BAL Chart
BAL Chart
BAL–FZ
BAL–LOW BAL–12.5 BAL–19 BAL–29 BAL–40
(FLAME ZONE)
Concrete slab on ground or enclosure by Concrete slab on ground or enclosure by Concrete slab on ground or enclosure by
No special Concrete slab on ground or enclosure by
external wall, metal mesh as above or flooring external wall, metal mesh as above or flooring external wall or protection of underside with a
FLOOR S construction As for BAL–19 less than 400 mm above ground level to be less than 400 mm above ground level to be non-combustible material such as fibre cement
external wall or an FRL of 30/30/30 or
protection of underside with 30 minute
requirements non-combustible, naturally fire resistant non-combustible, naturally fire resistant sheet or be non-combustible or be tested for
incipient spread of fire system or be tested
timber or protected on the underside with timber or protected on the underside with bushfire resistance to AS 1530.8.1
for bushfire resistance to AS 1530.8.2
sarking or mineral wool insulation sarking or mineral wool insulation
4mm Grade A Safety Glass or 5 mm toughened glass or glass blocks within Protected by bushfire shutter
or
EXTERNAL No special
glass blocks within 400 mm of 400 mm of ground, deck etc with Openable 5 mm toughened glass with openable portion 6 mm toughened glass. FRL of -/30/- and openable portion
ground, deck etc with Openable portion metal screened with frame of metal or screened and frame of metal or metal
construction Fixed and Openable portion screened screened with steel or bronze mesh or be
WINDOWS requirements
portion metal screened with metal reinforced PVC-U or bushfire resisting reinforced PVC-U, or bushfire resisting timber
with steel or bronze mesh tested for bushfire resistance to AS
frame of metal or metal reinforced timber. Above 400mm annealed glass can be and portion within 400 mm of ground, deck
PVC-U or bushfire resisting timber etc screened 1530.8.2
used with all glass screened
No special Non-combustible covering. Roof/wall junction Roof with FRL of 30/30/30 or tested for
As for BAL–19 Non-combustible covering. Roof/wall Non-combustible covering. Roof/wall
construction sealed. Openings fitted with non- bushfire resistance to AS 1530.8.2. Roof/wall
ROOFS (including roof to be junction sealed. Openings fitted with junction sealed. Openings fitted with
requirements combustible ember guards. Roof to be fully junction sealed. Openings fitted with non-
fully sarked) non-combustible ember guards. Roof to non-combustible ember guards. Roof to sarked and no roof mounted evaporative combustible ember guards. No roof
be fully sarked be fully sarked coolers mounted evaporative coolers