FireworX Catalog u Small Building Solutions

Intelligent Input-Output
Modules
Models: FX-2WIRE, FX-IDC1A,
FX-IDC2B, FX-IDCWS, FX-ISO,
FX-NAC, FX-RLY, FX-IDC1B

Overview Standard Features


FireworX intelligent modules are engineered to deliver high-perfor­ • Class A-B Two-Wire Module
mance features, superb reliability, and unbeatable quality. From Acts as an interface between conventional two-wire smoke
control of ancillary equipment, to enhanced signaling functionality, detectors and the FireworX control panel.
these products add flexibility and powerful options to FireworX
• Analog Class A Single Input Module
intelligent systems.
Used to connect a normally open, alarm, supervisory, or moni-
Designed expressly for small buildings, FireworX modules are tor type dry contact initiating device circuit to the FireworX
addressable devices that are uniquely identified on the system by control panel.
means of familiar rotary switches. Once registered, they share data • Analog Dual Input Module
and update status information that determines how the system Connects two normally open, alarm, supervisory, or monitor
behaves and how connected devices interact with one another. type dry contact initiating device circuits to the FireworX control
Unique to FireworX modules is ground fault detection so precise panel.
that it actually pinpoints the specific module where the wiring • Analog Dual Input Waterflow, Supervisory Module
problem has occurred. This saves hours of troubleshooting and Used to connect normally open waterflow alarm and supervi-
wire tracing. And only FireworX provides this important feature! sory initiating device circuits to the FireworX control panel. For
The FireworX family of intelligent modules also offers contractors Class B circuit operation.
and installers simple setup and installation, while delivering options • Analog SLC Fault Isolator Module
that take full advantage of intelligent fire alarm processing. With a Protects a Class A SLC from total collapse due to wire-to-wire
microprocessor in each device, intelligence is distributed through- short circuits.
out the system so that command decisions are made instantly
at the individual module, rather than bottlenecking at the control • Analog NAC Module
panel. Connects a supervised output circuit to a signal riser.
• Analog Contact Relay Module
This not only speeds event processing, it also makes a more ro-
Provides one Form C dry relay contact and can be configured
bust and reliable system – so robust, in fact, that when upgrading
to provide polarity reversal of its output.
from a conventional panel to a FireworX intelligent system, you can
usually use existing wiring – no twisted or shielded cable required! • Analog Single Input Mini Module
Connects a normally open, alarm, supervisory, or monitor type
dry contact initiating device circuit (IDC) to the FireworX control
panel. For Class B circuit operation.

Page 1 of 6 D ATA S H E E T FX85001-0611


Not to be used for installation purposes. Issue 1
Module Addressing Installation
Use a screwdriver to adjust the two rotary switches on the front of
the module. Set the TENS rotary switch (0 through 12) for the 10s
digit and the ONES rotary switch for the 0 through 9 digit.

Insert
screwdriver
here

Compatible
electrical box
Example: device address 21, set TENS rotary switch to 2
and set the ONES rotary switch to 1.
Module
Refer to the Specifications Table for available address numbers. Screw

4-24
LED operation screws

Modules provide a bicolor LED for status indication. Wall plate


Flashing Green LED Normal
Mount in a North American 4 inch square x 2-1/2 in. (64 mm)
Flashing Red LED Active
deep 2 gang box or a standard 4 in. square box 1-1/2 in. (38 mm)
deep.

Class A Single Input Module FX-IDC1A

The Class A Single Input Module is used to connect a normally Communication line voltage Maximum 20 V peak-to-peak
open, alarm, supervisory, or monitor type dry contact initiating Current
device circuit (IDC) to the FireworX control panel. The module is Standby 400 μA
designed for Class A circuit operation. Activated 500 μA
Ground fault impedance 10 k ohm
The module's device address is set using the two rotary switches Operating environment
located on the front of the module. One device address is re- Temperature 32 to 120°F (0 to 49°C)
quired. Humidity 0 to 93% RH, noncondensing at 90°F
(32°C)
The device can be preset for alarm or supervisory operation using
Storage temperature range –4 to 140°F (–20 to 60°C)
the slide switch located on the front of the module. The module
Compatible electrical boxes North American 4 inch square x 2-1/2
can also be configured for other device types through front panel in. (64 mm) deep 2 gang box
programming or the configuration utility. Standard 4 in. square box 1-1/2 in. (38
Style D Class A
mm) deep box
Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5,
( ) 1.0, or 0.75 sq. mm)  (Sizes 16 and 18
(+)
(+) RETURN
AWG are preferred)
( )
To next SLC out (+)
device SLC out ( ) SLC (+) IDC
Device address 01 to 64 (64 point control panel)
From ( ) 01 to 127 (127 point control panel)
SLC in (+)
previous TB2 TB1
Initiating device circuit (IDC)
device SLC in ( )
Typical NO Max. circuit resistance 50 Ω (25 Ω per wire)
Initiating device Max. circuit capacitance 0.1 μF

Warning Caution
This module will not operate without electrical power. As fires
frequently cause power interruption, you should discuss further Wire in accordance with NFPA 72 and CAN/
safeguards with your local fire protection specialist. ULC-S524. Be sure to observe the polarity of the
This module does not support conventional smoke detectors.
wires as shown in the diagram.

Page 2 of 6 D ATA S H E E T FX85001-0611


Not to be used for installation purposes. Issue 1
Class A-B Two-Wire Module FX-2WIRE

The FX-2WIRE module interfaces between conventional two-wire The FX-2WIRE can be set for Class B or Class A operation using
smoke detectors and the FireworX control panel. It monitors the the slide switch located on the front of the module.
circuit and smoke detectors, and signals the control panel of any
Note: This module cannot be used on a device loop with isolator
trouble or alarm conditions. The module also regulates and super-
modules or isolator bases.
vises the 24 VDC input power.
The FX-2WIRE is configured to operate as a two-wire alarm device Communication line voltage Maximum 20.6 V peak-to-peak
that does not require alarm verification. It can be set for two-wire Current Standby: 350 μA. Activated: 350 μA
alarm verified operation through front panel programming or the Control panel input power 12.4 to 28.3 VDC (not resettable)
configuration utility. When using the alarm verification feature of the Smoke power current Standby: 17 mA. Alarm: 58 mA
control panel, do not mix normally open contact initiating devices Smoke detector current 3 mA
with two-wire conventional smoke detectors. UL compatibility ID 0.0
Ground fault impedance 5 k ohm
This module recognizes the CleanMe signal from detectors that Operating environment
support this feature. Temperature 32 to 120°F (0 to 49°C)
Humidity 0 to 93% RH, noncondensing at 90°F
The device address is set using the two rotary switches located on (32°C)
the front of the module. One device address is required. Storage temperature –4 to 140°F (–20 to 60°C)
Compatible North American 4 inch square x
electrical boxes 2-1/2 in. (64 mm) deep 2 gang box.
Standard 4 in. square box 1-1/2 in. (38
From control 24 V +
panel (not
Style D (Class A) mm) deep
resettable) 24 V Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5,
(+) (+)
DET. PWR.
( ) ( ) RETURN 1.0, or 0.75 sq. mm)  (Sizes 16 and 18
To next SLC out (+)
(+) (+) AWG are preferred)
device SLC out ( ) SLC ( ) DET. Device address 01 to 64 (64 point control panel)
01 to 127 (127 point control panel)
( ) + +
From SLC in (+) TB2 TB1
previous
device
SLC in ( ) Initiating device circuit
Style B (Class B)
4.7 k Ohm EOLR
Used for
EOL resistor value 4.7 kΩ, (P/N: EOL-4.7)
Class B only Max. circuit resistance 50 Ω (25 Ω per wire)
Typical
Max. circuit capacitance 0.1 μF
initiating
device

Dual Input Module FX-IDC2B

The FX-IDC2B connects two normally open, alarm, supervisory, Communication line voltage Maximum 20 V peak-to-peak
or monitor type dry contact initiating device circuits (IDCs) to the Current
FireworX control panel. This module is designed for Class B circuit Standby 550 μA
operation. Activated 725 μA
Ground fault impedance 10 k ohm
The device address is set using the two rotary switches located on
Operating environment
the front of the module. Two consecutive addresses are required. Temperature 32 to 120°F (0 to 49°C)
The second address is automatically assigned one number higher Humidity 0 to 93% RH, noncondensing at 90°F
than the value set on the rotary switches. (32°C)
Storage temperature range –4 to 140°F (–20 to 60°C)
The FX-IDC2B can be preset for alarm or supervisory operation
Compatible electrical boxes North American 4 inch square x 2-1/2
using the slide switch located on the front of the module. It can
in. (64 mm) deep 2 gang box
also be configured for other device types through front panel pro- Standard 4 in. square box 1-1/2 in.
gramming or the configuration utility. (38 mm) deep
Style B (Class B) Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5,
1.0, or 0.75 sq. mm)  (Sizes 16 and 18
AWG are preferred)
(+)
47 k Ohm
EOLR Device address 01 to 63 (64 point control panel)
( ) IDC2 01 to 126 (127point control panel)
To next SLC out (+)
(+) (+) Initiating device circuit (IDC)
device SLC out ( ) SLC ( ) IDC1
EOL resistor value 47 kΩ, (P/N: EOL-47)
( ) 47 k Ohm
From SLC in (+) TB2 TB1 EOLR Max. circuit resistance 50 Ω (25 Ω per wire)
previous
device
SLC in ( ) Max. circuit capacitance 0.1 μF
Typical NO
initiating device

Page 3 of 6 D ATA S H E E T FX85001-0611


Not to be used for installation purposes. Issue 1
Dual Input Waterflow, Supervisory Module FX-IDCWS

The FX-IDCWS connects normally open waterflow alarm and contact initiating devices. When the NO input contact of an
supervisory initiating device circuits (IDCs) to the FireworX control initiating device is closed, a supervisory signal is sent to the
panel. The FX-IDCWS is designed for Class B circuit operation. control panel and the supervisory condition is not latched at
the module.
The device address is set using the two rotary switches located on
the front of the module. Two consecutive addresses are required. • Latching: Configures the module for normally open dry
The second address is automatically assigned one number higher contact initiating devices. When the NO input contact of an
that the value set on the rotary switches. initiating device is closed, a supervisory signal is sent to the
control panel and the supervisory condition is not latched at
The FX-IDCWS can operate in the following modes:
the module.
Waterflow
• Alarm latching delayed: Configures the module for use with Communication line voltage Maximum 20 V peak-to-peak
only nonretarded waterflow alarm switches. When the NO Current
input contact of an initiating device is closed, an alarm is Standby 550 μA
sent to the control panel, which after a 16 second time delay, Activated 725μA
generates an alarm signal. Ground fault impedance 10 k ohm
Operating environment
Supervisory Temperature 32 to 120°F (0 to 49°C)
• Supervisory active nonlatching US marketplace Humidity 0 to 93% RH
Storage temperature range –4 to 140°F (–20 to 60°C)
• Supervisory active latching Canadian marketplace Compatible electrical boxes North American 4 inch square x 2-1/2
in. (64 mm) deep 2 gang box
• Nonlatching: Configures the module for normally open dry
Typical NO
Standard 4 in. square box 1-1/2 in.
Style B (Class B)
Supervisory/ (38 mm) deep
Tamper Switch
Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5,
1.0, or 0.75 sq. mm)  (Sizes 16 and
(+)
47 k Ohm
EOLR
18 AWG are preferred)
( ) SUP. Device address 01 to 63 (64 point control panel)
To next SLC out (+)
(+) (+) 01 to 126 (127 point control panel)
Initiating device circuit (IDC)
device SLC out ( ) SLC ( ) W/FLOW
( ) 47 k Ohm
From SLC in (+) TB2 TB1 EOLR EOL resistor value 47 kΩ, (P/N: EOL-47)
previous SLC in ( )
device Max. circuit resistance 50 Ω (25 Ω per wire)
Typical NO
Max. circuit capacitance 0.1 μF
Waterflow Switch

SLC Fault Isolator Module FX-ISO


Communication line voltage Maximum 20 V peak-to-peak
The FX-ISO protects a Class A SLC from total collapse due to
Current
wire-to-wire short circuits. The module monitors line voltages and
Standby 175 μA
opens the SLC when a short is detected. A short is isolated be- Activated 200 μA
tween the two modules located electrically closest to the short. Ground fault impedance 10 k ohm
The device address is set using the two rotary switches located on Maximum circuit resistance 6 ohm
the front of the module. One device address is required. between isolators
Operating environment
Temperature 32 to 120°F (0 to 49°C)
Humidity 0 to 93% RH, noncondensing at 90°F
(32°C)
(+) Storage temperature range –4 to 140°F (–20 to 60°C)
To next
device SLC OUT ( ) Compatible electrical boxes North American 4 inch square x 2-1/2
( )
(+) in. (64 mm) deep 2 gang box
From
SLC IN Standard 4 in. square box 1-1/2 in.
previous ( )
device
( ) (38 mm) deep
TB2 Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5,
1.0, or 0.75 sq. mm)  (Sizes 16 and 18
AWG are preferred)
Module address 01 to 64 (64 point control panel)
01 to 127 (127 point control panel)

Page 4 of 6 D ATA S H E E T FX85001-0611


Not to be used for installation purposes. Issue 1
NAC Module FX-NAC

The FX-NAC connects a supervised output circuit to a signal riser. The FX-NAC is configured to operate as a Genesis Audible/Visual/
The output wiring is monitored for open and short circuits. A short Silence device type from the factory. It can also be configured
circuit causes the module to inhibit the activation of the audible/ for other device types through front panel programming or the
visual signal circuit so the riser is not connected to the wiring fault. configuration utility. Refer to the applicable control panel technical
Upon command from the control panel, the module connects the reference manual for a list of available device types.
output circuit to the riser input. The output circuit energizes a riser
Genesis Audible/Visual/Silence: Used with Genesis and En-
to operate polarized audible and visual signals. The module can
hanced Integrity horns and strobes. Signals maintain synchroniza-
be used for connection of a Class A or Class B (with EOL) output
tion per UL 1971. For Genesis devices, this configuration allows
notification appliance circuit (NAC).
connected horns to be silenced while strobes on the same two-
From 24 VDC (+) wire circuit continue to flash until the panel is reset.
listed Style Z (Class A)
power 24 VDC ( ) Communication line voltage Maximum 20 V peak-to-peak
supply Typical horn or
[4] (+)
strobe circuit Current
NAC PWR. IN ( ) ( ) RETURN Standby 350 μA
To next SLC out (+)
(+)
Activated 200 μA
device SLC
SLC out ( )
( )
( ) NAC
+ + Ground fault impedance 10 k ohm
From
previous
SLC in (+)
TB2 TB1
- - Operating environment
SLC in ( )
device Temperature 32 to 120°F (0 to 49°C)
47 k Ohm ELOR
Style Y (Class B) used for Humidity 0 to 93% RH, noncondensing at 90°F
Class B only (32°C)
Output ratings
Circuit current 24 VDC at 2 A max.
Style Z (Class A) EOL resistor value 47 kΩ UL listed
Typical bell circuit Storage temperature range –4 to 140°F (–20 to 60°C)
Circuit wired Compatible electrical boxes North American 4 inch square x 2-1/2
same as in. (64 mm) deep 2 gang box
diagram above
+ + + + Standard 4 in. square box 1-1/2 in.
(38 mm) deep
- - - -
Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5,
Style Y (Class B) 47 k Ohm EL
used for
OR
1.0, or 0.75 sq. mm)  (Sizes 16 and 18
Class B only AWG are preferred)
Device address 01 to 64 (64 point control panel)
(one address required) 01 to 127 (127 point control panel)

Contact Relay Module FX-RLY


The FX-RLY provides one Form C dry relay contact. It can also be Communication line voltage Maximum 20 V peak-to-peak
configured to provide polarity reversal of its output. The FX-RLY Current
can be used to control external appliances or shut down equip- Standby 125 µA
ment. Activated 125 µA
Contact ratings (pilot duty)
The FX-RLY is wired according to its operation. It is configured to
30 VDC 2A
operate as a relay nonsilence device type, and can function as either 125 VAC 0.5A resistive load 60 W or 62.5 VA
a control relay or polarity reversal relay, depending on how it is wired. max.
Control relay function: Provides one Form C dry relay contact. Relay type Form C, programmable
Ground fault impedance 10 k ohm
Polarity reversal relay function: Provides polarity reversal of its Operating environment
output. Temperature 32 to 120°F (0 to 49°C)
Humidity 0 to 93% RH, noncondensing at 90°F
Note: Additional device types are available through front panel (32°C)
programming or the configuration utility. Refer to applicable control Storage temperature range –4 to 140°F (–20 to 60°C)
panel technical reference manual. Compatible electrical boxes North American 4 inch square x 2-1/2
in. (64 mm) deep 1 gang box
North American 4 inch square x 2-1/2
in. (64 mm) deep 2 gang box
Standard 4 in. square box 1-1/2 in. (38
(NC)
(NO)
Normally closed mm) deep box
SLC out (+) (+) (C)
Normally open Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5,
To next Common
device SLC out ( )
SLC 1.0, or 0.75 sq. mm)  (Sizes 16 and 18
Not used
( ) AWG are preferred)
From SLC in (+) TB2 TB1
previous SLC in ( )
Module address 01 to 64 (64 point control panel)
device (one address required) 01 to 127 (127 point control panel)

Page 5 of 6 D ATA S H E E T FX85001-0611


Not to be used for installation purposes. Issue 1
Single Input Mini Module
FX-IDC1B
The FX-IDC1B connects a normally open, alarm, supervisory, or monitor type dry con-
tact initiating device circuit (IDC) to the FireworX control panel. This module is for Class B
Contact us... circuit operation.
Email: [email protected]
Web: http://fireworx.edwardsfire.com/ The device address is set using the two rotary switches located on the front of the mod-
FireworX is an EDWARDS brand.
ule. One device address is required.
1016 Corporate Park Drive The module is configured to operate as an alarm latching device type from the factory.
Mebane, NC 27302
When the NO contact of an initiating device is closed, an alarm signal is sent to the con-
© 2013 UTC Fire & Security Americas trol panel and the alarm condition is latched at the module.
Corporation, Inc. All rights reserved.
Specifications subject to change Additional device types are available through front panel programming or the configuration
without notice. Edwards is part of UTC utility. Refer to applicable control panel technical reference manual.
Climate, Controls & Security, a unit of
United Technologies Corporation.
Communication line voltage Maximum 20 V peak-to-peak
Current
Standby 350 μA
Activated 500 μA
Ground fault impedance 10 k ohm
Operating environment
Temperature 32 to 120°F (0 to 49°C)
Humidity 0 to 93% RH, noncondensing at 90°F (32°C)
Storage temperature range –4 to 140°F (–20 to 60°C)
Wire size 12, 14, 16, or 18 AWG wire (2.5, 1.5, 1.0, or 0.75 sq.
mm)  (Sizes 16 and 18 AWG are preferred)
Device address 01 to 64 (64 point control panel)
(two addresses required) 01 to 127 (127 point control panel)
Initiating device circuit (IDC)
EOL resistor value 47 kΩ, (P/N: EOL-47)
Max. circuit resistance 50 Ω (25 Ω per wire)
Max. circuit capacitance 0.1 μF

Wire nut LEDs on reverse side Style B (Class B)

SLC out ( ) Black ( ) 5 6 7 89 4 5 IDC( )


3 6
To next 4
7 Yellow 47 k Ohm
3 10 2
device 2 11 EOLR
SLC out (+) 1 0 12 1
0 9
8 Orange
From SLC in ( ) Red (+) IDC (+)
previous
device SLC in (+) Typical NO
Insert screwdriver here initiating device

Ordering Information
Model Description Ship Weight
FX-IDC1A Analog Class A Single Input Module 0.50 lbs. (0.23 kg.)
FX-IDC1B Analog Single Input Mini Module 0.34 lbs. (0.15 kg.)
FX-2WIRE Analog Class A-B Two-Wire Module 0.50 lbs. (0.23 kg.)
FX-IDC2B Analog Dual Input Module 0.50 lbs. (0.23 kg.)
FX-2IDCWS Analog Dual Input Waterflow-Supervisory Module 0.50 lbs. (0.23 kg.)
FX-NAC Analog NAC Module 0.50 lbs. (0.23 kg.)
FX-RLY Analog Contact Relay Module 0.50 lbs. (0.23 kg.)
FX-ISO Analog SLC Fault Isolator Module 0.50 lbs. (0.23 kg.)
06-27-13

Page 6 of 6 D ATA S H E E T FX85001-0611


Not to be used for installation purposes. Issue 1