06-651 Cheetah Xi Programming Manual PDF
06-651 Cheetah Xi Programming Manual PDF
®
10-068, Cheetah Xi
Addressable Fire Suppression Control System
P/N 06-651
Rev. 2, December 2016
SOLUTIONS
Fire Protection
Explosion Protection
Overpressure Protection
Pressure Activation
DEVELOPED BY Fike
704 SW 10th Street
P.O. Box 610
Blue Springs, Missouri 64013 U.S.A.
Phone: (800) 979-FIKE (3453)
(816) 229-3405
Fax: (866) 211-9239
DISCLAIMERS This document is only intended to be a guideline and is not applicable to all
situations. Information subject to full disclaimer at www.fike.com/disclaimer.
QUALITY Fike has maintained ISO 9001 certification since 1996. Prior to shipment, we
thoroughly test our products and review our documentation to assure the highest
quality in all respects.
WARRANTY Fike provides a one-year limited manufacturer’s warranty on this product. All
warranty returns must be returned from an authorized Fike Distributor. Contact
Fike’s Marketing department for further warranty information.
Fike maintains a repair department that is available to repair and return existing
electronic components or exchange/purchase previously repaired inventory
component (advance replacement). All returns must be approved prior to return.
A Material Return Authorization (MRA) number must be indicated on the box of
the item being returned. Contact the appropriate Regional Sales Manager for
further information regarding product return procedures.
LIMITATIONS OF LIABILITY Installation in accordance with this manual, applicable codes, and the
instructions of the Authority Having Jurisdiction is mandatory. Fike cannot be
held liable for any incidental or consequential damages arising from the loss of
property or other damages or losses resulting from the use or misuse of Fike
products beyond the cost of repair or replacement of any defective components.
Fike reserves the right to make product improvements and change product
specifications at any time.
While every precaution has been taken during the preparation of this manual to
ensure the accuracy of its content, Fike assumes no responsibility for errors or
omissions.
TABLE OF CONTENTS
TABLE OF CONTENTS
SECTION DESCRIPTION PAGE
1.0 About This Manual ........................................................................................................ 1-1
1.1 About This Manual........................................................................................................... 1-1
1.2 Product Support............................................................................................................... 1-1
1.3 Safety Information ........................................................................................................... 1-1
1.4 Related Information ......................................................................................................... 1-2
1.5 Revision History ............................................................................................................... 1-2
2.0 C-Linx Programming Options ...................................................................................... 2-1
2.1 Understanding Cheetah Xi .............................................................................................. 2-1
2.2 Software Programming Features ..................................................................... 2-2 thru 2-33
3.0 Getting Started ............................................................................................................... 3-1
3.1 User Interface .................................................................................................................. 3-1
3.2 Password Protection........................................................................................................ 3-2
3.2.1 How to Log onto the System ........................................................................................... 3-3
3.2.2 Changing the System Administrator Password ............................................................... 3-3
3.3 Configuring the System ................................................................................................... 3-4
3.3.1 Auto-Program .................................................................................................................. 3-4
3.3.2 Engineered Configure...................................................................................................... 3-4
3.4 How to Address a Device ................................................................................................ 3-5
3.4.1 How to Auto Address Field Devices ................................................................................ 3-5
3.4.2 How to Use the Panel’s Device Address Function .......................................................... 3-6
3.4.3 How to Address Devices with the IR Tool ....................................................................... 3-8
3.4.4 How to Address Devices with the Hand-Held Programmer .......................................... 3-10
3.4.5 How to Address Devices Using C-Linx Device Address Wizard ................................... 3-12
3.4.6 How to Address Devices Using C-Linx Device Address Function ................................ 3-13
4.0 Configuration Menu....................................................................................................... 4-1
4.1 Configuration Menu ......................................................................................................... 4-1
4.2 Configuration Menu 1 ...................................................................................................... 4-1
4.2.1 How to Configure a Field Device ..................................................................................... 4-1
4.2.1.1 How to Change a Devices Alarm Features ..................................................................... 4-2
4.2.1.1.1 How to Modify a Sensor .................................................................................................. 4-3
4.2.1.1.2 How to Modify a Control or Relay Module ....................................................................... 4-3
4.2.1.1.3 How to Modify a Monitor Module ..................................................................................... 4-8
4.2.1.1.4 How to Modify a Pull Station ........................................................................................... 4-9
4.2.1.1.5 How to Delete a Device from the System Configuration ................................................. 4-9
4.2.1.1.6 How to Read, Write, Enable or Disable a Device .......................................................... 4-10
4.2.1.2 How to Change a Devices Release Features ............................................................... 4-11
4.2.1.3 How to Perform a Configuration Check ......................................................................... 4-12
4.2.2 How to Modify the Panel’s NAC Circuits ....................................................................... 4-12
4.2.2.1 How to Modify NAC Functions ...................................................................................... 4-13
4.2.2.2 How to Set NAC Zone Assignments ............................................................................. 4-14
4.2.2.3 How to Set NAC Sync Protocol ..................................................................................... 4-15
4.2.3 How to Change SLC Supervision .................................................................................. 4-16
4.2.3.1 How to Set SLC Command Mode Functions................................................................. 4-17
4.2.3.2 How to Adjust Positive Alarm Sequencing Investigation Time ...................................... 4-17
4.2.4 How to Execute the Learn Function .............................................................................. 4-18
4.2.4.1 Learn New Devices Only ............................................................................................... 4-18
4.2.4.2 Learn All Devices ........................................................................................................... 4-19
4.2.5 How to Enable Panel Voice Operations ........................................................................ 4-20
4.2.5.1 How to Set Mass Notification Reset Timeout ................................................................ 4-21
4.2.5.2 How to Set Voice State Priority Levels .......................................................................... 4-21
LIST OF EXHIBITS
EXHIBIT DESCRIPTION PAGE
1-1 Related Documentation .......................................................................................................... 1-2
2-1 thru 2-32 C-Linx (V7.20) Programming Features ................................................................... 2-2 thru 2-33
3-1 Control Panel Keypad and Display ......................................................................................... 3-1
3-2 Password Access Levels ........................................................................................................ 3-2
3-3 Password Entry Screen .......................................................................................................... 3-3
3-4 Password Entry Screen (Password Change).......................................................................... 3-3
3-5 Auto Address Screen .............................................................................................................. 3-5
3-6 Device Address Screen .......................................................................................................... 3-6
3-7 Connect Device Screen .......................................................................................................... 3-6
3-8 New Device Detected Screen ................................................................................................. 3-7
3-9 Connect Device Screen .......................................................................................................... 3-7
3-10 Address Change Completed Screen ...................................................................................... 3-7
3-11 Address Change Failed Screen .............................................................................................. 3-7
3-12 IR Communication Screen ...................................................................................................... 3-8
3-13 IR Communication Tool .......................................................................................................... 3-9
3-14 Loop Start Screen ................................................................................................................. 3-10
3-15 Device Address Screen ........................................................................................................ 3-10
3-16 Connect Device Screen ........................................................................................................ 3-10
3-17 New Device Detected Screen ............................................................................................... 3-11
3-18 Connect Device Screen ........................................................................................................ 3-11
3-19 Address Change Completed Screen .................................................................................... 3-11
3-20 Address Change Failed Screen ............................................................................................ 3-11
4-1 Configuration Menu 1.............................................................................................................. 4-1
4-2 Device Configuration Menu..................................................................................................... 4-1
4-3 Alarm Features Screen ........................................................................................................... 4-2
4-4 Alarm Features Screen (Sensors and Detectors) ................................................................... 4-3
4-5 Alarm Features Screen (Control Module) ............................................................................... 4-3
4-6 Any of 3 Zones Function Screen............................................................................................. 4-4
4-7 All of 3 Zones Function Screen ............................................................................................... 4-5
4-8 Select Device Function Screen ............................................................................................... 4-6
4-9 Row Anding Function Screen ................................................................................................. 4-6
4-10 Addressable Relay AHU Restart Delay Screen ...................................................................... 4-7
4-11 Alarm Features Screen (Monitor Module) ............................................................................... 4-8
4-12 Alarm Features Screen (Pull Station Module)......................................................................... 4-9
4-13 Delete Device Screen ............................................................................................................. 4-9
4-14 Read/Write/Enable/Disable Screen ...................................................................................... 4-10
4-15 Release Features Screen ..................................................................................................... 4-11
4-16 Configuration Check Screen ................................................................................................. 4-12
4-17 NAC Configuration Menu ...................................................................................................... 4-12
4-18 NAC Functions Screen ......................................................................................................... 4-13
4-19 NAC Zone Assignment Screen ............................................................................................. 4-14
4-20 NAC Sync Protocol Screen ................................................................................................... 4-15
4-21 SLC Configuration Screen .................................................................................................... 4-16
4-22 SLC Command Mode Screen ............................................................................................... 4-17
4-23 PAS Investigation Time Screen ............................................................................................ 4-17
4-24 LEARN Screen...................................................................................................................... 4-18
4-25 LEARN New Devices Screen................................................................................................ 4-18
4-26 LEARN Mode Active Screen ................................................................................................. 4-18
4-27 LEARN All Devices Screen ................................................................................................... 4-19
4-28 LEARN Mode Active Screen ................................................................................................. 4-19
4-29 Voice Operations Screen ...................................................................................................... 4-20
4-30 MNS Reset Screen ............................................................................................................... 4-21
4-31 Voice States Priority Screen ................................................................................................. 4-21
4-32 Configuration Menu 2............................................................................................................ 4-22
4-33 Time Control Screen ............................................................................................................. 4-22
4-34 System Silence Screen ......................................................................................................... 4-23
a WARNING
Warnings are used to indicate the presence of a hazard
which will or may cause personal injury or death, or loss
of service if safety instructions are not followed or if the
hazard is not avoided.
I Caution
Cautions are used to indicate the presence of a hazard
which will or may case damage to the equipment if
safety instructions are not followed or if the hazard is not
avoided.
Permitted
in UL Settings
Circuit or 864? Possible Settings permitted
Component Program Feature or Option (Y/N) (Defaults shown bold) in UL 864 Notes
Main Board Configuration Options
MISC. Miscellaneous Options
AC Trouble Delay Y 0-30 hours, (Default 2) 1–3
Abort Type N 1 – 6 (Default 2) 1-4
Voice Panel Priorities
Alarm Y 1-251 (Default 4) 6
Test Alarm Y 2-252 (Default 5) 6
Supervisory Y 3-253 (Default 6) 6
Process Y 4-254 (Default 7) 6
Fan Restart Y Automatic/Manual
Drill/Silence/Acknowledge N Enabled / Disabled Enabled 1,2
Auto Message Y Enabled / Disabled
Walktest Y Enabled / Disabled
Supervision Options
Transformer Y 120VAC / 240VAC
Loop Style (SLC) Y 4,6, or 7 (A, B, or X)
Ground Fault Level 1 N Enabled / Disabled Enabled 2
Ground Fault Level 2 N Enabled / Disabled Enabled 2, 3
Main Battery N Supervised / Unsupervised Supervised
Auxiliary Battery N Supervised / Unsupervised Supervised
Auxiliary Loop Module Present Y Enabled / Disabled
Auxiliary Power Module Present Y Enabled / Disabled
Eclipse Device Error Trouble Y Enabled / Disabled Enabled 4
AHU Fire Dept Key Required for Y Yes / No
AHU Restart
First Event Latched on LCD Y Enabled / Disabled Enabled 7
Battery Cutoff Y Loop # and Address #
(L: 1-4 Address: 0-254)
Silence Options
Unsilence Time Y 1-24 hours
Silence Reminder Y Enabled / Disabled
Silence Inhibit Y Enabled / Disabled
Positive Alarm Sequence Y Enabled / Disabled
Silence Mode Y UL / ULC UL only 5,8
Automatic Alarm Silence Time N 1 – 4 (Hr) 8
Notes:
1. City of Chicago does not allow use of Drill, Silence and Acknowledge switches.
2. Can only be changed with Factory Level password.
3. Level 2 ground fault detection required for use with solenoids.
4. If device on SLC has an internal error then the panel produces a trouble state (Enabled) and does not just log it (Disabled). (i.e. Checksum
Error/Device Error:2000)
5. An audible signal that has been silenced at the protected premises shall automatically resound and remain energized until silenced and
retransmitted to any supervising station to which the original signal was transmitted, as applicable, at least once every 24 hours until the condition
is corrected and the product is restored to the normal supervisory condition.
6. Priorities must be set only if the panel is part of a panel network with CyberCat panels with voice operation.
7. LCD display to latch on initial Trouble or Supervisory events (YES) or LCD to display current Trouble or Supervisory event (NO).
When Silence Mode is set to ULC, a timer can be set to automatically silence the panel upon expiration of the timer. Panel is not ULC listed.
NAVIGATION (+, ►, -, ◄): The ◄► arrows are used to move about in the
configuration displays. The +/- buttons will increment or decrement the value at the
cursor when in a configuration display. They can also be used when cycling through
the event history. The Step Alarm button only cycles forward in events. These buttons
allow you to go forward and backward through the events.
ESCAPE: Press this key to toggle from Off-Normal Event display (if events are
present) to System Normal (no events preset) to Top Level Menu. If in a menu, this
button EXITS the current menu and returns to the previous menu screen. If in the
System Normal Menu, pressing ESCAPE takes you back to event #1.
FUNCTION KEYS: The function keys are used to navigate the control panel’s menu
system during system operation, maintenance and configuration of the system.
Password
Designation Privileges
Level
Default View system events on LCD display
(door panel closed)
Access to STEP keys for reviewing system history
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A E N T E R P A S SWO R D
B X X X X < - - - X X X X
C ACCE S S : DEN I ED
D CODE : X X X X
Exhibit 3-3: Password Entry Screen
Row B - Allows entry of a 4 digit password. Use the ◄► navigation buttons to move the cursor to the
appropriate field and the +/- buttons (cycles through 0-9) to enter a password.
Row C - Displays the access level (Denied, Level 2 (A-H), Sys Admin, Factory) allowed with the
password that has been entered.
Row D - Random 4 digit-code that changes periodically. Used by the factory to gain access to the
system if the Administrator password has been forgotten.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A E N T E R P A S SWO R D
B _ _ _ _ < - - - X X X X
C ACCE S S : DEN I ED
D CODE : X X X X
Exhibit 3-4: Password Entry Screen
Row B - Allows entry of a 4 digit password. Use the ◄► navigation buttons to move the cursor and
the +/- buttons (cycles through 0-9) to enter a password.
Row C - Displays the access level (Denied, Level 2 (A-H), Sys Admin, Factory) allowed with the
password that has been entered.
Row D - Random 4 digit-code that changes periodically. Used by the factory to gain access to the
system if the Administrator password has been forgotten.
3.3.1 AUTOPROGRAM
This configuration method is used for small systems requiring typically no more than one zone of operation.
This method allows you to connect all unaddressed devices to the panels SLC circuits and by using panel’s
AUTO ADDRESSING function, each device is randomly addressed in the order that they are recognized by
the panel. The panel’s LEARN function is then used to upload the default configuration held by each device
into the panel. Each device (inputs and outputs) is assigned to Zone 1 by default. At this point, the panel
configuration menus can be used to make simple changes to the system/device configurations. For more
extensive configuration changes, you should use the C-Linx configuration software to create a configuration
template, make necessary changes, and upload the modified configuration back into the control panel.
Note: The drawback to using the AUTOPROGRAMMING method is that the devices are randomly
addressed; therefore, you must document the actual location of each device during the functional testing
of the system. If any device was missed, you must manually add it into the configuration.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A A U T O AD D RE S S I NG : OF F
B S E L EC T L OO P S : 1 2 3 4
C S E L EC T A DD RS : 0 0 1→0 5 0
D P R E S S E N T E R TO S TORE
Exhibit 3-5: Auto Address Screen
Row A - This field allows you to turn the Auto Addressing feature ON/OFF. Use the ◄► arrow keys
to move cursor to the field; then use the +/- keys to toggle the field (ON/OFF).
Row B - This field allows you to select which addressable loops will be affected when Auto
Addressing is turned ON. Use the ◄► arrow keys to move cursor to the field; then use the +/- keys
to toggle the field.
Row C - This field allows you to select the address range that you would like to auto address. Use
the ◄► arrow keys to move cursor to the field; then use the +/- keys to toggle the field.
Row D - When you have the address range that you would like to have auto addressed, press the
ENTER key. Devices will NOT be addressed until it is added to the loop (NEW DEVICE record
identified) and the panel is reset.
3.4.2 HOW TO USE THE PANEL’S DEVICE ADDRESS FUNCTION TO ADDRESS A DEVICE
This method allows you to take a field device straight out of the box and connect it to the panel’s signaling line
circuit (SLC) to be addressed. The Device Address (DEV ADR) function when activated, allows the panel to
automatically assign an address to each new device as it is connected to the panel’s signaling line circuit
(SLC).
To Address devices:
1. Press the ESCAPE key until the Cheetah Xi’s TOP LEVEL MENU is displayed.
2. Press the F5 key to enter the systems MAINTENANCE MENU.
3. Press the F2 key to enter the DEVICE ADDRESS screen (DEV ADR).
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 89 0
A S E L EC T A D D R E S S
B LOOP : 1 ADDRE S S : 0 0 1
C
D P R E S S E N T E R T O S T A RT
Exhibit 3-6: Device Address Screen
Row B – Use these fields to set the loop (1 – 5) and starting address number (1 – 254) to be
assigned to the device. Use the ◄►arrow keys to move the cursor under the Loop and Address
fields; then use the +/- keys to increment/decrement the fields.
Row D - Press the ENTER key to start the automatic address function.
4. Once the chosen loop and address is set, press the ENTER key to start the automatic address function.
The following Connect Device screen will be displayed.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A C ON N E C T D E V I CE TO
B A DD R E S SA B L E LOO P
C P RE S S EN T E R WH E N
D C OM P L E T E
Exhibit 3-7: Connect Device Screen
Once the panel recognizes that a new device has been attached, a NEW DEVICE message will be briefly
displayed on Rows C & D:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 89 0
A CONN E CT D E V I CE TO
B ADDR E S SAB L E LOOP
C * N EW D E V I CE *
D * DE T E CT E D*
Exhibit 3-8: New Device Detected Screen
Note: The panel requires the NEW DEVICE record from the device before it will recognize it.
If the device
was already installed prior to accessing this screen, you must REMOVE and RE-INSTALL the device for
the panel to receive the NEW DEVICE record.
5. Once the panel has detected the New Device, Press the ENTER key to assign the new loop and address
to the attached device:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 89 0
A C ON N E CT D E V I CE TO
B A DD R E S S AB L E LOO P
C P RE S S E NT E R WH E N
D C OM P L E T E
Exhibit 3-9: Connect Device Screen
If the address change was successfully completed, the following screen will be displayed:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A LOOP : n A D D R E S S : n n n
B DE V I CE A D D R CH ANGE
C COM P L E T ED
DE N T ER FO R N E X T DE V I C
Exhibit 3-10: Address Change Completed Screen
You are now ready to program the next sequential loop-address (the panel will auto-increment the address
number after each successful address write), press the ENTER key to return to step #3.
If the address did NOT successfully change, the following screen will be displayed:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A LOOP : 1 ADDRE S S : NNN
B DE V I CE ADDR CHA NGE
C F A I L ED
DE N T ER FOR NE X T D E V I C
Exhibit 3-11: Address Change Failed Screen
Remove/disconnect the device being addressed from the SLC and press the ENTER key to return to step #3
and repeat the process.
To turn on IR Communication:
1. Press the ESCAPE key until the Cheetah Xi’s TOP LEVEL MENU is displayed.
2. Press the F6 key to display the IR COMMUNICATION screen (IR COMM).
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 89 0
A I R C OMMU N I C A T I O N
B LOO P 1 : D I S LOO P 2 : D I S
C LOO P 3 : D I S LOO P 4 : D I S
D
Exhibit 3-12: IR Communication Screen
Rows B & C - Displays the IR Communication status by loop. Enable only one loop at a time. Use
the ◄► keys to move the cursor to the field; then use the +/- keys to toggle the ENAble/DISable
status of the loop. Disable the IR when complete or Reset the control panel (turns IR back OFF).
The IR Tool, as shown in Exhibit 3-13, has many uses with the Cheetah Xi addressable devices. Consult the
individual Installation and Maintenance Instructions (P/N 55-051) for a complete description of its operation.
1 2 3
4 5 6
POWER BUTTON 7 8 9
0
PWR
3.4.4 HOW TO ADDRESS DEVICES WITH THE HAND-HELD PROGRAMMER (P/N 10-2648)
The Hand-Held programmer contains the same operating code as the Cheetah Xi and can be used to assign
an address to a new addressable device. Refer to Fike document 06-390, “Hand-Held Programmer
Operating Instructions” for a complete description of the programmer’s functions and operations.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 89 0
A S E L EC T AD D RE S S
B L OO P : 1 ADDR E S S : 0 0 1
CWA I T FOR L OO P S T AR T :
D > > > > > > > > > > > > > > > > > > >>
Exhibit 3-14: Loop Start Screen
3. Upon completion of the loop start-up, the following Device Address screen will be displayed:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 89 0
A S E L EC T A D D R E S S
B LOO P : 1 ADDRE S S : 0 0 1
C
DPRE S S EN T ER TO S T A RT
Exhibit 3-15: Device Address Screen
Row B – Use these fields to set the loop (1 – 4) and starting address number (1 – 254) to be
assigned to the device. Use the ◄►arrow keys to move the cursor under the Loop and Address
fields; then use the +/- keys to increment/decrement the fields.
4. Once the chosen loop and address is set, press the ENTER key to start the automatic address function.
The following Connect Device screen will be displayed:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A C ON N E C T D E V I CE TO
B A DD R E S SA B L E LOO P
C P RE S S EN T E R WH E N
D C OM P L E T E
Exhibit 3-16: Connect Device Screen
Attach sensor to the integral base on the programmer.
Attach module to the programmer using the supplied wire leads (Red wire to Loop positive
connection; Black wire to Loop negative connection).
Once the programmer recognizes that a new device has been attached, a NEW DEVICE message will be
briefly displayed on Rows C & D:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 89 0
A CONN E CT D E V I CE TO
B ADDR E S SAB L E LOOP
C * N EW D E V I CE *
D * DE T E CT E D*
Exhibit 3-17: New Device Detected Screen
Note: The programmer requires the NEW DEVICE record from the device before it will recognize it.
If the
device was already installed prior to accessing this screen, you must REMOVE and RE-INSTALL the
device for the Hand Held Programmer to receive the NEW DEVICE record.
5. Once the programmer has detected the New Device, Press the ENTER key to assign the new loop and
address to the attached device:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 89 0
A C ON N E CT D E V I CE TO
B A DD R E S S AB L E LOO P
C P RE S S E NT E R WH E N
D C OM P L E T E
Exhibit 3-18: Connect Device Screen
If the address change was successfully completed, the following screen will be displayed:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A LOOP : n A D D R E S S : n n n
B DE V I CE A D D R CH ANGE
C COM P L E T ED
DE N T ER FO R N E X T DE V I C
Exhibit 3-19: Address Change Completed Screen
You are now ready to program the next sequential loop-address (the panel will auto-increment the address
number after each successful address write), press the ENTER key to return to step #2.
If the address did NOT successfully change, the following screen will be displayed:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A LOOP : 1 ADDRE S S : NNN
B DE V I CE ADDR CHA NGE
C F A I L ED
DE N T ER FOR NE X T D E V I C
Exhibit 3-20: Address Change Failed Screen
Remove/disconnect the device being addressed from the programmer and press the ENTER key to return to
step #2 and repeat the process.
6. If complete, remove/disconnect all devices and power down the Hand Held Programmer.
1. Use C-Linx to open your existing configuration or create the configuration for the panel.
2. Click on ‘Diagnostics’.
3. Select/click on ‘Device Addressing Wizard’. A window will appear, titled ‘Device Addressing Wizard’.
4. Click the pull-down menu where it displays ‘No Panel’ and select the configuration of the panel that you
wish use for addressing the devices (that configuration needs to be already loaded in C-Linx Project
Explorer).
5. It will display each device loop and address information in the panel area.
7. Connect the programming cable from the communication port on the computer to the panel or the Hand
Held Programmer when it instructs to connect the Serial Cable.
9. The Status Message will display connection status. Connect the device to be addressed.
10. Once C-Linx receives the NEW DEVICE record from the device, it will highlight that TYPE of device in
step 1. It will display the type, serial number, and address in the Step 2 area. You need to click on the
appropriate box in Step 3 area of C-Linx. Either select ‘Overwrite current address in this device’ OR ‘Do
not address this device’. If there is no longer a device type in the list that matches the device type
connected, it will display Device not needed for this configuration, ’Skip Device’. Click ‘Skip Device’ to
continue to the next device.
11. If you selected ‘Overwrite current address in this device’ it will display ‘Storing New Device Address’ and
then it will remove that device loop-address from the list of available devices.
12. Click on ‘Stop Addressing’ and it will ask if you wish to save the session for you to come back at a later
time and pick up addressing where you left off.
3.4.6 HOW TO ADDRESS DEVICES USING C-LINX’S ASSIGN DEVICE ADDRESS FUNCTION
Use this software diagnostic for simple loop-address change when the panel configuration is not available.
2. Connect to panel.
3. Click on ‘Diagnostics’.
4. Click on ‘Assign Device Address’. A window will appear, titled ‘Assign Device Address’.
5. The Status Message will display connection status; it will then command the panel or Hand Held
Programmer to search for the devices attached. Once it resets the loop of device(s) it will report each
type of device with its loop number, address number and serial number information.
6. Select a specific row to modify, then change the loop number and/or address number in the bottom box.
Click ‘Change Address’ to send the device the new loop and address number.
9. Close Assign Device address screen. If properly completed, all devices should now have valid
addresses.
Note: This diagnostic is intended for loop devices that are already wired to an SLC loop.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A L - A D R : DE V I C E T Y P E
B F U N C : * F UNC T I ON - - - - NO
C C U S T OM ME S S AGE L - ADD
D Z O N E : 0 0 0 0 0 0 0 0 0 0 0 0
Exhibit 4-3: Alarm Features Screen
Row A (L-ADR) - Allows you to select the loop and address of a specific SLC device in order to
display its configuration parameters. Use the ◄► arrow keys to position the cursor under any of
the fields; then use the +/- keys to change to a different loop or address number.
When you select a device, the control panel displays information about the device. The screen does
not show all configuration options that are available for each device. In order to be able to view and
change all operating parameters for each device, you must use the C-Linx panel configuration
software. Refer to Fike document 06-448 “C-Linx User’s Guide” for additional configuration options.
Row A (Device Type) - Changes to display the type of device found at the selected loop-address:
Photo Sensor, Ion Sensor, Photo/Heat Sensor, Heat Sensor, Photo Duct Det, Control Module, Relay
Module, Monitor Module, Mini Module and Pull Station.
Row B (FUNC) - Allows you to change the function of the selected device address (if applicable).
Use the ◄► arrow keys to position the cursor under the field; then use the +/- keys to change the
device function. The ability to change the function field is available only on certain device types.
Row C - This range of fields allows you to enter a 20 character custom message for the selected
address. These fields can be edited using the ◄► arrow keys to position the cursor under any of
the fields; then use the +/- keys to cycle through all available ASCII characters.
Row D - The functionality of the fields in this row changes depending upon the device type displayed
in Row A. The programming options available for each device type are described as follows.
ICAUTION
If you change any of the devices configuration settings, you
MUST press the ENTER button to successfully change the
configuration at the device. Wait for the asterisk (*) shown next
to the device function on Row B to go away prior to leaving the
screen. Exiting the screen with the asterisk still visible will cause
the selected device to be partially configured which will result in
improper operation.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A 1 - 0 0 1 : PHOT O S ENSOR
B F U N C : * - - - - - - - - - - - - - -
C C U S T OM ME S SAGE 1 - 0 0 1
D Z O N E : 0 0 1 0 0 0 0 0 0 0 0 0
Exhibit 4-4: Alarm Features Screen
(Sensors and Detectors)
Row A - Displays the loop and address of the selected SLC device.
Row B - Displays the function of the device. Not editable for this device type.
Row C - Displays the 20 character custom message for the selected address. Use the ◄► arrow
keys to position the cursor under any of the fields; then use the +/- keys to cycle through all
available ASCII characters.
Row D - The fields in this row display the zone settings for the selected device address in Row A.
Use the ◄► arrow keys to position the cursor under one of the zone number fields (000); then use
the +/- keys to change the zone number. To add multiple zones, move the cursor to the 2nd-4th
zone number fields; then use the +/- keys to change or add the zone number.
Note: These programming options are typical for Photo Sensor, Ion Sensor, Photo/Heat Sensor,
Heat Sensor and Photo Duct Detector.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A 1 - 0 0 1 : CON T R O L MOD U L E
B F U N C : * - - - - - - - - - - - - - -
C C U S T OM ME S S AGE 1 - 0 0 1
D - - - - : 0 0 0 0 0 0 0 0 0 P : *
Exhibit 4-5: Alarm Features Screen
(Control Module)
Row A - Displays the loop and address of the selected SLC device.
Row B - This field allows you to switch the function of the control module between ANY OF 3
ZONES, ALL OF 3 ZONES, SELECT DEVICE or ROW ANDING. Each function is described as
follows. Use the ◄► arrow keys to position the cursor under the field; then use the +/- keys to
change the device function.
Row C - Displays the 20 character custom message for the selected address. Use the ◄► arrow
keys to position the cursor under any of the fields; then use the +/- keys to cycle through all
available ASCII characters.
Row D - The fields in this row change depending upon the device function displayed in Row B. The
programming options available for each device function are described as follows.
Note: These programming options are typical for both the control and relay modules.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A 1 - 0 0 1 : CON T R O L MOD U L E
B F U NC : * ANY O F 3 ZO N E S
C C U S T OM ME S S AGE 1 - 0 0 1
D A L RM : 0 0 0 0 0 0 0 0 0 P : *
Exhibit 4-6: Any of 3 Zones Function Screen
Row D - Provides access to the first row of the modules output priority control table. To cycle
through the possible states of activation, use the ◄► arrow keys to position the cursor under the
ALRM field; then use the +/- keys to change the activation state:
AVON = Alarm Verification On
LTRB = Low Power Trouble
STRB = Short Circuit Trouble
OTRB = Open Circuit Trouble
MTRB = Maintenance Trouble
TSTA = Test Alarm
TRBL = Trouble
PROC = Process
PRED = Predischarge
PRA2 = Pre-Alarm 2
PRA1 = Pre-Alarm 1
ABRT = Abort
RELE = Release
SUPV = Supervisory
SUMA = Summing Alarm
ALRM = Alarm
ALRT = Voice Alert
EVAC = Voice Evacuation
PAGE = Voice Page
MSSA = Mass Notification All Zones
MSSZ = Mass Notification by Zone
2ALL = Page to Alert, Page to EVAC, Page All, Page R&R All
ZDIS = Zone Disable
The 000 fields allow you to set zone settings for the selected device address in Row A. Use the ◄►
arrow keys to position the cursor under one of the zone number fields (000); then use the +/- keys to
change the zone number. To add multiple zones, move the cursor to the 2nd-3rd zone number
fields; then use the +/- keys to change or add the zone number.
P:X allows you to select the activation pattern for the modules output, where X signifies:
0 = OFF F = FAST
1 = ON T = TEMPORAL
S = SLOW W = WALKTEST)
Use the ◄► arrow keys to position the cursor under pattern field; then use the +/- keys to change
the activation pattern.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A 1 - 0 0 1 : CON T R O L MOD U L E
B F U NC : * A L L O F 3 ZO N E S
C C U S T OM ME S S AGE 1 - 0 0 1
D A L RM : 0 0 0 0 0 0 0 0 0 P : *
Exhibit 4-7: All of 3 Zones Function Screen
Row D - Provides access to the first row of the modules output priority control table. To cycle
through the possible states of activation, use the ◄► arrow keys to position the cursor under the
ALRM field; then use the +/- keys to change the activation state:
AVON = Alarm Verification On
LTRB = Low Power Trouble
STRB = Short Circuit Trouble
OTRB = Open Circuit Trouble
MTRB = Maintenance Trouble
TSTA = Test Alarm
TRBL = Trouble
PROC = Process
PRED = Predischarge
PRA2 = Pre-Alarm 2
PRA1 = Pre-Alarm 1
ABRT = Abort
RELE = Release
SUPV = Supervisory
SUMA = Summing Alarm
ALRM = Alarm
ALRT = Voice Alert
EVAC = Voice Evacuation
PAGE = Voice Page
MSSA = Mass Notification All Zones
MSSZ = Mass Notification by Zone
2ALL = Page to Alert, Page to EVAC, Page All, Page R&R All
ZDIS = Zone Disable
The 000 fields allow you to set zone settings for the selected device address in Row A. Use the
◄► arrow keys to position the cursor under one of the zone number fields (000); then use the +/-
keys to change the zone number. To add multiple zones, move the cursor to the 2nd-3rd zone
number fields; then use the +/- keys to change or add the zone number.
P:X allows you to select the activation pattern for the modules output, where X signifies:
0 = OFF F = FAST
1 = ON T = TEMPORAL
S = SLOW W = WALKTEST)
Use the ◄► arrow keys to position the cursor under pattern field; then use the +/- keys to change
the activation pattern.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A 1 - 0 0 1 : CON T R O L MOD U L E
B F UN C : * S E L E C T DE V I CE
C C US T OM ME S S AGE 1 - 0 0 1
D L OO P : 0 ADR : 0 0 1 P : *
Exhibit 4-8: Select Device Function Screen
Row D -These fields allow you to select the loop and address of a specific SLC device that will
activate the selected control module. Use the ◄► arrow keys to position the cursor under any of
the fields; then use the +/- keys to change to a different loop or address number.
P:X allows you to select the activation pattern for the modules output, where X signifies:
0 = OFF F = FAST
1 = ON T = TEMPORAL
S = SLOW W = WALKTEST)
Use the ◄► arrow keys to position the cursor under pattern field; then use the +/- keys to change
the activation pattern.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A 1 - 0 0 1 : CON T RO L MOD U L E
B F U N C : * R OW A N D I N G
C C U S T OM ME S S AG E 1 - 0 0 1
D R : 0 0 0 0 0 0 0 0 P : *
Exhibit 4-9: Row Anding Function Screen
Row D - These fields allow you to select the priority rows that must be active before the output of the
selected control module activates. Use the ◄► arrow keys to position the cursor under any of the
fields; then use the +/- keys to set the priority row.
P:X allows you to select the activation pattern for the modules output, where X signifies:
0 = OFF F = FAST
1 = ON T = TEMPORAL
S = SLOW W = WALKTEST)
Use the ◄► arrow keys to position the cursor under pattern field; then use the +/- keys to change
the activation pattern.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A AHU RE L AY RE - S T AR T
B DE L AY : 0 3 3 S ECONDS
C
D
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A 1 - 0 0 1 : MON I T OR MOD U L E
B F U N C : * - - - - - - - - - - - - NO
C C U S T OM ME S S AG E 1 - 0 0 1
D Z O N E : 0 0 0 0 0 0 0 0 0 0 0 0
Exhibit 4-11: Alarm Features Screen (Monitor Module)
Row A - Displays the loop and address of the selected SLC device.
Row B - This field allows you to select the input function for the selected device. To cycle through
the possible input functions, use the ◄► arrow keys to position the cursor under the function field;
then use the +/- keys to change the function:
Pre-Alarm 1 Process PAS Inhibit
Pre-Alarm 2 Trouble Watermist
Detection Supervisory Fan Restart
Man Alarm Reset Smoke Control Feedback
Waterflow Silence Manual Alarm 2nd Stage
Pre-Discharge Acknowledge AHU Fire Key
Manual Release Drill
Abort Zone Disable
Row B - The last two fields on this row allow you to select whether the module will be monitoring
Normally Open (NO) or Normally Closed (NC) contacts. Not all input functions provide the option of
NO/NC contacts as follows:
Pre-Alarm 1 (NO/NC) Process (NO/NC) PAS Inhibit (NO/NC)
Pre-Alarm 2 (NO/NC) Trouble (NO/NC) Watermist (NO)
Detection (NO) Supervisory (NO/NC) Fan Restart (NO/NC)
Man Alarm (NO) Reset (NO) Smoke Control Feedback (NO/NC)
Waterflow (NO/NC) Silence (NO/NC) Manual Alarm 2nd Stage (NO)
Pre-Discharge (NO) Acknowledge (NO/NC) AHU Fire Key (NO/NC)
Manual Release (NO) Drill (NO/NC)
Abort (NO) Zone Disable (NO/NC)
Row C - Displays the 20 character custom message for the selected address. Use the ◄► arrow
keys to position the cursor under any of the fields; then use the +/- keys to cycle through all
available ASCII characters.
Row D - The 000 fields allow you to set zone settings for the selected device address in Row A.
Use the ◄► arrow keys to position the cursor under one of the zone number fields (000); then use
the +/- keys to change the zone number. To add multiple zones, use the ◄► arrow keys to move
the cursor to the 2nd-4th zone number fields; then use the +/- keys to change or add the zone
number.
Note: These programming options are typical for the mini monitor module as well.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A 1 - 0 0 1 : PU L L S T A T I ON
B F U N C : * MAN A L ARM
C C U S T OM ME S S AGE 1 - 0 0 1
D Z O N E : 0 0 0 0 0 0 0 0 0 0 0 0
Exhibit 4-12: Alarm Features Screen
(Pull Station Module)
Row A - Displays the loop and address of the selected SLC device.
Row B - This field is allows you to select the input function for the selected device. To cycle through
the possible input functions, use the ◄► arrow keys to position the cursor under the function field;
then use the +/- keys to change the function: MAN ALARM, MAN RELEASE and PRE-DISCHARGE
(e.g., manual release with countdown).
Row C - Displays the 20 character custom message for the selected address. Use the ◄► arrow
keys to position the cursor under any of the fields; then use the +/- keys to cycle through all
available ASCII characters.
Row D The 000 fields allow you to set zone settings for the selected device address in Row A. Use
the ◄► arrow keys to position the cursor under one of the zone number fields (000); then use the
+/- keys to change the zone number. To add multiple zones, move the cursor to the 2nd-3rd zone
number fields; then use the +/- keys to change or add the zone number.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A L - ADR : DE V T Y P E
B PR E S S EN T ER TO
C DE L E T E DE V I CE
D
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A L - ADR : D E V T Y P E
B PRE S S EN T ER TO
C READ DE V I CE CON F I G
D
iCAUTION
Do not perform a DEVICE READ or LEARN ALL with devices disabled
on the system. Doing so will cause the disabled configuration stored in
the device(s) to be saved in the panel, rendering the panel’s enable
command useless. At this point, you must use C-Linx to download the
original configuration to the panel to re-enable the device.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A L - A DR : DE V I CE T Y P E
B P R E - D I SCH T Y P E : A
C COU N T D OWN : A U T OMA T I C
D
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A L - A D R : DE V T Y P E
B P AN E L : X X X DE V I CE : Z Z Z
C P RE S S EN T ER TO S T AR T
D C OM P AR I SON 0 - 0 0 0
Exhibit 4-16: Configuration Check Screen
Row A - This field allows you to select the Loop and Address of a specific SLC device to check its
configuration. Use the ◄► arrow keys to position the cursor under any of the L-ADR fields; then
use the +/- keys to change to a different loop number or address number. Device information for the
address shown is then displayed (if connected). The device type field is not editable, but will change
for each device type found on the loop.
Row B - Displays the panel and device checksum values for the device selected.
Row D - Indicates progress of configuration check.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A N A C # 1 : E NAB L ED
B S T A T E : S T A T E
C P R O TOCOL : CONS T AN T
D S I : N DR : N WL K : N WF : Y
Exhibit 4-18: NAC Functions Screen
Row A (NAC#) - This field allows you to select the NAC circuit to configure (NAC 1 or NAC 2). Use
the ◄► arrow keys to position the cursor under the field; then use the +/- keys to
increment/decrement the field.
Row A (ENABLED) - This field allows you to set the Enabled/Disabled status of the on-board
notification appliance circuits 1 & 2 (P10 & P11). Use the ◄► arrow keys to move cursor under the
Enabled/Disabled field; then use the +/- keys to toggle the field.
Note: If either NAC circuit is disabled, the panel will annunciate both a Trouble and Supervisory
condition until the circuit(s) is enabled.
Row B (State) - This field allows you to set the operating state for the NAC circuit displayed in Row
A. Use the ◄► arrow keys to move the cursor to Row B; then use the +/- keys to change the State
to the desired operation (i.e., Alarm, Pre-Discharge, Release, Pre Alarm #1, Pre Alarm #2,
Supervisory, Trouble and Process).
Row C (Protocol) - This field allows you to select whether the NAC circuit displayed in Row A will
use the NAC protocol set for the panel (see 4.2.2.3) or will activate constant. Use the ◄► arrow
keys to move the cursor to Row C; then use the +/- keys to change to the desired protocol.
Note: Both NAC 1 and NAC 2 must be set to the same protocol unless one of them is set to No
Sync Protocol.
Note: If a chime code is assigned to any zone, Row C will display ‘CHIME CODE’ by default and
cannot be changed. See section 4.3.5.1 for complete description of Chime Code functionality.
Row D - These fields allow you to set the Silenceable, Drill, Walktest and Waterflow Enabled
(Y)/Disabled (N) status for the NAC circuit displayed in Row A.
SILENCEABLE (SI:) - field determines whether or not the selected NAC circuit will turn off
when the panel’s SILENCE button is pressed.
DRILL (DR:) - field determines whether or not the selected NAC circuit will turn on when the
panel’s DRILL button is pressed.
WALKTEST (WLK:) - field determines whether or not the selected NAC circuit will turn on
when the panel receives a Walktest Alarm from any one of the configured zones.
WATERFLOW (WF:) – field determines whether or not the selected NAC circuit will turn on
when the panel receives a Waterflow Alarm.
To change the Enabled/Disabled status of these fields, use the ◄► arrow keys to position cursor
under Y or N; then use the +/- keys to toggle the field.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A N A C # 1 : A N Y ZO N E
B Z O N E RAN G E : 0 0 1 - 0 2 0
C 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
D - - - - - - - - - - - - - - - - - - - -
Exhibit 4-19: NAC Zone Assignment Screen
Row A (NAC#) – This field allows you to select the NAC circuit to configure (NAC 1 or NAC 2). Use
the ◄► arrow keys to position the cursor under the field; then use the +/- keys to
increment/decrement the field.
Row A (Any Zone) – This field allows you to set whether the selected NAC circuit will activate on
ANY ZONE or MULTI ZONE. Use the ◄► arrow keys to move cursor to the field (ANY ZONE or
MULTI ZONE); then use the +/- keys to toggle the field.
Note: The Any Zone option sets the selected NAC to activate on the configured state for any
zone. The Multi Zone option sets the selected NAC to activate on the configured state for any
zone selected in Row D.
Row B - This field allows you to set the 20 zone range that is displayed in Rows C & D. Use the
◄► arrow keys to position the cursor under the zone range field; then use the +/- keys to
increment/decrement the group of 20 forward or backwards (Zones 001-254).
Row C - These numbers act as placeholders and zone number indicators for the range of zones
selected on Row B.
Row D - This range of fields allows you to set the zone assignment programming for the circuit
displayed in Row A if MULTIZONE is selected.
- = not programmed for this zone
Y = programmed for this zone
Use the ◄► arrow keys to position the cursor under the specific zone position; then use the +/- keys
to toggle the status.
Note: The Any Zone option sets the selected NAC to activate on the configured state for any
zone. The Multi Zone option sets the selected NAC to activate on the configured state for any
zone selected in Row D.
Note: The panel NACs will not sound in a voice zone. Panel NACs are not selectable for voice
states.
Note: Amplifiers can be individually configured to silence its notification appliance circuit in response
to silencing of the main panel.
I CAUTION
SLM must be set to ‘YES’ before trying to send system
configuration to panel. Having a SLM installed on the panel and
not changing this field to Yes could result in delayed SLC
communication.
Row C (PAS:) - This field allows you to turn on Positive Alarm Sequencing function on the detection
circuits (Yes/No). Use the +/- keys to change the field.
Note: This feature is enabled or disabled for all sensors present on the panel. Refer to Cheetah
Xi Operations Manual for full description of this feature.
Row C (ACK:) - This field allows you to adjust the time frame in which the Alarm event must be
Acknowledged in order to initiate the panel’s Positive Alarm Sequence. The timer can be set
between 15 and 30 seconds. Use the ◄► arrow keys to move cursor under the field; then use the
+/- keys to increment or decrement the field.
Row C (00/00) - This field allows you to select specific voice message ID’s (primary/secondary) to
play during the PAS investigative period. Use the ◄► arrow keys to move cursor under the field;
then use the +/- keys to increment or decrement the field.
Row D - This field allows you to set the Loop Wiring Style used for all 4 addressable loops (Style 4,
6 or 7). Use the +/- keys to change the field.
Note: This is a system wide setting. All loops will be configured to use the selected wiring style.
If Style 6 or 7 is chosen and the loop is unused, jumpers must be installed to prevent open circuit
troubles.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A S TORE T R OUB L E FOR NO
B N EW D E V I CE E V EN T : NO
C S END AU T O C OMMA N D
D A T M I DN I GH T : NO
Exhibit 4-22: SLC Command Mode Screen
Row B - This field allows you to set whether the panel will record a “DEVICE NOT READY” trouble
for all output devices (i.e. Control, Relay, and Release modules) that fail to report a “New Device”
message following a reset (YES/NO). If the “New Device” message is received, then “DEVICE
RETURN” will be recorded. The factory default condition is NO. Use the +/- keys to change the
field.
Row D - This field allows you to set whether the panel will transmit an “AUTO” command onto the
loops each midnight if no alarms, troubles, supervisory, pre-alarm, drill, or process states are active
(YES/NO). The factory default condition is NO. Use the +/- keys to change the field.
Note: This feature ensures that output devices will act correctly in the event a device has been
inadvertently placed in the ‘Command Mode’.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
B PAS I NV E S T I GA T I ON
C M I NU T E S : 0 3
D
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A S E L EC T RE S E T MOD E :
B NON E S E L EC T ED
C P R E S S EN T E R TO S T AR T
D PANE L W I L L RE S E T
Exhibit 4-24: LEARN Screen
Row B - This field allows you to set the LEARN mode to be used. Press +/- to change from None
Selected to Learn New Devices or Learn All Devices. A complete description of each mode is
described as follows.
Note: Each addressable device connected to the SLC holds its own configuration. After the
LEARN function has been completed, you can modify the configuration as needed using either the
panel configuration menus or the C-Linx programming software.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A S E L E C T R E S E T MO D E :
B L E A R N N EW D E V I C E S
C P RE S S EN T ER TO S T AR T
D PANE L W I L L RE S E T
Exhibit 4-25: LEARN NEW DEVICES Screen
The panel will reset and enter the Learn Mode:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A L E A R N MO DE I S AC T I V E
B WA I T TO COMP L E T E > >
C 0 9 : 2 7 : 4 7 A 0 3 / 1 0 / 2 0 0 9
D A L : 0 0 0 S U : 0 0 0 T R : 0 0 0
Exhibit 4-26: LEARN Mode Active Screen
The display keypad is locked while learn mode is Active. Panel will display “LEARN MODE COMPLETE”
when process ends.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A S E L E C T R E S E T MO D E :
B L EARN A L L DE V I C E S
C P RE S S EN T ER TO S T AR T
D PANE L W I L L RE S E T
Exhibit 4-27: LEARN ALL DEVICES Screen
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A L E A R N MO DE I S AC T I V E
B WA I T TO COMP L E T E > >
C 0 9 : 2 7 : 4 7 A 0 3 / 1 0 / 2 0 0 9
D A L : 0 0 0 S U : 0 0 0 T R : 0 0 0
Exhibit 4-28: LEARN Mode Active Screen
The display keypad is locked while learn mode is Active. Panel will display “LEARN MODE COMPLETE”
when process ends.
I CAUTION
The Learn ALL method will delete and/or add supervision to
devices. Testing or review of the configuration should be
performed to ensure that all required devices are supervised.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A C H A N N E L MOD E : S I NG L E
B S EQUENCE : S T ANDARD
C V O I CE OU T PU T S : ON
D F 1 - MNS R F 2 - PR I OR I T Y
Exhibit 4-29: Voice Operations Screen
Row A - This field allows you to select whether all system amplifiers will operate in single or dual-
channel mode. Press +/- to change from Single to Dual channel mode. A complete description of
each mode is described as follows.
Single Channel – each amplifier operates independently and is capable of playing a single
audio message in response to a system event.
Dual Channel – two amplifiers are tied together to form a single dual-channel, 50 watt
amplifier with 8 speaker circuits. One amp is dedicated for EVAC operation and the other is
dedicated for Alert operation.
Note: Certain cities require the voice system to operate in a specific manner that differs from the
standard operation of the voice system. By default, the Cheetah Xi will be set to STANDARD (no
city sequence).
Row C – This field allows you to enable Eclipse messages that are unique to voice operation to be
transmitted onto the SLC for the purpose of activating control or relay modules for voice operation.
Use the ◄► arrow keys to position the cursor under the field; then use the +/- keys to toggle the
field to ON or OFF. By default, the Cheetah Xi will be set to ON.
Row D – Press the F1 function button to access the mass notification reset screen or press the F2
function button to access the voice state priority screen.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A MAS S NOT I F Y S Y S T EM
B T I MEOU T : 0 0 0 M I NU T E S
C D I SAB L ED
D
Exhibit 4-30: MNS Reset Screen
Row B - This field allows you to set the MNS timeout delay. The selection ranges from “000 – 255
minutes”. Use the ◄► arrow keys to position the cursor under the field; then press +/- to change
the field value.
Row C – This field will toggle from DISABLED to ENABLED when time field is changed from “000”.
Note: This command is the same as pressing the F1 - MNS RST button in maintenance menu 2.
Note: Any change made to the panel’s voice state priorities only affects the operation of the voice system.
It does not affect the normal operation of the Cheetah Xi system with regards to state priorities.
Note: The Cheetah Xi system will NOT allow you to set the priority level for Alarm lower than the priority
level settings for Test Alarm, Supervision, and Process. Alarm must always be set a higher priority.
Note: A panel event or input switch with a lower priority setting cannot override a panel event or input
switch with a higher priority. A panel event or input switch with the same or higher priority can override
another panel event or input switch with the same or a lower priority setting.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A C O N F I GURA T I ON M ENU 2
B F 1 - T I ME F 4 - DA Y S EN
C F 2 - S I L ENC F 5 - ZO NE
D F 3 - P OWE R F 6 - ME NU 3
Exhibit 4-32: Configuration Menu 2
F1 = System Time Control Screen
F2 = System Silence Screen
F3 = System Power Screen
F4 = System Day/Night Sensitivity Screen
F5 = Zone Enable/Disable Screen
F6 = Configuration Menu 3
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A T I M E : H H : MM : S S AM
B D A T E : MM / D D / Y Y Y Y
C D AY : D A Y O F WE E K
D D AY L I GH T SAV I NGS : Y E S
Exhibit 4-33: Time Control Screen
Row A - This field allows you to set the Hour (HH), Minute (MM), Second (SS), and AM/PM values
for the system. Use the ◄► arrow keys to position the cursor under the field; then use the +/- keys
to increment/decrement the field to a different number.
Row B - This field allows you to set the Month (MM), Day (DD), and Year (YYYY) values for the
system. Use the ◄► arrow keys to position the cursor under the field; then use the +/- keys to
increment/decrement the field to a different number.
Row C - This field allows you to set the Day of the week for the system. Use the ◄► arrow keys to
position the cursor under the field; then use the +/- keys to increment/decrement the field to a
different day.
Row D - This field allows you to set whether Daylight savings time will be recognized by the system
(Yes/No). Use the ◄► arrow keys to position the cursor under the field; then use the +/- keys to
toggle the status.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A I NH I B I T : OF F REM : OF F
B AU T O UNS I L ENCE : 2 4 HRS
C A L A RM UNS I L E NCE : Y E S
D
Row A (REM) - This field allows you to turn the system Silence Reminder (On/Off). Use the ◄►
arrow keys to position the cursor under the field; then use the +/- keys to toggle status.
This feature requires that the panel produce a momentary pulse from the panel piezo/buzzer
following the silencing of outputs. If this is configured to be ON, the momentary piezo pulse is ½
second long every 14 seconds on a silenced panel.
Row B (AUTO UNSILENCE) - This field allows you to set how much time must elapse (1 – 24 hours)
before the panel will automatically unsilence after the panel’s SILENCE button has been pressed.
Use the ◄► arrow keys to position the cursor under the field; then use the +/- keys to
increment/decrement the time.
Note: NFPA 72 requires that a silenced panel shall be unsilenced within 24 hours.
Row C (ALARM UNSILENCE) - This field allows you to select whether a new alarm event will un-
silence the supervisory, trouble and process states. Use the ◄► arrow keys to position the cursor
under the field; then use the +/- keys to toggle status.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A A U X P OWE R MO DU L E : N O
B X F ORME R S I Z E : 1 2 0 V AC
C B A T T ERY MA I N : Y A U X : N
D S U P ERV AUX P OWE R : Y E S
Exhibit 4-35: Power Screen
Row A - This field allows you to turn on/off supervision of the Supplemental Power Supply (SPS), if
installed (Yes/No). Use the ◄► arrow keys to position the cursor under the field; then use the +/-
keys to toggle status.
Row B - This field allows you to select which AC power transformer is wired to the AC input terminal
(120/240VAC). Use the ◄► arrow keys to position the cursor under the field; then use the +/- keys
to toggle status.
I CAUTION
Selecting the incorrect transformer size could result in erratic
panel trouble conditions.
Row C - The BATTERY MAIN field allows you to turn on/off supervision of the Main controller
Battery Input terminals (Yes/No). Use the ◄► arrow keys to position the cursor under the field;
then use the +/- keys to toggle status.
The AUX field allows you to turn on/off supervision of the Supplemental Power Supply Battery input
(Yes/No), if Supplemental Power Supply is installed. Use the ◄► arrow keys to position the cursor
under the field; then use the +/- keys to toggle status.
Note: Main or Auxiliary Supervision of battery selection of NO is not an allowed setting for UL.
Row D - This field allows you to turn on/off supervision of the 24 VDC Auxiliary Power circuits
(Yes/No). Use the ◄► arrow keys to position the cursor under the field; then use the +/- keys to
toggle status.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A F 1 - DA Y T I ME S EN RANGE
B F 2 - S E L E C T HOL I DAY S
C
D
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A D A Y T I ME S E NS I T I V I T Y
B S T AR T : HH : MMA
C S T OP : HH : MM P
D D A Y O F WE E K : S M TWR F S
Exhibit 4-37: Daytime Sensitivity Range Screen
Row B - This field allows you to set the Daytime sensitivity start time: Hour (HH), Minute (MM),
AM/PM. Use the ◄► arrow keys to position the cursor under the field; then use the +/- keys to
increment/decrement the value at the field.
Row C - This field allows you to set the Daytime sensitivity stop time: Hour (HH), Minute (MM),
AM/PM. Use the ◄► arrow keys to position the cursor under the field; then use the +/- keys to
increment/decrement the value at the field.
Row D - This field allows you to set the Days of the week that will utilize the Daytime sensitivity
option. Use the ◄► arrow keys to position the cursor under the field; then use the +/- keys to turn
ON letter representing the day of the week. Toggle letter OFF if it stays with night sensitivity all day.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A HO L I D A Y S ( 1 ) 0 1 - 0 1
B 0 1 - 0 1 0 1 - 0 1 0 1 - 0 1
C 0 1 - 0 1 0 1 - 0 1 0 1 - 0 1
D 0 1 - 0 1 0 1 - 0 1 0 1 - 0 1
Exhibit 4-38: Holidays Screen
Row A-D - These 10 editable fields allow you to enter the Month (MM)-Day (DD) of holiday. Use the
◄► arrow keys to position the cursor under the field; then use the +/- keys to increment/decrement
the value at the field.
There are 2 holiday screens available to provide 20 holidays. To access the Holidays (2) menu, use
the ◄► arrow keys to move the cursor to the last field on the right (D18) on Row D; then press the
right ► direction arrow.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A ZO N E 0 0 1 : E NAB L ED
B CU S T OM M E S S ZONE 0 0 1
C AU T O COU N T D OWN : 0 3 0 S
D MA N U COU N T D OWN : 0 1 0 S
Exhibit 4-39: Zone Parameters Screen
Row A - These fields allows you to set the Enable/Disable status of the selected Zone. Use the ◄►
arrow keys to position the cursor under the field; then use the +/- keys to change zone number.
Use the ◄► arrow keys to position the cursor under the enable status field; then use the +/- keys to
toggle the status (Enable/Disable).
Row B - This range of fields allows you to set the Custom Message for the zone displayed in Row A.
Use the ◄► arrow keys to position the cursor under the field; then use the +/- button to cycle
through all ASCII characters and display the desired character.
Row C – Allows you to set the automatic pre-discharge countdown time for the selected zone (0 –
255 seconds, default 30 seconds).
Row D – Allows you to set the manual pre-discharge countdown time for the selected zone (0 – 30
seconds, default 10 seconds).
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A S I GNA L CODE
B ZONE 0 0 1
C 0 - 0 - 0 - 0
D NUM OF COD E S S E T : 0 0 0
Exhibit 4-40: Chime Code Screen
Row B - These fields allows you to select the zone number to assign a Chime Code to. Use the
◄► arrow keys to position the cursor under the field; then use the +/- keys to change zone number.
Row C - This range of fields allows you to set the custom chime code (3 or 4 digits) for the zone
displayed in Row B. Use the ◄► arrow keys to position the cursor under the field; then use the +/-
button to select the digit range from 0 to 9. If a three digit chime code is required, the fourth field
must be left at 0.
The codes chime at 1 second intervals. The time between digits is roughly 2 seconds. The time
between a 3 and 4 digit signal is about 6 seconds.
Row D – Displays the number of zones that have been assigned a chime code. As long as this field
is greater than 0, NAC #1 will be dedicated to chime code production.
Note: Pressing the F4 key from this screen will allow you to clear all chime codes to 0-0-0-0.
Factory initialization will also clear all chime codes.
Chime codes are produced on NAC #1 only. If a chime code is assigned to any zone, the configuration
screen for NAC #1 will show ‘CHIME CODE’ as the default protocol assignment on Row C, as shown below.
Neither Drill nor Walktest is allowed for NAC #1 when chimes codes are assigned.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A N A C # 1 : E NAB L ED
B S T A T E : S T A T E
C P R O T OCOL : CH I ME CODE
D S I L : N DR I L L : N WA L K : N
Exhibit 4-41: NAC Functions Screen
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A C O N F I G URA T I ON MENU 3
B F 1 - P E R I PH F 4 - ABOR T
C F 2 - WA L K F 5 - S EN CHG
D F 3 - GR O UND F 6 - MENU 4
Exhibit 4-42: Configuration Menu 3
F1 = Peripheral Device Configuration Menu
F2 = System Walktest Enable/Disable Screen
F3 = System Ground Fault Screen
F4 = Abort Configuration Screen
F5 = Day/Night Sensitivity Enable/Disable
F6 = Configuration Menu 4
Note: Detailed programming of each peripheral device is set using the panel configuration
software C-Linx.
Row C (Supervise) - This field allows you to turn on/off supervision of the RS485 peripheral
device/address shown in Rows A and B (Yes/No). Use the ◄► arrow keys to position the cursor
under the field; then use the +/- keys to toggle the status of the field.
Note: When a peripheral device is supervised and communications is lost between the
peripheral and the panel, a Peripheral Missing trouble will result.
Note: Peripheral devices with control capabilities must be supervised (i.e., Remote display with
reset button).
Row C (Z:) - This field allows you to assign zone number to a remote display unit (RDU). The zone
number will be used for the display of pre-discharge countdown, release, and abort functions for the
set zone (Cheetah Xi panels only), or for the activation or deactivation of process commands from
the RDU for the set zone.
Row D - This range of fields allows you to enter a 20 character custom message for the peripheral
device listed in Row B. Use the ◄► arrow keys to position the cursor under the field; then use the
+/- keys to cycle through all ASCII characters and display the desired character.
Note: This message will be displayed with each event associated with the selected peripheral.
4.4.1.1.1 PERIPHERAL DEVICE TESTING
When the peripheral device type is set to either SWITCH 20-ZONE or ANNUNC 20-ZONE, additional test
features can be performed on the selected peripheral device by pressing the F1, F2 or F3 keys:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A P E R I PHERA L ADDR : 0 2
B T Y P E : SMOK E CON T R OL
C S U P E RV I S E : Y E S Z : 0 0 0
D * * S E ND I NG L ED T E S T * *
Exhibit 4-45: LED Test Screen
Row D – Toggles to display the feedback message for the test initiated.
Press F1 to send a LED test command to the selected peripheral device. The feedback message
“**SENDING LED TEST**” will be indicated on Row D of the display, as shown above.
Press F2 to force the selected peripheral device to perform a checksum test on its configuration
memory. The feedback message “**CHECKSUM TEST**” will be indicated on Row D of the display.
If the checksum fails, a trouble message “PER #aa CONFIG ERROR” will be reported to the panel.
Press F3 to force the selected peripheral device to perform a checksum calculation on its
configuration memory. The feedback message “**CHECKSUM CALC**” will be indicated on Row D
of the display, as shown below.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A P E R I PHERA L A D DR : 0 2
B T Y P E : SMO KE C ON T ROL
C S U P E RV I S E : Y E S Z : 0 0 0
D * * C HECKS UM C A L C * *
Exhibit 4-46: Checksum Calc Screen
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A P E R I PHERA L ADDR : 0 2
B T Y P E : 2 5 6 L ED GRAPH I C
C S U P E RV I S E : Y E S Z : 0 0 0
D B U Z Z : Y
Exhibit 4-47: 256 LED Graphic Configuration Screen
Row D (BUZZ) - Allows you to Enable/Disable the piezo sounder on the graphic controller card
(Y/N). Use the ◄► arrow keys to position the cursor under each field; then use the +/- keys to
toggle the value at the cursor.
Note: After a system reset, the peripheral source will return to the default PANEL mode.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
B P E R I P H E RA L BUS S P E ED
C 3 8 4 0 0 b p s
D
I CAUTION
All devices connected to the peripheral bus must be capable of
supporting the higher 38400 bps communication speed if the
setting is to be used. Otherwise, 9600 bps must be used.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
AWA L K T E S T : E N A B L E D
B
C
D
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A GN D F A U L T S U P ERV I S E :
B L E V E L 1 : E N AB L ED
C L E V E L 2 : E N AB L ED
D O F F S E T : + 0 0 / + 0 0 AVG : 3
Exhibit 4-52: Ground Fault Screen
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A S E L E C T DE L A Y FOR AC
B P OWE R LOS S T ROUB L E :
C 0 0 HO URS
D
Exhibit 4-56: AC Delay Screen
Row C - This field allows you to set the AC trouble delay. Use the +/- keys to toggle the field value.
Enter 0 for no delay or enter a number (01 – 30 hours) to provide a delay for the trouble to be
transmitted to the DACT.
Row B - This field is used to select the protocol of the HLI that is connected to the control panel.
Use the +/- keys to toggle the selection between “OPEN PROTOCOL” or “MODBUS”.
OPEN PROTOCOL – This setting must be used when the open protocol HLI (P/N 68-023) is used.
MODBUS – This setting must be used when the Modbus HLI (P/N 68-517) is used.
Press the ENTER key to accept the change and advance to the VESDA Configuration menu. The
options presented in the VESDA Configuration menu will vary depending upon the HLI type
selected.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A V E S D A CON F I G U R A T I ON
B F 1 - A L ARM F E A T U RE S
C F 2 - S EC TOR F 4 - R E L EAS E
D F 3 - E VAX F 5 - C OMMA N D
Exhibit 4-58: VESDA Configuration Menu
F1 = VESDA Alarm Configuration Screen
F2 = VESDA Sector Zone Assignment Screen
F3 = VESDA Point Configuration Screen
F4 = VESDA Release Configuration Screen
F5 = VESDA HLI Command Set Screen
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A V E S DA ZONE NUM : 0 0 1
B T Y P E : COMP A C T A L M E NA
C C U S T OM ME S S AG E V Z 0 0 1
D Z O N E: 0 0 0 0 0 0 0 0 0 0 0 0
Exhibit 4-59: VESDA Alarm Features Screen
Row A - This field allows you to select the VESDA Detector Zone number to be configured. Use the
◄► arrow keys to position the cursor under the field; then use the +/- keys to change to a different
zone number.
Note: The zone number set here corresponds to zone number assigned to the VESDA detector
during programming.
Row B - The TYPE field allows you to select the VESDA Detector type associated with the selected
zone number from Row A. Use the ◄► arrow keys to position the cursor under the field; then use
the +/- keys to select the desired detector type (i.e., Compact, Laser-P, Scanner, L-Focus, VLI-885).
The ALM field allows you to select the state of operation for the detector (ALM default). Use the
◄► arrow keys to position the cursor under the STATE field; then use +/- keys to select the state of
operation for the detector.
The ENA field allows you to select the Enable/Disabled state of the detector. Use the ◄► arrow
keys to position the cursor under the ENA field; then use the +/- keys to enable or disable that
detector
Row C - This range of fields allows you to assign a Custom Message for detector that will be
displayed on the Cheetah Xi panel. Use the ◄► arrow keys to position the cursor under the field;
then use the +/- keys to cycle through all ASCII characters and display the desired character.
Repeat for each field until custom message is completed.
Row D - These fields allow you to select up to four Cheetah Xi zones that this detector will
participate in. Use the ◄► arrow keys to position the cursor under each field; then use the +/- keys
to change zones to that desired. Repeat for each of 4 zones required. Remember, Zone 255 is
ANY Zone.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A V E S DA ZON E NUM 0 0 1
B LOOP : 0
C ADDR : 0 0 0
D F 1 - S EC TO R ME S SAGE S
Exhibit 4-61: VESDA Loop/Addr Screen
Row A - This field allows you to select the VESDA detector Zone Number to be configured. Use the
◄► arrow keys to position the cursor under the field; then use the +/- keys to change to VESDA
detector zone number.
Row B - This field allows you to select a virtual loop number that the VESDA detector activation will
correspond with. Use the ◄► arrow keys to position the cursor under the field; then use the +/-
keys to change the loop number.
Row C - This field allows you to select a virtual address number that the VESDA detector activation
will correspond with. Use the ◄► arrow keys to position the cursor under the field; then use the +/-
keys to change the address number.
Note: The VESDA virtual address number does not require a physical component on the SLC
loop. It does require a virtual address that cannot be used for any other physical device on the
SLC loop.
Row D – This feature is only available if HLI type is set to MODBUS.
Note: The zones involved in suppression are the four zone numbers selected in the Alarm
Features screen (see 4.5.2.1.1). Sector zones are NOT involved in suppression.
Row C – This field allows you to select whether the selected VESDA unit will initiate the pre-
discharge state upon the VESDA unit reaching Fire-1 or Fire-2 alarm level. Use the ◄► arrow keys
to position the cursor under the field; then use the +/- keys to change the field value.
Row D – This field allows you to select whether the selected VESDA unit will utilize the Automatic or
Manual countdown timer set for the zone should it cause a pre-discharge in any of its assigned
zones (see 4.5.2.1.1). Use the ◄► arrow keys to position the cursor under the fields; then use the
+/- keys to change the field value.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A H L I T Y P E :
BMA S T E R - S L A V E ( N EWE R )
C S O F TWA RE V ERS I ON :
D 0 0 3 . 0 0 8 . 0 0 0
Exhibit 4-63: VESDA Command Set Screen
Pressing ENTER will cause the panel to query the connected HLI to determine its software version.
The software version of the HLI will be displayed on Row D.
MASTER-SLAVE (NEWER): Allows communication with up to 40 VESDA units while still meeting UL
and NFPA’s 10 second supervision response time. HLI firmware version 3.08.00 or higher.
PEER-TO-PEER (OLDER): Allows communication with up to 40 VESDA units, but only 10 can be
connected to the HLI and still meet UL and NFPA’s 10 second supervision response time. HLI
firmware versions older than 3.08.00.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A F 1 - D E T E C TORS
B F 2 - S EC T ORS AND P I P E S
C F 3 - T EM P L A T E S F 5 - H L I
D F 4 - A NN U N F 6 - RE L EAS E
Exhibit 4-64: VESDA Configuration Menu
Row A (ZONE) - This field is used to select the VESDA detector (zone) to be configured. Use the +/-
keys to change to a different detector (zone) number.
Note: The zone number selected here corresponds to zone number assigned to the VESDA detector
during programming. Each detector on the VESDAnet must be assigned a unique zone number (1–
246). This identifier is typically different than the zone that it is programmed to participate in the panel
(Row D).
Row B (TYPE) - This field is used to select the VESDA detector type associated with the selected
detector (zone) number from Row A. Use the ◄► arrow keys to position the cursor under the field; then
use the +/- keys to select the desired detector type: VLC, VLP, VLS, VLF, VLI, VFT-15, VEP, VEP-1,
VEP-2, VEU, VEA-40, VEA-60, VEA-80, VEA-100, VEA-120.
Note: If the detector type is set to VFT-15, the next 15 consecutive VESDA zone numbers directly
after the zone number selected in Row A will automatically be assigned to the VFT detectors
sampling tubes (sectors). No other VESDA detector can occupy these zones.
Row B (ALM) - This field is used to select the state the panel will enter when the VESDA reaches the
FIRE-1 level. Use the ◄► arrow keys to position the cursor under the “ALM” field; then use +/- keys to
select the state of operation for the detector; “ALM” (Alarm-default) or “SUP” (Supervisory).
Note: If the panel is configured for Alarm operation at VESDA Fire-1 level, the VESDA detector must
be programmed to latch the event at the Fire-1 and Fire-2 levels.
Row B (ENA) - This field is used to select the Enable/Disable state of the detector. Disabling will stop the
panel’s supervision of the detector. Use the ◄►arrow keys to position the cursor under the “ENA” field;
then use the +/- keys to enable or disable the detector. If the VESDA is disabled and still attached to P4,
the panel will treat this condition as an un-configured VESDA and will display a “VESDA CFG ERR” for
this condition.
Row C - This range of fields is used to assign a Custom Message for detector that will be displayed on
the Fike control panel. Use the ◄► arrow keys to position the cursor under the field; then use the +/-
keys to cycle through all ASCII characters and display the desired character. Repeat for each field until
custom message is completed.
Row D - These fields are used to select up to four panel zones that this detector will participate in. These
zone assignments are used to activate alarm notification appliances and other control functions
associated with the panel. Use the ◄► arrow keys to position the cursor under each field; then use the
+/- keys to change zones to that desired (1–253). Repeat for each of four zones required.
Press the ESCAPE key to return to the Modbus HLI configuration menu.
From the “MODBUS HLI MENU”, press the F2 key to access the “SECTORS AND PIPES” screen.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A V E S D A ZONE NUM : 0 0 1
B T Y P E : V EA - 1 2 0
C P I P E : 0 0 1 A L ARM
D Z O N E : 0 0 1
Exhibit 4-66: VESDA Sectors and Pipes Screen
Row A - This field is used to select the VESDA detector (zone) to be configured (1-246). Use the +/-
keys to change to a different detector (zone) number.
Note: The zone number selected here corresponds to zone number assigned to the VESDA
detector during programming. Each detector on the VESDAnet must have a unique zone
number. This identifier is different than the zone that it is programmed to participate in the panel
(Row D).
Row A (VZ) - This field displays the control panel zone number that has been assigned to the
VESDA detector.
Row B (Type) - This field displays the type of VESDA associated with the detector (zone) number
selected in Row A: VLC, VLP, VLS, VLF, VLI, VFT-15, VEP, VEP-1, VEP-2, VEU VEA-40, VEA-60,
VEA-80, VEA-100, VEA-120.
Row C (Pipe) – These fields are used to assign a panel operational state “Alarm” or “Supervisory” to
the selected VESDA pipe number. Use the ◄► arrow keys to position the cursor under the pipe
field (000); then use the +/- keys to select the desired pipe. Use the ◄► arrow keys to position the
cursor under the state field; then use the +/- keys to toggle between the available states “ALARM”
and “SUPERVISORY”. Repeat for each pipe (sector).
Note: If the main detector configuration is set for “SUPERVISORY”, pipes can only be assigned
to the “SUPERVISORY” state. If the main detector configuration is set for “ALARM”, pipes can
be assigned to either the “SUPERVISORY” or “ALARM” state.
Row D (Zone) – This field is used to assign a panel zone that the VESDA pipe (sector) selected in
Row C will participate in. Use the ◄► arrow keys to position the cursor under the field; then use
the +/- keys to assign the pipe to the zone for annunciation purposes (1-253). Repeat for each pipe
(sector).
Row D (Templates) - If the VESDA type indicated in Row B is a VEA detector, Row D will change
from “Zone” to “Templates”. The three template fields are used to assign the VEA detectors multiple
sampling pipes to individual zone templates for annunciation purposes. Use the ◄► arrow keys to
position the cursor under each field; then use the +/- keys to assign the zone templates. Repeat for
each template field.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A V E S D A ZONE NUM : 0 0 1
B T Y P E : V EA - 1 2 0
C P I P E : 0 0 1 A L ARM
D T E M P L A T E S : 0 0 0 0 0 0
Exhibit 4-67: VESDA Sectors and Pipes Screen (templates)
Press the ESCAPE key to return to the Modbus HLI configuration menu.
From the “MODBUS HLI MENU”, press the F3 key to access the “TEMPLATES” screen.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A T E M P 0 0 P 0 1 - 1 0 0 1 : 0 0 0
B 0 2 : 0 0 0 0 3 : 0 0 0 0 4 : 0 0 0
C 0 5 : 0 0 0 0 6 : 0 0 0 0 7 : 0 0 0
D 0 8 : 0 0 0 0 9 : 0 0 0 1 0 : 0 0 0
Exhibit 4-68: VESDA Templates Screen
Row A (TEMP) – This field is used to select the zone template to be configured. Use the +/- keys to
change to a different template number (00 – 19).
Row A (P01-10) – This field is used to select the group of pipes to be configured for the selected
template in Row A.
Rows A–D (Zone fields) – These fields are used to assign a zone that the VESDA pipe (sector) will
participate in. Use the ◄► arrow keys to position the cursor under the field; then use the +/- keys to
assign the pipe to the zone for annunciation purposes (1-253). Repeat for each pipe (sector).
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A V E S DA ZON E NUM 0 0 1
B LOOP : 0
C ADDR : 0 0 0
D F 1 - S EC TO R ME S SAGE S
Exhibit 4-69: VESDA Loop/Addr Screen
Row A - This field allows you to select the VESDA detector Zone Number to be configured. Use the
◄► arrow keys to position the cursor under the field; then use the +/- keys to change to VESDA
detector zone number (1 – 246).
Note: The zone number set here corresponds to zone number assigned to the VESDA detector during
programming. Each detector on the VESDAnet must have a unique zone number.
Row B - This field allows you to select a virtual loop number that the VESDA detector activation will
correspond with. Use the ◄► arrow keys to position the cursor under the field; then use the +/-
keys to change the loop number.
Row C - This field allows you to select a virtual address number that the VESDA detector activation
will correspond with. Use the ◄► arrow keys to position the cursor under the field; then use the +/-
keys to change the address number (1 – 254).
Note: The VESDA virtual address number does not require a physical component on the SLC
loop. It does require a virtual address that cannot be used for any other physical device on the
SLC loop.
Row D - Press the F1 key to access the VESDA sectors custom message configuration screen.
Refer to Section 4.5.2.2.5.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A M E S S AGE NUM BER : 0 0 1
B V E S D A : 0 0 1 S EC TOR : 0 0 1
C C U S T OM ME S S AGE V Z 0 0 1
D T Y P E : - - - - - - -
Exhibit 4-70: VESDA Sectors Screen
Row A - This field is used to select the VESDA sector message number to be configured. Use the
◄► arrow keys to position the cursor under the fields; then use the +/- keys to change to VESDA
sector message number (1 – 400).
Row B – These fields are used to select the VESDA zone (1 - 246) and sector number (1 - 120) that
will be assigned to the message number selected in Row A. Use the ◄► arrow keys to position the
cursor under the fields; then use the +/- keys to change to VESDA zone and sector number.
Row C – These fields are used to define the 20 character custom message that will be assigned to
the message number selected in Row A. Use the ◄► arrow keys to position the cursor under the
fields; then use the +/- keys to change the field value.
Row D – Displays the detector type for the VESDA zone selected in Row B. Informational purposes
only.
Note: A factory level password must be entered in order to enable this panel feature.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A H L I T Y P E :
B MO D B U S
C P RO T OC OL : 0 0 0 . 0 2 2 . 0 2 0
D S O F TWA RE : 0 0 0 . 0 0 0
Exhibit 4-72: HLI Protocol and Software Screen
Row B (TYPE) – Displays the HLI type (Open Protocol / Modbus) the panel is configured to
communicate with.
Row C (PROTOCOL) – Displays the protocol version used by the connected HLI.
Row D (SOFTWARE) – Displays the software version used by the connected HLI.
Press the ENTER key will cause the panel to query the connected HLI to determine its protocol and software
version. The protocol and software version numbers will briefly show all ‘0’s after ENTER is pressed until the
HLI returns these values and they are displayed on rows C and D.
The PWR CUT screen allows you to set the address of the relay module that will be used to perform power
cutoff to the panel should the standby battery voltage drop below 18 volts.
From the Configuration Menu 4 screen, press the F4 key to access the PWR CUT relay assignment screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A S E L EC T P OWE R
B CU TOF F DE V I CE A T
C LOOP : 0 ADDR : 0 0 0
D
Note: The addressable relay module contacts will transfer and latch when a panel voltage
trouble is recorded. The relay contacts will remain latched even if the panel power is removed.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A F 1 - S E L E C T MO DU L E
B F 2 - R E L AY F UN C T I ONS
C F 3 - R E L AY ZON E AS S I GN
D F 4 - F A N RE S T A R T MOD E
Exhibit 4-74: Relay Configuration Menu
F1 = Select Module Screen
F2 = Assign Relay Functions Screen
F3 = Relay Zone Assignment Screen
F4 = Fan Restart Mode Screen
The Select Module screen allows you to select the type of module that is installed in the Cheetah Xi’s P12
and P13 optional card mounting positions.
From the “Relay Configuration Menu” screen, press the F1 key to access the “Select Module” screen, as
shown below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A MODU L E A T
B P 1 2 : BOSCH DAC T
C P 1 3 : CRM4
D
ICAUTION
It is important that the panel configuration for P12 & P13 match
the module type actually installed to avoid improper operation.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A R E L A Y P 1 2 A : D I S AB L ED
B S T A T E : S T A T E P R OG
C S I L E NCE : NO DR L L : NO
D R E S T AR T DE L AY : 0 0 0 S EC
Exhibit 4-76: Relay Functions Screen
Row A - This field allows you to select the relay to configure (P2 relays NUM1-3, P12A-D, P13A-D).
Use the ◄► arrow keys to move the cursor under the field; then use the +/- keys to select a
different relay.
This field allows you to set the Enable/Disable status of the selected relay. Use the ◄► arrow keys
to move the cursor under the field; then use the +/- keys to toggle the relay status.
Note: The default state for Relay NUM3 is Trouble and it’s configuration parameters cannot be
changed.
Row B - This field allows you to set the relay activation state (i.e., Alarm, Pre-Discharge, Release,
Pre Alarm #2, Process, Trouble, Supervisory, Abort, Zone Disable, Pre Alarm #1) for the relay
selected in Row A. Use the ◄► arrow keys to move the cursor under the field; then use the +/-
keys to toggle the desired state.
Row C - This field allows you to set the Silenceable and Drill Enabled/Disabled (Y/N) status for the
relay selected in Row A. Use the ◄► arrow keys to move the cursor under the field; then use the
+/- keys to toggle to the desired status.
Row D - This field allows you to set the CRM4 relay selected in Row A for fan restart operation by
assigning it a restart delay time (40 – 250 seconds). Use the ◄► arrow keys to move the cursor
under the field; then use the +/- keys to toggle to the desired delay time. Once a delay time is
selected, the relay will become normally energized and will only de-energize upon activation of the
assigned state and zone. Once de-energized, the relay will not energize until after the panel has
been reset and the set time delay has expired. Fan restart relays will not change state through a
panel reset.
Note: By default, the restart delay is set to ‘000’ allowing the relay to operate as a normally de-
energized relay with no restart delay.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A R E L AY P 1 2 A : M U L T I ZO
B Z O N E RAN G E : 0 0 1 - 0 2 0
C 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
D - - - - - - - - - - - - - - - - - - - -
Exhibit 4-77: Relay Zone Assign Screen
Row A - This field allows you to set whether the relay shown in Row A will activate on ANY ZONE or
MULTI ZONE. To select a different relay, use the ◄► arrow keys to move the cursor under the
relay field; then use the +/- keys to increment/decrement the field.
To change the Zone Selection Status of the circuit, use the ◄► arrow keys to move cursor to the
zone selection field; then use the +/- keys to toggle the field (ANY ZONE or MULTI ZONE).
Note: The Any Zone option sets the selected relay to activate on the configured state for any
zone. The Multi Zone option sets the selected relay to activate on the configured state for any
zone selected in Row D.
Row B - This field allows you to set the 20 zone range that is displayed in Rows C & D. To change
the zone range, use the ◄► arrow keys to position the cursor under the zone range field; then use
the +/- keys to increment/decrement the group of 20 forward or backwards (Zones 001-254).
Row C - These numbers act as placeholders and zone number indicators for the range of zones
selected on Row B.
Row D - This range of fields allows you to set the zone assignment programming for the relay
displayed in Row A if MULTIZONE is selected.
- = not programmed for this zone
Y = programmed for this zone
Use the ◄► arrow keys to position the cursor under the specific zone position; then use the +/- keys
to toggle the status.
Note: The Any Zone option sets the selected relay to activate on the configured state for any
zone. The Multi Zone option sets the selected relay to activate on the configured state for any
zone selected in Row D.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A S E L EC T F AN RE S T AR T
B MOD E : A U T OMA T I C
C
D
Row B - This field allows you to select whether relays configured for Fan Restart automatically
transfer after set time or if the set time begins upon a manual input.
AUTOMATIC (factory default) – Upon activation of an ALARM event, the CRM4 relays will activate and
remain active until panel is reset. Once the panel is reset, the fan restart sequence begins and fan restart
relays will deactivate according to their programmed time delay.
MANUAL – Upon activation of an ALARM event, the CRM4 relays will activate and remain active until panel
is reset. After panel reset, the fan restart sequence is delayed until the operator activates any of the following
switch sources: 1) Panel’s ENTER key, 2) monitor module configured for Fan Restart, 3) RDU switch
configured for Fan Restart. Upon switch activation, the panel will initiate the automatic fan restart sequence
and the relays will deactivate according to their programmed time delay. Once all relays are deactivated, the
panel will return to normal operation.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A C O N F I GURA T I ON M ENU 5
B F 1 - LOGO F 4 - D I A L ER
C F 2 - AU TO A F 5 - NE T WO R K
D F 3 - F 6 - ME NU 6
Exhibit 4-79: Configuration Menu 5
F1 = Edit Panel Logo Screen
F2 = Auto Addressing Screen
F3 = Not Used
F4 = Dialer Auto Test Screen
F5 = Network Configuration Menu
F6 = Configuration Menu 6
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A PANE L LOGO
B ON L I NE 2 :
C F I KE CORPORA T I ON
D
Row C - This range of fields allows you to set a logo (name) that will appear on the second line of
the panel display. To change the logo, use the ◄► arrow keys to move cursor to the field; then use
the +/- keys to advance/decrement the character at the selected field.
Note: This is NOT the message that identifies the panel on the network or with panel generated
events. Refer to the Network configuration menu to configure the panel custom message.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A A U T O AD D RE S S I NG : OF F
B S E L EC T L OO P S : 1 2 3 4
C S E L EC T A DD RS : 0 0 1→0 5 0
D P R E S S E N T E R TO S TORE
Exhibit 4-81: Auto Address Screen
Row A - This field allows you to turn the Auto Addressing feature ON/OFF. Use the ◄► arrow keys
to move cursor to the field; then use the +/- keys to toggle the field (ON/OFF).
Row B - This field allows you to select which addressable loops will be affected when Auto
Addressing is turned ON. Use the ◄► arrow keys to move cursor to the field; then use the +/- keys
to toggle the field.
Row C - This field allows you to select the address range that you would like to auto address. Use
the ◄► arrow keys to move cursor to the field; then use the +/- keys to toggle the field.
Row D - When you have the address range that you would like to have auto addressed, press the
Enter key. Devices will NOT be addressed until it is added to the loop (NEW DEVICE record
identified) and the panel is reset.
Row B - This field allows you to set the number of hours that must elapse before the second and
successive dialer tests are performed. Configurable options include ‘06Hours’, ‘12Hours’, and
‘24Hours’. Use the +/- keys to change the value at the cursor. Default is ‘DISABLE’ for no test.
Row C - This field allows you to set the starting hour to begin the daily dialer test. Configurable
between 0 and 23 hours, where the default is 2 AM. Use the ◄► arrow keys to move cursor to the
field; then use the +/- keys to increment/decrement the time.
Note: The Contact ID dialer is capable of performing its own operational tests. Configuring the
panel to initiate its own test might be redundant and could be considered a nuisance to the
monitoring company. Only utilize this feature if instructed to do so by the local authority.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A CON F I G U R E N E T WO R K
B F 1 - I D ‘ S F 4 - H I S T T R
C F 2 - M O D U L E F 5 - SW I T C H
D F 3 - Z O N E S F 6 -
Exhibit 4-83: Network Configuration Menu
Note: To ensure proper panel network operation, all panels must utilize the same firmware version and
all network cards must utilize the same firmware version.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A N E T WO R K PAN E L I D : 0 0 1
B A L L NE T I D ‘ S : 0 0 1 - 0 2 0
C 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
D
Row A - This field allows you to set a unique network ID (Address) for the respective panel. Use the
◄► arrow keys to move cursor to the field; then use the +/- keys to change network ID.
Row B - This field allows you to select the 20 IDs range displayed in Rows C & D. To change the ID
range, use the ◄► arrow keys to position the cursor under the range field; then use the +/- button
to increment/decrement the range in groups of 20 forward or backwards (ID’s 001 – 128)
Row C - These numbers act as placeholders and zone number indicators for the range of zones
selected on Row B.
Row D - These fields allow you to select the Network panel ID’s to be supervised by this panel. The
fields show the panel IDs on the network in groups of 20. Move the cursor with the ◄► arrow keys
to position under desired ID number shown on Row C; then use the +/- keys to toggle a Y under
each network panel ID that you want this panel to supervise.
Y = Supervise this panel ID
Blank = No supervision of that network ID
To set the custom message for network panels, press the F1 key:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A C U S T OM ME S S AG E
B FOR PANE L : 0 0 1
C
D CU S T OM MSG PANE L 0 0 1
Exhibit 4-85: Network Panel Custom Message Screen
Row B - This field allows you to select the network panel address to assign a custom message to.
This message will be shown for history events. Use the ◄► arrow keys to move cursor to the field;
then use the +/- keys to change panel address.
Row D - This field allows you to assign the custom message for the respective panel. Use the ◄►
arrow keys to move cursor to the field; then use the +/- keys to change the field value.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A MOD U L E T Y P E : N O NE
B NE TW W I R I NG : S T Y L E - 4
C SW F U N CT I ON : L O CA L
D CUS TO M M S G PA N E L 0 0 1
Exhibit 4-86: Network Module Config Screen
Row A - This field allows you to define the location of the panel under configuration with respect to
other panels on the network. Use the ◄► arrow keys to move cursor to the field; then use the +/-
keys to toggle module type.
NONE (default) – Select this option if the respective fire panel has no network module installed or to
temporarily isolate the panel from the network. All network messages (incoming and outgoing) will
be ignored. The network module will continue to operate and pass along messages to other panels
as long as the network wiring remains in place.
FIRST – A Cheetah Xi network must have at least two panels. One of the two panels, regardless of
wiring style, must be configured as the First panel. This requirement is present to provide
directionality to the network wiring and provide assistance in diagnostics.
MIDDLE – If the Cheetah Xi network has more than two panels (maximum of 128), every panel on
the network not configured as either a First or Last, must be configured as Middle or None.
LAST – A Cheetah Xi network must have at least two panels. One of the two panels, regardless of
wiring style, must be configured as the Last panel. This requirement is present to provide
directionality to the network wiring and provide assistance in diagnostics.
Row B - This field allows you to set the wiring style used by the network (Class B/Style 4 or Class
A/Style 7). Use the ◄► arrow keys to move cursor to the field; then use the +/- keys to toggle
between the Network Wiring Styles. When set for Style 7 wiring, the First panel will monitor the
Class-A homerun wires.
Row C - This field allows you to control the switch functionality of the panel. Use the ◄► arrow
keys to position the cursor under the LOCAL/GLOBAL field; then use the +/- keys to toggle between
those values.
LOCAL – The respective panel will accept switch functions only from network panel IDs selected by
the network switch configuration screen. See Section 4.6.4.5.
GLOBAL – The respective panel will accept switch functions from any panel on the network. When
set to Global, all of the panel IDs in the “Network Switch Configuration” screen (See Section 4.6.4.5)
will have a lower case “y”.
Row D - This range of fields allows you to set a custom message for this network panel. Use the
◄► arrow keys to move cursor to the field; then use the +/- keys to cycle through all ASCII
characters and display the desired character. Arrow to next character and repeat until custom
message is completed.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A A S S I G N T O N E T WO R K
B ZONE RANGE : 0 0 1 - 0 2 0
C 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
D
Row B - This field allows you to set the 20 zone range that will be displayed in Row C & D below.
Use the ◄► arrow keys to move cursor to the field; then use the +/- button to increment/decrement
the range in groups of 20 to display at one time. This will cycle through the 254 zones available on
the Cheetah Xi.
Note: Pressing the F5 key will select all zones and pressing the F6 key will deselect all zones.
Row C - These numbers act as placeholders and zone number indicators for the range of zones
selected on Row B.
Row D - This range of fields allows you to select the zones that the specific panel will react to.
Blank = will ignore events in this zone
Y = will react to events in this zone
Use the ◄► arrow keys to position the cursor under the specific zone field; then use the +/- keys to
toggle to Y to participate and – to not participate. If a zone is not selected to participate, it will still
show up in History but does not act on the state indicated in that zone. Events from this panel are
still transmitted onto the network regardless of this setting. For example: A panel with a “–“ in the
Zone 3 field, will cause a panel with “Y” in the same field to react to that zone.
Note: Zone 254 is the panel zone. Any states activated by zones 1 – 253 will generate the same
state in zone 254. In order to prevent the selected panel from reacting to a network panel event
while a respective hazard zone (1 – 253) is disabled, but still allow the panel to react on “Any
Zone”, you will need to specifically select zones 1 – 253 and leave Zone 254 not selected so as
to not slow down network response times.
Note: Increasing the number of history transmits is recommended where the Cheetah Xi panel is
installed in a noisy environment.
Row C – This field allows you to turn message filtering on for transmission of network history events.
Message filtering provides a means to prevent invalid history events from being recorded by network
panels. If this feature is used, all panels on the network must have the same filter setting. No mixing
is allowed. Use the ◄► arrow keys to move cursor to the field; then use the +/- buttons to change
the value between “ON” or “OFF”. The factory default value is “ON”.
Row D – This field allows you to turn “ON” or “OFF” the panel’s 1000 event history buffer limit. A
System Administrator level password is required to change this setting.
ON = When a new event on the SLC is recorded (or VESDA), the appropriate zones are
activated and output devices respond correctly. However, after 1000 events are recorded
(after the 1st alarm), history events are no longer recorded or transmitted across the network
and peripheral buses. The result is that not all events will be transmitted to the network
panels, peripheral bus devices, or Precise Vision.
OFF = All history events are recorded and transmitted onto both the network and peripheral
buses. Once the 3200th event is recorded, all succeeding events are recorded into the
3200th history position.
Row B - This field allows you to set the 20 IDs range that will be displayed in Rows C & D below.
Position the cursor under the first number in this line; then use the +/- button to
increment/decrement the range in groups of 20 to display at one time. This will cycle through the
128 panels available on the Cheetah Xi
Row C - These numbers act as placeholders and zone number indicators for the range of zones
selected on Row B.
Row D - This range of fields allows you to select the network panel IDs that the specific panel will
act upon when a switch command is received.
- = not programmed for this network ID.
Y = will react to switches from this network ID (Local switch function)
y = will react to switches from all other network panels (Global switch function)
Use the ◄► arrow keys to position the cursor under the specific zone field; then use the +/- keys to
toggle to Y to accept switch inputs and – to not accept switch inputs.
Row B - The SRC (Source) field allows you to set the unique Internet Protocol (IP) Address for the
selected fire panel. This address is required to uniquely identify the fire panel on a given Ethernet
network. Use the ◄► arrow keys to position the cursor under the field; then use the +/- keys to
increment/decrement the field.
Row C - The HIST (History) field allows you to set the unique Internet Protocol (IP) Address of the
panel that will receive history messages from this panel. Use the ◄► arrow keys to position the
cursor under the field; then use the +/- keys to increment/decrement the field.
Note: The History IP Address should equal the Source IP Address of the receiving panel.
Row D - The SUPV (Supervision) field allows you to set the unique Internet Protocol (IP) Address of
the panel that is supervising the selected panel. Use the ◄► arrow keys to position the cursor
under the field; then use the +/- keys to increment/decrement the field.
Exception: If the “Monitor” panel has none of these states active; Alarm, Supervisory, Trouble, Pre-Alarm, or
Process, then the “Monitor” panel will not request histories from the panels it is supervising. If the
“Monitor” has any of these five states active prior to reset, then the “Monitor” will request a re-
send of the histories received via the Ethernet port.
The Clear IP Address screen allows you to clear the IP addresses of those panels that have sent history
messages to the “Monitor” panel, temporarily disabling the history resend request. Press the F1 key to
access the “Clear IP Addresses” screen, as shown below; then press the ENTER key to clear all of the
“Monitor” panels stored IP addresses.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A P R E S S EN T ER T O C L EAR
B H I S TORY REC E I V ED
C I P ADDRE S S E S
D
Row D - This field allows you to enter the Source IP Address for the panel ID selected in Row B.
Use the ◄► arrow keys to position the cursor under the field; then use the +/- keys to
increment/decrement the field.
Note: Any fire panel added to the list of supervised panels must have its Supervision IP Address
set to match that of the supervising fire panel’s Source IP Address.
Note: To remove a panel from the list, simply select it and change the panel address to all zeros.
To set the custom message for network panels, press the F1 key:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A C U S T OM ME S S AG E
B FOR PANE L : 0 0 1
C
D CU S T OM MSG PANE L 0 0 1
Exhibit 4-94: Network Panel Custom Message Screen
Row B - This field allows you to select the network panel address to assign a custom message to.
Use the ◄► arrow keys to move cursor to the field; then use the +/- keys to change panel address.
Row D - This field allows you to assign the custom message for the respective panel. Use the ◄►
arrow keys to move cursor to the field; then use the +/- keys to change the field value.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A I P SUP ERV I S I ON
B T I MEOU T : 0 4 M I NU T E S
C H I S TOR Y T R ANSM I T S : 0 1
D I P T I M E : D I SAB L ED
Exhibit 4-95: IP Time Screen
Row B - This field allows you to set how long the supervising panel will wait to annunciate a
“MISSING” trouble should the supervising panel lose communication with a supervised panel. Use
the ◄► arrow keys to position the cursor under the field; then use the +/- keys to toggle to select
time.
This parameter can be configured in one of the following increments:
5-55 seconds, 5 second increments
1-59 minutes, 1 minute increments
1-18 hours, 1 hour increments
Note: This parameter only applies when the respective panel is configured to supervise other
panels.
Row C - This field allows you to set how many times a single history event will be transmitted to the
peripheral bus. This setting greatly affects the reliability of the Ethernet reporting system. The value
can be configured from 1 to 10:
1 = Provides the greatest amount of speed but is the least reliable.
10 = Provides a reduction in speed but is the most reliable.
Use the ◄► arrow keys to position the cursor under the field and use the +/- keys to
increment/decrement the field.
Note: For Ethernet applications, Fike recommends a History Transmit setting of 2. Otherwise,
the default value of 1 is recommended.
Row D - This field allows you to set whether the date and time of networked panels will be
synchronized with the main panel (DISABLED, ACCEPT, SEND):
DISABLED = Turns panel date/time synchronization feature off. Each panel will use its own
date/time settings.
ACCEPT = Sets panel to accept date/time synchronization settings from sending panel.
SEND = Sets panel to transmit date/time synchronization settings to all network panels.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A SW I T CH OP E RA T I ON
B FOR DR I L L / S I L ENCE :
C NORM A L
D K E Y P A D DR I L L : D I SAB L E
Exhibit 4-96: Panel Switch Operation Screen
Row C - Use the +/- keys to toggle the functionality of the Drill and Silence keys between
NORMAL/DISABLED
Note: If the panel is ordered with the “COC” extension in the part number, it will be shipped with
a display that has the Drill and Silence keys blanked out. The functionality of these keys will be
disabled and will require a factory level password to re-enable.
Row D - Use the +/- keys to toggle the functionality of the Drill key between ENABLED/DISABLE.
Activation of the Drill function from other sources are unaffected by disabling the keypad drill switch.
Note: Disabling the keypad drill switch requires a System Administrator level password.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
B L ED OP ERA T I ON :
C PRE - D / RE L E / R - D I S / AB T
D
Row C - Use the +/- keys to toggle the functionality of the panel’s LEDs between:
Fire Alarm = Pre-Alarm 1, Pre-Alarm 2, Disabled, Walk Test
Fire Suppression = Pre-Discharge, Release, Release-Disable, Abort
F1 = AHU Key
F2 = Not Used
F3 = Not Used
F4 = First Event Display
F5 = Not Used
F6 = Configuration Menu 1
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A AHU KE Y REQU I RED : NO
B
C
D
Row A - Use the +/- keys to toggle the field from ‘No’ to ‘Yes’. ‘Yes’ will require an AHU fire key
switch to be active before fan restart sequence is allowed.
Row D - Use the +/- keys to toggle the field from ‘Yes’ to ‘No’.
‘Yes’ - panel will latch the display onto the first trouble or supervisory event that is recorded.
Subsequent events of like type will be recorded in the panel history but will not be displayed
as they occur unless they are of higher priority. For example: supervisory events take
priority over trouble events; therefore, first supervisory event will be displayed over trouble
events. The LCD will remain fixed on the first of these events until the user presses a switch
for other actions, the event clears and the system times out and returns to the “System
Normal” display, or an alarm event occurs. Should an alarm event occur, the LCD will latch
on the first alarm event and will remain fixed on the event until the user presses a switch for
other actions.
“No’ – panel will display supervisory and trouble events as they occur until the first alarm
event is recorded, at which time the LCD will latch on the first alarm event. The LCD will
remain fixed on the first alarm event until the user presses a switch for other actions.
SYSTEM STATUS SYSTEM EVENT LEVEL 2 (USER): ALL LEVEL 1 PRIVILEGES PLUS VIEW
CONFIGURATION, SET SYSTEM TIME AND CONFIGURATION
CHEETAH Xi v7.20 ALARM: DEVICE TYPE
CHECK.
FIKE CORPORATION CUSTOM MESSAGE
ESCAPE
HH:MM:SSP MM/YY/DD HH:MM:SSP MM/YY/DD LEVEL 3 (ADMIN): ALL LEVEL 1 AND 2 PRIVILEGES PLUS
AL:000 SU:000 TR:000 EVENT XXXX OF YYYY CONFIGURATION CHANGES.
F1-EVENT SOURCE LEVEL 4 (FACTORY): ACCESS TO ALL MENUS PLUS
ESCAPE F2-EXP CUSTOM MESSAGE FACTORY INITIALIZE SYSTEM AND PASSWORD OVERRIDE.
MAINT MENU 1
F1-DEV RD 1-4
F2-DEV ADR 1-4
F3-DEV RPL 2-4
F4-WALKTS 2-4
F5-BUZZER 2-4
F6-MENU 2
MAINT MENU 2
F1-MNS RST 2-4 F1-READ UNIT
F2-MNS SIL 2-4 F2-ISOLATE UNIT
F3- F3-DISABLE UNIT
F4-CFG RD 2-4
F5-FAAST 1-4
F6-AHU ON 2-4