PVV Solar Cell US0123 PDF
PVV Solar Cell US0123 PDF
3. Terminal positions
10 10
10
10
2 PVV 140 to 6 PVV 900 7 PVV 1050 to 12 PVV 2280 13 PVV 2470 to 16 PVV 3040 17 PVV 3230 to 26 PVV 4940
Technical Specification for BAE SECURA PVV SOLAR
4. Design
Positive electrode Tubular - plate with a polyester gauntlet and solid grids in a corrosion-
resistant PbCaSn-alloy
Negative electrode Round-grid flat plate in a PbCaSn alloy with long-life expander material
Separation Microporous separator
Electrolyte Sulphuric acid with a density of 1.24 kg/l, fixed as GEL by fumed silica
Container and Lid High impact SAN (Styrol-Acrylic-Nitrile), grey colored, UL-94 rating: HB
(Alternatively container and lid in ABS (Acrylonitrile-Butadiene-Styrene),
UL-94 rating: V0)
Flame arrestors Valve with flame arrestor, opening pressure approx.120 mbar,
closing pressure approx. 50 mbar
Pole - bushing 100% gas and electrolyte tight, sliding, plastic coated “Panzerpol”
Kind of pole M10 brass insertion
Kind of protection IP 25 regarding EN 60529, touch protected according to BGV A3
Horizontal Operation Please use BAE special type PVV “horizontal”
5. Installation
BAE SECURA PVV SOLAR batteries are designed for indoor applications.
For outdoor applications an appropriately designed enclosure is to be used,
please contact BAE.
6. Maintenance
Every 6 months Check and record battery voltage, pilot cell voltage and temperature
Every 12 months Check and record battery voltage, cell voltages and temperatures
7. Operational Data
Depth of discharge (DOD) Max. 80 % (Ue = 1.91 V/cell for discharge times >10 h; 1.74 V/cell for 1 h),
deep discharges of more than 80 % DOD have to be avoided
Initial Charge Current Imax without limitation, minimum charge current has to be 1.5A/100Ah C10
(I or bulk phase)
Charge voltage, cyclic operation Restricted from 2.30 V to 2.40 V/cell, operating instructions to be followed
Float voltage/non-cyclic U = 2.25 V/cell
Adjustment of charge voltage No adjustment necessary if battery temperature is between 10°C and 45°C
(50°F and 86°F)U/T = +/- 0.003 V/K below 10°C in the monthly average
Recharge to 100% Within period of 1 up to 4 weeks
Battery temperature -20°C to 45°C (-4°F to 113°F); recommended 10°C to 30°C (50°F to 86°F)
Self-discharge App. 2% per month at 20°C (68°F)
IEC 61427 cycles >3,000 (A+B) at 40°C (104°F)
IEC 60896-21 cycles >1,500 at 20°C (68°F)
10500
9000
Cycles
7500
6000
4500
3000
1500
0
0 10 20 30 40 50 60 70 80 90
Depth of discharge (DOD) in %
US-0123