JU6H-UF34
INSTALLATION & OPERATION DATA (I&O)
UK Produced
Exhaust System (Single Exhaust Outlet) 2350 2600 2800 3000
Exhaust Flow - m³/min (ft.³/min) ......................................................................................................................................................
30.6 (1081) 35.2 (1243) 38.7 (1365) 45.7 (1614)
Exhaust Temperature - °C (°F) ......................................................................................................................................................
527 (980) 511 (951) 507 (944) 530 (986)
Maximum Allowable Back Pressure - kPa (in H2O) ......................................................................................................................................................
7.5 (30) 7.5 (30) 7.5 (30) 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in) ³ ......................................................................................................................................................
127 (5) 127 (5) 127 (5) 127 (5)
Lubrication System
Oil Pressure - normal - kPa (lb/in²) ......................................................................................................................................................
345 (50) - 655 (95)
Low Oil Pressure Alarm Switch - kPa (lb/in²) ......................................................................................................................................................
138 (20)
In Pan Oil Temperature - °C (°F) ......................................................................................................................................................
104 (220) - 118 (245)
Total Oil C apacity with Filter - L (qt) ......................................................................................................................................................
18.6 (19.7)
NOTE: This engine is intended for indoor installation or in a weatherproof enclosure. ¹ Derate 3% per every 1000 ft. 304.8m above 300 ft. 91.4m and derate 1%
for every 10°F 5.55 °C above 77°F 25°C. ² Positive and Negative Cables Combined Length. ³ Minimum Exhaust Pipe Diameter is based on: 15 feet of pipe, one
90° elbow, and one Industrial silencer. A Back-pressure flow analysis must be performed on the actual field installed exhaust system to assure engine maximum
allowable back pressure is not exceeded. See Exhaust Sizing Calculator on www.clarkefire.com. { } indicates component reference part number.