DV-5A Red-E Cabinet


Integrated Preaction Fire Protection Package
Integral to the DV-5A Red-E Cabinet is a
IMPORTANT control panel and back-up batteries for
Refer to Technical Data Sheet providing electrical alarm, supervisory,
TFP2300 for warnings pertaining to and trouble functions. All switches
regulatory and health information. within the cabinet are pre-wired to the
control panel, making the electrical
connections for power, detection cir-
Scan the QR code or enter the URL cuits, and alarms the only remaining
in a web browser to access the most connections to complete the system.
up-to-date electronic version of this
document. Data rates may apply. In addition to the control panel being
integral to the DV-5A Red-E Cabinet,
windows are provided in the door for
viewing the releasing panel functions
and essential system pressure gauges.
A lock for the control panel access door
is standard, and a lock for the cabinet
door is optional.
Features and benefits are as follows: NOTICE
The DV-5A Red-E Cabinets described
• Aesthetically pleasing appearance herein must be installed and main-
• Professionally assembled tained in compliance with this docu-
• Internally wired ment and with the applicable standards
• Custom manufactured of the NATIONAL FIRE PRO­TECTION
• All gauges and panel display are ASSOCIATION (NFPA), in addition to
docs.jci.com/tycofire/dv-5a-red-e- the standards of any authorities having
cab-inte-pre-fire-pro-pack externally visible
jurisdiction. Failure to do so may impair
• Industrial grade rollers (4) are stan- the performance of these devices.
dard at bottom of cabinet
General • Forklift compatible The owner is responsible for main-
taining their fire protection system
Description • Two-door cabinet design for ease of
maintenance
and devices in proper operating con-
dition. Contact the installing contrac-
The TYCO DV-5A Red-E Cabinet is a • Internal, gauge panel, and control tor or product manufacturer with any
pre-assembled fire protection valve panel lighting questions.
package enclosed within a free-stand- • Optional Model QRS Electronic
ing cabinet designed to occupy minimal
floor space and to provide an aestheti-
Accelerator for the 6 in. and 8 in.
Double Interlock Electric/Electric
Technical
cally pleasing enclosure for a fire pro-
tection valve riser. The entire package
Actuation system types
• Optional seismic kit
Data
is pre-wired and the water inlet and The DV-5A Red-E Cabinet is designed Approvals
outlets to the valve riser are grooved to readily incorporate 1-1/2 to 8 in.
to provide minimal installation time. UL and C-UL Listed, FM Approved,
(DN40 to DN200) valve risers for the CSFM Listed System Types
The valve package includes a system following types of preaction systems:
(manual) shut-off control valve, an auto- • Single Interlock Wet Pilot Actuation
matic water control valve, and water- • Single Interlock Wet Pilot Actuation • Single Interlock Dry Pilot Actuation
flow/supervisory switches. A built-in • Single Interlock Dry Pilot Actuation • Single Interlock Electric Actuation
air compressor with associated con- • Single Interlock Electric Actuation • Double Interlock Electric/
trols provides an automatic air supply Pneumatic Actuation
for use as either supervision and pneu- • Double Interlock Electric/Pneumatic
• Double Interlock Electric/Electric • Double Interlock Electric/Electric
matic actuation of the automatic water Actuation
control valve. • Preaction Type A

Page 1 of 8 JULY 2022 TFP1401


TFP1401
Page 2 of 8

Nominal Riser Size


Nominal Dimension
in. (mm)1
DIM Description 1 1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150) 8 (DN200)

A System Discharge 1 1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150) 8 (DN200)


B Supply Header 4 (DN100) 8 (DN200)
C Drain Header 2 (DN50)
D Header Left 17.0 (431,8) 24.75 (628,7)
E Header Right 16 (406,4) 26.75 (679,5)
F Riser Height 68.26 (1733,8) 68.40 (1737,4) 68.44 (1738,4) 67.34 (1710,4) 67.9 (1724,7)
G Connection Offset 9.42 (239,3) 9.34 (237,2)
H Connection Offset 5.0 (127,0) 8.6 (218,4)
J Connection Offset 4.88 (124,0) 8.5 (215,9)
K Connection Offset 6.88 (174,8) 9.5 (241,3)
L Connection Offset 5.63 (143,0) 6.57 (166,9)
M Connection Offset 19.5 (495,3) 25.15 (638,8)
N Cabinet Height 73.25 (1860,6) 73.5 (1866,9)
P Cabinet Width 38.15 (969,0) 48.15 (1223,0)
R Cabinet Depth 23.73 (602,7) 29.64 (752,9)
Notes
1. All pipe connections are grooved
2. Supply and drain header connections made internal to cabinet

R P

H A M

L
B

K D E
FIGURE 1
INSTALLATION DIMENSIONS AND REFERENCE POINTS
TFP1401
Page 3 of 8

1 - Supply Header
4 2 - Drain Header
15 3 - Supply and Drain Header
Connections on Left or
20 Right Side
14 4 - System Discharge
Connection
5 - System Air Supply
8 Connection with Plug
6 - DV-5A Valve with
Preaction Trim
18 7 - Manual System Shut-Off
Valve
12 8 - System Pressure Gauges
5
9 - Manual Control Station
19 10 - Splash-Proof Drip Cup
9 11 - Drain Header Integrated
Drip Cup Connection
6 12 - Waterflow Pressure Alarm
10 Switch
13 - Main Drain Valve
7 14 - Releasing Panel
17 13 15 - Electrical Conduit
Connections
16 16 - Main Compartment
2 11 Access Door with
Optional Lock
17 - System Air Compressor
1 3 18 - Low Air Pressure Alarm
Switch
19 - Manual System Shut-Off
Valve
20 - Air Tank
FIGURE 2
TYPICAL ASSEMBLY ARRANGEMENT
(4 IN. DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/ELECTRIC ACTUATION SHOWN)

System Types drain valve - are individually tagged for sor sized to meet the requirements
The technical data sheets referenced in easy identification. All prefabricated of the largest system in the group to
Table A provide complete details for each piping is Schedule 40 steel. supply all the cabinets in the group, or
system type arrangement.
alternatively, connect to the factory air
A splash-resistant drain cup is pro-
Working Pressure Range vided that ensures water does not supply. The air supply line contains a
DV-5A Valve: 20 to 300 psi (1,4 to 20,7 bar) tee and plug which is used to connect
splash into the cabinet during flow
DV-5A Valve Trim: Refer to individual trim a hydraulic test pump that pressurizes
testing. The discharging water can be
technical data sheets for rated trim pres- the sprinkler system above the butterfly
sures as shown in Table A. observed through a clear tube attached
valve for hydraulic testing of the system
to the drain cup. It is designed with a
Construction in accordance with NFPA 13.
fail-safe feature allowing water to over-
The Red-E Cabinet is constructed of a flow in the event the drain is blocked. Table A provides list of riser compo-
minimum thickness of 14 gauge steel nents and a cross reference to indi-
and is free standing. The standard paint The hard piped funnel drain is con-
vidual technical data sheets, as well
finish is bright red and black. The front nected through a swing check valve to
as individual component laboratory
doors of the enclosure are fully hinged the main drain header, eliminating the
approval information.
(and removable) and open nearly to the need to run a separate drain line from
cabinet floor level allowing easy access the funnel. The cabinet floor is provided Figure 1 shows dimensional infor-
to the couplings when connecting the with a drain opening to allow water to mation for Red-E Cabinets, and
water supply and drain. Pre-drilled drain out. A plug is also provided to Figure 2 illustrates the typical assem-
holes on tabs along the base of the prevent water from draining from the bly arrangement.
cabinet provide an anchor point for the cabinet if necessary.
cabinet to be secured to the floor when The air supply connection for cabinets
required. Industrial grade rollers at the without compressors (using AMD-1) are
bottom of the cabinet are standard. terminated at a common height across
Internal controls that provide functions all model sizes allowing the connec-
to reset a system after operation - for tion of groups of cabinets easier. This
example, the alarm test valve or main allows a single tank mounted compres-
TFP1401
Page 4 of 8

Description Model TDS* UL C-UL/ULC FM Global CSA


Automatic Water Control Valve and Preaction Trim
Single Interlock Wet Pilot Actuation TFP1411 X X X
Single Interlock Dry Pilot Actuation TFP1416 X X X
Single Interlock Electric Actuation DV-5A TFP1421 X X X
Double Interlock Electric/Pneumatic Actuation TFP1461 X X X
Double Interlock Electric/Electric Actuation TFP1466 X X X
Preaction Type A TFP1485
System Shut-off Valve, 1 1/2 to 2 in. (DN40 to DN50) POWERBALL X5 X5 X5
System Shut-off Valve, 3 to 8 in. (DN80 to DN200) BFV-300 TFP1511 X X X
Pressure Alarm Switch, POTTER PS10-2A X6 X6 X6
Pressure Alarm Switch, POTTER PS40-2A X6 X6 X6
Control Panel1, POTTER PFC-4410RC X6 X6 X6
Automatic Supervisory Air Supply2 G16AC812 TFP1620 X7 X7
Air Maintenance Device3, Regulator Type AMD-1 TFP1221 X X X
Air Maintenance Device4, Switch Type AMD-2 TFP1231 X X X
Nitrogen Maintenance Device4 AMD-3 TFP1241 X X X
Model QRS Electronic Accelerator QRS TFP1100 X X
Notes
1. The Model PFC-4410RC is standard. The Red-E Cabinet may be ordered without an integral control panel. Preaction Type A systems are not approved for use with PFC-
4410RC Control Panel, utilizing model Fast 2000 instead.
2. The Model G16AC812 is utilized to maintain supervisory air pressure in all sizes of single interlock preaction systems with either electric actuation or wet pilot actuation.
3. The Model AMD-1 Air Maintenance Device, in addition to an auxiliary air tank, is utilized as standard equipment in single interlock preaction systems with dry pilot actuation, as
well as double interlock preaction systems with electric/electric actuation and double interlock systems with electric/pneumatic actuation having a compressor that delivers air
at 5.5 ft³/min (0.16 m³/min) or higher. In the case of single interlock preaction systems with dry pilot actuation, two AMD-1’s are utilized to accomplish the two different pressure
settings that are necessary for the system piping and the dry pilot line. In the case of double interlock preaction systems with electric/electric actuation, one AMD-1 is utilized
to maintain the system pressure.
4. The Model AMD-2 Air Maintenance Device and Model AMD-3 Nitrogen Maintenance Device, as well as the Model AMD-1 Air Maintenance Device, are offered as options when
the Red-E Cabinet is ordered without a built-in (for example, air compressor) automatic air supply.
5. Approvals under the name of LANSDALE VALVE & MANUFACTURING.
6. Approvals under the name of POTTER.
7. Approvals for the compressor and motor are under the name of GENERAL AIR PRODUCTS, and the approvals for the pressure operated switch are under the name of HUB-
BELL or CONDOR.
* TDS – Technical Data Sheet

TABLE A
PRINCIPAL COMPONENTS
TECHNICAL DATA SHEETS AND LABORATORY APPROVALS

Electric/Electric Electric/Pneumatic
Actuation Actuation
Model Number Horsepower Voltage1
System Volume System Volume
@20 psi in 30 min. @40 psi in 30 min.
gal (L) gal (L)
115/208-230 VAC
OLR12016AC 1/6 240 (909) 120 (454)
60 Hz
115/208-230 VAC
OLR25033AC 1/3 475 (1795) 250 (945)
60 Hz
115/208-230 VAC
OLR40050AC 1/2 800 (3028) 400 (1514)
60 Hz
115/208-230 VAC
OLR43075AC 3/4 930 (3520) 430 (1625)
60 Hz
115/208-230 VAC
OLR615100AC2 1 1430 (5410) 615 (2325)
60 Hz
115/208-230 VAC
OLR915150AC2 1 1/2 2320 (8780) 915 (3460)
60 Hz
208-230 VAC
OLR1225200AC2 2 3040 (11500) 1225 (4635)
60 Hz
Notes
1. Unless otherwise specified, 115 VAC, 60 Hz is provided.
2. 6 in. (DN150) and 8 in. (DN200) cabinets only.

TABLE B
AIR COMPRESSOR SELECTION FOR DOUBLE INTERLOCK PREACTION SYSTEM ARRANGEMENTS
TFP1401
Page 5 of 8

60 Hz Model Electric/Electric Electric/Pneumatic


Power Equivalent Actuation Actuation
Model Horsepower
Rating Voltage
Number Rating1 System Volume System Volume
(kW)
(hp) @20 psi (1.36 bar) in 30 mins @40 psi (2.76 bar) in 30 mins
gal (L) gal (L)
220-240 VAC 192 96
OLR12016AC-50 0.12 1/6 50 Hz (727) (362)
220-240 VAC 414 207
OLR25033AC-50 0.25 1/3 50 Hz (1567) (785)
220-240 VAC 664 332
OLR40050AC-50 0.56 1/2 50 Hz (2514) (1257)
220-240 VAC 989 357
OLR43075AC-50 0.75 3/4 50 Hz (3743) (1350)
220-240 VAC 517
OLR615100AC-502 1.2 1 —
50 Hz (1956)
220-240 VAC 758
OLR915150AC-502 1.5 1 1/2 —
50 Hz (2870)
220-240 VAC 1014
OLR1225200AC-502 2 2 —
50 Hz (3840)
Notes
1. Denotes the equivalent model of 60 Hz compressor for part number use. 50 Hz must specifically be request in ordering process. The horsepoer model equivalent is not a direct
conversion to kW. Actual conversion from kilowatts (kW) to horsepower units (hp) is based on 1 kW = 1.34102 hp.
2. For 6 in. (DN150) and 8 in. (DN200) cabinets only.

TABLE C
50 HZ AIR COMPRESSOR SELECTION CRITERIA
FOR DOUBLE INTERLOCK PREACTION SYSTEM ARRANGEMENTS
BASED ON SYSTEM TYPE AND VOLUME

Design Installation Inspection, testing, and maintenance


must be performed in accordance
Considerations The TYCO Red-E Cabinet is to be
installed following the directions
with the requirements of the NFPA, and
any impairment must be immediately
The automatic sprinklers and/or given in the “Red-E Cabinet Install- corrected.
nozzles, fire detection devices, manual er’s Manual” provided with the Red-E The TYCO Red-E Cabinet does not
pull stations, and signaling devices Cabinet. Instructions pertain to the fol- require any regularly scheduled inspec-
that are to be utilized with the Red-E lowing items: tion or maintenance. The riser com-
Cabinet must be UL Listed, ULC Listed, • Placing the cabinet ponents enclosed within the Red-E
C-UL Listed, or FM Approved, as appli- Cabinet, however, must be main-
cable. With reference to Figure 3, the • Connecting the system piping tained in accordance with their appli-
system designer must consider and • Electrical connections cable technical data sheet as shown in
make preparations for use of a Red-E • System start-up Table A. In addition, the control panel
Cabinet as follows: and automatic air supply components
• Adequate floor space to facilitate Care and must be maintained in accordance with
their applicable instructions provided
opening of the cabinet doors
• Minimum ambient temperature of Maintenance with the Red-E Cabinet.
40°F (4°C) The owner is responsible for the inspec-
The TYCO DV-5A Red E-Cabinet must tion, testing, and maintenance of their
• Installation of a suitably sized water be maintained and serviced in accor-
supply to the water supply header fire protection system and devices in
dance with this section. compliance with this document, as well
(Port B, Figure 1)
Before closing a fire protection system as with the applicable standards of any
• Installation of system piping (Port A, main control valve for maintenance authorities having jurisdiction. Contact
Figure 1) including automatic sprin- work on the fire protection system that the installing contractor or product
klers and/or nozzles from the Red-E it controls, permission to shut down manufacturer with any questions.
cabinet outlet the affected fire protection systems
• Installation of drains from main drain Automatic sprinkler systems are rec-
must first be obtained from the proper ommended to be inspected, tested,
header (Port C, Figure 1) authorities. All personnel who may and maintained by a qualified Inspec-
• Installation of the detection system be affected by this decision must be tion Service in accordance with local
components and alarms notified. requirements and/or national codes.
• Determination of air compressor size
for double interlock preaction sys-
tems as a function of system type
and volume as shown in Table B
• Power supply to Red-E Cabinet
• Separate power supply to the air
compressor
TFP1401
Page 6 of 8

Red-E Cabinet ELECTRICAL POWER CIRCUITS


FROM BUILDING BREAKER PANEL
Technical ONE CIRCUIT FOR RELEASING
PANEL (IF APPLICABLE)
Support CAPABLE OF PROVIDING
120 VAC 60 Hz MAX. 165 VA OR
Technical support for the Red-E 220 VAC 50/60 Hz 185 VA MAX.
Cabinet is available by calling 888-572-­ ADDITIONAL POWER CIRCUIT
4638 during regular business hours of FROM BREAKER PANEL FOR AIR
8:30-12:00 and 1:00-5:00 Eastern Time COMPRESSOR AS APPLICABLE
Monday through Friday.
Contact Red-E Cabinet Technical
Support for special request cabinet DETECTION CIRCUITS
configuration or electrical connection/
control panel programming inquiries.
An answering service will take mes-
sages outside of the regular business AUDIBLE &
hours. VISUAL SIGNALING
DEVICES
Limited
Warranty REMOTE SIGNALS
For warranty terms and conditions, visit TO BUILDING FIRE
www.tyco-fire.com. ALARM PANEL

Ordering ELECTRICAL

Procedure WATER SUPPLY INLET


The Part Numbers (P/Ns) in this section FROM WATER
are provided for standard cabinets with SUPPLY PIPING
integral control panel, built-in automatic
air supply, for example, air compres-
sor and controls, and galvanized pipe,
nipples, and fittings. MAIN DRAIN & DRIP
DV-5a Red-E Cabinet with FUNNEL DRAIN TO
Single Interlock Preaction System FLOOR DRAIN OR
EQUIVALENT
Specify: Size (specify) DV-5A Red-E
Cabinet with (specify actuation) Single
Interlock Preaction System Riser, P/N
(specify per Table D)
SPRINKLER SYSTEM
PIPING, AS WELL AS
NOTICE SPRINKLERS AND/OR
Electric Actuation and Wet Pilot Actu- NOZZLES
ation are provided standard with
the Model G16AC812 Automatic Air MECHANICAL
Supply utilizing a 1/6 HP motor. Dry
FIGURE 3
Pilot Actuation is provided standard
SYSTEM DESIGN CONSIDERATIONS
with an OL12516AC (1/6 HP) Air Com-
pressor and Auxiliary Air Tank complete
with Model AMD-1 Air Maintenance
Devices.

DV-5a Red-E Cabinet with


Double Interlock Preaction System
and Electric/Electric Actuation
Specify: Size (specify) DV-5A Red-E
Cabinet with Electric/Electric-Actu-
ated Double Interlock Preaction System
Riser with (specify model from Table B
or C) Air Compressor, P/N (specify from
Table D)
TFP1401
Page 7 of 8

P/N 53 — X — X — XX — X — X — X — X

Air Maintenance Control


Solenoid Pressure Rating Device1 Compressor1,4
Panel
0 300 psi solenoid (standard) 0 None 0 None 0 None
1 AMD-1 A Included 1 1/6 hp 120 Gal
2 AMD-2 2 1/3 hp 250 Gal
Trim
3 AMD-3 Type2 3 1/2 hp 400 Gal
1 NPT Galvanized 4 3/4 hp 430 Gal
Size System
in. Type3 1. Air Maintenance Device does not apply 5 1 hp 615 Gal
(select “0” - None) when a Compressor (1-8) is
1 1 1/2 11 Single Interlock Wet Pilot Actuation selected. 6 1 1/2 hp 915 Gal
2. Black trim types are available only on request.
2 2 12 Single Interlock Dry Pilot Actuation Contact Red-E Cabinet Technical Support for 7 2 hp 1225 Gal*
information.
3 3 13 Single Interlock Electric Actuation 3. Special Order DV-5A Red-E Cabinet Integrated 8 S/I Compressor
Preaction Fire Protection Package featuring
4 4 14 Double Interlock Electric/Pneumatic Actuation Model QRS Electronic Accelerator is available * Requires 230V/60Hz
in configurations limited to 6 in. or 8 in. Size,
6 15 Double Interlock Electric/Electric Actuation Double Interlock Electric/Electric Actuation System Type, Model AMD-1 Air
6 Maintenance Device, NPT Galvanized Trim Type, Control Panel Included and No
(168,3 mm)
16 Preaction Type A Compressor. Part Numbers: 6 in. 53061511A0Q; 8 in. 53081511A0Q.
8 8 4. A 50 Hz compressor model is available on request, select the equivalent horse-
power rating (1-8).

TABLE D
DV-5 a RED-E CABINET PREACTION SYSTEMS
PART NUMBER SELECTION

DV-5a Red-E Cabinet with Options


Double Interlock Preaction System • with sight flow gage (provides a
and Electric/Pneumatic Actuation visual indication of flow through the
main drain)
Specify: Size (specify) DV-5A Red-E
Cabinet with Electric/Pneumatic-Actu- • with extra capacity batteries (12V up
ated Double Interlock Preaction System to 18Ah) for longer battery time and/
Riser with (specify model from Table B or systems with heavy power require-
or C) Air Compressor, P/N (specify from ments , for example, numerous audi-
Table D) ble signaling devices
• with Class “A” initiating appliance cir-
Special Orders cuits (this option permits the connec-
The DV-5A Red-E Cabinet can be pro- tion of Class “A” style wiring to the
vided as follows as part of a special initiating zones)
request cabinet configuration:
• with Class “A” indicating appliance
• without the control panel circuits (this option permits the con-
• without built-in automatic air sup- nection of Class “A” style wiring to
ply, for example, air compressor and the indicating zones)
controls • with auxiliary relay modules to
• with an optional air/nitrogen mainte- provide extra-dry contacts when
nance device when ordered without required; up to an 8 ARM-44 module
built-in automatic air supply per cabinet can be added
• with trim black pipe, nipples, and fit- • w i t h R A - 4 410 R C R e m o te
tings, as may be desired for AFFF Annunciator
systems Contact Red-E Cabinet Technical
• with Model QRS Electronic Acceler- Support for information about special
ator, for the 6 in. and 8 in. Double request cabinet configurations.
Interlock Electric/Electric Actuation
system types as shown in Table D,
note 3; and refer to Technical Data
Sheet TFP1100 for more information
• with special size air compressors for
single interlock systems
• with 50 Hz air compressors
• with seismic kit. Kit must be ordered
separately.
Valve Size Part No.
1 1/2 to 4 in. . . . . . . . . . . . . . . . 53-040-0-001
4 to 8 in. . . . . . . . . . . . . . . . . . . 53-080-0-001
TFP1401
Page 8 of 8

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;