FIGURE 1
INSTALLATION DIMENSIONS AND REFERENCE POINTS
TFP1401
Page 3 of 8
1 - Supply Header
4 2 - Drain Header
15 3 - Supply and Drain Header
Connections on Left or
20 Right Side
14 4 - System Discharge
Connection
5 - System Air Supply
8 Connection with Plug
6 - DV-5A Valve with
Preaction Trim
18 7 - Manual System Shut-Off
Valve
12 8 - System Pressure Gauges
5
9 - Manual Control Station
19 10 - Splash-Proof Drip Cup
9 11 - Drain Header Integrated
Drip Cup Connection
6 12 - Waterflow Pressure Alarm
10 Switch
13 - Main Drain Valve
7 14 - Releasing Panel
17 13 15 - Electrical Conduit
Connections
16 16 - Main Compartment
2 11 Access Door with
Optional Lock
17 - System Air Compressor
1 3 18 - Low Air Pressure Alarm
Switch
19 - Manual System Shut-Off
Valve
20 - Air Tank
FIGURE 2
TYPICAL ASSEMBLY ARRANGEMENT
(4 IN. DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/ELECTRIC ACTUATION SHOWN)
System Types drain valve - are individually tagged for sor sized to meet the requirements
The technical data sheets referenced in easy identification. All prefabricated of the largest system in the group to
Table A provide complete details for each piping is Schedule 40 steel. supply all the cabinets in the group, or
system type arrangement.
alternatively, connect to the factory air
A splash-resistant drain cup is pro-
Working Pressure Range vided that ensures water does not supply. The air supply line contains a
DV-5A Valve: 20 to 300 psi (1,4 to 20,7 bar) tee and plug which is used to connect
splash into the cabinet during flow
DV-5A Valve Trim: Refer to individual trim a hydraulic test pump that pressurizes
testing. The discharging water can be
technical data sheets for rated trim pres- the sprinkler system above the butterfly
sures as shown in Table A. observed through a clear tube attached
valve for hydraulic testing of the system
to the drain cup. It is designed with a
Construction in accordance with NFPA 13.
fail-safe feature allowing water to over-
The Red-E Cabinet is constructed of a flow in the event the drain is blocked. Table A provides list of riser compo-
minimum thickness of 14 gauge steel nents and a cross reference to indi-
and is free standing. The standard paint The hard piped funnel drain is con-
vidual technical data sheets, as well
finish is bright red and black. The front nected through a swing check valve to
as individual component laboratory
doors of the enclosure are fully hinged the main drain header, eliminating the
approval information.
(and removable) and open nearly to the need to run a separate drain line from
cabinet floor level allowing easy access the funnel. The cabinet floor is provided Figure 1 shows dimensional infor-
to the couplings when connecting the with a drain opening to allow water to mation for Red-E Cabinets, and
water supply and drain. Pre-drilled drain out. A plug is also provided to Figure 2 illustrates the typical assem-
holes on tabs along the base of the prevent water from draining from the bly arrangement.
cabinet provide an anchor point for the cabinet if necessary.
cabinet to be secured to the floor when The air supply connection for cabinets
required. Industrial grade rollers at the without compressors (using AMD-1) are
bottom of the cabinet are standard. terminated at a common height across
Internal controls that provide functions all model sizes allowing the connec-
to reset a system after operation - for tion of groups of cabinets easier. This
example, the alarm test valve or main allows a single tank mounted compres-
TFP1401
Page 4 of 8
TABLE A
PRINCIPAL COMPONENTS
TECHNICAL DATA SHEETS AND LABORATORY APPROVALS
Electric/Electric Electric/Pneumatic
Actuation Actuation
Model Number Horsepower Voltage1
System Volume System Volume
@20 psi in 30 min. @40 psi in 30 min.
gal (L) gal (L)
115/208-230 VAC
OLR12016AC 1/6 240 (909) 120 (454)
60 Hz
115/208-230 VAC
OLR25033AC 1/3 475 (1795) 250 (945)
60 Hz
115/208-230 VAC
OLR40050AC 1/2 800 (3028) 400 (1514)
60 Hz
115/208-230 VAC
OLR43075AC 3/4 930 (3520) 430 (1625)
60 Hz
115/208-230 VAC
OLR615100AC2 1 1430 (5410) 615 (2325)
60 Hz
115/208-230 VAC
OLR915150AC2 1 1/2 2320 (8780) 915 (3460)
60 Hz
208-230 VAC
OLR1225200AC2 2 3040 (11500) 1225 (4635)
60 Hz
Notes
1. Unless otherwise specified, 115 VAC, 60 Hz is provided.
2. 6 in. (DN150) and 8 in. (DN200) cabinets only.
TABLE B
AIR COMPRESSOR SELECTION FOR DOUBLE INTERLOCK PREACTION SYSTEM ARRANGEMENTS
TFP1401
Page 5 of 8
TABLE C
50 HZ AIR COMPRESSOR SELECTION CRITERIA
FOR DOUBLE INTERLOCK PREACTION SYSTEM ARRANGEMENTS
BASED ON SYSTEM TYPE AND VOLUME
Ordering ELECTRICAL
P/N 53 — X — X — XX — X — X — X — X
TABLE D
DV-5 a RED-E CABINET PREACTION SYSTEMS
PART NUMBER SELECTION