Design of 7 Stories Apartment Building A. Design Specification / Reference

This document provides specifications for designing a 7 story apartment building, including design references, materials, loadings, and modeling approach. Concrete strength is 20.7 MPa with Grade 60 and 50 rebars. Loadings include dead loads from self-weight and finishes, live loads from floors and roof, and seismic loads following NSCP 2015 and UBC 1997 codes. The building will be modeled with a grid system and master story approach using predefined section properties for beams, columns, and slabs. Reinforcement will be designed for beams and columns.

Uploaded by

Ryugi Kamasaki
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
65 views

Design of 7 Stories Apartment Building A. Design Specification / Reference

This document provides specifications for designing a 7 story apartment building, including design references, materials, loadings, and modeling approach. Concrete strength is 20.7 MPa with Grade 60 and 50 rebars. Loadings include dead loads from self-weight and finishes, live loads from floors and roof, and seismic loads following NSCP 2015 and UBC 1997 codes. The building will be modeled with a grid system and master story approach using predefined section properties for beams, columns, and slabs. Reinforcement will be designed for beams and columns.

Uploaded by

Ryugi Kamasaki
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 8

DESIGN OF 7 STORIES APARTMENT BUILDING

A. DESIGN SPECIFICATION / REFERENCE


1 NSCP 2015
2 ACI 318-14 (CONCRETE)
3 UBC 1997 (EARTHQUAKE)
4 ASCE 7-10 (WIND)

B.MATERIALS
Concrete F'c = 20.7 Mpa (3000 psi)
Rebars fy (415 Mpa) Grade 60 - Rebars >= 16mm
fy (275 Mpa) Grade 50 - Rebars < 16mm

C. LOADINGS
DEADLOAD
Self-weight
Unit Wt. Concrete = 23.5631 kN/m^3

SUPERIMPOSED DEADLOAD (section 204)


Distribured Loads:
100 mm CHB WALL 2.98 kPa (2 faces plastered)

Floor Loads:
Floor finish 1.1 kPa *For suspended floors
Partitiion Load 1 kPa (add all)
Ceiling 0.15 kPa *For Roof deck
Insulation 0.08 kPa (Ceiling to MEPF)
Waterproofing 0.26 kPa
MEPF 0.10 kPa

LIVE LOADS (section 205)


Ground floor 2.40 kPa
Suspended Floors 1.90 kPa

ROOF LIVE LOAD (Section 205.4) *See table 205-3 and Section 206-7 (For Ponding L
Roof Load 1.32 kPa *Ponding load - Accumulation of water
0.6 + 1.2*0.6 = 1.32 *Section 203.3.2
SEISMIC LOAD (NSCP 2015 / UBC 1997) Ponding Load = 1.2*P
Direction and Eccentricity
X Dir + Ecc
Y Dic + Ecc
X Dir - Ecc
Y Dir - Ecc

Eccentricity Ratio = 0.05


Ct Value (Section 208.5.2.2, NSCP 2015 / Section 1630.2.2, UBC 1997)
Ct = 0.0731
Overstrength Factor ( R )
R = 8,5 (SMRF)
R = 8.5 (Shear Walls)

Soil profile type = SD


Maximum Moment Magnitude (M) - (Regional Geo-Hazard Map)
M = 7.2
Distance to Source = 25.60 kM (faultfinder.phivolcs.dost.gov.ph)
Sesimic Source Type = A (Table 208-4, NSCP 2015)
Sesimic Zone Factor Z = 0.4 (Zone 4) - Sectin 208.4.4.1, NSCP 2015)

Na = 1
Nv = 1 Table 208-5, 6, 7, 8 - NSCP 2015
Ca = 0.44
Cv = 0.64

Occupancy Category = IV
Importance Factor = I = 1.0

WINDLOADS (NSCP 2015, ASCE7-10)

C. MODELLING

GRID SYSTEM DATA


BASE (FND) = 0 meters
FND - NGL = 2 meters
NGL- 2F = 3 meters
2f - 3f - 4f - 5f - 6f - 7g - RD = 3 meters

MASTER STORY - For ez changing of floors (similar floors)

SIZE ASSUMPTION PROPERTY NAME:


BEAM 300X400 RB300X400FC3FY60FYS40

COLUMN 400X400 RC400X400FC3FY60FYS40

SLAB 125mm RS125FC3FY60FYS40


DEFINE - DEFINE MATERIALS - ADD NEWMATERIALS
MATERIAL TYPE: CONCRETE
STANDARD: CUSTOMARY
GRADE: fc' 3000 psi
MODULUS OF ELASTICITY = 4700 sqrt (f'c)

MOMENT OF INERTIA AND CROSSSECTIONAL AREA (ELASTIC ANALYSIS AT FACTORED LOAD


COLUMN 0.70 Ig
BEAM 0.35 Ig (See table 406.6.3.1.1 (a), NSCP 2015)
FLAT SLAB 0.25 Ig

REINFORCEMENT TO BE DESIGNED
Check for Beam (M2 only)
Check for Column (P-M2-M3 Interaction Diagram)

SLAB SECTION SLAB PROPERTY DATA


modelling type Shell - thin >> Part of structural member (resist lateral force)
Membrane >> Slab only carries the load (not part of structural member)

>> check minimum thickness >> Check for deflection


Type: Slab
Thk: 125 mm
d Section 206-7 (For Ponding Load)
umulation of water

oad = 1.2*P
esist lateral force)
ot part of structural member)