0% found this document useful (0 votes)
164 views5 pages

1SFL427001R1311-af116-30-11-13 Contactor PDF

The document provides product details for an AF116-30-11-13 contactor. It is a 3 pole contactor that can control motors up to 55 kW at 400V AC or 75 hp at 480V, and switch power circuits up to 160A. It has a wide control voltage range of 100-250V and built-in surge protection. The contactor has a block type design and can be extended with additional auxiliary contacts and accessories.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
164 views5 pages

1SFL427001R1311-af116-30-11-13 Contactor PDF

The document provides product details for an AF116-30-11-13 contactor. It is a 3 pole contactor that can control motors up to 55 kW at 400V AC or 75 hp at 480V, and switch power circuits up to 160A. It has a wide control voltage range of 100-250V and built-in surge protection. The contactor has a block type design and can be extended with additional auxiliary contacts and accessories.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

PRODUCT-DETAILS

AF116-30-11-13
AF116-30-11-13 Contactor

General Information
Extended Product Type AF116-30-11-13

Product ID 1SFL427001R1311

EAN 7320500476376

Catalog Description AF116-30-11-13 Contactor

The AF116-30-11-13 is a 3 pole - 690 V IEC or 600 V UL contactor with pre-mounted


auxiliary contacts and double clamp, controlling motors up to 55 kW / 400 V AC (AC-3) or 75
hp / 480 V UL and switching power circuits up to 160 A (AC-1) or 160 A UL general use.
Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V
Long Description 50/60 Hz and DC), managing large control voltage variations, reducing panel energy
consumptions and ensuring distinct operations in unstable networks. Furthermore, surge
protection is built-in, offering a compact solution. AF contactors have a block type design,
can be easily extended with add-on auxiliary contact blocks and an additional wide range of
accessories.

Ordering
Minimum Order Quantity 1 piece

Customs Tariff Number 85364900

Popular Downloads
Data Sheet, Technical 1SBC100192C0206
Information
AF116-30-11-13 2

Instructions and Manuals 1SFC100003M0201

Dimension Diagram 1SFB535001G1051

Dimensions
Product Net Width 90 mm

Product Net Depth / 126 mm


Length

Product Net Height 150 mm

Product Net Weight 1.55 kg

Technical
Number of Main Contacts 3
NO

Number of Main Contacts 0


NC

Number of Auxiliary 1
Contacts NO

Number of Auxiliary 1
Contacts NC

Rated Operational Voltage Main Circuit 690 V

Rated Frequency (f) Main Circuit 50 / 60 Hz

Conventional Free-air acc. to IEC 60947-4-1, Open Contactors q = 40 °C 160 A


Thermal Current (I th )

Rated Operational Current (690 V) 40 °C 160 A


AC-1 (I e ) (690 V) 60 °C 145 A
(690 V) 70 °C 130 A

Rated Operational Current (415 V) 55 °C 116 A


AC-3 (I e ) (440 V) 55 °C 116 A
(500 V) 55 °C 110 A
(690 V) 55 °C 65 A
(380 / 400 V) 55 °C 116 A
(220 / 230 / 240 V) 55 °C 116

Rated Operational Power (415 V) 55 kW


AC-3 (P e ) (440 V) 75 kW
(500 V) 75 kW
(690 V) 55 kW
(380 / 400 V) 55 kW
(220 / 230 / 240 V) 30 kW

Rated Breaking Capacity 8 x Ie AC-3


AC-3

Rated Making Capacity 10 x Ie AC-3


AC-3

Short-Circuit Protective gG Type Fuses 250 A


Devices

Rated Short-time at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 928 A
Withstand Current Low at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 160 A
Voltage (I cw ) at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 379 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1160 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 536 A

Maximum Breaking cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 2000 A
Capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1000 A

Maximum Electrical (AC-1) 300 cycles per hour


Switching Frequency (AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour

Rated Operational Current (110 V) 2 Poles in Series, 40 °C 145 A


AF116-30-11-13 3

DC-1 (I e ) (220 V) 3 Poles in Series, 40 °C 145 A

Rated Operational Current (110 V) 2 Poles in Series, 40 °C 145 A


DC-3 (I e ) (220 V) 3 Poles in Series, 40 °C 145 A

Rated Operational Current (110 V) 2 Poles in Series, 40 °C 145 A


DC-5 (I e ) (220 V) 3 Poles in Series, 40 °C 145 A

Rated Insulation Voltage acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
(U i ) acc. to UL/CSA 600 V

Rated Impulse Withstand Main Circuit 8 kV


Voltage (U imp )

Mechanical Durability 5 million

Maximum Mechanical 300 cycles per hour


Switching Frequency

Coil Operating Limits (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)

Rated Control Circuit 50 Hz 100 ... 250 V


Voltage (U c ) 60 Hz 100 ... 250 V
DC Operation 100 ... 250 V

Coil Consumption Holding at Max. Rated Control Circuit Voltage 50 Hz 6 V·A


Holding at Max. Rated Control Circuit Voltage 60 Hz 6 V·A
Holding at Max. Rated Control Circuit Voltage DC 3 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 130 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 130 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 135 W

Operate Time Between Coil De-energization and NO Contact Opening 37 ... 47 ms


Between Coil Energization and NO Contact Closing 25 ... 55 ms

Connecting Capacity Main Flexible 2 x 10 ... 70 mm²


Circuit Rigid Cu-Cable 2 x 10 ... 95 mm²

Connecting Capacity Flexible with Ferrule 2x 0.75 ... 2.5 mm²


Auxiliary Circuit Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible 2x0.75 ... 2.5 mm²
Solid 2 x 1 ... 4 mm²
Stranded 2 x 1 .... 4 mm²

Degree of Protection acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00

Terminal Type Double Clamp

Technical UL/CSA
Maximum Operating Main Circuit 600 V
Voltage UL/CSA

General Use Rating (600 V AC) 160 A


UL/CSA

Horsepower Rating (200 V AC) Three Phase 30 hp


UL/CSA (208 V AC) Three Phase 30 hp
(220 ... 240 V AC) Three Phase 40 hp
(440 ... 480 V AC) Three Phase 75 hp
(550 ... 600 V AC) Three Phase 100 hp

Environmental
Ambient Air Temperature Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C
Close to Contactor for Storage -40 ... +70 °C

Maximum Operating Without Derating 3000 m


Altitude Permissible

RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
AF116-30-11-13 4

Certificates and Declarations (Document Number)


ABS Certificate 14-LD1092198-PDA

BV Certificate BV_36353_A0BV

CB Certificate SEMKO_SE-70479M1

CCS Certificate GB14T00030

CQC Certificate CQC2013010304604055

cUL Certificate 20120925-E36588

Declaration of Conformity 2020980304001304


- CCC

Declaration of Conformity 2CMT2015-005439


- CE

DNV Certificate DNV_E-14043

DNV GL Certificate DNV_E-14043

EAC Certificate 9AKK107046A8618

Environmental Information 2CMT004732


1SAC200032H0002

GL Certificate DNV_E-14043

Instructions and Manuals 1SFC100003M0201

LR Certificate LR_14_70011(E1)

PRS Certificate TE_2092_880423_16

RINA Certificate ELE060313XG_002

RMRS Certificate 9AKK107045A6978

RoHS Information 2CMT2015-005439

UL Listing Card UL_E36588

Container Information
Package Level 1 Units box 1 piece

Package Level 1 Width 207 mm

Package Level 1 Depth / 216 mm


Length

Package Level 1 Height 150 mm

Package Level 1 Gross 1.75 kg


Weight

Package Level 1 EAN 7320500476376

Classifications
Object Classification Code Q

ETIM 4 EC000066 - Magnet contactor, AC-switching

ETIM 5 EC000066 - Magnet contactor, AC-switching

ETIM 6 EC000066 - Power contactor, AC switching

ETIM 7 EC000066 - Power contactor, AC switching

eClass V11.0 : 27371003

UNSPSC 39121529

IDEA Granular Category 4755 >> Contactors


Code (IGCC)

E-Number (Finland) 3706167


AF116-30-11-13 5

E-Number (Norway) 4117610

E-Number (Sweden) 3210068

Where Used (as part of "kit")


Identifier Description Type

3HAC059249-001 Contactor set Kit