Hart - 7 Data' PDF
Hart - 7 Data' PDF
GS 01C31T01-01EN
FEATURES
● Remote Ranging and Monitoring Functions
Ranges can be remotely set and monitored through
HART communication.
● On-line Communication
Output signal and communication signal do not
interfere making on-line communication possible.
● Enhanced Burst Mode and Event Notification
(HART 7)
Advanced burst mode includes the variety of
transmission setting by specifying burst variables,
update period, and message triger mode, and event
notification function gives you alert signal based
on the status change in preset values and self-
diagnosis.
● Long Tag Supporting Up to 32 Characters
(HART 7)
Long tag secures a better asset management with
abundant digits in its software.
● Self-Diagnostic
Pressure input outside of range limit, excessive
ambient temperature, incorrect span setting etc. can
be diagnosed through HART communication.
● HART protocol revision selectable
(Output signal code -J)
Selectable from HART 5 and HART 7.
STANDARD SPECIFICATIONS
600
For items other than those described below, refer to
each General Specification sheet. E–10.5
External R=
0.0244
HART Protocol Revision load Communication
Output signal code -J resistance applicable
HART protocol revision can be selected from 5 or 7 R (Ω) range
when ordering. The protocol revision can be changed 250
by user configuration.
Output signal code -Q
HART 7
Write Protection Switch
Hardware/software write protection switch 10.5 16.6 25.2 42
Conditions of Communication Line Power supply voltage E (V DC)
(Output signal code -J) F01E.ai
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31T01-01EN June 20, 2012-00
<<Contents>> <<Index>> 3
MODEL AND SUFFIX CODES
EJA E-J - /
Output signal . . . 4 to 20 mA DC with digital communication (HART 5/HART 7 protocol*)
EJA E-Q - /
Output signal . . . Low Power, 1 to 5 V DC with digital communication (HART 7 protocol)
Selection guide
Specified item when ordering HART protocol
Requirement for HART 7 Note
“HART protocol revision” revision
functionality
Indicate the most typical selection for HART
communication. In case of selecting HART 7
Select when HART 7 functionality
Specify ‘5’ HART 5 without conforming to Table 2, communication
is not required.
will not be available. Select this when HART 7
functionality is not required.
Select when HART 7 functionality
is required.
Specify ‘7’ HART 7 In this case, be sure to confirm
that HART configuration tool
supports HART 7 by Table 2.
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31T01-01EN Oct. 24, 2014-00
<<Contents>> <<Index>> 4
All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31T01-01EN April 10, 2018-00