This document provides information on parameter settings and error codes for Zanotti SB-Uniblock, DBO Bi-block, and SPO Split units. It explains how to access two levels of parameter settings, with level two requiring a password, and how to change parameter values. The document also provides a table describing common error codes, their causes, and recommended remedies.

Uploaded by

Sinan Bulut
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
634 views

Zanotti Parameter SP Splitaggregat

This document provides information on parameter settings and error codes for Zanotti SB-Uniblock, DBO Bi-block, and SPO Split units. It explains how to access two levels of parameter settings, with level two requiring a password, and how to change parameter values. The document also provides a table describing common error codes, their causes, and recommended remedies.

Uploaded by

Sinan Bulut
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 17

ESIE 17-03

Technical Info
Technical Services Division – Daikin Europe NV

Parameter and Error list


Zanotti SB-Uniblock
Zanotti DBO-Biblock
Zanotti SPO-Split

SB DB-O SP-O
1
Technical Info
Technical Services Division – Daikin Europe NV

SUBJECT: Parameter and Error list Zanotti SB-Uniblock, DBO Bi-block & SPO Split

Attached, please find the Zanotti SB-Uniblock, DBO Bi-block & SPO Split Parameter and Error list.
This document explains how to work with the units controller, gives an overview of all the parameter
settings and gives an thoroughly explanation about the error codes.

Before performing design, construction, or maintenance, thoroughly read the "Installation Manual" that
come with this product.

1. Table of contents

1. Table of contents ............................................................................................................................. 2


2. Version log ...................................................................................................................................... 2
3. PCB: Technical data ....................................................................................................................... 3
4. Keyboard Technical Data ................................................................................................................ 4
5. How to enter the parameter levels .................................................................................................. 5
6. Changing parameter values ............................................................................................................ 6
7. Alarm signalling ............................................................................................................................... 7
8. Parameters ...................................................................................................................................... 9

2. Version log

Month/Year Revised contents


09/2017 -

2
Technical Info
Technical Services Division – Daikin Europe NV
3. PCB: Technical data

Power supply: 230Vac or. 110Vac ± 10%, 50 / 60Hz


Power consumption: 10 VA max
Inputs: 3 NTC probes.
Relay outputs: Total current on loads MAX 20A
Compressor: relay SPST 20 (8) A, 250Vac
Light: relay relay 8 (3) A, 250Vac
Fans: relay SPST 16 (3) A, 250Vac
Defrost: relay SPST 16 (3) A, 250Vac
Alarm: SPST relay 8 (3) A, 250Vac
Serial output: TTL (standard), RS485 (Optional)
Communication protocol: MODBUS-RTU
Data storage: EEPROM
Operating temperature: from 0 to 60 ° C (32 to 140 ° F)
Storage temperature: -25 to 60 ° C (-13 to 140 ° F)
Relative Humidity: 20 to 85% (non-condensing)
measurement and control range: NTC probe: -40 to 110 ° C (-58 to 230 ° F)
PTC probe: -40 to 150 ° C (-58 to 302 ° F)
Resolution: 0.1 ° C or 1 ° F
Accuracy at 25 ° C: ± 0.5 ° C ± 1 digit

3
Technical Info
Technical Services Division – Daikin Europe NV
4. Keyboard Technical Data

Control LED (GREEN)


ON : compressor is running, unit is refrigerating.
Flashing : compressor is in start delay mode.
Control LED (GREEN)
ON : evaporator fan is running.
Flashing : evaporator fan is in start delay mode.
OFF : evaporator fan is off. Defrost is in course.
Control LED (YELLOW)
ON : Automatic or manual defrost is in course.
Alarm LED (RED)
ON : alarm has been activated because of a
malfunctioning sensor, or pressure switch
intervention, or cold room temperature exceeding
allowed tolerances.
OFF: Unit is operating normally.
DISPLAY : on connection to the mains it shows
OFF to indicate the condition of the unit. By
pressing ON/OFF key for 3 seconds the unit is
turned ON and the display shows the cold room
temperature. In programming mode the
parameters to be set are displayed; in alarm mode
the alarm code is displayed.
"SET" key : when pressed it lights up and allows
room temperature to be set. During programming
it is used to pass from a submenu to an upper
one.
"DOWN/ROOM LIGHT" key: in programming
mode or when setting room temperature it is used
to reduce the value displayed; otherwise it is used
to switch on/off the cold room light.
"SB.M./UP" key: in programming mode it is used
to increase the values displayed. If pressed for
more than 5 seconds it enables manual defrost to
be carried out.
"ON/OFF" key: when pressed for 3 seconds it
turns the unit on or off.
"Enter" key: it gives access to programming menu
and submenus. Access to the programming mode
requires the installator’s assistance and should be
effected only if necessary.

4
Technical Info
Technical Services Division – Daikin Europe NV
5. How to enter the parameter levels
 Level 1 parameters:

1. Press the ENTER key for 5 seconds.


2. The instrument will show the first parameter present in level 1.

3. Use the pushbuttons to scroll through the menu.

4. Press the SET key to access a folder.

 Level 2 parameters:

To access parameters in "Pr2" There are two possibilities:

Option 1:

1. Press the ENTER key for 5 seconds.

2. Use the pushbuttons to scroll through the menu.

3. Select the "Pr2" parameter and press SET.


4. You will see the "PAS" flashing followed by "0 - -" with a flashing 0.

5. Enter the password "321" using the keys.

6. Press SET to confirm.

Option 2:

1. Press the ENTER-key within 30 seconds after switching on the instrument.

Level 2 parameters should not be changed, they are unit related and critical for
the unit operation.

5
Technical Info
Technical Services Division – Daikin Europe NV
6. Changing parameter values

1. Enter the Programming mode.


2. Select the desired parameter.

3. Press the SET key to display its value.

4. Change it with the keys.

5. Press "SET" to store the new value and move to the parameter code next.

6. To exit: Press SET-key + UPPER-key, or wait 15s without pressing no key. +

NOTE: the new parameter value is stored even when you exit without pressing the SET-key.

6
Technical Info
Technical Services Division – Daikin Europe NV
7. Alarm signalling

ALARM DISPLAY CAUSE REMEDY

High temperature HA, alternating with cold Excessive door


room temperature. openings. Too high
temperature of products
stored.

Malfunction of the unit.

Low temperature LA, alternating with cold Malfunction of electronic Service intervention
room temperature. controller

Room sensor P1 (Steady) Sensor not connected Replace sensor

Broken thermostat
probe

Evaporator sensor P2, alternating with cold Sensor not connected Replace sensor
room temperature
Broken evaporator
probe

Condenser (extra) P3 Broken probe Replace sensor


sensor

Open Door dA, alternating with cold Door opening time Automatic reset when the door is
room temperature exceeds max opening closed.
by parameter

High pressure PrE, alternating with room Faulty operation of Switch off the refrigerating unit,
temperature; LED (4) lights condenser fan. wait a few seconds and switch
up each time the high on again.
pressure switch is tripped. If Dirty condenser.
more than 10 trips occur in
one hour, then (PAL)
alternating with cold room
temperature is displayed and
alarm relay is activated
together with LED (4).

In this situation all functions


are interrupted.

7
Technical Info
Technical Services Division – Daikin Europe NV
ALARM DISPLAY CAUSE REMEDY

Voltage monitor bAL, alternating with cold Wrong supply voltage


room temperature. The
voltage monitor is an
electronic device which
checks the supply voltage of
the unit when voltage
variations exceed +/-12%.
The unit stops for about 6
minutes and restarts
automatically if voltage is
within the prescribed limits.

Warning: on first starting the


monitor carries out a
counting phase of 7 minutes,
during which the unit should
be left connected but in OFF
condition.

Abnormality in the Flashing “EE” alarm in Press whatever key during the
memory alternation with the alarm.
temperature signals a data
abnormality Subsequently the message “rSt”
will appear for about 3 seconds
before restarting normal
operation.

The signal remains on the display until the alarm situation is called off. All the alarm messages flash
in alternation with the probe temperature except “P1” which is always flashing.

8
Technical Info
Technical Services Division – Daikin Europe NV

8. Parameters

Label Name Medium Low Medium Low MDB BDB Unit Range Level Description
electric electric hot gas hot gas electric electric
HY Differential 2 2 2 2 2 2 °C 0,1…25,5 1 Intervention differential for
setpoint.
Compressor Cut IN is Setpoint +
differential (Hy).
Compressor Cut OUT is when
the temperature reaches the
setpoint.
LS Minimum set point -5 -25 -5 -25 -5 -25 °C -50,0°C…SET 1 Sets the minimum value for the
setpoint.
US Maximum set point 10 -15 10 -15 10 -15 °C SET…150,0°C 1 Sets the maximum value for the
setpoint.
OdS Outputs activation 0 0 0 0 0 0 min 0…255 1 This function is enabled at the
delay at start up initial start-up of the controller
and inhibits any output activation
for the period of time set in the
parameter.
AC Anti-short cycle delay 2 2 2 2 2 2 min 0…30 1 Minimum interval between the
compressor stop and the
following restart
Con Compressor ON time 15 15 15 15 15 15 min 0…255 1 Time during which the
with faulty probe compressor is active in case of
faulty thermostat probe. With
Con = 0, compressor is always
OFF.

9
Technical Info
Technical Services Division – Daikin Europe NV
Label Name Medium Low Medium Low MDB BDB Unit Range Level Description
electric electric hot gas hot gas electric electric
CoF Compressor OFF time 30 30 30 30 30 30 min 0…255 1 Time during which the
with faulty probe compressor is OFF in case of
faulty thermostat probe. With
CoF = 0, compressor is always
active.
CF Temperature °C °C °C °C °C °C °C/°F 0/1 1 Selection of °C or °F to display
measurement unit the temperature read by the
probe.
0=°C
1=°F
CAUTION! When the
measurement unit is changed,
the setpoint and the values off
the parameters Hy, LS, US, ot,
ALU, and ALL have to be
checked and modified if
necessary
rES Resolution dE dE dE dE dE dE 0/1 1 0=in=integer (1°C)
(integer/decimal point) 1=dE=decimal point (0,1°C)
Lod Local display P1 P1 P1 P1 P1 P1 0/1/2 1 Selects which probe is displayed
by the controller:
0=P1:Probe 1, Ambient
Temperature
1=P2: Probe 2, End defrost
Temperature
2=P3 = Probe 3, Condensing
temperature (only for model with
this option enabled)

tdF Defrost type rE rE rE rE rE rE 0/1 1 0= rE: Electric defrost


1= Sd: Hot gas defrost

10
Technical Info
Technical Services Division – Daikin Europe NV
Label Name Medium Low Medium Low MDB BDB Unit Range Level Description
electric electric hot gas hot gas electric electric
EdF Defrost mode in in in in in in 0/1 1 0=in: Interval mode: The defrost
starts when the time Idf is
expired
1=Sd: Smart Defrost: the interval
between 2 defrosts is calculated
with compressor ON
SdF Set point for SMART 0 0 0 0 0 0 °C -30…30 1 Temperature to activate the
DEFROST counter of interval defrost if sd is
selected
dtE Defrost termination 8 8 15 15 8 8 °C _50…150 1 Sets the temperature measured
temperature by the evaporator probe, which
causes the end of defrost
IdF Interval between 4 4 4 4 6 6 hours 1…120 1 Determines the time interval
defrost cycles between the beginning of two
defrost cycles.
MdF (Maximum) length for 30 30 20 20 25 35 min 0…255 1 When P2P=n, it sets the defrost
1° defrost duration.
When P2P=y, it sets the
maximum duration for defrost.
dFd Displaying during it it it it it it 0/1/2/3/4 1 0=rt: Real temperature
defrost 1=it: Temperature at defrost
start
2=Set: Setpoint
3=dEF: dEF label
4=dEG: dEG label
dAd MAX display delay 15 15 15 15 15 15 min 0…255 1 Sets the maximum time between
after defrost the end of defrost and the
restarting of the real room
temperature display.
dSd Defrost delay after 0 0 0 0 0 0 min 0…99 1 This is useful when different
calling defrost start times are necessary
to avoid overloading the plant.
11
Technical Info
Technical Services Division – Daikin Europe NV
Label Name Medium Low Medium Low MDB BDB Unit Range Level Description
electric electric hot gas hot gas electric electric
Fdt Draining time 2 2 2 2 2 2 min 0…60 1 Time interval between reaching
defrost termination temperature
and the restoring of the
controller’s normal operation.
This time allows the evaporator
to eliminate water drops that
might have formed due to
defrost.
Dpo First defrost after start n n n n n n 0/1 1 0=n=after the IdF time,
up n(0 1=Y=immediate
FnC Fans operating mode C-n C-n C-n C-n C-n C-n 0/1/2/3 1 0=C_n: Evaporator fan on when
compressor ON - Stop in
defrost.
1=C_Y: Evaporator fan on when
compressor ON - ON in defrost.
2=O_n: Evaporator fan on
continuously - Stop in defrost.
3= O_Y: Evaporator fan on
continuously - Stop in defrost.
Fnd Fans delay after 3 3 3 3 3 3 min 0…255 1 Fan delay after defrost - The fan
defrost must be stop during drain time
ad 1 min after compressor start.

FSt Fans stop temperature 40 40 40 40 40 40 °C -50…150 1 Fan stop temperature - used if


you prefer to have fan ON only if
evaporating temp. Is lower that
FSt.

12
Technical Info
Technical Services Division – Daikin Europe NV
Label Name Medium Low Medium Low MDB BDB Unit Range Level Description
electric electric hot gas hot gas electric electric
ALC Temperature alarms rE rE rE rE rE rE 0/1 1 1=Ab = Absolute temperature:
configuration alarm temperature is given by
the ALL or ALU values
0=rE0= Temperature alarms are
referred to the setpoint
Temperature alarm is enabled
when the temperature exceeds
the SEt + ALU or SEt- ALL
values.
ALU MAXIMUM 5 5 5 5 5 5 re[0.0 - 50.0]; 1 When this temperature is
temperature alarm Ab[ -50.0 - 150.0] reached, the alarm is enabled
after the ALd delay time.
ALL minimum temperature 5 5 5 5 5 5 re[0.0 - 50.0];Ab[ - 1 When this temperature is
alarm 50.0 - 150.0] reached, the alarm is enabled
after the ALd delay time.
AFH Temperature alarm 2 2 2 2 2 2 °C 0,1…25,5 1 Intervention differential for
and fan differential recovery of temperature alarm
Ald Temperature alarm 0 0 0 0 0 0 min 0…255 1 Time interval between the
delay detection of an alarm condition
and alarm signaling.
dAo Delay of temperature 3 4 3 4 3 4 0…23H5(143) 1 Time interval between the
alarm at start up detection of the temperature
alarm condition after controller
power ON and alarm signaling.
EdA Alarm delay at the end 60 60 60 60 60 60 min 0…255 1 After defrost temperature alarm
of defrost is delayed of 60 min
dot Delay of temperature 60 60 60 60 60 60 min 0…255 1 After door open, temperature
alarm after closing the alarm is delayed of 60 min
door
doA Open door alarm delay 60 60 60 60 60 60 min 0…254 1 If the door remain open for 60
min, the alarm of door open
appear.

13
Technical Info
Technical Services Division – Daikin Europe NV
Label Name Medium Low Medium Low MDB BDB Unit Range Level Description
electric electric hot gas hot gas electric electric
tbA Alarm relay silencing Y Y Y Y Y Y 0/1 1 0=n: the alarm relay remains ON
until the alarm condition
recovers.
1=y: the relay is silenced by
pressing any key.
nPS Pressure switch 10 10 10 10 10 10 0…15 1 Number of activation of the
activation number pressure switch, during the nPn
interval, before signaling the
alarm event (i2F= PAL).
If the nPS activation in the nPn
time is reached, switch OFF and
ON the controller to restart
normal regulation.
nPn Pressure switch 60 60 60 60 60 60 min 0…60 1 Establishes the range in which
interval you must check nPS pressure
switch for generating the alarm.
AU2 High temperature 55 55 55 55 55 55 °C -50… 150 1 When this temperature is
alarm of Probe 3 reached the AH2 alarm is
signaled, possibly after the Ad2
delay.
AH2 Differential 2 2 2 2 2 2 °C 0,1…25,5 1 Differential temperature alarm
temperature alarm for for probe 3.
probe 3

Ad2 Temperature alarm 0 0 0 0 0 0 min 0…255 1 Temperature alarm delay for


delay for probe 3 probe 3.
AC2 Lock of regulation with N N N N N N 0/1 1 0=N= no: compressor keeps on
P3 probe temperature working.
alarm 1=Y= yes: compressor is
switched OFF till the alarm is
present, in any case regulation
restarts after Ac time at
minimum.
14
Technical Info
Technical Services Division – Daikin Europe NV
Label Name Medium Low Medium Low MDB BDB Unit Range Level Description
electric electric hot gas hot gas electric electric
ot Thermostat probe 0 0 0 0 0 0 -12…12 1 Allows to adjust possible offset
calibration of the thermostat probe.
oE Evaporator probe 0 0 0 0 0 0 -12…12 1 Allows to adjust possible offset
calibration of the evaporator probe.
o3 Auxiliary probe 0 0 0 0 0 0 -12…12 1 Allows to adjust possible offset
calibration of the third probe.
P2P Evaporator probe Y Y Y Y N N N/Y 1 n = not present: the defrost
presence stops by time.
y = present: the defrost stops by
temperature.
P3P Auxiliary probe N N N N N N N/Y 1 N= not present
presence Y= present
HES Temperature increase 0 0 0 0 0 0 °C -30…30 1 Sets the increasing value of the
during the Energy setpoint during the Energy
Saving cycle Saving cycle.
odC Open door control F-C F-C F-C F-C F-C F-C 0/1/2/3 1 0=no= normal
1=Fan= normal
2=CPr= Compressor OFF
3=F-C= Compressor OFF
rrd Regulation restart with Y Y Y Y Y Y N/Y 1 No = outputs not affected by the
door open alarm (doA) doA alarm
Yes = outputs restart with the
doA alarm
i1P Digital input 1 polarity OP OP OP OP OP OP 0/1 1 0=CL: CL: the input is activated
by closing the contact
1=OP: the input is activated by
opening the contact.
i2P Digital input 2 polarity cL cL cL cL cL cL 0/1 1 0=CL: CL: the input is activated
by closing the contact
1=OP: the input is activated by
opening the contact.

15
Technical Info
Technical Services Division – Daikin Europe NV
Label Name Medium Low Medium Low MDB BDB Unit Range Level Description
electric electric hot gas hot gas electric electric
i3P Digital input 3 polarity OP OP OP OP OP OP 0/1 1 0=CL: CL: the input is activated
by closing the contact
1=OP: the input is activated by
opening the contact.
i2F Digital input 2 function BAL BAL BAL BAL BAL BAL 0/1/2/3/4/5 1 0=EAL: External alarm, EAL
message is displayed
1=BAL: external alarm (block),
BAL message is displayed
2=dFr: Defrost cycle start
3=dor: Door switch function
4=ES: Energy saving
5=OnF: To switch the controller
OFF from remote
i3F Digital input 3 function DOR DOR DOR DOR DOR DOR 0/1/2/3/4/5 1 0=EAL: External alarm, EAL
message is displayed
1=BAL: Exterrnal alarm (block),
BAL message is displayed
2=dFr: Defrost cycle srtart
3=dor: Door switch function
4=ES: Energy saving
5=OnF: To switch the controller
OFF from remote
did Digital input alarm 0 0 0 0 0 0 min 0-255 1 i2F = EAL or i2F = bAL: Delay
delay between the detection of the
external alarm condition and its
signaling.
i2F = PAL: Time interval to
calculate the number of the
pressure switch activation

16
Technical Info
Technical Services Division – Daikin Europe NV
Label Name Medium Low Medium Low MDB BDB Unit Range Level Description
electric electric hot gas hot gas electric electric
AoP Alarm relay polarity cL cL cL cL cL cL 0/1 1 0=CL: CL: the input is activated
by closing the contact
1=OP: the input is activated by
opening the contact.
Pbc Kind of probe selection NTC NTC NTC NTC NTC NTC 0/1 1 0=PTC
1=NTC
Adr Serial address 1 1 1 1 1 1 1 - 247 1
dP1 Probe 1 display read only 1 Thermostat probe display.
dP2 Probe 2 display read only 1 Evaporator probe display.
dP3 Probe 3 display read only 1 Third probe display (optional).
rEL Software release read only 1 For internal use only.
Ptb Map code read only 1
Pr2 Access parameter list 1

17