Control Valve
Control Valve
3
15" 32 4 "
VALVE CL
1
12 4 "
B VALVE ACTUATOR B
3
24 4 "
3"
3" NO CONDUIT ENTRIES
IN NEMA 7 ENCLOSURE TOP
1
44"
4X 3/4" NPT
CUSTOMER ELECTRIC 2" 3
INPUT CONNECTIONS 1 47 4 "
22"
NEMA 7 ENCLOSURE ASSEMBLY
VIEW A-A
ELECTRIC MOTOR WIRING BOX
B
TOPWORX
VALVE CONTROLLER
1
39 2 " B
HYDRAULIC VALVE
MANIFOLD ASSEMBLY
HAND PUMP
A A
2.5 GALLON
BLADDER ACCUMULATOR
A A SECTION B-B
TOTAL ASSEMBLY WEIGHT = APPROX. 965 LBS.
1 HYDRAULIC OIL NOTES DRAWN NJS 07/06/2018
18 4 " RESERVOIR
1. NOT SHOWN ON DRAWING:
• HYDRAULIC CONNECTIONS BETWEEN
37" HPU & ACTUATOR, TO BE S.S. TUBES. CHECKED BLM 07/06/2018
• ELECTRIC CONNECTIONS BETWEEN
NEMA ENCLOSURES & VALVE
TULSA, OKLAHOMA
APPROVED
REVISIONS CONTROLLER, TO BE FLEX CONDUIT.
CAMERON-GEOPARK
PART
2 1
TopWorx Valve Controller DXP-TX1GNEB
RD81K-DAEC2-120-EP-ENC.2A BKT-ES120 (Mount Bracket)
NEMA 7 Enclosure RESET Visual Display: Green = OPEN
XHPB Red = CLOSE
Remote 3/4" NPT Switch #1 (CLOSE)
1N4004 DIODE Bottom 3
Reset 24 2 1
R 26
R
25
1
6
27 5 4
1/2" NPT Right Side 1N4004 DIODE 300-3000-1-1-45-1 29
500 Ohm
Hydraulic Connection + Pr - 4-20 mA Pressure Transmitter 28
to NEMA 4X Enclosure T
Switch #2 (OPEN)
PST 9
1 XHPB
500 Ohm 30 8 7
32
1 11
ESD 31
Remote PST
XHPPM
12
DIP Switch Settings
ON
1 12 OUTPUT INPUT 33 11 10
Remote ESD 0-20mA 0-20 mA
OPEN 1 2 3 4 5 6 7 8 9 10 35
XHSS 34
MANUAL
SIGNAL CONDITIONER
CLOSE Red Lion IAMA3535
17
2 12 3/4" NPT Position Transmitter
LOCAL OPEN OUTPUT (S2) Bottom 4-20 mA (4 mA = CLOSE)
XHSS Customer Contact 3 10 10 18
20MA
OFF 13 14
4 1MA
1
REMOTE POSITION FEEDBACK
+ CUSTOMER -
36 37
1 15 4-20 mA
INTERMEDIATE
OL's A
XLA-GH
M1
CLOSED
R
XLR-GH
N H 17 16
C D E VALVE INFORMATION:
1 CB101AS10 CB101AS10 1 1 4 Brand: WKM
Part No.: 370D6
3 3 POC CPD084P Type: Ball
C08-4
Size: 14"
2 3 25.901-5000 ANSI Rating: 600 #
2 2
CB CB 2 4 Fluid: Oil
C10-3 C10-3
DMH085C4D Provided By: Customer
FA101S 1
FC
1 FA101S 4-WAY Operation Torque: 45,288 in-lb (BTO)
FC C08-4
PUSH IN (TOWARD MNFLD)
TO CLOSE ACTUATOR
C10-2 C10-2 SWS-N04-A1
3 1 REQUIREMENTS:
2 F Actuator: Rotary Double Acting, 1/4 Turn
2 2
241871-S
RDH101S50 Main Electric Input: 120 VAC, 1 Ph, 60 Hz
2 4 PUMP .601 in^3/stroke Set @ 3200 psi
C10-2 Fail Position: Closed on Loss of Control Signal or Power
4-SOL DSL104B 241016 Handle
C10-4
Control Signal: 24 VDC, Maintain to Hold Actuator Shifted
HLC10LD024JN
1 2 1 Electrical Classification: Class 1, Division 1, Groups C & D
3 1 End of Stroke Limit Switches: Quantity 2 DPDT & 4-20 mA
Actuator to Valve Adaption Provided By: Customer
G 1
Manual Operation Type to Shift: Hand Pump
REL
REG PRH082S30
C10-2 Closing Time: 8-105 sec (adjustable)
BA02B3T01P2 C08-3 3
Set @ 1150 psi Opening Time: 8-105 sec (adjustable)
AS2-18792, Clamp Brkt (HAND PUMP)
B-5L, Base Brkt Ambient Temperature Range: 0-120°F
1000 psi 2
Nitrogen Precharge
Electric Motor Power: 3/4 HP
1 System Pressure Relief Valve Setting: 3,200 psi
SY1010H-S VALVE ACTUATOR
2-SOL DSL101NR CLOCKWISE TO CLOSE Accumulator Recharge Time: 1.6 min/stroke
C10-2 HLC10LD024JN Accumulator Stored Strokes: 2 (Open to Close = 1 Stroke)
2
515966-AO23KL-MAN-ALM B A
2800 psi
Hyd Oil Charge 300-3000-1-1-45-1
Pr
T
3928-1-PS-CONNECT
N400SS
DT-370-MOMF-5
(Inside NEMA 7 Enclosure)
VL5007A
3/4 HP 9152T
SDB-093/2 10.6 FLA EK9052 (ELEMENT)
RD-093 (DESICCANT)
DBA-75
775679 (Adapter 550 56C)
M 1725 RPM
XPFC
L971
RD88KR-DAEC2-1-RES 410542
4 Gallons Total
2BVL2004F
1/4-HP-SS
NOTES:
1. 4-WAY valve operation: push in toward mnfld to close actuator, & pull out away from mnfld to open actuator.
OM00024
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
1. INTRODUCTION
Thank you for purchasing this Aberdeen Dynamics product. This Installation & Operation
Manual (IOM) provides a general overview of this product along with information regarding
safety, components, installation, operation, maintenance, drawings, and specifications.
2. SAFETY
Read and understand this IOM prior to installation, setup, and operation of this product.
Below is an explanation of the safety alert symbols that may be used in this IOM.
Indicates a hazardous situation which, if not avoided, will result in serious injury or death.
Indicates a hazardous situation which, if not avoided, could result in serious injury or death.
Indicates hazardous situation which, if not avoided, could result in minor or moderate injury.
Hydraulic accumulators utilize compressed nitrogen gas to store hydraulic energy. Follow
all warnings and general safety precautions explained in the Parker “Pre-Charging
Instructions for Bladder Accumulators, catalog # HY10-1632-M2.2/US.” Failure to follow
safety precautions will result in serious injury or death.
Always wear proper personal protective equipment (PPE) when performing any work
associated with this HPU.
Ensure all personnel installing, operating, or maintaining the HPU are properly trained.
Ensure all hydraulic and electrical connections are properly tightened before operation.
Ensure HPU electric power input conforms to the required NEC electrical classification.
Always disconnect and/or lock-out / tag-out electric power to the HPU when performing
maintenance operations.
OM00024 Page 2 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
3. OVERVIEW
This hydraulic power unit and valve actuator assembly (HPU) is Class 1, Division 1, Groups
C & D rated self-contained electro-hydraulic unit that mounts onto and powers a pipeline
quarter-turn valve (not included). In the event of either an electric power or control signal
outage/failure, the HPU will fail close the pipeline valve.
The HPU’s electric motor driven hydraulic pump, accumulator, oil reservoir, control valves,
and manual override system are located inside a lockable NEMA 4X rated stainless steel
enclosure. The electrical control system is located in a NEMA 7 rated enclosure.
The HPU automatically maintains charge pressure on the hydraulic accumulator. Stored
hydraulic energy from the accumulator is used to stroke the valve actuator. The
accumulator stores 2 actuator strokes minimum (open to close or vice versa = 1 stroke).
The valve actuator is a double-acting quarter-turn scotch yoke style actuator, and includes a
valve controller (limit switch) that sends valve open/close position information to the HPU
control system. The system controls the opening and closing of the pipeline valve via either
remote command signals by the pipeline electrical control system or local switch and
pushbutton commands by the operator.
4. COMPONENTS
OM00024 Page 3 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
OM00024 Page 4 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
4.2.1. OPEN: Green light illuminates when actuator is in fully open position.
4.2.4. RESET: Press button after ESD has been pressed to reset local control.
4.2.5. PARTIAL STROKE TEST: Press button to initiate partial stroke test when
selector switches are LOCAL and OPEN and actuator is fully open.
4.2.6. ESD: Emergency shut down. Press button to close actuator when selector
switches are LOCAL and OPEN.
4.2.7. OPEN / MANUAL / CLOSE: Selector switch used to operate actuator when
other selector switch is LOCAL.
4.2.8. LOCAL / OFF / REMOTE: Selector switch used to choose operation method.
OM00024 Page 5 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
5. INSTALLATION
Utilize proper load-rated lifting equipment when lifting, handling, and installing the HPU. Do
not remove lifting equipment until actuator to valve mounting is secure.
Refer to actuator manufacturer for detailed valve mounting instructions and hardware
requirements. Below are basic HPU and valve actuator to valve mounting steps:
Verify the valve is in the closed position.
Adjust the actuator mechanical stops to allow for full valve travel open and close.
Align actuator bore, keyway, and mounting holes to valve shaft and mounting holes.
Install actuator onto valve using proper mounting hardware, shaft key, etc.
Properly torque all mounting hardware.
Adjust the open and/or close travel stops and limit switch if necessary.
Electrical connections should only be made by qualified personnel that understand electrical
schematics, electrical systems, all local electrical codes, and the electrical classification
requirements. Ensure all electrical connections conform to the minimum required
environmental electrical classification for the HPU and surrounding equipment.
Reference DRAWINGS section for terminal numbers on the electrical schematic. Use
the four 3/4” NPT bottom port connections for all electrical inputs & outputs.
OM00024 Page 6 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
Hydraulic oil cleanliness is critical for optimal performance and longevity of hydraulic
components. Always fill oil reservoir with clean, filtered hydraulic oil. New oil from an
unopened container should not be assumed to be sufficiently clean oil to install in the HPU
without first filtering the oil. Additionally, ensure the oil reservoir maintains proper fill level
after hydraulic components have been filled at initial system startup.
Fill the hydraulic oil reservoir through the oil fill port until the oil is at the top of the oil level
sight glass. Fill with a premium quality mineral based hydraulic oil that is fully compatible
with all system components, Buna-N seals, and maintains a viscosity between 12-150 cSt
for the expected ambient temperature range of the unit.
OM00024 Page 7 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
6. OPERATION
There are three operation methods for the HPU and valve actuator assembly:
Remote
Local
Manual
OM00024 Page 8 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
6.3.4. Actuator will also close if LOCAL / OFF / REMOTE switch is OFF.
6.3.5. When selector switches are in LOCAL and OPEN, actuator will close if:
6.3.5.1. There is a 24VDC electric power failure.
6.3.5.2. ESD button is pushed.
6.3.6. RESET button must be pushed before local operation will work if the actuator
automatically closes due to electric power failure or due to pushing ESD button.
6.4.1. Use the hand pump and manual directional control valve for manual operation.
6.4.2. Insert the hand pump handle into the hand pump.
OM00024 Page 9 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
6.4.6. When not using manual operation method, ensure manual directional control
valve is in its center position.
6.5.5. The actuator will proceed through the following partial stroke test steps:
6.5.5.1. Actuator closes to 80% of full open, & INTERMEDIATE light flashes.
6.5.5.2. Actuator pauses for 10 seconds, & INTERMEDIATE light flashes.
6.5.5.3. Actuator re-opens to full open position, & INTERMEDIATE light is on.
6.5.5.4. At actuator full open, INTERMEDIATE light is off, & OPEN light is on.
6.5.6. If actuator fails partial stroke test, the partial stroke test alarm contact opens.
OM00024 Page 10 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
Viewing the Smart Relay controller display requires the electrical enclosure door to be open.
An open enclosure door nullifies the NEMA hazardous location electrical protection of the
HPU and valve actuator assembly. Do not open the enclosure door unless and until the
hazardous environmental conditions allow for safe electrical operation of job site equipment.
Be aware that changing the installed software program may result in undesired or incorrect
HPU and valve actuator assembly operation. Be familiar with the programming software,
parameters, ladder logic, and Smart Relay controller operation before installing a different
software program. Refer to the IDEC Smart Relay user’s manual for further information.
The IDEC Smart Relay controller uses WindLGC programming software and includes a
factory installed program in ladder logic format. Reference the DRAWINGS section for the
software program ladder logic diagram.
The controller uses digital inputs and outputs, analog inputs, internal relay outputs, timers,
and analog triggers, which all can be monitored on the controller display during operation.
The timer and trigger settings can be changed during operation and may require program
changes based on actuator stroke time.
If any parameter settings are changed while the program is running, these changes are
transferred to the program. If the program is uninstalled / reinstalled, the original program
settings will take effect and any changed parameters will not be included.
Special functions in the program such as triggers and timers have labels corresponding to
the Smart Relay display. For example, a program trigger labeled SF001 corresponds to a
Smart Relay display B001, and a program timer labeled T006 corresponds to a Smart Relay
display B006. Below is a list of the program parameter labels with their corresponding
Smart Relay display labels in parentheses.
SF001 (B001): Electric motor start / stop pressures [On 2800, Off 2600]
SF003 (B003): Determines if actuator is open & turns on open light at 98% open [980]
SF004 (B004): Determines if actuator is closed & turns on closed light at 2% open [20]
SF005 (B005): Determines if actuator is 80% open for partial stroke test [800]
SF011 (B011): Determines if actuator position signal is working [-60 less than 4mA]
SF012 (B012): Determines if pressure signal is working [-60 less than 4mA]
OM00024 Page 11 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
SF013 (B013): Determines low accumulator pressure less than 1200psi [Off 1200]
SF014 (B014): Determines if partial stroke test went too far [65%, 650]
T002 (B002): Timer [10 minutes], electric motor run limit. Turns motor off if it runs
continuously for 10 minutes (accumulator should fully pressurize within
5 minutes). To reset, turn LOCAL / OFF / REMOTE switch to OFF then
back to REMOTE. Also activates COMMON ALARM.
T006 (B006): Timer [10 seconds], partial stroke test pause time
T007 (B007): Timer [5 seconds], solenoid valve delay to ensure actuator is fully open
T009 (B009): Timer [30 seconds], partial stroke test actuator at 80% open within time
T010 (B010): Timer [70 seconds], partial stroke test actuator closed within time
T015 (B015): Timer [5 seconds], solenoid valve delay to ensure actuator is fully close
T008 (B008): Timer [flashing – on and off times 00.30 seconds], on / off time for
intermediate light during partial stroke test
Analog triggers are internal relays with adjustable set points based on an analog input from
the actuator position transmitter’s 4-20 mA current signal. The Smart Relay controller only
accepts 0-10 VDC analog voltage inputs, so the 4-20 mA signal is converted to 0-10 VDC.
The controller then scales the analog signal to counts.
The actuator position signal is used to turn on and off the solenoid valves and electrical
enclosure lights. Analog position signals can change slightly from many variables
(temperature fluctuations, mechanical linkage wear/damage, etc.). Therefore, to account for
these variables, the controller incorporates timers to slightly delay (5 seconds) the on and off
solenoid valve controls to ensure the actuator is fully open or fully closed.
OM00024 Page 12 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
8. MAINTENANCE
8.1.1. Fill hydraulic reservoir with hydraulic oil to the top of the reservoir level sight
gauge. Use filter when filling reservoir with hydraulic oil.
Before any maintenance is attempted the accumulator must be opened to drain accumulator
stored pressure.
8.2.2. Accumulator must be charged before running the motor driven pump.
8.2.3. Accumulator drain valve must be open before charging accumulator with
nitrogen.
8.2.5. For detailed nitrogen charging instructions follow the instructions found in
Parker catalog #HY10-1632-M2.2/US.
9. DRAWINGS
The following pages are the assembly layout, hydraulic schematic, electric schematic, and
Smart Relay program for the HPU and valve actuator assembly.
OM00024 Page 13 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
OM00024 Page 14 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
OM00024 Page 15 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
OM00024 Page 16 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
OM00024 Page 17 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
OM00024 Page 18 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
OM00024 Page 19 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
10. SPECIFICATIONS
10.1. GENERAL:
Operating Ambient Temperature: 0°F to 120°F
Valve Fail Position: Close on loss of electric power or remote signal
Open Time, Full Stroke: 8 – 105 seconds (adjustable)
Close Time, Full Stroke: 8 – 105 seconds (adjustable)
10.2. ELECTRIC:
Main Electric Input 120 Volts AC, 1 Phase, 60 Hertz
Control Signal Input: 24 Volts DC, maintain to hold actuator shifted
Electrical Protection: NEMA Class 1, Division 1, Groups C & D
Electric Motor Power: 3/4 HP
Electric Motor Overloads: 3.2 – 16 Amps, adjustable
Valve Controller: (2) DPDT limit switches + 4-20 mA Position Trans.
10.3. HYDRAULIC:
Pressure: System = 3000 psi max / Actuator = 1150 psi
Flow Rate: Pump = 0.25 gpm / Accumulator = varies
Manual Hand Pump: .601 in3 per stroke
Oil Reservoir Capacity, Total: 4 Gallons
Accumulator Charging Time: Approx. 1.6 min / stroke
Accumulator Storage Capacity: 2 actuator strokes min. (open to close = 1 stroke)
10.4. ACTUATOR:
Model: Ledeen # SY1010H-S
Torque Mechanism: Quarter-Turn Scotch Yoke
Displacement: 116 in3
Break-to-Open Torque: 92,575 lb-in
End-to-Close Torque: 77,855 lb-in
OM00024 Page 20 of 21
17717 E. Admiral Pl.
P.O. Box 582510
Tulsa, OK 74158
Office: 918-437-8000
Fax: 918-437-8420
OM00024 Page 21 of 21
4.3. Partes de Repuesto Recomendadas