Ducted Split Unit Selection

The document contains technical specifications for multiple ceiling concealed ducted split air conditioning units. It includes details such as room area and cooling load calculations, indoor and outdoor unit dimensions, capacity and power input details, sound pressure levels, and piping requirements for various models. Performance parameters like EER, airflow rates, and total vs sensible cooling capacities are provided for indoor units operating with outdoor conditions of 43C and 46C.

Uploaded by

نور مجسم
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views

Ducted Split Unit Selection

The document contains technical specifications for multiple ceiling concealed ducted split air conditioning units. It includes details such as room area and cooling load calculations, indoor and outdoor unit dimensions, capacity and power input details, sound pressure levels, and piping requirements for various models. Performance parameters like EER, airflow rates, and total vs sensible cooling capacities are provided for indoor units operating with outdoor conditions of 43C and 46C.

Uploaded by

نور مجسم
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 7

46 C O

Total Sensible Flow Rate


Room Claculated Unit Model
Area "m2" m2/T.R Capacity Capacity @ 50 Pa
REF. Load (KW) Name Number
"KW" "KW" "L/S"

20 16 4.4 IU-02 53QDMT18-718 4.5 3.7 116

43 C O

Total Sensible Flow Rate


Room Claculated Unit Model
Area "m2" m2/T.R Capacity Capacity @ 50Pa
REF. Load (KW) Name Number
"KW" "KW" L/S

20 16 4.4 IU-02 53QDMT18-718 4.6 3.7 116


46 C Outdoor Conditions

Indoor Outdoor Max.


Outdoor Unit
Power Input Power Supply EER Indoor Unit Dim. Unit Unit Pipe
Dim.
"KW" "V/ph/Hz" "W/W" "WxHxD" Weight Weight Length
"WxHxD"
"Kg" "Kg" "m"

1.85 220-240/1/60 3.03 920 × 210 × 635 24 760 × 590 × 285 42 20

43 C Outdoor Conditions

Indoor
Outdoor Unit Outdoor Max.
Power Input Power Supply EER Indoor Unit Dim. Unit
Dim. Unit Pipe
KW V/ph/Hz W/W WxHxD Weight
"Kg" "WxHxD" Weight Length

1.8 220-240/1/50 3.03 920 × 210 × 635 24 760 × 590 × 285 42 20


Indoor Sound Outdoor
Max.Height Condensate
Pressure Sound
Difference drain hose
@Med. Speed Pressure
"m" diameter
"dB(A)" dB(A)

10.00 33 57 25

Indoor Sound Outdoor


Condensate
Max.Height Pressure Sound
drain hose
Difference @Med. Speed Pressure
dB(A) dB(A) diameter

10.00 33 57 25
Total Total Sensible
Capacity Range Unit Name Model Number
Capacity "KW" Capacity "KW"
"KW"

1 3 2.5 IU-01 53QDMT12-718


3.1 4.5 3.7 IU-02 53QDMT18-718
4.6 5.8 4.7 IU-03 53QDMT24-718
5.9 6.9 6.2 IU-04 53QDMT30-718
7 8.7 7.1 IU-05 53QDMT36-718
8.8 9.3 7.5 IU-06 53QDMT42-718
9.4 10.5 8.5 IU-07 53QDMT48-518
10.6 12.3 10 IU-08 53QDMT60-518
12.4 0 0 No unit 0

* Indoor Conditions 21Db , 15Wb


** IU-01 @ 40 Pa

Total
Total Sensible
Capacity Range Unit Name Model Number
Capacity "KW" Capacity "KW"
"KW"

1 3.1 2.5 IU-01 53QDMT12-718


3.2 4.6 3.7 IU-02 53QDMT18-718
4.7 5.9 4.8 IU-03 53QDMT24-718
6 7 5.7 IU-04 53QDMT30-718
7.1 8.9 7.2 IU-05 53QDMT36-718
9 9.5 7.7 IU-06 53QDMT42-718
9.6 10.7 8.6 IU-07 53QDMT48-518
10.8 12.5 10.1 IU-08 53QDMT60-518
12.6 0 0 No unit 0

* Indoor Conditions 21Db , 15Wb


** IU-01 @ 40 Pa

*Source :Carrier Ceiling Concealed Ducted Split Systems (CCD 2013)


46 C Outdoor Conditions

EER Flow Rate @ Flow Rate @ 50Pa Power Input Indoor Unit Dim. Indoor Unit
50Pa
W/W L/S KW WxHxD Weight "Kg"
CFM

3.01 193 91 1.2 700 × 210 × 635 20


3.03 246 116 1.85 920 × 210 × 635 24
3.12 290 137 2.3 920 × 270 × 635 28
2.5 550 260 3.3 1140 × 270 × 775 41
2.63 550 260 4 1140 × 270 × 775 41
2.57 693 327 4.3 1200 × 300 × 865 47
3.1 693 327 3.9 1200 × 300 × 865 47
3.24 880 415 4.4 1200 × 300 × 865 47
0 0 0 0 0.00 0

43 C Outdoor Conditions
Flow Rate @ Flow Rate @ 50Pa
EER Power Input Indoor Unit Dim. Indoor Unit
50Pa
W/W L/S KW WxHxD Weight "Kg"
CFM

3.01 193 91 1.2 700 × 210 × 635 20


3.03 246 116 1.8 920 × 210 × 635 24
3.12 290 137 2.3 920 × 270 × 635 28
2.5 550 260 3.3 1140 × 270 × 775 41
2.63 550 260 3.9 1140 × 270 × 775 41
2.57 693 327 4.2 1200 × 300 × 865 47
3.1 693 327 3.9 1200 × 300 × 865 47
3.24 880 415 4.4 1200 × 300 × 865 47
0 0 0 0 0.00 0
ns
Indoor Sound
Outdoor Unit Dim. Outdoor Unit Power Supply Max. Pipe Max.Height Pressure @Med.
WxHxD2 Weight V/ph/Hz Length Difference Speed
dB(A)
780 × 540 × 250 34 220-240/1/60 10 4 29.4
760 × 590 × 285 42 220-240/1/60 20 10 33
860 × 570 × 350 58 220-240/1/60 20 10 39
860 × 570 × 350 62 220-240/1/60 25 10 42.4
860 × 720 × 350 65 220-240/1/60 25 10 42.4
860 × 720 × 350 65 220-240/1/60 25 10 40.6
860 × 1150 × 350 68 380-420/3/60 30 15 40.6
860 × 1150 × 350 69 380-420/3/60 30 15 44.3
0.00 0 0 0 0 0

ns
Indoor Sound
Outdoor Unit Dim. Outdoor Unit Power Supply Max. Pipe Max.Height Pressure @Med.
WxHxD2 Weight V/ph/Hz Length Difference Speed
dB(A)
780 × 540 × 250 34 220-240/1/50 10 4 29.4
760 × 590 × 285 42 220-240/1/50 20 10 33
860 × 570 × 350 58 220-240/1/50 20 10 39
860 × 570 × 350 62 220-240/1/50 25 10 42.4
860 × 720 × 350 65 220-240/1/50 25 10 42.4
860 × 720 × 350 65 220-240/1/50 25 10 40.6
860 × 1150 × 350 68 380-420/3/50 30 15 40.6
860 × 1150 × 350 69 380-420/3/50 30 15 44.3
0.00 0 0 0 0 0
Outdoor Sound Condensate
Pressure drain
dB(A) hose diameter

56 25
57 25
62 25
62 25
65 25
65 25
68 25
69 25
0 0

Outdoor Sound Condensate


Pressure drain
dB(A) hose diameter

56 25
57 25
62 25
62 25
65 25
65 25
68 25
69 25
0 0