2


Description First fault of INT:
LSU diode failure
Causes Broken diode in LSU
Rectification - Check diodes in LSU regarding short circuit
- Check also in other UNIT\'s the semiconductors
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B14
Related Parameters Related IO

Panel Text INT1 1STFL:OV DC L


Description First fault of INT:
Overvoltage in lower DC link half
Causes - Overvoltage in DC circuit
- Fiber optic link from CVMII to INT faulty
- Defective circuit board
Rectification - Check fault logger of all units
- Check the operating point e.g. braking (160.18/161.02)
- Check DC link values (160.11/160.13/160.09) and compare them to the trip limits (186.02)
- Check network values (161.04)
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B19
Related Parameters 186.02 186.03 186.04 Related IO

34/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT1 1STFL:OV DC U
Description First fault of INT:
Overvoltage in upper DC link half
Causes - Overvoltage in DC circuit
- Fiber optic link from CVMII to INT faulty
- Defective circuit board
Rectification - Check fault logger of all units
- Check the operating point e.g. braking (160.18/161.02)
- Check DC link values (160.11/160.13/160.09) and compare them to the trip limits (186.02)
- Check network values (161.04)
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B20
Related Parameters 186.02 186.03 186.04 Related IO

Panel Text INT1 1STFL:OVERCURR


Description First fault of INT:
Overcurrent
Causes - Overcurrent in a phase
- Poor cable grounding or shielding between LEM and CVMI
- CVMI failure
- Current scaling print (SCA on CVMI) failure
Rectification - Check IGCT\'s and Diodes respecting short circuit
- Check current (160.07) compared to the trip value (186.01)
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B21
Related Parameters 186.01 Related IO

Panel Text INT1 1STFL:PF CVMI


Description First fault of INT:
Auxiliary power failure on CVMI
Causes - Damaged CVMI
- Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B08
Related Parameters Related IO

Panel Text INT1 1STFL:PF INT


Description First fault of INT:
Auxiliary power failure on INT
Causes - Damaged INT
- Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B07
Related Parameters Related IO

LSCI6570 ACS6000 SD 35/89


 
Panel Text INT1 1STFL:PF VLU
Description First fault of INT: VLU GUSP power failure
Causes - Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B12
Related Parameters Related IO

Panel Text INT1 1STFL:PHA PSU 1


Description First fault of INT:
GUSP power failure
Causes - Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B09
Related Parameters Related IO

Panel Text INT1 1STFL:PHA PSU 2


Description First fault of INT:
GUSP power failure
Causes - Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B10
Related Parameters Related IO

Panel Text INT1 1STFL:PHA PSU 3


Description First fault of INT:
GUSP power failure
Causes - Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B11
Related Parameters Related IO

Panel Text INT1 1STFL:SC EXT L


Description First fault of INT:
Short circuit detected by di/dt measurement device (FSCD or VLSCD) in lower commutation
group
Causes - Converter short circuit on another unit (ARU or INU)
- Defective circuit board
Rectification - Check fault logger of other units because the fault is external. So one other unit should have a
fault which is detected by his own.
- Check diodes and IGCT\'s respecting short circuit.
- Concentrate on the parts which are connected to the DC- but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B17
Related Parameters 186.01 191.08 Related IO

36/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT1 1STFL:SC EXT U
Description First fault of INT:
Short circuit detected by di/dt measurement device (FSCD or VLSCD) in upper commutation
group
Causes - Converter short circuit on another unit (ARU or INU)
- Defective circuit board
Rectification - Check fault logger of other units because the fault is external. So one other unit should have a
fault which is detected by his own.
- Check diodes and IGCT\'s respecting short circuit.
- Concentrate on the parts which are connected to the DC+ but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B18
Related Parameters 186.01 191.08 Related IO

Panel Text INT1 1STFL:SC INU L


Description First fault of INT:
Short circuit detected by di/dt measurement device (FSCD or VLSCD) in lower commutation
group
Causes - Converter short circuit
- Defective circuit board
Rectification - Check diodes and IGCT\'s in respect of short circuit in this unit
- Concentrate on the parts which are connected to the DC- but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B15
Related Parameters 186.01 191.08 Related IO

Panel Text INT1 1STFL:SC INU U


Description First fault of INT:
Short circuit detected by di/dt measurement device (FSCD or VLSCD) in Upper commutation
group
Causes - Converter short circuit
- Defective circuit board
Rectification - Check diodes and IGCT\'s in respect of short circuit in this unit
- Concentrate on the parts which are connected to the DC+ but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B16
Related Parameters 186.01 191.08 Related IO

Panel Text INT1 1STFL:SC VLU L


Description First fault of INT:
Short circuit in lower VLU
Causes - Short circuit
- Wrong fibre optic cabling
Rectification - Check diodes and IGCT\'s in respect of short circuit in this unit
- Check also the other units
-Concentrate on the parts which are connected to the DC- but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B25
Related Parameters Related IO

LSCI6570 ACS6000 SD 37/89


 
Panel Text INT1 1STFL:SC VLU U
Description First fault of INT:
Short circuit in upper VLU
Causes - Short circuit
- Wrong fibre optic cabling
Rectification - Check diodes and IGCT\'s in respect of short circuit in this unit
- Check also the other units
-Concentrate on the parts which are connected to the DC+ but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.38: EPLD1 First Fault Bit B26
Related Parameters Related IO

Panel Text INT1 AuxiliaryPower


Description Auxiliary voltage supply malfunction (SYN, CVMI or INT boards)
Causes - Aux power failure
- Fiber optic link faulty
- Defective SYN, CVMI or INT board
- GUSP failure
Rectification - Check auxiliary supply and fuses
- Check auxiliary supply wiring
- Check fiber optic cables and connections
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.07: FW CntrlHardware Bit B10
Related Parameters Related IO

Panel Text INT1 Block Modulatio


Description Redundant drive: in case of firing thorough other drive has to block modulation with FC2,
automatic reseting afterwards.
Causes Reason should be a FT in other drive. See firing through, additionally malfunction of the INT-INT
link.
Rectification 1) Check if other drive did a FT.
2) See firing through and INT-INT link.
FaultClass INU FC2
FaultClass ARU ND
Fault Word 183.35: FW Other Bit B09
Related Parameters Related IO

Panel Text INT1 Curr Asym High


Description Sum of motor three phase current exceeds 27% of the maximum measurable CVMI current.
Causes Earth fault
Defective circuit board
Communication faulty
Rectification Check for other related faults
Check main circuit isolation
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.16: FW Current Bit B10
Related Parameters 186.12 Related IO

Panel Text INT1 DI/DT SuperVi


Description Di/dt measurement malfunction (FSCF or VLSCD)
Causes - Fiber optic link from FSCD- to INT-board faulty
- FSCD- or INT-board failure
- Internal parameter setting
Rectification Check fiber optic cables and connections to FSCD-board
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.20: FW Short Circuit Bit B08
Related Parameters 191.08 Related IO

38/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT1 Firing-Through
Description Fault with Firing-Through occured.
Causes Firing-through via FT Link (Other INU/ARU), Overvoltage, Overcurrent, Phase module short-
circuit , VLU short-circuit, LSU short-circuit, Arcguard firing-through, or CBU (DC-Link).
Rectification Find firing-through root-cause.
Acknowledge firing-through fault through parameter 16.24
FaultClass INU FC1
FaultClass ARU
Fault Word 183.85: Other 1 Bit B09
Related Parameters Related IO

Panel Text INT1 FT Link


Description Firing through (FT) link communication failure
Causes - Fiber optic link between INT-boards of two power stages faulty
- INT-board failure
Rectification Check fiber optic cables and connections status
Ceck int board HW status
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.02: FW Communication Bit B05
Related Parameters Related IO

Panel Text INT1 INT2INT FT


Description INT 1 has been tripped with FT command because of fault in the other INT.
Causes 1) Other INT tripped.
2) Link malfunction.
3) INT malfunction.
Rectification 1) Check if other drive had a fault.
2) See INT-INT link.
3) Check INT board and fibre optic link.
FaultClass INU FT
FaultClass ARU ND
Fault Word 183.36: FW1 Other Bit B09
Related Parameters Related IO

Panel Text INT1 INT2INT MCB


Description INT 1 has been tripped with opening MCB command because of fault in the other INT.
Causes 1) Other INT tripped.
2) Link malfunction.
3) INT malfunction.
Rectification 1) Check if other drive had a fault.
2) See INT-INT link.
3) Check INT board and fibre optic link.
FaultClass INU FC1
FaultClass ARU ND
Fault Word 183.36: FW1 Other Bit B05
Related Parameters Related IO

Panel Text INT1 INT2INT Trip


Description INT 1 has been tripped because of fault in the other INT.
Causes 1) Other INT tripped.
2) Link malfunction.
3) INT malfunction.
Rectification 1) Check if other drive had a fault.
2) See INT-INT link.
3) Check INT board and fibre optic link.
FaultClass INU FC2
FaultClass ARU ND
Fault Word 183.36: FW1 Other Bit B01
Related Parameters Related IO

LSCI6570 ACS6000 SD 39/89


 
Panel Text INT1 INTtoINT Link
Description Fault in communication between INT0 and INT1
Causes - Fiber optic from INT1 to INT0
Rectification - Check fiber optic cables between INT0 and INT1
FaultClass INU FC2
FaultClass ARU ND
Fault Word 183.03: FW1 Communication Bit B01
Related Parameters Related IO

Panel Text INT1 LSU DiodeFault


Description EAF board installed in LSU has detected a damage in the LSU
Causes Broken LSU diode
Rectification Check LSU hardware.
Verify the diode conductivity with a multimeter
FaultClass INU FC1
FaultClass ARU Not Appl.
Fault Word 183.07: FW CntrlHardware Bit B14
Related Parameters Related IO

Panel Text INT1 Overcurrent


Description Overcurrent detected by CVMI
Causes - Overcurrent in a phase
- Poor cable grounding or shielding between LEM and CVMI
- CVMI failure
- Current scaling ptint (SCA on CVMI) failure
Rectification - Use datalogger to check if there was too high current
- Check wires between CVMI and LEM
- Check LEM
- Check current scaling print on CVMI
- Check for other related faults
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.16: FW Current Bit B11
Related Parameters 186.01 Related IO

Panel Text INT1 Overcurrent FT


Description Firing through because of too high current
Causes - Overcurrent in a phase
- Curernt measurement problem
- Unstable control
Rectification - Use datalogger to check if current was too high
- Check current measurement chain
FaultClass INU FT
FaultClass ARU ND
Fault Word 183.18: FW2 Current Bit B01
Related Parameters 186.01 Related IO

40/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT1 Overvoltage
Description DC-overvoltage detected by INT1 board in the second INU
Causes - Overvoltage in DC circuit
- Fiber optic link from ADCVI to INT faulty
- Defective circuit board
Rectification - SW overvoltage faults should be triggered as well
- check SVA subprint
- check optic link between CVMI and interface board
- Check if mains supply voltage is within the limits
- Is ARU modulating
- Check the situation (e.g. braking)
- Check for other related faults
- Check parameter 186.02
- Check value 160.09
- Check parmeter settings respecting braking equipment (Grp.192)
- Use datalogger to check if there was too high voltage
- Check IOV fiber between CVMI and INT
- Check CVMI
- Check voltage scaling print (SVA)
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.12: FW DC LinkVolt Bit B10
Related Parameters 186.02 186.03 186.04 Related IO

Panel Text INT1 Overvoltage FT


Description Firing Through because of too high DC link voltage detected by CVMI
Causes - Overvoltage in DC link
- Fiber optic failure (IOV)
- CVMI board failure
- Voltage scaling board (SVA on CVMI) failure
Rectification - Use datalogger to check if there was too high voltage
- Check IOV fiber between CVMI and INT
- Check CVMI
- Check voltage scaling print (SVA)
FaultClass INU FT
FaultClass ARU ND
Fault Word 183.13: FW1 DC LinkVolt Bit B09
Related Parameters 186.02 186.03 186.04 Related IO

Panel Text INT1 PHA PSU AuxPwr


Description Auxiliary voltage supply malfunction in gate unit supply power (PSU)
Causes - Aux power failure
- Fiber optic link faulty
- GUSP failure
Rectification - Check auxiliary supply and fuses
- Check auxiliary supply wiring
- Check fiber optic cables and connections
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.07: FW CntrlHardware Bit B07
Related Parameters Related IO

LSCI6570 ACS6000 SD 41/89


 
Panel Text INT1 PPCS Link
Description INT has detected a problem in at least one of the PPCS communication links
Causes - Fiber optic link from CVMI, AMC3, PUBPFF or SYN to INT faulty
- No Aux power on CVMI, or SYN
- Defect CVMI or SYN
Rectification Check fiber optic cables and connections clean eventual dust on it.
Change CVMI or SYN board
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.02: FW Communication Bit B04
Related Parameters Related IO

Panel Text INT1 ShortCircuit


Description Short circuit detected by di/dt measurement device (FSCD or VLSCD)
Causes - Converter short circuit
- Defective circuit board
Rectification - Check diodes and IGCT\'s finding short circuit in this unit
- Check also the other units
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.20: FW Short Circuit Bit B04
Related Parameters 186.01 Related IO

Panel Text INT1 VLU Control


Description ACS 6000: VLU of INT1 was switched on but no feedback was received
Causes - Fibre optic link to VLU IGCT interrupted
- Broken VLU Gate unit
- Broken VLU VLSCD board
Rectification Check IGCT status Leds
Check VLSCD Board connections
FaultClass INU FC2
FaultClass ARU Not Appl.
Fault Word 183.07: FW CntrlHardware Bit B13
Related Parameters Related IO

Panel Text INT1 VLU ShortCirc


Description Short circuit in VLU circuit (feedback from VLU is not matching control signal)
Causes - Short circuit inside the VLU
- Wrong VLU feedback signal connected
Rectification - Check diodes and IGCT\'s finding short circuit in this unit
- Check also the other units
FaultClass INU FT
FaultClass ARU Not Appl.
Fault Word 183.20: FW Short Circuit Bit B05
Related Parameters Related IO

Panel Text INT2 1STFL:ASYMCUR


Description First fault of INT:
Sum of current is exceeding the limits
Causes - Earth fault
- Communication faulty
Rectification - Verify the main circuit Isolation
- Verify the current transducer
- Verify the CVMI boad HW connections and status
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B22
Related Parameters Related IO

42/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT2 1STFL:COMER A
Description First fault of INT: Communication error in PPCC link A
Causes PPCC link A between AMC or PUB and INT is faulty
Rectification Verify the optical fiber connection between AMC or PUB and INT.
Verify the overall cleaness of the cabinet.
Dust can create trouble in optical connections
Verify that optical fiber are not bended or broken
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B01
Related Parameters Related IO

Panel Text INT2 1STFL:COMER B


Description First fault of INT: Communication error in PPCC link B
Causes PPCC link B between AMC or PUB and INT is faulty
Rectification Verify the optical fiber connection between AMC or PUB and INT.
Verify the overall cleaness of the cabinet.
Dust can create trouble in optical connections
Verify that optical fiber are not bended or broken
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B02
Related Parameters Related IO

Panel Text INT2 1STFL:COMER C


Description First fault of INT: Communication error in PPCC link C
Causes PPCC link C between INT and CVMI is faulty
Rectification Verify the optical fiber connection between AMC or PUB and INT.
Verify the overall cleaness of the cabinet.
Dust can create trouble in optical connections
Verify that optical fiber are not bended or broken
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B03
Related Parameters Related IO

Panel Text INT2 1STFL:COMER D


Description First fault of INT: Communication error in PPCC link D
Causes PPCC link D between INT and CVMI is faulty
Rectification Verify the optical fiber connection between AMC or PUB and INT.
Verify the overall cleaness of the cabinet.
Dust can create trouble in optical connections
Verify that optical fiber are not bended or broken
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B04
Related Parameters Related IO

Panel Text INT2 1STFL:COMER FT


Description First fault of INT: Communication error in Firing Through link
Causes - Fibre optic connected to FT receiver is damaged
- Transmitting INT or PINT are disturbed by EMC
Rectification Ceck fiber optic, change if damaged.
Verify the EMC protection sealings are all installed properly
FaultClass INU FT
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B05
Related Parameters Related IO

LSCI6570 ACS6000 SD 43/89


 
Panel Text INT2 1STFL:CTRVLU L
Description First fault of INT:
Control fault in lower VLU
Causes - Damaged VLSCD in VLU
- Damaged fibre optic between VLU and INT
Rectification - Check the part of the VLU which is conected to the DC- in respect of fibre optic connections
and damages
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B23
Related Parameters Related IO

Panel Text INT2 1STFL:CTRVLU U


Description First fault of INT:
Control fault in upper VLU
Causes - Damaged VLSCD in VLU
- Damaged fibre optic between VLU and INT
Rectification - Check the part of the VLU which is conected to the DC+ in respect of fibre optic connections
and damages
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B24
Related Parameters Related IO

Panel Text INT2 1STFL:EX TRIP


Description First fault of INT:
Stop modulation command received via INT to INT link
Causes External fault generated by another component (ARU or INU)
Rectification Check fault on other units, because this fault is generated external.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B39
Related Parameters Related IO

Panel Text INT2 1STFL:EX TRIP FT


Description First fault of INT:
Firing Through command received vie INT to INT link
Causes External fault generated by another component (ARU or INU)
Rectification Check fault on other units, because this fault is generated external.
FaultClass INU FT
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B37
Related Parameters Related IO

Panel Text INT2 1STFL:EX TRIPMCB


Description First fault of INT:
Command to open MCB via INT to INT link received
Causes External fault generated by another component (ARU or INU)
Rectification Check fault on other units, because this fault is generated external.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B38
Related Parameters Related IO

44/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT2 1STFL:FT OC
Description First fault of INT:
Firing Through due to overcurrent
Causes Main component as IGCT or Diode in short circuit.
Short on the power circuit
Rectification - Check fault logger of all units, in case of an short circuit also other units could be damaged
- Check IGCT and Diodes in respect of a short circuit
- Check LED on IGCT\'s
FaultClass INU FT
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B33
Related Parameters 186.01 Related IO

Panel Text INT2 1STFL:FT OV DC


Description First fault of INT:
Firing Through due to overvoltage
Causes To high voltage on the DC bus
exceeding the Overvoltage Firing Trough limit
Rectification - Check fault logger of all units
- Check the operating point e.g. braking (160.18/161.02)
- Check DC link values (160.11/160.13/160.09) and compare them to the trip limits (186.02)
- Check network values (161.04)
FaultClass INU FT
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B32
Related Parameters 186.02 186.03 186.04 Related IO

Panel Text INT2 1STFL:FTC FT


Description First fault of INT:
INT has received Firing Through command via FT Link
Causes - Short circuit detected by another INT or PINT
- FT started by Control
Rectification Check fault on other units, because this fault is generated external.
FaultClass INU FT
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B06
Related Parameters Related IO

Panel Text INT2 1STFL:INT-INT


Description First fault of INT:
Communication error in INT to INT link
Causes - Damaged fibre optics
Rectification - Check the connection of the fibre optic
- Check the fibre optic in respect of bending and damages
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B27
Related Parameters Related IO

Panel Text INT2 1STFL:LSU DIO1


Description First fault of INT:
LSU diode failure
Causes Broken diode in LSU
Rectification - Check diodes in LSU regarding short circuit
- Check also in other UNIT\'s the semiconductors
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B13
Related Parameters Related IO

LSCI6570 ACS6000 SD 45/89


 
Panel Text INT2 1STFL:LSU DIO2
Description First fault of INT:
LSU diode failure
Causes Broken diode in LSU
Rectification - Check also in other UNIT\'s the semiconductors
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B14
Related Parameters Related IO

Panel Text INT2 1STFL:OV DC L


Description First fault of INT:
Overvoltage in lower DC link half
Causes - Overvoltage in DC circuit
- Fiber optic link from CVMII to INT faulty
- Defective circuit board
Rectification - Check fault logger of all units
- Check the operating point e.g. braking (160.18/161.02)
- Check DC link values (160.11/160.13/160.09) and compare them to the trip limits (186.02)
- Check network values (161.04)
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B19
Related Parameters 186.02 186.03 186.04 Related IO

Panel Text INT2 1STFL:OV DC U


Description First fault of INT:
Overvoltage in upper DC link half
Causes - Overvoltage in DC circuit
- Fiber optic link from CVMII to INT faulty
- Defective circuit board
Rectification - Check fault logger of all units
- Check the operating point e.g. braking (160.18/161.02)
- Check DC link values (160.11/160.13/160.09) and compare them to the trip limits (186.02)
- Check network values (161.04)
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B20
Related Parameters 186.02 186.03 186.04 Related IO

Panel Text INT2 1STFL:OVERCURR


Description First fault of INT:
Overcurrent
Causes - Overcurrent in a phase
- Poor cable grounding or shielding between LEM and CVMI
- CVMI failure
- Current scaling print (SCA on CVMI) failure
Rectification - Check IGCT\'s and Diodes respecting short circuit
- Check current (160.07) compared to the trip value (186.01)
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B21
Related Parameters 186.01 Related IO

46/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT2 1STFL:PF CVMI
Description First fault of INT:
Auxiliary power failure on CVMI
Causes - Damaged CVMI
- Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B08
Related Parameters Related IO

Panel Text INT2 1STFL:PF INT


Description First fault of INT:
Auxiliary power failure on INT
Causes - Damaged INT
- Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B07
Related Parameters Related IO

Panel Text INT2 1STFL:PF VLU


Description First fault of INT: VLU GUSP power failure
Causes - Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B12
Related Parameters Related IO

Panel Text INT2 1STFL:PHA PSU 1


Description First fault of INT:
GUSP power failure
Causes - Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B09
Related Parameters Related IO

Panel Text INT2 1STFL:PHA PSU 2


Description First fault of INT:
GUSP power failure
Causes - Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B10
Related Parameters Related IO

LSCI6570 ACS6000 SD 47/89


 
Panel Text INT2 1STFL:PHA PSU 3
Description First fault of INT:
GUSP power failure
Causes - Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B11
Related Parameters Related IO

Panel Text INT2 1STFL:SC EXT L


Description First fault of INT:
Short circuit detected by di/dt measurement device (FSCD or VLSCD) in lower commutation
group
Causes - Converter short circuit on another unit (ARU or INU)
- Defective circuit board
Rectification - Check fault logger of other units because the fault is external. So one other unit should have a
fault which is detected by his own.
- Check diodes and IGCT\'s respecting short circuit.
- Concentrate on the parts which are connected to the DC- but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B17
Related Parameters 186.01 191.08 Related IO

Panel Text INT2 1STFL:SC EXT U


Description First fault of INT:
Short circuit detected by di/dt measurement device (FSCD or VLSCD) in upper commutation
group
Causes - Converter short circuit on another unit (ARU or INU)
- Defective circuit board
Rectification - Check fault logger of other units because the fault is external. So one other unit should have a
fault which is detected by his own.
- Check diodes and IGCT\'s respecting short circuit.
- Concentrate on the parts which are connected to the DC+ but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B18
Related Parameters 186.01 191.08 Related IO

Panel Text INT2 1STFL:SC INU L


Description First fault of INT:
Short circuit detected by di/dt measurement device (FSCD or VLSCD) in lower commutation
group
Causes - Converter short circuit
- Defective circuit board
Rectification - Check diodes and IGCT\'s in respect of short circuit in this unit
- Concentrate on the parts which are connected to the DC- but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B15
Related Parameters 186.01 191.08 Related IO

48/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT2 1STFL:SC INU U
Description First fault of INT:
Short circuit detected by di/dt measurement device (FSCD or VLSCD) in upper commutation
group
Causes - Converter short circuit
- Defective circuit board
Rectification - Check diodes and IGCT\'s in respect of short circuit in this unit
- Concentrate on the parts which are connected to the DC+ but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B16
Related Parameters 186.01 191.08 Related IO

Panel Text INT2 1STFL:SC VLU L


Description First fault of INT:
Short circuit in lower VLU
Causes - Short circuit
- Wrong fibre optic cabling
Rectification - Check diodes and IGCT\'s in respect of short circuit in this unit
- Check also the other units
-Concentrate on the parts which are connected to the DC- but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B25
Related Parameters Related IO

Panel Text INT2 1STFL:SC VLU U


Description First fault of INT:
Short circuit in upper VLU
Causes - Short circuit
- Wrong fibre optic cabling
Rectification - Check diodes and IGCT\'s in respect of short circuit in this unit
- Check also the other units
-Concentrate on the parts which are connected to the DC+ but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.39: EPLD2 First Fault Bit B26
Related Parameters Related IO

Panel Text INT2 Block Modulatio


Description Redundant drive: in case of firing thorough other drive has to block modulation with FC2,
automatic reseting afterwards.
Causes Reason should be a FT in other drive. See firing through, additionally malfunction of the INT-INT
link.
Rectification 1) Check if other drive did a FT.
2) See firing through and INT-INT link.
FaultClass INU FC2
FaultClass ARU ND
Fault Word 183.35: FW Other Bit B10
Related Parameters Related IO

LSCI6570 ACS6000 SD 49/89


 
Panel Text INT2 Curr Asym High
Description Sum of motor three phase current exceeds 27% of the maximum measurable CVMI current.
Causes Earth fault
Defective circuit board
Communication faulty
Rectification Check for other related faults
Check main circuit
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.17: FW1 Current Bit B01
Related Parameters 186.12 Related IO

Panel Text INT2 DI/DT SuperVi


Description Di/dt measurement malfunction (FSCF or VLSCD)
Causes - Fiber optic link from FSCD- to INT-board faulty
- FSCD- or INT-board failure
- Internal parameter setting
Rectification Check fiber optic cables and connections to FSCD-board
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.20: FW Short Circuit Bit B09
Related Parameters 191.08 Related IO

Panel Text INT2 Firing-Through


Description Fault with Firing-Through occured.
Causes Firing-through via FT Link (Other INU/ARU), Overvoltage, Overcurrent, Phase module short-
circuit , VLU short-circuit, LSU short-circuit, Arcguard firing-through, or CBU (DC-Link).
Rectification Find firing-through root-cause.
Acknowledge firing-through fault through parameter 16.24
FaultClass INU
FaultClass ARU
Fault Word 183.85: Other 1 Bit B10
Related Parameters Related IO

Panel Text INT2 FT Link


Description Firing through (FT) link communication failure
Causes - Fiber optic link between INT-boards of two power stages faulty
- INT-board failure
Rectification Check fiber optic cables and connections status
Ceck int board HW status.
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.07: FW CntrlHardware Bit B07
Related Parameters Related IO

Panel Text INT2 INT2INT FT


Description INT 2 has been tripped with FT command because of fault in the other INT.
Causes 1) Other INT tripped.
2) Link malfunction.
3) INT malfunction.
Rectification 1) Check if other drive had a fault.
2) See INT-INT link.
3) Check INT board and fibre optic link.
FaultClass INU FT
FaultClass ARU ND
Fault Word 183.36: FW1 Other Bit B10
Related Parameters Related IO

50/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT2 INT2INT MCB
Description INT 2 has been tripped with opening MCB command because of fault in the other INT.
Causes 1) Other INT tripped.
2) Link malfunction.
3) INT malfunction.
Rectification 1) Check if other drive had a fault.
2) See INT-INT link.
3) Check INT board and fibre optic link.
FaultClass INU FC1
FaultClass ARU ND
Fault Word 183.36: FW1 Other Bit B06
Related Parameters Related IO

Panel Text INT2 INT2INT Trip


Description INT 2 has been tripped because of fault in the other INT.
Causes 1) Other INT tripped.
2) Link malfunction.
3) INT malfunction.
Rectification 1) Check if other drive had a fault.
2) See INT-INT link.
3) Check INT board and fibre optic link.
FaultClass INU FC2
FaultClass ARU ND
Fault Word 183.36: FW1 Other Bit B02
Related Parameters Related IO

Panel Text INT2 INTtoINT Link


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.03: FW1 Communication Bit B02
Related Parameters Related IO

Panel Text INT2 MF I2I Link


Description Communication fault in INT to INT link between Master and Follower detected on INT2
Causes Only on ACS6000 RSD
Fibre optics or connected baords faulty
Rectification Check fiber optic cables and connections
FaultClass INU FC2
FaultClass ARU Not Appl.
Fault Word 183.03: FW1 Communication Bit B12
Related Parameters Related IO

Panel Text INT2 Overcurrent


Description Overcurrent detected by CVMI
Causes - Overcurrent in a phase
- Poor cable grounding or shielding between LEM and CVMI
- CVMI failure
- Current scaling ptint (SCA on CVMI) failure
Rectification - Use datalogger to check if there was too high current
- Check wires between CVMI and LEM
- Check LEM
- Check current scaling print on CVMI
- Check for other related faults
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.17: FW1 Current Bit B02
Related Parameters 186.01 Related IO

LSCI6570 ACS6000 SD 51/89


 
Panel Text INT2 Overcurrent FT
Description Firing through because of too high current
Causes - Overcurrent in a phase
- Curernt measurement problem
- Unstable control
- Saturated trafo
Rectification - Use datalogger to check if current was too high
- Check current measurement chain
FaultClass INU FT
FaultClass ARU ND
Fault Word 183.18: FW2 Current Bit B02
Related Parameters 186.01 Related IO

Panel Text INT2 Overvoltage


Description DC-overvoltage detected by INT2 board (ACS6000: third INU; ACS5000: phase B module)
Causes - Overvoltage in DC circuit
- Fiber optic link from ADCVI to INT faulty
- Defective circuit board
Rectification - SW overvoltage faults should be triggered as well
- check SVA subprint
- check optic link between CVMI and interface board
- Check if mains supply voltage is within the limits
- Is ARU modulating
- Check the situation (e.g. braking)
- Check for other related faults
- Check parameter 186.02
- Check value 160.09
- Check parmeter settings respecting braking equipment (Grp.192)
- Use datalogger to check if there was too high voltage
- Check IOV fiber between CVMI and INT
- Check CVMI
- Check voltage scaling print (SVA)
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.13: FW1 DC LinkVolt Bit B00
Related Parameters 186.02 186.03 186.04 Related IO

Panel Text INT2 Overvoltage FT


Description Firing Through because of too high DC link voltage detected by CVMI
Causes - Overvoltage in DC link
- Fiber optic failure (IOV)
- CVMI board failure
- Voltage scaling board (SVA on CVMI) failure
Rectification - Use datalogger to check if there was too high voltage
- Check IOV fiber between CVMI and INT
- Check CVMI
- Check voltage scaling print (SVA)
FaultClass INU FT
FaultClass ARU ND
Fault Word 183.13: FW1 DC LinkVolt Bit B10
Related Parameters 186.02 186.03 186.04 Related IO

52/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT2 PHA PSU AuxPwr
Description Auxiliary voltage supply malfunction in gate unit supply power (PSU)
Causes - Aux power failure
- Fiber optic link faulty
- GUSP failure
Rectification - Check auxiliary supply and fuses
- Check auxiliary supply wiring
- Check fiber optic cables and connections
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.08: FW1 CntrlHardware Bit B01
Related Parameters Related IO

Panel Text INT2 PPCS Link


Description INT has detected a problem in at least one of the PPCS communication links
Causes - Fiber optic link from CVMI, AMC3, PUBPFF or SYN to INT faulty
- No Aux power on CVMI, or SYN
- Defect CVMI or SYN
Rectification Check fiber optic cables and connections clean eventual dust on it.
Change CVMI or SYN board
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.02: FW Communication Bit B06
Related Parameters Related IO

Panel Text INT2 ShortCircuit


Description Short circuit detected by di/dt measurement device (FSCD or VLSCD)
Causes - Converter short circuit
- Defective circuit board
Rectification - Check diodes and IGCT\'s finding short circuit in this unit
- Check also the other units
FaultClass INU FC1
FaultClass ARU FC1
Fault Word 183.20: FW Short Circuit Bit B07
Related Parameters 190.02 191.08 Related IO

Panel Text INT2 VLU ShortCirc


Description Short circuit in VLU circuit (feedback from VLU is not matching control signal)
Causes - Short circuit inside the VLU
- Wrong VLU feedback signal connected
Rectification - Check diodes and IGCT\'s sercing short circuit in this unit
- Check also the other units
FaultClass INU FT
FaultClass ARU Not Appl.
Fault Word 183.20: FW Short Circuit Bit B08
Related Parameters Related IO

Panel Text INT3 1STFL:ASYMCUR


Description First fault of INT:
Sum of current is exceeding the limits
Causes - Earth fault
- Communication faulty
Rectification - Verify the main circuit Isolation
- Verify the current transducer
- Verify the CVMI boad HW connections and status
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B22
Related Parameters Related IO

LSCI6570 ACS6000 SD 53/89


 
Panel Text INT3 1STFL:COMER A
Description First fault of INT: Communication error in PPCC link A
Causes PPCC link A between AMC or PUB and INT is faulty
Rectification Verify the optical fiber connection between AMC or PUB and INT.
Verify the overall cleaness of the cabinet.
Dust can create trouble in optical connections
Verify that optical fiber are not bended or broken
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B01
Related Parameters Related IO

Panel Text INT3 1STFL:COMER B


Description First fault of INT:Communication error in PPCC link B
Causes PPCC link B between AMC or PUB and INT is faulty
Rectification Verify the optical fiber connection between AMC or PUB and INT.
Verify the overall cleaness of the cabinet.
Dust can create trouble in optical connections
Verify that optical fiber are not bended or broken
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B02
Related Parameters Related IO

Panel Text INT3 1STFL:COMER C


Description First fault of INT:Communication error in PPCC link C
Causes PPCC link C between INT and CVMI is faulty
Rectification Verify the optical fiber connection between INT and CVMI board.
Verify the overall cleaness of the cabinet.
Dust can create trouble in optical connections
Verify that optical fiber are not bended or broken
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B03
Related Parameters Related IO

Panel Text INT3 1STFL:COMER D


Description First fault of INT:Communication error in PPCC link D
Causes PPCC link D between INT and CVMI is faulty
Rectification Verify the optical fiber connection between INT and CVMI board.
Verify the overall cleaness of the cabinet.
Dust can create trouble in optical connections
Verify that optical fiber are not bended or broken
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B04
Related Parameters Related IO

Panel Text INT3 1STFL:COMER FT


Description First fault of INT: Communication error in Firing Through link
Causes - Fibre optic connected to FT receiver is damaged
- Transmitting INT or PINT are disturbed by EMC
Rectification Ceck fiber optic, change if damaged.
Verify the EMC protection sealings are all installed properly
FaultClass INU FT
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B05
Related Parameters Related IO

54/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT3 1STFL:CTRVLU L
Description First fault of INT:
Control fault in lower VLU
Causes - Damaged VLSCD in VLU
- Damaged fibre optic between VLU and INT
Rectification - Check the part of the VLU which is conected to the DC- in respect of fibre optic connections
and damages
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B23
Related Parameters Related IO

Panel Text INT3 1STFL:CTRVLU U


Description First fault of INT:
Control fault in upper VLU
Causes - Damaged VLSCD in VLU
- Damaged fibre optic between VLU and INT
Rectification - Check the part of the VLU which is conected to the DC+ in respect of fibre optic connections
and damages
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B24
Related Parameters Related IO

Panel Text INT3 1STFL:FT OC


Description First fault of INT:
Firing Through due to overcurrent
Causes Main component as IGCT or Diode in short circuit.
Short on the power circuit
Rectification - Check fault logger of all units, in case of an short circuit also other units could be damaged
- Check IGCT and Diodes in respect of a short circuit
- Check LED on IGCT\'s
FaultClass INU FT
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B33
Related Parameters 186.01 Related IO

Panel Text INT3 1STFL:FT OV DC


Description First fault of INT:
Firing Through due to overvoltage
Causes To high voltage on the DC bus
exceeding the Overvoltage Firing Trough limit
Rectification - Check fault logger of all units
- Check the operating point e.g. braking (160.18/161.02)
- Check DC link values (160.11/160.13/160.09) and compare them to the trip limits (186.02)
- Check network values (161.04)
FaultClass INU FT
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B32
Related Parameters 186.02 186.03 186.04 Related IO

Panel Text INT3 1STFL:FTC FT


Description First fault of INT:
INT has received Firing Through command via FT Link
Causes - Short circuit detected by another INT or PINT
- FT started by Control
Rectification Check fault on other units, because this fault is generated external.
FaultClass INU FT
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B06
Related Parameters Related IO

LSCI6570 ACS6000 SD 55/89


 
Panel Text INT3 1STFL:INT-INT
Description First fault of INT:
Communication error in INT to INT link
Causes - Damaged fibre optics
Rectification - Check the connection of the fibre optic
- Check the fibre optic in respect of bending and damages
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B27
Related Parameters Related IO

Panel Text INT3 1STFL:LSU DIO1


Description First fault of INT:
LSU diode failure
Causes Broken diode in LSU
Rectification - Check diodes in LSU regarding short circuit
- Check also in other UNIT\'s the semiconductors
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B13
Related Parameters Related IO

Panel Text INT3 1STFL:LSU DIO2


Description First fault of INT:
LSU diode failure
Causes Broken diode in LSU
Rectification - Check diodes in LSU regarding short circuit
- Check also in other UNIT\'s the semiconductors
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B14
Related Parameters Related IO

Panel Text INT3 1STFL:OV DC L


Description First fault of INT:
Overvoltage in lower DC link half
Causes - Overvoltage in DC circuit
- Fiber optic link from CVMII to INT faulty
- Defective circuit board
Rectification - Check fault logger of all units
- Check the operating point e.g. braking (160.18/161.02)
- Check DC link values (160.11/160.13/160.09) and compare them to the trip limits (186.02)
- Check network values (161.04)
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B19
Related Parameters 186.02 186.03 186.04 Related IO

56/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT3 1STFL:OV DC U
Description First fault of INT:
Overvoltage in upper DC link half
Causes - Overvoltage in DC circuit
- Fiber optic link from CVMII to INT faulty
- Defective circuit board
Rectification - Check fault logger of all units
- Check the operating point e.g. braking (160.18/161.02)
- Check DC link values (160.11/160.13/160.09) and compare them to the trip limits (186.02)
- Check network values (161.04)
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B20
Related Parameters 186.02 186.03 186.04 Related IO

Panel Text INT3 1STFL:OVERCURR


Description First fault of INT:
Overcurrent
Causes - Overcurrent in a phase
- Poor cable grounding or shielding between LEM and CVMI
- CVMI failure
- Current scaling print (SCA on CVMI) failure
Rectification - Check IGCT\'s and Diodes respecting short circuit
- Check current (160.07) compared to the trip value (186.01)
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B21
Related Parameters 186.01 Related IO

Panel Text INT3 1STFL:PF CVMI


Description First fault of INT:
Auxiliary power failure on CVMI
Causes - Damaged CVMI
- Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B08
Related Parameters Related IO

Panel Text INT3 1STFL:PF INT


Description First fault of INT:
Auxiliary power failure on INT
Causes - Damaged INT
- Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B07
Related Parameters Related IO

LSCI6570 ACS6000 SD 57/89


 
Panel Text INT3 1STFL:PF VLU
Description First fault of INT: VLU GUSP power failure
Causes - Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B12
Related Parameters Related IO

Panel Text INT3 1STFL:PHA PSU 1


Description First fault of INT:
GUSP power failure
Causes - Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B09
Related Parameters Related IO

Panel Text INT3 1STFL:PHA PSU 2


Description First fault of INT:
GUSP power failure
Causes - Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B10
Related Parameters Related IO

Panel Text INT3 1STFL:PHA PSU 3


Description First fault of INT:
GUSP power failure
Causes - Damaged GUSP
- Loss of auxiliary power
Rectification - Check aux. Power supply voltage and connections
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B11
Related Parameters Related IO

Panel Text INT3 1STFL:SC EXT L


Description First fault of INT:
Short circuit detected by di/dt measurement device (FSCD or VLSCD) in lower commutation
group
Causes - Converter short circuit on another unit (ARU or INU)
- Defective circuit board
Rectification - Check fault logger of other units because the fault is external. So one other unit should have a
fault which is detected by his own.
- Check diodes and IGCT\'s respecting short circuit.
- Concentrate on the parts which are connected to the DC- but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B17
Related Parameters 186.01 191.08 Related IO

58/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT3 1STFL:SC EXT U
Description First fault of INT:
Short circuit detected by di/dt measurement device (FSCD or VLSCD) in upper commutation
group
Causes - Converter short circuit on another unit (ARU or INU)
- Defective circuit board
Rectification - Check fault logger of other units because the fault is external. So one other unit should have a
fault which is detected by his own.
- Check diodes and IGCT\'s respecting short circuit.
- Concentrate on the parts which are connected to the DC- but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B18
Related Parameters 186.01 191.08 Related IO

Panel Text INT3 1STFL:SC INU L


Description First fault of INT:
Short circuit detected by di/dt measurement device (FSCD or VLSCD) in lower commutation
group
Causes - Converter short circuit
- Defective circuit board
Rectification - Check diodes and IGCT\'s in respect of short circuit in this unit
- Concentrate on the parts which are connected to the DC- but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B15
Related Parameters 186.01 191.08 Related IO

Panel Text INT3 1STFL:SC INU U


Description First fault of INT:
Short circuit detected by di/dt measurement device (FSCD or VLSCD) in upper commutation
group
Causes - Converter short circuit
- Defective circuit board
Rectification - Check diodes and IGCT\'s in respect of short circuit in this unit
- Concentrate on the parts which are connected to the DC+ but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B16
Related Parameters 186.01 191.08 Related IO

Panel Text INT3 1STFL:SC VLU L


Description First fault of INT:
Short circuit in lower VLU
Causes - Short circuit
- Wrong fibre optic cabling
Rectification - Check diodes and IGCT\'s respecting short circuit in this unit
- Check also the other units
- Concentrate on the parts which are connected to the DC- but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B25
Related Parameters Related IO

LSCI6570 ACS6000 SD 59/89


 
Panel Text INT3 1STFL:SC VLU U
Description First fault of INT:
Short circuit in upper VLU
Causes - Short circuit
- Wrong fibre optic cabling
Rectification - Check diodes and IGCT\'s respecting short circuit in this unit
- Check also the other units
- Concentrate on the parts which are connected to the DC+ but check also the others.
FaultClass INU FC1
FaultClass ARU
Fault Word 183.40: EPLD3 First Fault Bit B26
Related Parameters Related IO

Panel Text INT3 AuxiliaryPower


Description Auxiliary voltage supply malfunction (SYN, CVMI or INT boards)
Causes - Aux power failure
- Fiber optic link faulty
- Defective SYN, CVMI or INT board
- GUSP failure
Rectification - Check auxiliary supply and fuses
- Check auxiliary supply wiring
- Check fiber optic cables and connections
FaultClass INU FC2
FaultClass ARU
Fault Word 183.08: FW1 CntrlHardware Bit B04
Related Parameters Related IO

Panel Text INT3 AuxiliaryPower


Description Auxiliary voltage supply malfunction (SYN, CVMI or INT boards)
Causes - Aux power failure
- Fiber optic link faulty
- Defective SYN, CVMI or INT board
- GUSP failure
Rectification - Check auxiliary supply and fuses
- Check auxiliary supply wiring
- Check fiber optic cables and connections
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.08: FW1 CntrlHardware Bit 4
Related Parameters Related IO

Panel Text INT3 Block Modulatio


Description Redundant drive: in case of firing thorough other drive has to block modulation with FC2,
automatic reseting afterwards.
Causes Reason should be a FT in other drive. See firing through, additionally malfunction of the INT-INT
link.
Rectification 1) Check if other drive did a FT.
2) See firing through and INT-INT link.
FaultClass INU FC2
FaultClass ARU ND
Fault Word 183.35: FW Other Bit B11
Related Parameters Related IO

60/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT3 Curr Asym High
Description Sum of motor three phase current exceeds 27% of the maximum measurable CVMI current.
Causes Earth fault
Defective circuit board
Communication faulty
Rectification Check for other related faults
Check main circuit isolation
FaultClass INU FC2
FaultClass ARU
Fault Word 183.17: FW1 Current Bit B10
Related Parameters 186.12 Related IO

Panel Text INT3 DI/DT SuperVi


Description Di/dt measurement malfunction (FSCF or VLSCD)
Causes - Fiber optic link from FSCD- to INT-board faulty
- FSCD- or INT-board failure
- Internal parameter setting
Rectification Check fiber optic cables and connections to FSCD-board
FaultClass INU FC2
FaultClass ARU ND
Fault Word 183.20: FW Short Circuit Bit B10
Related Parameters 191.08 Related IO

Panel Text INT3 Firing-Through


Description Fault with Firing-Through occured.
Causes Firing-through via FT Link (Other INU/ARU), Overvoltage, Overcurrent, Phase module short-
circuit , VLU short-circuit, LSU short-circuit, Arcguard firing-through, or CBU (DC-Link).
Rectification Find firing-through root-cause.
Acknowledge firing-through fault through parameter 16.24
FaultClass INU FC1
FaultClass ARU
Fault Word 183.85: Other 1 Bit B11
Related Parameters Related IO

Panel Text INT3 FT Link


Description Firing through (FT) link communication failure
Causes - Fiber optic link between INT-boards of two power stages faulty
- INT-board failure
Rectification Check fiber optic cables and connections status
Ceck int board HW status.
FaultClass INU FC2
FaultClass ARU ND
Fault Word 183.03: FW1 Communication Bit B05
Related Parameters Related IO

Panel Text INT3 INT2INT FT


Description INT 3 has been tripped with FT command because of fault in the other INT.
Causes 1) Other INT tripped.
2) Link malfunction.
3) INT malfunction.
Rectification 1) Check if other drive had a fault.
2) See INT-INT link.
3) Check INT board and fibre optic link.
FaultClass INU FT
FaultClass ARU ND
Fault Word 183.36: FW1 Other Bit B11
Related Parameters Related IO

LSCI6570 ACS6000 SD 61/89


 
Panel Text INT3 INT2INT MCB
Description INT 3 has been tripped with opening MCB command because of fault in the other INT.
Causes 1) Other INT tripped.
2) Link malfunction.
3) INT malfunction.
Rectification 1) Check if other drive had a fault.
2) See INT-INT link.
3) Check INT board and fibre optic link.
FaultClass INU FC1
FaultClass ARU ND
Fault Word 183.36: FW1 Other Bit B07
Related Parameters Related IO

Panel Text INT3 INT2INT Trip


Description INT 3 has been tripped because of fault in the other INT.
Causes 1) Other INT tripped.
2) Link malfunction.
3) INT malfunction.
Rectification 1) Check if other drive had a fault.
2) See INT-INT link.
3) Check INT board and fibre optic link.
FaultClass INU FC2
FaultClass ARU ND
Fault Word 183.36: FW1 Other Bit B03
Related Parameters Related IO

Panel Text INT3 INTtoINT Link


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.03: FW1 Communication Bit B03
Related Parameters Related IO

Panel Text INT3 LSU DiodeFault


Description
Causes
Rectification
FaultClass INU FC1
FaultClass ARU
Fault Word 183.08: FW1 CntrlHardware Bit B08
Related Parameters Related IO

Panel Text INT3 LSU DiodeFault


Description
Causes
Rectification
FaultClass INU FC1
FaultClass ARU
Fault Word 183.08: FW1 CntrlHardware Bit 8
Related Parameters Related IO

62/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT3 MF I2I Link
Description Communication fault in INT to INT link between Master and Follower detected on INT3
Causes Only on ACS6000 RSD
Fibre optics or connected baords faulty
Rectification Check fiber optic cables and connections
FaultClass INU FC2
FaultClass ARU Not Appl.
Fault Word 183.03: FW1 Communication Bit B13
Related Parameters Related IO

Panel Text INT3 Overcurrent


Description Overcurrent detected by CVMI
Causes - Overcurrent in a phase
- Poor cable grounding or shielding between LEM and CVMI
- CVMI failure
- Current scaling ptint (SCA on CVMI) failure
Rectification - Use datalogger to check if there was too high current
- Check wires between CVMI and LEM
- Check LEM
- Check current scaling print on CVMI
- Check for other related faults
FaultClass INU FC2
FaultClass ARU ND
Fault Word 183.17: FW1 Current Bit B11
Related Parameters 186.01 Related IO

Panel Text INT3 Overcurrent FT


Description Firing through because of too high current
Causes - Overcurrent in a phase
- Curernt measurement problem
- Unstable control
- Saturated trafo
Rectification - Use datalogger to check if current was too high
- Check current measurement chain
FaultClass INU FT
FaultClass ARU ND
Fault Word 183.18: FW2 Current Bit B03
Related Parameters 186.01 Related IO

LSCI6570 ACS6000 SD 63/89


 
Panel Text INT3 Overvoltage
Description DC-overvoltage detected by INT3 board fourth INU
Causes - Overvoltage in DC circuit
- Fiber optic link from ADCVI to INT faulty
- Defective circuit board
Rectification - SW overvoltage faults should be triggered as well
- check SVA subprint
- check optic link between CVMI and interface board
- Check if mains supply voltage is within the limits
- Is ARU modulating
- Check the situation (e.g. braking)
- Check for other related faults
- Check parameter 186.02
- Check value 160.09
- Check parmeter settings respecting braking equipment (Grp.192)
- Use datalogger to check if there was too high voltage
- Check IOV fiber between CVMI and INT
- Check CVMI
- Check voltage scaling print (SVA)
FaultClass INU FC2
FaultClass ARU ND
Fault Word 183.13: FW1 DC LinkVolt Bit B07
Related Parameters 186.02 186.03 186.04 Related IO

Panel Text INT3 Overvoltage FT


Description Firing Through because of too high DC link voltage detected by CVMI
Causes - Overvoltage in DC link
- Fiber optic failure (IOV)
- CVMI board failure
- Voltage scaling board (SVA on CVMI) failure
Rectification - Use datalogger to check if there was too high voltage
- Check IOV fiber between CVMI and INT
- Check CVMI
- Check voltage scaling print (SVA)
FaultClass INU FT
FaultClass ARU ND
Fault Word 183.13: FW1 DC LinkVolt Bit B11
Related Parameters 186.02 186.03 186.04 Related IO

Panel Text INT3 PHA PSU AuxPwr


Description Auxiliary voltage supply malfunction in gate unit supply power (PSU)
Causes - Aux power failure
- Fiber optic link faulty
- GUSP failure
Rectification - Check auxiliary supply and fuses
- Check auxiliary supply wiring
- Check fiber optic cables and connections
FaultClass INU FC2
FaultClass ARU
Fault Word 183.08: FW1 CntrlHardware Bit B07
Related Parameters Related IO

64/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT3 PPCS Link
Description INT has detected a problem in at least one of the PPCS communication links
Causes - Fiber optic link from CVMI, AMC3, PUBPFF or SYN to INT faulty
- No Aux power on CVMI, or SYN
- Defect CVMI or SYN
Rectification Check fiber optic cables and connections clean eventual dust on it.
Change CVMI or SYN board
FaultClass INU FC1
FaultClass ARU ND
Fault Word 183.03: FW1 Communication Bit B04
Related Parameters Related IO

Panel Text INT3 ShortCircuit


Description Short circuit detected by di/dt measurement device (FSCD or VLSCD)
Causes - Converter short circuit
- Defective circuit board
Rectification - Check diodes and IGCT\'s serching short circuit in this unit
- Check also the other units
FaultClass INU FC1
FaultClass ARU ND
Fault Word 183.20: FW Short Circuit Bit B10
Related Parameters 190.02 191.08 Related IO

Panel Text INT3 VLU Control


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.08: FW1 CntrlHardware Bit B07
Related Parameters Related IO

Panel Text INT3 VLU Control


Description
Causes
Rectification
FaultClass INU FC2
FaultClass ARU
Fault Word 183.08: FW1 CntrlHardware Bit 7
Related Parameters Related IO

Panel Text INT3 VLU ShortCirc


Description Short circuit in VLU circuit (feedback from VLU is not matching control signal)
Causes - Short circuit inside the VLU
- Wrong VLU feedback signal connected
Rectification - Check diodes and IGCT\'s sercing short circuit in this unit
- Check also the other units
FaultClass INU FT
FaultClass ARU ND
Fault Word 183.03: FW1 Communication Bit B11
Related Parameters Related IO

LSCI6570 ACS6000 SD 65/89


 
Panel Text INT3 VLU ShortCirc
Description Communication fault in INT to INT link between Master and Follower detected on INT1
Causes Only on ACS6000 RSD
Fibre optics or connected baords faulty
Rectification Check fiber optic cables and connections
FaultClass INU FC2
FaultClass ARU Not Appl.
Fault Word 183.03: FW1 Communication Bit 11
Related Parameters Related IO

Panel Text Low Speed During RT


Description Lowest allowed speed in ride through operation reached.
Causes Supply voltage does not return before speed dropped too low
Rectification Check parameter 132.32
Check supply network
FaultClass INU FC1
FaultClass ARU
Fault Word 183.13: FW1 DC LinkVolt Bit B15
Related Parameters 186.05 Related IO

Panel Text Master EXU no RdyRn


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.36: FW1 Other Bit b15
Related Parameters Related IO

Panel Text Master EXU not RdyRun


Description Forces the Follower Drive in a Master-Follower Configuration to initiate an Auto-Restart
sequence in case the Master drive performs an Auto-Restart sequence
Causes This is not a real fault since it is only used to force the Auto-Restart sequence
Rectification No actions needed
FaultClass INU FC2
FaultClass ARU
Fault Word 183.36: FW1 Other Bit B14
Related Parameters Related IO

Panel Text Max RT Time Elapsed


Description Maximum Ridethrough time Elapsed
Causes Mains supply low
Internal parameter settings
Defective circuit board
Rectification Check supply voltage of mains, check SYN board, check network voltage after reset
FaultClass INU FC1
FaultClass ARU
Fault Word 183.12: FW DC LinkVolt Bit B15
Related Parameters Related IO

Panel Text Motor Protection SW


Description (UL characteristic)
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.35: FW Other Bit b02
Related Parameters Related IO

66/89 Version LSCI6570 Troubleshooting Manual



Panel Text Motor Underload
Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.35: FW Other Bit b03
Related Parameters Related IO

Panel Text Network Disturbed


Description DC link oscillations exceed a protection limit for a specified time frame.
Causes One or two phases of the supply network have reduced amplitude or are missing
Rectification Check parameters 186.17 and 186.18
Check DC link during operation
Check supply network
Disable with ARU drives
FaultClass INU FC1
FaultClass ARU
Fault Word 183.26: FW Network Bit B00
Related Parameters 186.15 186.16 Related IO

Panel Text NP Voltage


Description Unbalance of DC link voltage detected
Causes Tuning parameters
Faulty capacitor in CBU
Faulty diode
Rectification Check for other related faults
Check signals 160.09/160.11/160.13 and compare to the trip value 186.06
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.12: FW DC LinkVolt Bit B03
Related Parameters 186.06 Related IO

Panel Text Operating System


Description Operating system has detected wrong behaviour of SW.
Causes - EMC disturbance of AMC
- Broken AMC
- Bug in the SW
Rectification - Switch OFF and ON auxiliary power and restart system
- Change AMC
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.35: FW Other Bit B00
Related Parameters Related IO

LSCI6570 ACS6000 SD 67/89


 
Panel Text Overcurrent
Description Overcurrent detected by AMC software. One of the measured phase currents is above the fixed
current limit
Causes - Motor load not matched with inverter rating
- Incorrect motor data
- Acceleration too steep
- Stray currents in motor cables
- Fiber optic link faulty
- PPCS communication error
Rectification - Check for other related messages
- Check dimensioning of motor and drive. Check if fault occurs only in acceleration phases. in
this case the acceleration is too fast
- Check motor cable connections
- Check fiber optic cables and connections between ADCVI and INT boards
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.16: FW Current Bit B00
Related Parameters 186.01 Related IO

Panel Text Overfrequency


Description Frequency of output voltage is too high (Motor speed is too high).
Causes Sudden loss of motor load or load forces motor to rotate too fast.
Motor nominal data.
Parameter settings (i.e. speed and torque limits not set correctly).
Speed measurement defective.
Rectification Check motor data and load conditions.
Check motor speed.
Check current and torque limits.
Check motor speed and overspeed trip limits.
Check that the measured speed corresponds to motor frequency.
Check NTAC pulse number setting
Related parameters:
Drive current limits:
20.06 MAXIMUM TORQUE
20.07 MINIMUM TORQUE
20.08 SPC TORQMAX
20.09 SPC TORQMIN
20.10 TREF TORQMAX
20.11 TREF TORQMIN
Speed controller tuning parameters:
24.02 KPS
24.08 TIS
Overspeed and frequency limiter limit should be a little smaller than frequency trip limit (internal
parameter, not accessible) and speed limits should be little smaller than overspeed limit.
For details of speed controller tuning see the Signal Parameter Table Groups 23 and 24.
Overspeed trip limits set with parameter:
20.05 OVERSPEED LIMIT
Maximum and minimum speed limits set with parameters:
20.01 MINIMUM SPEED
20.02 MAXIMUM SPEED
Motor speed can be observed with parameter:
01.07 MOTOR SPEED
FaultClass INU FC2
FaultClass ARU
Fault Word 183.29: FW SpeedPosition Bit B00
Related Parameters 186.07 Related IO

68/89 Version LSCI6570 Troubleshooting Manual



Panel Text PFF Comm INU 1
Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.02: FW Communication Bit b03
Related Parameters Related IO

Panel Text PFF Comm INU 2/WCU


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.02: FW Communication Bit b04
Related Parameters Related IO

Panel Text PFF Comm INU 3


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.02: FW Communication Bit b05
Related Parameters Related IO

Panel Text PFF Comm INU 4


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.02: FW Communication Bit b06
Related Parameters Related IO

Panel Text PFF Comm INU 5


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.02: FW Communication Bit b07
Related Parameters Related IO

Panel Text PFF Comm INU 6


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.02: FW Communication Bit b08
Related Parameters Related IO

LSCI6570 ACS6000 SD 69/89


 
Panel Text PFF Comm INU 7
Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.02: FW Communication Bit b09
Related Parameters Related IO

Panel Text PFF Comm INU 8


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.02: FW Communication Bit b10
Related Parameters Related IO

Panel Text PFF Comm INU 9/ARU


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.02: FW Communication Bit b11
Related Parameters Related IO

Panel Text PFF Communication


Description Communication error in PFF (Power feed forward) communication
Causes - Fiber optic link(s) faulty
- Aux power on PUB/PFF board and AMC3
Rectification Check fiber optic cables and connections between all AMC3\'s and PUB board in ARU
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.02: FW Communication Bit B01
Related Parameters Related IO

Panel Text Phase A Lost


Description Phase A of the motor/inverter phases in the master unit lost
Causes Software parameters
Motor/Inverter cabling: loose connections
Current transducer defective
Loose or disconnected wire(s) in measurement or supply circuit
DC voltage measurement board defective
Check for other fault messages
Rectification Check software parameters, detection might be too sensitive and trigger wrongly at low speed.
Check Dataloggers to see current waveforms
Measure the current, if it\'s very low or maybe zero for a to long time (see 186.14)
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.16: FW Current Bit B01
Related Parameters 186.13 186.14 186.12 Related IO

70/89 Version LSCI6570 Troubleshooting Manual



Panel Text Phase B Lost
Description Phase B of the motor/inverter phases in the master unit lost
Causes Motor cabling: loose connections
Current transducer defective
Loose or disconnected wire(s) in measurement or supply circuit
DC voltage measurement board defective
Check for other faultmessages
Rectification Check software parameters, detection might be too sensitive and trigger wrongly at low speed.
Check the Dataloggers to see the current waveforms
Measure the current to if it\'s very low or maybe zero for a to long time (see 186.14)
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.16: FW Current Bit B02
Related Parameters 186.13 186.14 186.12 Related IO

Panel Text Phase C Lost


Description Phase C of the motor/inverter phases in the master unit lost
Causes Motor cabling: loose connections
Current transducer defective
Loose or disconnected wire(s) in measurement or supply circuit
DC voltage measurement board defective
Check for other faultmessages
Rectification Check software parameters, detection might be too sensitive and trigger wrongly at low speed.
Check the Dataloggers to see the current waveforms
Measure the current to if it\'s very low or maybe zero for a to long time (see 186.14)
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.16: FW Current Bit B03
Related Parameters 186.13 186.14 186.12 Related IO

Panel Text PositionMeasurement


Description Error detected in position measurement devices (fault in both position and speed measurement)
In case of a fault in GRAY the position is automatically calculated from the speed measurement
of NTAC module.
Causes If fault reaction is selected via par. 166.44 = FCL1, MCB will opened after Position measurement
fault
- GRB module (LD-GRB01) defective
- Position encoder defective
- Cabling or connections between position encoder and GRB module
- Internal parameter setting
Rectification See alarm messages: PositionMeasurement and SpeedMeasurement
1 Check cabling and connections between position encoder and GRB module
FaultClass INU FC1 FC2
FaultClass ARU
Fault Word 183.29: FW SpeedPosition Bit B01
Related Parameters Related IO

Panel Text PPCS Communication


Description Communication error in PPCS link
Causes Fiber optic link(s) faulty
Rectification Check fiber optic cables and connections between AMC3 and INT boards and AMC3 and PUB
boards.
Service: Check correct configuration of inverter in SW (Single, Double,...)
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.02: FW Communication Bit B00
Related Parameters Related IO

LSCI6570 ACS6000 SD 71/89


 
Panel Text PUB ArcGuard FT
Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.21: FW1 Short Circuit Bit b12
Related Parameters Related IO

Panel Text PUB: AuxiliaryPower


Description Auxiliary voltage supply malfunction
Causes - Aux power failure
- Defective PUBPFF board
- GUSP failure
Rectification - Check auxiliary supply and fuses
- Check auxiliary supply wiring
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.08: FW1 CntrlHardware Bit B13
Related Parameters Related IO

Panel Text PUB: Communication


Description PUBPFF has detected a problem in at least one of the PPCS communication links
Causes - Fiber optic links between AMC PUBPFF or between PUBPFF INT faulty
- No Aux power on INT
- Defect INT
Rectification Check fiber optic cables and connections cleaness.
Ceck INT Power supply
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.02: FW Communication Bit B08
Related Parameters Related IO

Panel Text PUB: WrongSwitch 1


Description In double, triple, or quadruple INU hard-parallel configurations only. The 2nd INU modulator did
not output the same switching command as the first INU.
Causes Too high switching frequency, or noisy current feedbacks. In exceptional cases a defective
PhaseINT.
Rectification Monitor switching frequency (SF) -- watch especially the 50 ms counter
Correct SF if too high by tuning hysteresis bands in the related operating point
Enable current estimation for torque calculation (see I EST ENABLE parameter group 153.x)
Replace PhaseINTboard if defective.
FaultClass INU FC2
FaultClass ARU
Fault Word 183.23: FW Switching Bit B08
Related Parameters Related IO

Panel Text PUB: WrongSwitch 2


Description In triple, or quadruple INU hard-parallel configurations only. The 3rd INU modulator did not
output the same switching command as the first INU.
Causes Too high switching frequency, or noisy current feedbacks. In exceptional cases a defective
PhaseINT.
Rectification Monitor switching frequency (SF) -- watch especially the 50 ms counter
Correct SF if too high by tuning hysteresis bands in the related operating point
Enable current estimation for torque calculation (see I EST ENABLE parameter group 153.x)
Replace PhaseINTboard if defective.
FaultClass INU FC2
FaultClass ARU
Fault Word 183.23: FW Switching Bit B13
Related Parameters Related IO

72/89 Version LSCI6570 Troubleshooting Manual



Panel Text PUB: WrongSwitch 3
Description In quadruple INU hard-parallel configurations only. The 4th INU modulator did not output the
same switching command as the first INU.
Causes Too high switching frequency, or noisy current feedbacks. In exceptional cases a defective
PhaseINT.
Rectification Monitor switching frequency (SF) -- watch especially the 50 ms counter
Correct SF if too high by tuning hysteresis bands in the related operating point
Enable current estimation for torque calculation (see I EST ENABLE parameter group 153.x)
Replace PhaseINTboard if defective.
FaultClass INU FC2
FaultClass ARU
Fault Word 183.24: FW1 Switching Bit B04
Related Parameters Related IO

Panel Text RMS Ground Current


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.18: FW2 Current Bit b07
Related Parameters Related IO

Panel Text SineFiltCap


Description Damaged sine filter capacitor detected by the AMC SW./ Trips the drive if the filter capacitor
currents do not match an expected value
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.35: FW Other Bit b01
Related Parameters Related IO

Panel Text Speed Measurement


Description Error detected in speed measurement devices.
Causes - If only one device is faulty, an alarm will be generated
- NTAC.02 module defective
- Pulse encoder (speed measurement) defective
- Cabling or connections between position encoder and GRB module
- Internal parameter setting
it is also possible that GRAY module or Position encoder is defective
Rectification See alarm messages: PositionMeasurement and SpeedMeasurement
1 Check cabling and connections between pulse encoder and NTAC module
2 Check cabling and connections between position encoder and GRB module
FaultClass INU FC2
FaultClass ARU
Fault Word 183.29: FW SpeedPosition Bit B02
Related Parameters Related IO

Panel Text SwitchingFreq 1ms1


Description One of the IGCTs/IGBTs in Phase A has switched to often in 1ms window.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.23: FW Switching Bit b04
Related Parameters Related IO

LSCI6570 ACS6000 SD 73/89


 
Panel Text SwitchingFreq 1ms2
Description One of the IGCTs/IGBTs in Phase B has switched to often in 1ms window.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.23: FW Switching Bit b09
Related Parameters Related IO

Panel Text SwitchingFreq 1ms3


Description One of the IGCTs/IGBTs in Phase C has switched to often in 1ms window.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.24: FW1 Switching Bit b00
Related Parameters Related IO

Panel Text SwitchingFreq 1s 1


Description One of the IGCTs/IGBTs in Phase A has switched to often in 1s window.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.23: FW Switching Bit b07
Related Parameters Related IO

Panel Text SwitchingFreq 1s 2


Description One of the IGCTs/IGBTs in Phase B has switched to often in 1s window.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.23: FW Switching Bit b12
Related Parameters Related IO

Panel Text SwitchingFreq 1s 3


Description One of the IGCTs/IGBTs in Phase C has switched to often in 1s window.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.24: FW1 Switching Bit b03
Related Parameters Related IO

Panel Text SwitchingFreq 1ms


Description One of the IGCTs has switched to often in 1ms window.
Causes Hardware problem or mistuning of modulator and motor model.
Rectification '- Check parameter 186.08.
- Call ABB service organization.
- Tune the drive according the commissioning manual.
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.23: FW Switching Bit B0
Related Parameters 186.51 186.52 186.53 186.63 Related IO

74/89 Version LSCI6570 Troubleshooting Manual



Panel Text SwitchingFreq 1s
Description One of the IGCTs has switched to often in 1sec window.
Causes Hardware problem or mistuning of modulator and motor model.
Rectification - Check parameter 186.11.
- Call ABB service organization.
- Tune the drive according to the commissioning manual.
Note! 50 ms, 250 ms, and 1s switching frequency faults are usually disabled. Switching
protection is now based on a thermal model.
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.23: FW Switching Bit B03
Related Parameters 186.60 186.61 186.62 186.66 Related IO

Panel Text SwitchingFreq 50ms


Description One of the IGCTs has switched to often in 50ms window.
Causes Hardware problem or mistuning of modulator and motor model.
Rectification - Check parameter 186.09.
- Call ABB service organization.
- Tune the drive according to the commissioning manual.
Note! 50 ms, 250 ms, and 1s switching frequency faults are usually disabled. Switching
protection is now based on a thermal model.
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.23: FW Switching Bit B01
Related Parameters 186.54 186.55 186.56 186.64 Related IO

Panel Text SwitchingFreq 50ms1


Description One of the IGCTs/IGBTs in Phase A has switched to often in 50ms window.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.23: FW Switching Bit b05
Related Parameters Related IO

Panel Text SwitchingFreq 50ms2


Description One of the IGCTs/IGBTs in Phase B has switched to often in 50ms window.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.23: FW Switching Bit b10
Related Parameters Related IO

Panel Text SwitchingFreq 50ms3


Description One of the IGCTs/IGBTs in Phase C has switched to often in 50ms window.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.24: FW1 Switching Bit b01
Related Parameters Related IO

LSCI6570 ACS6000 SD 75/89


 
Panel Text SwitchingFreq250ms
Description One of the IGCTs has switched to often in 250ms window.
Causes Hardware problem or mistuning of modulator and motor model.
Rectification - Check parameter 186.10.
- Call ABB service organization.
- Tune the drive according to the commissioning manual.
Note! 50 ms, 250 ms, and 1s switching frequency faults are usually disabled. Switching
protection is now based on a thermal model.
FaultClass INU FC2
FaultClass ARU FC1
Fault Word 183.23: FW Switching Bit B02
Related Parameters 186.57 186.58 186.59 186.65 Related IO

Panel Text SwitchingFreq250ms1


Description One of the IGCTs/IGBTs in Phase A has switched to often in 250ms window.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.23: FW Switching Bit b06
Related Parameters Related IO

Panel Text SwitchingFreq250ms2


Description One of the IGCTs/IGBTs in Phase B has switched to often in 250ms window.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.23: FW Switching Bit b11
Related Parameters Related IO

Panel Text SwitchingFreq250ms3


Description One of the IGCTs/IGBTs in Phase C has switched to often in 250ms window.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.24: FW1 Switching Bit b02
Related Parameters Related IO

Panel Text UDC Discharge FT


Description Activated if after 50ms after a discharge FT command no feedback from EPLD is given that FT
has been activated.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.14: FW2 DC LinkVolt Bit b12
Related Parameters Related IO

76/89 Version LSCI6570 Troubleshooting Manual



Alarms

Panel Text AUTORESTART


Description Shows when an auto-restart sequence is performed
Causes depends on the cause for the auto-restart
Rectification Check cause of Autorestart
FaultClass INU A
FaultClass ARU
Fault Word 183.34: AW Other Bit B00
Related Parameters Related IO

Panel Text CCB Communication


Description CCB excitation unit has detected a communication error.
Causes - Wrong node address of the CCB board.
- Fiber optic connection between AMC and CCB board.
- Could happen at the initialization after power cycle.
Rectification - Check node address of CCB board.
- Check F.O. between AMC and CCB.
- Check auxiliary power on CCB.
FaultClass INU A
FaultClass ARU Not used
Fault Word 183.01: AW Communication Bit B11
Related Parameters 131.04 Related IO

Panel Text DCS ArmCurrDev


Description DCS Armature Current Deviation
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.43: AW2 CntrlHardware Bit b11
Related Parameters Related IO

Panel Text DCS Aux Undervolt


Description Auxiliary undervoltage fault from DCS excitation unit.
Causes - Connection to powersupply loose
.
- Power supply turned off by external source.
Rectification - Check hardware.
-
Check control of auxiliary power supply of EXU
FaultClass INU A
FaultClass ARU Not used
Fault Word 183.06: AW1 CntrlHardware Bit B04
Related Parameters Related IO

LSCI6570 ACS6000 SD 77/89


 
Panel Text DCS CH0 DDCS COM
Description DCS excitation unit CH0 communication error.
Causes - Fiber optic link or connected boards faulty.
- Wrong node address of DCS
.
- No Aux power in DCS EXU.
Rectification - Check fiber optic cables and connections
.
- Check node address of DCS.
- Check aux power of DCS.
FaultClass INU A
FaultClass ARU
Fault Word 183.01: AW Communication Bit B06
Related Parameters 131.04 Related IO

Panel Text DCS Cur Ripple


Description DCS excitation unit detected too high current ripple.
Causes - Broken fuse or broken thyristor.
- Too big gain of the current controller.
- Broken current transformer.
Rectification - Check paramneter setting in EXU
.
- Check hardware of EXU.
FaultClass INU A
FaultClass ARU
Fault Word 183.15: AW Current Bit B06
Related Parameters Related IO

Panel Text DCS Ext Fault


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.43: AW2 CntrlHardware Bit b14
Related Parameters Related IO

Panel Text DCS MCB Acknowleg


Description MCB of DCS EXU does not show correct position feedback 10 seconds after closing command.
Causes - Broken wiring to EXU MCB.
- Broken EXU MCB.
Rectification - Check connections in EXU.
-
Check MCB of EXU.
FaultClass INU A
FaultClass ARU Not used
Fault Word 183.06: AW1 CntrlHardware Bit B07
Related Parameters Related IO

Panel Text DCS No Fan Acknowlg


Description Fan contactor in DCF EXU does not show correct feedback 10 seconds after command (EXU fan
may not be running).
Causes - Broken wiring to fan contactor.
- Broken fan contactor.
Rectification - Check connections in EXU
.
- Check fan contactor.
FaultClass INU A
FaultClass ARU Not used
Fault Word 183.06: AW1 CntrlHardware Bit B06
Related Parameters Related IO

78/89 Version LSCI6570 Troubleshooting Manual



Panel Text DCS Overtemperature
Description Overtemperature fault from DCS excitation unit
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.43: AW2 CntrlHardware Bit b05
Related Parameters Related IO

Panel Text DCS: Mains Underv


Description DCS excitation unit detected undervoltage in mains supply.
Causes - Wrong parameter setting in DCS EXU
.
- Lost mains supply of EXU.
Rectification - Check parameter setting in EXU
.
- Check hardware of EXU.
FaultClass INU A
FaultClass ARU
Fault Word 183.25: AW Network Bit B11
Related Parameters Related IO

Panel Text DCS: Not Sync


Description DCS excitation lost synchronization with the supplying network.
Causes - Wrong parameter setting in EXU.
Rectification - Check auxiliary supply and fuses.
- Check auxiliary supply wiring
.
- Check fiber optic cables and connections.
FaultClass INU A
FaultClass ARU
Fault Word 183.25: AW Network Bit B13
Related Parameters Related IO

Panel Text Exu ridethrough


Description EXU mains undervoltage ridethrough ongoing.
Causes EXU mains voltage got to low.
Rectification Check mains voltage level during operation.
FaultClass INU A
FaultClass ARU
Fault Word 183.34: AW Other Bit B02
Related Parameters Related IO

Panel Text EXU: Alarm


Description Generic EXU alarm.
Causes EXU alarm pending.
Rectification - Check Fault logger for pending EXU alarm.
FaultClass INU A
FaultClass ARU
Fault Word 183.31: AW Generic Faults Bit B15
Related Parameters Related IO

LSCI6570 ACS6000 SD 79/89


 
Panel Text EXU: Alpha Min Flt
Description EXCITATION BRIDGE ALPHA MIN LIMIT FAULT
CCB excitation bridge alpha min limit alarm.
Causes - Firing angle alpha is in minimum limit.
Rectification - Check parameters settings.
FaultClass INU A
FaultClass ARU
Fault Word 183.15: AW Current Bit B04
Related Parameters Related IO

Panel Text EXU: Alpha Min Flt


Description Armature overcurrent in DCS excitation unit.
Causes - Broken fuse or broken thyristor
.
- Too big gain of the current controller.
- Broken current transformer.
Rectification - Check parameter setting in EXU.
- Check hardware of EXU.
FaultClass INU A
FaultClass ARU
Fault Word 183.15: AW Current Bit 4
Related Parameters Related IO

Panel Text EXU: BCO Fault


Description EXU: Bridge change over fault.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.34: AW Other Bit B07
Related Parameters Related IO

Panel Text EXU: Communication


Description Issue with the communication between the EXU and the AMC boards
Causes - Wrong node address of the CCB board.
- Fiber optic connection between AMC and CCB board.
- Could happen at the initialization after power cycle.
Rectification - Check node address of CCB board.
- Check F.O. between AMC and CCB.
- Check auxiliary power on CCB.
FaultClass INU A
FaultClass ARU
Fault Word 183.01: AW Communication Bit B12
Related Parameters 131.04 Related IO

Panel Text EXU: CSM1 Timeout


Description EXU: CSM1 Timeout, Current too high for a too long time.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.34: AW Other Bit B06
Related Parameters Related IO

80/89 Version LSCI6570 Troubleshooting Manual



Panel Text EXU: Fault Class 1
Description Class 1 Fault detected in CCB software. Fault reaction is Block Pulses, Trip MCB.
Causes most faults on CCB can be configured to different fault class reactions. e.g. Powerfail is a fault
class 1.
Rectification Check for CCB related faults in the fault buffer. Each faults results in two records in fault buffer:
fault class (this one) and fault message (other fault texts in this file).
FaultClass INU A
FaultClass ARU
Fault Word 183.31: AW Generic Faults Bit B04
Related Parameters Related IO

Panel Text EXU: Fault Class 2


Description Class 2 Fault detected in CCB software. Fault reaction is a phase retard, Trip MCB and block
pulses.
Causes most faults on CCB can be configured to different fault class reactions. e.g. Undervoltage1 is a
fault class 2.
Rectification Check for CCB related faults in the fault buffer. Each faults results in two records in fault buffer:
fault class (this one) and fault message (other fault texts in this file).
FaultClass INU A
FaultClass ARU
Fault Word 183.31: AW Generic Faults Bit B05
Related Parameters Related IO

Panel Text EXU: Fault Class 3


Description Class 3 Fault detected in CCB software. Fault reaction is phase retard and block pulses. MCB
stays closed.
Causes most faults on CCB can be configured to different fault class reactions. e.g. FLGC1_BCO_FLT is
a fault class 3.
Rectification Check for CCB related faults in the fault buffer. Each faults results in two records in fault buffer:
fault class (this one) and fault message (other fault texts in this file).
FaultClass INU A
FaultClass ARU
Fault Word 183.31: AW Generic Faults Bit B06
Related Parameters Related IO

Panel Text EXU: Fuse/TmpSwitch


Description Excitation bridge fuse failure.
Causes - Fuse failure
.
- PAI IO indication fault.
Rectification - Replace fuse if defect.
- Check PAI IO's if connection okay, and fuses okay than PAI is defect => replace PAI.
FaultClass INU A
FaultClass ARU
Fault Word 183.06: AW1 CntrlHardware Bit B03
Related Parameters 131.01 Related IO

Panel Text EXU: No Sync


Description Error indicating that CCB phase locked loop is no longer synchron.
Causes - Synchronisation voltage is missing or out of limit.
Rectification - Check supply voltage.
- Check measurements.
FaultClass INU A
FaultClass ARU
Fault Word 183.25: AW Network Bit B09
Related Parameters Related IO

LSCI6570 ACS6000 SD 81/89


 
Panel Text EXU: Overcurrent
Description CCB excitation DC-overcurrent
Causes Actual current is too big or max limit is set too low.
Rectification - Measure actual current, check par. 155.10 and max limit in par 182.01.
- Check tuning of EXU (CCB parameters).
FaultClass INU A
FaultClass ARU
Fault Word 183.15: AW Current Bit B03
Related Parameters 131.01 Related IO

Panel Text EXU: PAI Communica.


Description Communication error between PAI and CCB.
Firing instant link fault (missing firing instant) => CCB parameter 145.03/Bit3 and 169.05
or PAI1_OVERLOAD : Overload in PAI1 communication => CCB par. 145.03/Bit7 and 169.16.
Causes - Fibre optic links
- Broken PAI
- Aux power on PAI missing
- Broken CCB receiver
Rectification - Check fiber optic cables between between CCB AND PAI boards located in the EXU cabinet.
- Check Aux power on PAI by checking the LED 7(green = Aux power ok)
- Check PAI node address, check CCB node address.
- LED 1 on PAI is red => PAI not ok.
FaultClass INU A
FaultClass ARU
Fault Word 183.01: AW Communication Bit B13
Related Parameters Related IO

Panel Text EXU: Rotor Diode Shrt


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.31: AW Generic Faults Bit b16
Related Parameters Related IO

Panel Text EXU: SupplyFreq


Description Network frequency deviation detected (frequency is below or over a certain limit).
Causes - Network frequency is not within the specified range.
- Measurement device defective.
- PLL not correctly tuned.
Rectification - Check system voltage and frequency
.
- Check measurement
.
- Check tuning of PLL according to SW commissioning manual.
FaultClass INU A
FaultClass ARU
Fault Word 183.25: AW Network Bit B10
Related Parameters Related IO

82/89 Version LSCI6570 Troubleshooting Manual



Panel Text EXU: Undervoltage
Description Supply undervoltage detected by CCB-board: supply voltage magnitude = sqrt(Ud^2 + Uq^2) is
below limit for bridge input voltage (usually = 60% of nominal input voltage)
Causes - Loss of supply voltage for EXU
.
- Variation of supply voltage down to 60% (voltage Dip).
- Measurement Unit Interface MUI-board is defect or connection is wrong.
Rectification - Check supply voltage magnitude and variations.
- Check MUI-board, node address and cable connections.
- Measure ADC channels 0, 1 and 2.
FaultClass INU A
FaultClass ARU
Fault Word 183.25: AW Network Bit B08
Related Parameters Related IO

Panel Text IGCT Test Mode ON


Description IGCT test mode running.
Causes IGCT test mode has been enabled and is now running
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.34: AW Other Bit B17
Related Parameters Related IO

Panel Text INT: EPLD Versions


Description INTs of a multi-inverter configuration, e.g. double, have not the same EPLD version
Causes - Mistake while downloading EPLD
Rectification Download correct version (see loading package version dokuments)
FaultClass INU
FaultClass ARU
Fault Word 183.06: AW1 CntrlHardware Bit B00
Related Parameters Related IO

Panel Text INT0 DI/DT SuperVi


Description Di/dt measurement malfunction (FSCF or VLSCD)
1st inverter
Causes - Fiber optic link from FSCD- to INT-board faulty
- FSCD- or INT-board failure
- Internal parameter setting
Rectification Check fiber optic cables and connections to FSCD-boar
Check clamping diode
FaultClass INU
FaultClass ARU
Fault Word 183.19: AW Short Circuit Bit B03
Related Parameters 186.01 191.08 Related IO

Panel Text INT0 PHA PSU AuxPwr


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.43: AW2 CntrlHardware Bit b02
Related Parameters Related IO

LSCI6570 ACS6000 SD 83/89


 
Panel Text INT0 Wrong EPLD Ver
Description Installed EPLD in INT0 Board not compatible with the SW
Causes
Rectification Check release note of SW for compatible EPLD Version.
FaultClass INU
FaultClass ARU
Fault Word 183.05: AW CntrlHardware Bit B07
Related Parameters Related IO

Panel Text INT1 DI/DT SuperVi


Description Di/dt measurement malfunction (FSCF or VLSCD).
2nd inverter
Causes - Fiber optic link from FSCD- to INT-board faulty
- FSCD- or INT-board failure
- Internal parameter setting
Rectification Check fiber optic cables and connections to FSCD-board
Check clamping diode
FaultClass INU
FaultClass ARU
Fault Word 183.19: AW Short Circuit Bit B06
Related Parameters 191.08 Related IO

Panel Text INT1 PHA PSU AuxPwr


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.43: AW2 CntrlHardware Bit b11
Related Parameters Related IO

Panel Text INT1 Wrong EPLD Ver


Description Installed EPLD in INT1 Board not compatible with the SW
Causes Wrong HW installed
Rectification Check release note of SW for compatible EPLD Version.
FaultClass INU
FaultClass ARU
Fault Word 183.06: AW1 CntrlHardware Bit B01
Related Parameters Related IO

Panel Text INT2 DI/DT SuperVi


Description Di/dt measurement malfunction (FSCF or VLSCD)
3rd inv (Alarm)
Causes - Fiber optic link from FSCD- to INT-board faulty
- FSCD- or INT-board failure
- Internal parameter setting
Rectification Check fiber optic cables and connections to FSCD-board
Check clamping diode
FaultClass INU
FaultClass ARU
Fault Word 183.19: AW Short Circuit Bit B09
Related Parameters 191.08 Related IO

84/89 Version LSCI6570 Troubleshooting Manual



Panel Text INT2 PHA PSU AuxPwr
Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.43: AW2 CntrlHardware Bit b05
Related Parameters Related IO

Panel Text INT2 Wrong EPLD Ver


Description Installed EPLD in INT2 Board not compatible with the SW
Causes Wrong HW installed
Rectification Check release note of SW for compatible EPLD Version.
FaultClass INU
FaultClass ARU
Fault Word 183.06: AW1 CntrlHardware Bit B10
Related Parameters Related IO

Panel Text INT3 DI/DT SuperVi


Description Di/dt measurement malfunction (FSCF or VLSCD)
4th inv (Alarm)
Causes - Fiber optic link from FSCD- to INT-board faulty
- FSCD- or INT-board failure
- Internal parameter setting
Rectification Check fiber optic cables and connections to FSCD-board
Check clamping diode
FaultClass INU
FaultClass ARU
Fault Word 183.19: AW Short Circuit Bit B12
Related Parameters 191.08 Related IO

Panel Text INT3 PHA PSU AuxPwr


Description
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.43: AW2 CntrlHardware Bit b05
Related Parameters Related IO

Panel Text INT3 Wrong EPLD Ver


Description Installed EPLD in INT3 Board not compatible with the SW
Causes Wrong HW installed
Rectification Check release note of SW for compatible EPLD Version.
FaultClass INU
FaultClass ARU
Fault Word 183.05: AW CntrlHardware Bit B10
Related Parameters Related IO

Panel Text LicenseComm missing


Description Commissioning license missing
Causes Commissioning license missing or wrong in parameter "100.22 ACCESS CODE STR".
Rectification Contact regional service center for a license key. ID number in parameter "100.21 DONGLE ID
NUMBER" must be provided.
FaultClass INU Alarm
FaultClass ARU
Fault Word 183.107: License Alarm Bit B00
Related Parameters Related IO

LSCI6570 ACS6000 SD 85/89


 
Panel Text Motor Underload
Description The actual rms motor current is outside the operating range.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.34: AW Other Bit B03
Related Parameters Related IO

Panel Text PositionMeasurement


Description Error detected in position measurement device LD-GRB01
Causes - GRB Driver is not initialised correctly e.g. incorrect node number
- Fiber optic connection from Driver to AMC-33 ch2 is disconnected
Rectification See fault messages NTAC Missing and
GRAY Missing
1 check fiber optic cables from AMC-board Ch2 to LD-GRB01 module
2 check node number of LD-GRB01 and adjust it if necessary
3 check aux. supply of module, indication of LED
4 cycle aux. power in COU to re-initialise the LD-GRB01 by AMC-card.
FaultClass INU
FaultClass ARU
Fault Word 183.28: AW SpeedPosition Bit B01
Related Parameters Related IO

Panel Text PUB ArcGuard Link FLT


Description Communication link problem between PUB and ArcGuard.
Causes AMC can't communicate to ArcGuard device via the MainINT (PUB) board
Rectification If no ArcGuard device installed, disable ArcGuard protection in the software
Check connections between AMC and ArcGuard
Check ArcGuard device
FaultClass INU A
FaultClass ARU
Fault Word 183.19: AW Short Circuit Bit B13
Related Parameters Related IO

Panel Text PUB: INT0 Faulted


Description There is a fault pending on INT0
Causes All possible INT faults
Rectification Check fault buffer for related INT0 faults
FaultClass INU
FaultClass ARU
Fault Word 183.31: AW Generic Faults Bit B04
Related Parameters Related IO

Panel Text PUB: INT1 Faulted


Description There is a fault pending on INT1
Causes All possible INT faults
Rectification Check fault buffer for related INT1 faults
FaultClass INU
FaultClass ARU
Fault Word 183.31: AW Generic Faults Bit B05
Related Parameters Related IO

86/89 Version LSCI6570 Troubleshooting Manual



Panel Text PUB: INT2 Faulted
Description There is a fault pending on INT2
Causes All possible INT faults
Rectification Check fault buffer for related INT2 faults
FaultClass INU
FaultClass ARU
Fault Word 183.31: AW Generic Faults Bit B06
Related Parameters Related IO

Panel Text PUB: INT3 Faulted


Description There is a fault pending on INT3
Causes All possible INT faults
Rectification Check fault buffer for related INT3 faults
FaultClass INU
FaultClass ARU
Fault Word 183.31: AW Generic Faults Bit B10
Related Parameters Related IO

Panel Text PUB: Wrong EPLD Ver


Description Installed EPLD in PUB Board not compatible with the SW
Causes Old PUB version installed or downloaded
Rectification Check release note of SW for compatible PUB EPLD Version
FaultClass INU
FaultClass ARU
Fault Word 183.06: AW1 CntrlHardware Bit B14
Related Parameters Related IO

Panel Text RBU Disabled


Description DIU/VLU/RBU/BCU operation is disabled. The temperature rise has reached 192.18 RBU ON-
>OFF TEMP.
Causes High dc-link voltage, braking, NP-control with NP-limiter, dc-voltage measurement problem,
parameters.
Rectification 1) Check operation mode.
2) Check dc-voltages.
3) Check NP-voltages.
4) Check parameters in 192.
FaultClass INU
FaultClass ARU
Fault Word 183.11: AW DC LinkVoltage Bit B14
Related Parameters 192.16 192.17 192.18 192.19 192.20 Related IO

Panel Text RBU Temp rise


Description Max RBU/BCU temp rise has reached level of 134.17 DIS NP LIM T RISE - the NP-limiter is
disabled.
Causes High dc-link voltage, braking with RBU/BCU, NP-control with NP-limiter, dc-voltage
measurement problem, parameters.
Rectification Ignore in case of generative/braking operation - note that NP-voltage has to be controlled in
other means than NP-limiter after the alarm.
1) Check the dc-link voltages.
2) Check NP-voltages.
FaultClass INU
FaultClass ARU
Fault Word 183.11: AW DC LinkVoltage Bit B13
Related Parameters 192.14 192.15 Related IO

LSCI6570 ACS6000 SD 87/89


 
Panel Text Ridethrough
Description Torque control is in ridethrough mode: torque reference is generated by ridethrough control
Causes - Supply voltage interruppted
- DC voltage below ridethrough level
- Supply voltage too low
Rectification \'- check supply network quality
- Check parameter 132.25 UDC NORM2RT
FaultClass INU
FaultClass ARU
Fault Word 183.11: AW DC LinkVoltage Bit B00
Related Parameters Related IO

Panel Text Ridethrough NetUnVo


Description Indicating that the drive is in undervoltage limiter operation.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.11: AW DC LinkVoltage Bit b04
Related Parameters Related IO

Panel Text RMS Ground Current


Description Current in sine filter star point connection to ground is exceeding threshold
Causes Weak ground fault
Measurement system fault
Rectification Check and measure the complete ACS1000 drive system (transformer, converter, motor and
power cables) for possible cause of the earth fault. Test if a current transducer is the cause of
the fault. Check The ADCVI - , INT-board or SCA subprint
FaultClass INU A
FaultClass ARU Not Appl.
Fault Word 183.15: AW Current Bit B07
Related Parameters Related IO

Panel Text RSD: F Pos Encoder


Description Remote position difference too large.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.28: AW SpeedPosition Bit B02
Related Parameters Related IO

Panel Text RSD: Redundancy lost


Description RSD: Redundancy control lost.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.34: AW Other Bit B01
Related Parameters Related IO

88/89 Version LSCI6570 Troubleshooting Manual



Panel Text Speed Measurement
Description Error detected in speed measurement device NTAC-02
Causes - Driver not initialised correctly e.g. encoder enabled without cycling aux. power.
- fiber optic connection from Driver to AMC-33 ch2 is disconnected.
Rectification See fault messages NTAC Missing and GRAY Missing
1 check fiber optic cables from AMC-board Ch2 to NTAC-02 module
2 check power supply of NTAC-02 module and correct jumper
3 cycle aux. power in COU to allow re-initialisation of NTAC-02 driver by AMC-card.
FaultClass INU
FaultClass ARU
Fault Word 183.28: AW SpeedPosition Bit B02
Related Parameters Related IO

Panel Text SSI Parity Error


Description SSI parity counter alarm.
Causes
Rectification
FaultClass INU
FaultClass ARU
Fault Word 183.28: AW SpeedPosition Bit B05
Related Parameters Related IO

Panel Text SSI Redu Enc Mismatch


Description Speed mismatch between redundant SSI encoders
Causes In system with a redundant SSI encoder present. Speed is compare between the 2 encoders. If
speed mismatch for a defined time period, this alarm is shown.
Rectification Verify encoders.
FaultClass INU
FaultClass ARU
Fault Word 183.28: AW SpeedPosition Bit B08
Related Parameters Related IO

For missing information contact ABB support line.

LSCI6570 ACS6000 SD 89/89