Fire Stopping Standard Details
Fire Stopping Standard Details
Interested?
Fire Stopping For further information on
▪ Structural protection
▪ Penetration seals
▪ Joints
▪ Cavity barriers
▪ Building services protection
(V10/NOV22) 2
Changelog
General changes Detail amendments
Supporting evidence reference changed to reflect new assessments Single sided double Cable insulation performance reduced to 60 minutes. Additional non
RWSD-ACB-0102
50mm batt combustible pipe and PVC conduit coverage added
Fire Stopping Guide Unlagged & lagged cable performance confirmed. Additional non
RWSD-ACB-0201 50mm batt face fix
Point 4) Note added on shaft walls combustible pipe coverage added
Double 50mm batt floor Cable performance without additional pattress added. Additional non
Point 5) Note on sandwich or composite walls added RWSD-ACB-0501
seal combustible pipe coverage added. Damper reference removed
Point 9) 400mm service support distance Single 60mm batt Damper reference removed. Scope enhanced in terms of cables, trunking
RWSD-ACB-1001
Point 10) Separation note added to reflect BS EN 1366-3:2021 double skin & non combustible pipes
Double 60mm batt Damper reference removed. Scope enhanced in terms of cables & non
Point 11) Clarification on cable carriers - any length in accordance with BS EN 1366-3:2021 RWSD-ACB-1101
double skin combustible pipes
Details omitted Unlagged & lagged cable performance confirmed. Additional non
RWSD-ACB-1201 60mm batt face fix
combustible pipe coverage added
SD-140 - L/I H&V Pipe lagging through batt seals
Additional requirements to u/s of steel. Increased scope in terms of seal
SD-141 - L/S H&V Pipe lagging through batt seals RWSD-ACB-1301 60mm batt HoW
height and length
SD-126 - 50mm ablative batt head of wall Damper note removed. Detail revised in line with current assessment -
RWSD-ACB-1501 60mm batt floor seal
cable coverage removed
Additional details
RWSD-SS-0101 Softseal linear joint Cavity width reduced inline with new assessment
RWSD-ACB-0002 - Single skin single 50mm batt
RWSD-ACB-0103 - Single skin double 50mm batt Single 50mm batt High
RWSD-HE-0001 Tracpipe coverage added
Expansion
RWSD-COM-1001 - High strength compound wall seal
Double 50mm batt High Flexible substrate removed, medium cable performance reduced to E 120
RWSD-HE-0050
RWSD-COM-1510 - High strength compound rigid floors - Cables Expansion EI 90 in line with current assessment. Small cables added EI 120
RWSD-COM-1511 - High strength compound floor seal - Cables with plinth / wrap RWSD-HE-0054 CPVC application range Error on single skin detail amended
RWSD-SS-0010 - Softseal deflection head High expansion sealant
RWSD-HE-0102 Armaflex details combined
RWSD-COL-0004 - Single skin single batt - Pipe collar CE 100mm wall
High expansion sealant
RWSD-COL-0503 - Double batt floor seal - Pipe collar CE RWSD-HE-0501 PVC pipe detail combined
double batt floor seal
RWSD-AIS-0110 - Single skin AIS cables Oval duct scope added for 100mm wall & single/double 50mm batt
RWSD-IFS-1003 Oval IFS
RWSD-AIS-0120 - Single skin AIS pipe penetrations applications
Face fix 50mm batt -
RWSD-SP-0001 - SP Slab linear joint seal data reinstated RWSD-PWR-0101 Table reduced - scope refined
PWR insulated pipes
(V10/NOV22) 3
Contents
Orientation
Page FIREPRO® product Application area Drawing no.
of use
7 Single 50mm Ablative Coated Batt - 100mm Wall Multiple Service Penetrations Wall Seal RWSD-ACB-0001
8 Single 50mm Ablative Coated Batt - 75mm Wall Multiple Service Penetrations Wall Seal RWSD-ACB-0002
9 Double 50mm Ablative Coated Batt Multiple Service Penetrations Wall Seal RWSD-ACB-0101
10 Double 50mm Ablative Coated Batt - Single Sided Install Multiple Service Penetrations Wall Seal RWSD-ACB-0102
11 Double 50mm Ablative Coated Batt - Single Skin 100mm Wall Multiple Service Penetrations Wall Seal RWSD-ACB-0103
12 Double 50mm Ablative Coated Batt - Timber Penetrations Timber Penetrations Wall Seal RWSD-ACB-0120
13 50mm Ablative Coated Batt - Face Fix Multiple Service Penetrations Wall Seal RWSD-ACB-0201
14 Double 50mm Ablative Coated Batt - Floor Seal Multiple Service Penetrations Floor Seal RWSD-ACB-0501
15 Single 60mm Ablative Coated Batt - 100mm Wall Multiple Service Penetrations Wall Seal RWSD-ACB-1001
16 Double 60mm Ablative Coated Batt Multiple Service Penetrations Wall Seal RWSD-ACB-1101
17 60mm Ablative Coated Batt - Face Fix Multiple Service Penetrations Wall Seal RWSD-ACB-1201
18 60mm Ablative Coated Batt - Head of Wall Head of Wall / Linear Joint Wall Seal RWSD-ACB-1301
19 Single 60mm Ablative Coated Batt - Floor Seal Multiple Service Penetrations Floor Seal RWSD-ACB-1501
20 Firestop Compound Multiple Service Penetrations Floor Seal RWSD-COM-0501
21 Firestop Compound - H&V Pipe Section Pipe Penetrations Floor Seal RWSD-COM-0503
22 Firestop Compound - Sleeved Services Pipe Penetrations Floor Seal RWSD-COM-0510
23 High Strength Compound Multiple Service Penetrations Wall Seal RWSD-COM-1001
24 High Strength Compound Multiple Service Penetrations Floor Seal RWSD-COM-1510
25 High Strength Compound Cable Penetrations Floor Seal RWSD-COM-1511
26 SoftSeal - 100mm Wall Multiple Service Penetrations Wall Seal RWSD-SS-0001
27 SoftSeal - Masonry Wall Multiple Service Penetrations Wall Seal RWSD-SS-0002
28 SoftSeal - 100mm Wall Pipe Penetrations Wall Seal RWSD-SS-0003
29 SoftSeal - Deflection Head with Double 50mm Ablative Coated Batt Multiple Service Penetrations Wall Seal RWSD-SS-0010
30 SoftSeal Linear Joint Floor Seal RWSD-SS-0101
31 Pipe Collar CE - 100mm Wall Pipe Penetrations Wall Seal RWSD-COL-0001
32 Pipe Collar CE - Double 50mm Ablative Coated Batt Pipe Penetrations Wall Seal RWSD-COL-0002
33 Pipe Collar CE - 50mm Ablative Coated Batt - Face Fix Pipe Penetrations Wall Seal RWSD-COL-0003
34 Pipe Collar CE - Single 50mm Ablative Coated Batt - 75mm Wall Pipe Penetrations Wall Seal RWSD-COL-0004
35 Pipe Collar CE - Floor Seal Pipe Penetrations Floor Seal RWSD-COL-0501
36 Pipe Collar CE - Profiled Metal Deck Pipe Penetrations Floor Seal RWSD-COL-0502
37 Pipe Collar CE - Double 50mm Ablative Coated Batt Pipe Penetrations Floor Seal RWSD-COL-0503
38 High Expansion Sealant - 50mm Ablative Coated Batt Pipe Penetrations Wall Seal RWSD-HE-0001
(V10/NOV22) 4
Page FIREPRO® product Application area Orientation of use Drawing no.
39 High Expansion Sealant - Double 50mm Ablative Coated Batt Multiple Service Penetrations Wall Seal RWSD-HE-0050
40 High Expansion Sealant - Sleeved CPVC Pipes Pipe Penetrations Wall Seal RWSD-HE-0051
41 High Expansion Sealant - CPVC Pipes Pipe Penetrations Wall Seal RWSD-HE-0054
42 High Expansion Sealant - 100mm Wall Pipe Penetrations Wall Seal RWSD-HE-0102
43 High Expansion Sealant - 120mm Wall Pipe Penetrations Wall Seal RWSD-HE-0103
44 High Expansion Sealant - 75mm Wall Conduits Wall Seal RWSD-HE-0110
45 High Expansion Sealant - 75mm Wall Pipe Penetrations / Conduits Wall Seal RWSD-HE-0111
46 High Expansion Sealant - Double 50mm Ablative Coated Batt Multiple Service Penetrations Floor Seal RWSD-HE-0501
47 High Expansion Sealant - 150mm Floor Sealed Both Side Multiple Service Penetrations Floor Seal RWSD-HE-0601
48 High Expansion Sealant - 150mm Floor Sealed Top Side Multiple Service Penetrations Floor Seal RWSD-HE-0602
49 Insulated Fire Sleeve - Ablative Coated Batt Seals Pipe Penetrations Wall Seal RWSD-IFS-0001
50 Insulated Fire Sleeve - Ablative Coated Batt Single Sided Pipe Penetrations Wall Seal RWSD-IFS-0002
51 Insulated Fire Sleeve - Angled Pipes (SoftSeal) Pipe Penetrations Wall Seal RWSD-IFS-0003
52 Insulated Fire Sleeve - Flexible Walls Pipe Penetrations Wall Seal RWSD-IFS-0101
53 Insulated Fire Sleeve - Double 50mm Ablative Coated Batt Pipe Penetrations Floor Seal RWSD-IFS-0501
54 Insulated Fire Sleeve - 150mm Floor Pipe Penetrations Floor Seal RWSD-IFS-0601
55 Oval Insulated Fire Sleeve -Flexible Wall / Softseal Oval Duct Penetrations Wall Seal RWSD-IFS-1003
56 Pipe Wrap CE - 100mm Wall Pipe Penetrations Wall Seal RWSD-PW-0001
57 Pipe Wrap CE - 150mm Floor Pipe Penetrations Floor Seal RWSD-PW-0501
58 Pipe Wrap Roll - Double 50mm Ablative Coated Batt Pipe Penetrations Wall Seal RWSD-PWR-0001
59 Pipe Wrap Roll - Double 50mm Ablative Coated Batt Insulated Pipe Penetrations Wall Seal RWSD-PWR-0002
60 Pipe Wrap Roll - Face Fix 50mm Ablative Coated Batt Insulated Pipe Penetrations Wall Seal RWSD-PWR-0101
61 Pipe Wrap Roll - 100mm Wall Pipe Penetrations Wall Seal RWSD-PWR-0201
62 Pipe Wrap Roll - 150mm Floor Pipe Penetrations Floor Seal RWSD-PWR-0502
63 Acoustic Intumescent Sealant Linear Joint Seals Wall & Floor Seals RWSD-AIS-0001
64 Acoustic Intumescent Sealant - 75mm Wall Sleeved Services / Cables Wall Seal RWSD-AIS-0101
65 Acoustic Intumescent Sealant - 75mm Wall Cable Penetrations Wall Seal RWSD-AIS-0110
66 Acoustic Intumescent Sealant - 75mm Wall Pipe Penetrations Wall Seal RWSD-AIS-0120
67 Acoustic Intumescent Sealant - 100mm Wall Cable Penetrations Wall seal RWSD-AIS-0210
68 Acoustic Intumescent Sealant - 100mm Wall Cables / Pipe Penetrations Wall Seal RWSD-AIS-0220
69 Acoustic Intumescent Sealant - 100mm Wall H&V Lagged Pipe Penetrations Wall Seal RWSD-AIS-0221
70 Acoustic Intumescent Sealant - Masonry Wall Sleeved Services Pipes Wall Seal RWSD-AIS-0301
71 Ablative Coated Batt with EZ Path EZ Path Cable Transit Wall Seal RWSD-EZP-0001
72 Ablative Coated Batt with EZ Path & Cover Plate EZ Path Cable Transit Wall Seal RWSD-EZP-0002
73 Firestop Compound with EZ Path EZ Path Cable Transit Floor Seal RWSD-EZP-0501
74 Linear & Trapezoidal Fire Stops Linear Joint Seals Wall Seal RWSD-LTF-0001
75 SP Firestop Systems Linear Joint Seal Wall & Floor Seal RWSD-SP-0001
76 SP Firestop Systems - Masonry Support Angle Penetration Linear Joint Seal Floor Seal RWSD-SP-0101
77 SP Firestop Systems SP Plus Penetrations Linear Joint Seal - Pipe Penetrations Floor Seal RWSD-SP-0102
5
ROCKWOOL® Fire Stopping Guide
1. ROCKWOOL will not support the mixing of different fire protection manufacturers systems/products of any type in line with ASFP
recommendations (ASFP Advisory Note 6), unless proven by fire testing at an accredited fire test laboratory.
2. ROCKWOOL products should be installed in accordance with the relevant product data sheet and within the field of application identified
within the standard details. For applications that fall outside of the parameters identified in the standard details or data sheets please contact
ROCKWOOL for further guidance.
3. Some on-site applications may be outside the scope of the standard detail pack. Please contact ROCKWOOL in these instances as we may be
able to offer a manufacturer technical evaluation. Technical evaluations are an appraisal of the likely performance of the installed ROCKWOOL
products in that application when subjected to a fire resistance test. They are offered in lieu of direct formal testing and are based upon
ROCKWOOL’s experiences of product performance during fire resistance testing. For this reason, before installation, technical evaluations
used on-site should be reviewed and accepted by Building Control and/or the scheme Fire Officer or the overseeing body for the project.
ROCKWOOL have adopted the processes outlined in the PFPF guide to manage the conflict of interest inherent with a manufacturers technical
evaluation compared to an assessment developed by UKAS accredited third party, allowing for a clear a rigorous examination of the proposal
by the approving body
4. All openings for penetrations within the dry lining system shall be framed and lined. As a reflection of the fire test standard, all partitions are
based upon single-skin, or double-skin flexible wall constructions. Shaft walls are not covered by standard flexible wall constructions and
should be treated independently. For the interchangeability of tested wall types please refer to ASFP Advisory Note 15. Face-fix options, with
ROCKWOOL Ablative Coated Batt, are available, but please check for its suitability against the site conditions.
5. For solutions in sandwich panel or composite wall constructions please contact ROCKWOOL technical.
6. Design of the opening for penetrations, and its fire stopping, should correspond to the integrity and insulation requirements of the host wall or
floor, unless leniency on the insulation rating is provided by the fire officer or overseeing body via a derogation.
7. Under the CPR it is a requirement that fire dampers are CE marked and as such that they are installed (and fire stopped) in line with the
relevant damper manufacturer’s installation guides. Damper manufacturers can now provide a tested fire stopping solution for sealing
around their damper systems. Therefore, ROCKWOOL’s default position is to guide the Client and/or Installer to contact the relevant damper
manufacturer for its tested and certified fire stopping solution.
8. Services of different types can pass through the same penetration seal, with the exception of ducts and dampers which should pass exclusively
through its own opening, as per the EN test guidance. Where services of different types pass through the same opening (i.e. a duct passes
through the same opening as a pipe) please contact ROCKWOOL.
9. Service support positions should be installed as a reflection of the fire test as per industry and ASFP guidance (ASFP Advisory Note 8). Support
for services passing through walls should be within 400mm on each side. Services passing through floors should be supported above the floor.
10. With reference to penetration spacings, please refer to the performance tables within the relevant ROCKWOOL standard detail. If no
dimension is given, for service or aperture separation, then the separation is 100mm in line with BS EN 1366-3:2021.
11. In line with BS EN 1366-3:2021 steel cable carriers, ladders and/or trays can be any width. Please refer to the relevant standard detail for the
limiting performance of cable trays, ladders and cables.
(V10/NOV22) 6
SINGLE 50MM ABALTIVE COATED BATT 100MM WALL
Classification Spacing
Service type Substrate Seal Service treatment Identical
Integrity Insulation Aperture
Services
Bl ank seal ≤ 1200 x 1200 60 60 N/A N/A
Electrical cables ≤ Ø ≤15mm 60 60 55mm 0mm
Ø 16mm - 21mm 60 30 55mm 0mm
Ø 22mm - 50mm 60 60 55mm 0mm
Ø 51mm - 80mm 60 30 0mm 0mm
Electrical cables Ø 16mm - 21mm
Additional pattress to both 60 60 55mm 0mm
faces
Ø 51mm - 80mm 60 60 0mm 0mm
Cabl e tray ≤ 500mm (w) x 60mm (h) x 100mm Flexible 1no, 50mm
60 30 55mm 0mm
1.5mm (t) Wall Construction Abl ative
Cable ladder ≤ 350mm (w) x 125mm (d) x or Masonry Wal l Coated Batt
60 60 0mm 0mm
1.5mm (t)
Tel ecomm cabl es ≤ Ø 100mm bundle 60 60 55mm 0mm
Unsheathed cables ≤ Ø 24mm 60 30 55mm 0mm
Steel or copper conduits ≤ Ø 16mm 60 - 55mm 0mm
Plastic conduits ≤ Ø 16mm 60 30 55mm 0mm
Steel pipe ≤ 219mm 1000mm length of 25mm H&V 60 60 0mm 0mm
Copper pipe ≤ 159mm pipe section (L/S) 60 60 0mm 0mm
Copper & Steel pipes ≤ 159mm 60 - 0mm 100mm
(V10/NOV22) 7
SINGLE 50MM ABALTIVE COATED BATT 75MM WALL - PIPE PENETRATIONS
Classification Spacing
Service type Substrate Seal Service Treatment
Identical
Integrity Insulation Aperture
Services
Bl ank seal ≤ 1200 x 1200 30 30 N/A N/A
N/A
≤ 600 x 900 60 60 N/A N/A
Steel pipe ≤ 219mm 60 60 0mm 0mm
Copper pipe ≤ 159mm 75mm thick flexible wall 1000mm length of 25mm H&V pipe
50mm Ablative Coated Batt 60 60 0mm 0mm
construction section L/S
Copper pipe ≤ 42mm 60 60 0mm 0mm
Copper & Steel pipe ≤ 159mm N/A 60 - 0mm 100mm
CPVC ≤ 73mm x 11mm High Expansion Sealant 20mm annular -
60 60 40mm 70mm
full depth (50mm)
SINGLE 50MM ABALTIVE COATED BATT 75MM WALL - CABLES
Electrical cables ≤ Ø ≤21mm 30 30 0mm 0mm
≤ Ø 22-50mm 30 30 0mm 0mm
≤ Ø 51 - 80mm 30 30 0mm 0mm
Perforated Tray ≤ 500mm (w) x 25mm (d) x
30 30 0mm 0mm
1.0mm (t)
Cable ladder ≤ 350mm (w) x 125mm (d) x N/A 30 30 0mm 0mm
1.5mm (t)
Tel ecomm cabl es ≤ Ø 100mm bundle 75mm thick flexible wall
50mm Ablative Coated Batt 30 30 0mm 0mm
construction
Unsheathed cables ≤ Ø 24mm 30 30 0mm 0mm
PVC conduits ≤ Ø 16mm 30 30 0mm 0mm
Copper Conduits ≤ Ø 16mm 30 - 0mm 0mm
Steel Trunking ≤ 150mm x 150mm 60 60 0mm 100mm
300mm length full depth RWA45 (45
≤ 300mm x 150mm kg/m3) stonewool positioned centrally
to the seal 60 30 0mm 100mm
(V10/NOV22) 8
DOUBLE 50MM ABALTIVE COATED BATT 100MM WALL - NON COMBUSTIBLE PIPES
Classification Spacing
Service type Substrate Seal Service Treatment Identical
Integrity Insulation Aperture
Services
Bl ank seal ≤ 1200 x 900 100mm Flexible Wall 120 120 N/A N/A
Construction or Masonry
≤ 2600 x 2600 N/A 90 90 N/A N/A
Wal l
≤ 1100 x 1100 150mm Masonry Wall 120 120 N/A N/A
Steel pipe ≤ 168mm 1000mm length of 40mm H&V 120 120 0mm 0mm
Copper pipe ≤ 108mm pipe section L/S 120 120 0mm 0mm
≤ 168mm
Steel pipe 100mm Flexible Wall 120 90 0mm 0mm
Construction or Masonry 2 No. 50mm
1000mm length of 25mm H&V
≤ 108mm Abl ative Coated
Copper pipe Wal l pipe section L/S 120 90 0mm 0mm
Batts
Copper pipe ≤ 42 120 120 100mm 100mm
Steel pipes ≤ 219mm N/A 120 15 0mm 100mm
Steel pipe ≤ 610mm 1000mm length of 40mm H&V
180 60 0mm 100mm
pipe section L/S
Steel pipe ≤ 610mm 100mm Masonry Wall
N/A 180 15 0mm 100mm
Construction
Steel pipe ≤ 324mm 300mm length of Ablative Liquid 120 45 100mm 100mm
Copper pipe ≤ 159mm 2mm DFT (L/S) 120 15 100mm 100mm
DOUBLE 50MM ABALTIVE COATED BATT 100MM WALL - CABLES
Electrical cables ≤ Ø ≤21mm 120 90 0mm 0mm
≤ Ø 22-50mm 120 60 0mm 0mm
≤ Ø 51 - 80mm 90 60 0mm 0mm
Perforated Tray ≤ 500mm (w) x 60mm (d) x
1.0mm (t) 120 90 0mm 0mm
(V10/NOV22) 9
DOUBLE 50MM ABALTIVE COATED BATT 100MM WALL - SINGLE SIDED INSTALL
Classi fi cati on Spacing
Servi ce type Substrate Seal Servi ce Treatment Identical
Integrity Insulation Aperture
Servi ces
Blank seal ≤ 1200 x 600 120 90 N/A N/A
Electrical cables ≤ Ø ≤21mm 120 60 0mm 0mm
≤ Ø 22-50mm 120 60 0mm 0mm
≤ Ø 51 - 80mm 90 60 0mm 0mm
Perforated Tray ≤ 500 x 60 x 1.0mm 120 60 0mm 0mm
Cable ladder ≤ 350mm (w) x 125mm (d)
N/A 90 90 0mm 0mm
x 1.5mm (t)
Telecomm cables ≤ Ø 100mm bundle 120 90 0mm 0mm
Unsheathed cables ≤ Ø 24mm 120 45 0mm 0mm
PVC conduits ≤ Ø 16mm
120 90 0mm 0mm
Copper ≤ 108mm 100mm Flexible Wall 2 No. 50mm Ablative 120 90 0mm 0mm
Construction or Coated Batts (Single
Masonry Wall sided install) 1000mm length of 40mm H&V pipe
Copper ≤ 108mm 120 120 0mm 0mm
secti on C/S
(V10/NOV22)
Soli d Tray
≤ Ø 51 - 80mm
500
120
120
60
60
0mm
0mm 10
Perforated Tray ≤ 500 x 25 x 1.0mm 100mm Flexible Wall 120 60 0mm
2 No. 50mm ablative
Cable ladder ≤ 350mm (w) x 125mm (d) Construction or N/A
Coated Batts 120 90 0mm
x 1.5mm (t) Masonry Wall
Telecomm cables ≤ Ø 100mm bundle 120 90 0mm
Unsheathed cables ≤ Ø 24mm 120 60 0mm
DOUBLE 50MM ABALTIVE COATED BATT SINGLE SKIN 100MM WALL - NON COMBUSTIBLE PIPES
DOUBLE 50MM ABALTIVE COATED BATT SINGLE SKIN 100MM WALL - CABLES
Electrical cables ≤ Ø ≤21mm 60 60 0mm 0mm
≤ Ø 22-50mm 60 60 0mm 0mm
≤ Ø 51 - 80mm 60 60 0mm 0mm
Perforated Tray ≤ 500mm (w) x 25mm (d) x 1.0mm
(t) 60 60 0mm 0mm
(V10/NOV22) 11
(V10/NOV22) 12
DOUBLE 50MM ABALTIVE COATED BATT FACE FIX
Classification Spacing
Service type Substrate Seal Service Treatment
Integrity Insulation Aperture Identical Services
Blank seal ≤ 1000 x 1000 120 120 N/A N/A
Electrical cables ≤ Ø ≤21mm 120 90 0mm 0mm
≤ Ø 22-50mm 120 60 0mm 0mm
≤ Ø 51 - 80mm 90 60 0mm 0mm
Perforated Tray ≤ 500 mm (w) x 25mm (h) x
120 90 0mm 0mm
1.0mm (t)
N/A
Cable ladder ≤ 350mm (w) x 125mm (d) x
90 90 0mm 0mm
1.5mm (t)
Telecomm cables ≤ Ø 100mm bundle 120 90 0mm 0mm
Unsheathed cables ≤ Ø 24mm 120 45 0mm 0mm
PVC conduits ≤ Ø 16mm 120 90 0mm 0mm
Copper Conduits ≤ Ø 16mm 120 15 0mm 0mm
Electrical cables ≤ Ø ≤80mm 120 120 100mm 0mm
Cable tray ≤ 500mm (w) x 60mm (h) x 100mm Flexible Wall
120 120 100mm 0mm
1.5mm (t) Construction or Masonry
Cable ladder ≤ 350mm (w) x 125mm (d) x Wall 40mm thick 45kg/m3 120 120 100mm 0mm
1.5mm (t) stonewool lagging
Telecomm cables ≤ Ø 100mm bundle 2 No. 50mm Ablative (RWA45) L/I 300mm 120 120 100mm 0mm
Steel or copper conduits ≤ Ø 16mm Coated Batts Face Fixed 120 120 100mm 0mm
Plastic conduits ≤ Ø 16mm 120 120 100mm 0mm
Unsheathed cables ≤ Ø 24mm 120 120 100mm 0mm
Steel pipe ≤ 168mm 120 120 0mm 0mm
1000mm length of 40mm
Copper pipe ≤ 108mm H&V pipe section L/S 120 120 0mm 0mm
Steel pipes ≤ 219mm N/A 120 15 0mm 0mm
Steel pipe ≤ 168mm 90 60 0mm 0mm
≤ 108mm 1000mm length of 25mm
Copper pipe 90 30 0mm 0mm
H&V pipe section L/S
Copper pipe ≤ 42 120 120 100mm 100mm
Steel pipe ≤ 610mm
1000mm length of 40mm
180 60 0mm 100mm
H&V pipe section L/S
Steel pipe ≤ 610mm 100mm Masonry Wall
N/A 180 15 0mm 100mm
Construction
Steel pipe ≤ 324mm 120 45 100mm 100mm
300mm length of Ablative
Copper pipe ≤ 159mm Liquid 2mm DFT (L/S) 120 20 100mm 100mm
(V10/NOV22) 13
DOUBLE 50MM ABALTIVE COATED BATT 150MM FLOOR
Classification Spacing
Service type Substrate Seal Service treatment Identical
Integrity Insulation Aperture
Services
Blank seal ≤ 1600 x 1100
120 120 N/A N/A
Electrical cables ≤ Ø ≤15mm 120 90 60mm 0mm
Ø 16mm - 21mm 120 30 60mm 0mm
Ø 22mm - 50mm 120 30 60mm 0mm
Ø 51mm - 80mm 120 30 60mm 0mm
Cable tray ≤ 500mm (w) x 60mm (h) x 1.5mm N/A
120 60 60mm 0mm
(t)
Cable ladder ≤ 350mm (w) x 125mm (d) x
120 60 60mm 0mm
1.5mm (t)
Telecomm cables ≤ Ø 100mm bundle 120 120 60mm 0mm
Steel or copper conduits ≤ Ø 16mm 120 - 60mm 0mm
Plastic conduits ≤ Ø 16mm 2no, 50mm Ablative 120 90 60mm 0mm
Electrical cables Ø ≤15mm Coated Batt 120 120 60mm 0mm
Ø 16mm - 80mm 150mm Concrete 120 60 60mm 0mm
Cable tray ≤ 500mm (w) x 60mm (h) x 1.5mm Floor (800 kg/m3)
Additional 50mm pattress to both faces 120 90 60mm 0mm
(t)
of batt
Cable ladder ≤ 350mm (w) x 125mm (d) x
120 90 60mm 0mm
1.5mm (t)
Unsheathed cables ≤ Ø 17mm 120 90 60mm 0mm
Copper or steel pipe ≤ Ø 42mm 120 120 0mm 0mm
Copper or steel pipe ≤ Ø 108mm 25mm thick H&V pipe section 1000mm 120 120 0mm 0mm
Steel pipe ≤ Ø 168mm length L/S 120 120 0mm 0mm
Steel pipe ≤ Ø 219mm 120 90 0mm 100mm
Steel pipe ≤ Ø 219mm 40mm thick H&V pipe section 1000mm
120 120 0mm 100mm
length L/S
Steel or Copper pipe ≤ 42mm 40mm thick 40 Kg/m3 stonewool
**700mm x 1100mm
(RWA45) lagging 300mm both sides of 120 120 100mm 100mm
Max void**
seal L/I
(V10/NOV22) 14
SINGLE 60MM ABALTIVE COATED BATT 100MM WALL
Classi fi cati on Spacing
Servi ce type Substrate Seal Servi ce treatment Identical
Integrity Insulation Aperture
Servi ces
Blank seal ≤ 1200mm x 600mm 100mm Flexible Wall N/A 120 120 N/A N/A
≤ 2.6m x 2.6m Construction or N/A 120 90 N/A N/A
≤ 1200 x 1200 Masonry Wall N/A 60 60 N/A N/A
Electrical cables ≤ Ø ≤21mm N/A 120 60 0mm 0mm
Ø 22mm - 50mm N/A 120 60 0mm 0mm
Ø 51mm - 80mm N/A 60 60 0mm 0mm
150mm masonry wall
Telecomm cables ≤ Ø 100mm bundle N/A 60 60 0mm 0mm
Cable ladder ≤ 350mm (w) x 125mm (d) x
N/A 120 60 0mm 0mm
1.5mm (t)
Electrical cables ≤ Ø ≤21mm N/A 90 60 0mm 0mm
Ø 22mm - 50mm N/A 60 60 55mm 0mm
Ø 51mm - 80mm N/A 60 30 0mm 0mm
Ø 51mm - 80mm
Additional pattress to both faces 60 60 0mm 0mm
Cable tray ≤ 500mm (w) x 60mm (h) x 1no, 60mm Ablative
Coated Batt N/A 60 30 0mm 0mm
1.5mm (t)
Cable ladder ≤ 350mm (w) x 125mm (d) x N/A 60 30 0mm 0mm
Telecomm cables ≤ Ø 100mm bundle N/A 60 30 0mm 0mm
Unsheathed cables ≤ Ø 24mm 100mm Flexible Wall N/A 60 30 0mm 0mm
Steel or copper conduits ≤ Ø 16mm Construction or N/A 90 - 0mm 0mm
Plastic conduits ≤ Ø 16mm Masonry Wall N/A 90 60 0mm 0mm
Steel trunking ≤ 300mm x 150mm x 1mm
(Small cables ≤ 21mm or 300mm length of 45Kg/m3
100mm bundle) stonewool (RWA45) positioned 120 30 100mm 100mm
centrally to the seal
(V10/NOV22) 15
DOUBLE 60MM ABALTIVE COATED BATT 120MM WALL - NON COMBUSTIBLE PIPES
Classification Spacing
Service type Substrate Seal Service Treatment Identical
Integrity Insulation Aperture
Services
Bl ank seal ≤ 1200 x 900 100mm Flexible 120 120 N/A N/A
≤ 2600 x 2600 Wal l 90 90 N/A N/A
N/A
≤ 1100 x 1100 150mm Masonry
120 120 N/A N/A
Wal l
Steel pipe ≤ 168mm 1000mm length of 120 120 0mm 0mm
Copper pipe ≤ 108mm 100mm Flexible 40mm H&V pipe 120 120 0mm 0mm
Steel pipe ≤ 168mm Wal l 1000mm length of 90 60 0mm 0mm
Copper pipe ≤ 108mm Construction or 2 No. 60mm 25mm H&V pipe 90 30 0mm 0mm
Copper pipe ≤ 42 Masonry Wal l abl ative Coated section L/S 120 120 100mm 100mm
Batts
Steel pipes ≤ 219mm N/A 120 15 0mm 100mm
Steel pipe ≤ 610mm 1000mm length of
40mm H&V pipe 120 60 0mm 100mm
100mm Masonry
section L/S
Wal l
Steel pipe ≤ 610mm Construction N/A 120 15 0mm 100mm
Steel pipe ≤ 324mm 300mm length of 120 45 100mm 100mm
Copper pipe ≤ 159mm Ablative Liquid 2mm 120 15 100mm 100mm
DOUBLE 60MM ABALTIVE COATED BATT 120MM WALL - CABLES
Electrical cables ≤ Ø ≤21mm 120 90 0mm 0mm
≤ Ø 22-50mm 120 60 0mm 0mm
≤ Ø 51 - 80mm 90 60 0mm 0mm
Perforated Tray ≤ 500 x 25 x 1.0mm 100mm Flexible 120 90 0mm 0mm
Cable ladder ≤ 350mm (w) x 125mm (d) Wal l
x 1.5mm (t) N/A 90 90 0mm 0mm
Construction or
Tel ecomm cabl es ≤ Ø 100mm bundle Masonry Wal l 120 90 0mm 0mm
Unsheathed cables ≤ Ø 24mm 120 45 0mm 0mm
PVC conduits ≤ Ø 16mm 2 No. 60mm 120 90 0mm 0mm
Copper Conduits ≤ Ø 16mm abl ative Coated 120 15 0mm 0mm
Electrical cables ≤ Ø ≤21mm Batts 120 120 100mm 0mm
≤ Ø 22mm - 80mm 120 90 100mm 0mm
Cabl e tray ≤ 500mm (w) x 60mm (h) x
1.5mm (t) 40mm thick 45kg/m3 120 120 100mm 0mm
150mm Masonry
stonewool l agging
Cable ladder ≤ 350mm (w) x 125mm (d) Wal l
(RWA45) L/I 300mm 120 120 100mm 0mm
x 1.5mm (t)
Tel ecomm cabl es ≤ Ø 100mm bundle 120 120 100mm 0mm
Unsheathed cables ≤ Ø 24mm 120 120 100mm 0mm
(V10/NOV22) 16
DOUBLE 60MM ABALTIVE COATED BATT FACE FIX
Classification Spacing
Service type Substrate Seal Service Treatment Identical
Integrity Insulation Aperture
Services
Blank seal ≤ 1000 x 1000 120 120 N/A N/A
Electrical cables ≤ Ø ≤21mm 120 90 0mm 0mm
≤ Ø 22-50mm 120 60 0mm 0mm
≤ Ø 51 - 80mm 90 60 0mm 0mm
Perforated Tray ≤ 500 mm (w) x 25mm (h) x
120 90 0mm 0mm
1.0mm (t)
N/A
Cable ladder ≤ 350mm (w) x 125mm (d)
90 90 0mm 0mm
x 1.5mm (t)
Telecomm cables ≤ Ø 100mm bundle 120 90 0mm 0mm
Unsheathed cables ≤ Ø 24mm 120 45 0mm 0mm
PVC conduits ≤ Ø 16mm 120 90 0mm 0mm
Copper Conduits ≤ Ø 16mm 120 15 0mm 0mm
Electrical cables ≤ Ø ≤80mm 120 120 100mm 0mm
Cable tray ≤ 500mm (w) x 60mm (h) x
100mm Flexible Wall 120 120 100mm 0mm
1.5mm (t)
Construction or
Cable ladder ≤ 350mm (w) x 125mm (d) 40mm thick 45kg/m3
Masonry Wall 120 120 100mm 0mm
x 1.5mm (t) stonewool lagging (RWA45)
Telecomm cables ≤ Ø 100mm bundle L/I 300mm 120 120 100mm 0mm
Steel or copper conduits ≤ Ø 16mm 2 No. 60mm Ablative 120 120 100mm 0mm
Plastic conduits ≤ Ø 16mm Coated Batts Face Fixed
120 120 100mm 0mm
Unsheathed cables ≤ Ø 24mm 120 120 100mm 0mm
≤ 168mm
Steel pipe 120 120 0mm 0mm
1000mm length of 40mm
≤ 108mm H&V pipe section L/S
Copper pipe 120 120 0mm 0mm
Steel pipe ≤ 610mm 100mm Masonry Wall N/A 180 15 0mm 100mm
Construction
Steel pipe ≤ 324mm 120 45 100mm 100mm
Copper pipe ≤ 159mm 300mm length of Ablative
Liquid 2mm DFT (L/S) 120 20 100mm 100mm
(V10/NOV22) 17
(V10/NOV22) 18
SINGLE 60MM ABALTIVE COATED BATT 150MM FLOOR
Classification Spacing
Service type Substrate Seal Service treatment Identical
Integrity Insulation Aperture
Services
Blank seal ≤ 1200 x 600 240 120 N/A N/A
Steel pipe ≤ 168mm 1no, 60mm 240 - 100mm 100mm
150mm Concrete
Copper pipe ≤ 108mm Ablative 240 - 100mm 100mm
Floor (800 kg/m3)
Steel pipe ≤ 168mm Coated Batt 40mm thick H&V pipe section 240 120 100mm 100mm
Copper pipe ≤ 108mm L/I & L/S 240 120 100mm 100mm
(V10/NOV22) 19
60 Minutes 90 Minutes 120 Minutes 240 Minutes
Service type
Integrity Insulation Integrity Insulation Integrity Insulation Integrity Insulation
75mm Blank seal up to 500 mm x 500 mm* ü ü ü ü ü ü
100mm Blank seal up to 750 mm x 750 mm* ü ü ü ü ü ü ü ü
75mm Seal with services no reinforcement - 500mm x any length* ü ü ü ü ü ü
100mm Seal with services, Simply Reinforced - 1500mm x any length* ü ü ü ü ü ü ü ü
Cable Tray ≤ 500mm x 50mm ü ü ü ü ü ü
Bunched cables ≤100 mm ü ü ü ü
Electrical cables up to 21mm ü ü ü ü ü ü
Electrical cables 21mm - 50mm ü ü ü ü ü
Electrical cables 51mm - 80mm ü ü ü ü
Steel pipes ≤165 Unlagged ü ü ü ü
Steel pipes ≤165 lagged with Fire Tube ü ü ü ü ü ü ü
Copper pipes ≤ 108 mm lagged with Fire Tube ü ü ü ü ü ü ü
Copper pipes ≤ 108 mm unlagged ü ü ü ü
≤160mm PVC, uPVC, PP, MDPE & HDPE pipe Rockwool Pipe Wrap ü ü ü ü ü ü
* Load bearing performance in line with BS6399 for workspaces and cupboards
(V10/NOV22) 20
Service Substrate Supporting Performance
Penetration Type/Size (mm) Formation Insulation Thickness (mm) Seal
Separation Separation construction Integrity Insulation
Copper 42 150mm thick 240 120
40mm H&V pipe lagging - 500mm to top 100mm thick ROCKWOOL Standard 0mm 0mm
Copper 43 - 159 Cluster AAC concrete 120 45
of slab only Compound (From lagging) (From lagging)
Steel < 219 slab (650 kg/m³) 240 120
(V10/NOV22) 21
Penetration Type/Size Service Substrate Supporting Performance
Formation Insulation Thickness (mm) Seal
(mm) Separation Separation construction Integrity Insulation
40mm H&V pipe section -
0mm 0mm 150mm thick AAC
Steel < 219 Single 1000mm length through the 100mm thick ROCKWOOL 120 120
(Between (Between concrete slab (650
seal (L/S) Standard Compound
sleeves) sleeves) kg/m³)
Steel < 219 Single N/A 120 15
(V10/NOV22) 22
HIGH STRENGTH COMPOUND 150MM THICK
Classification Spacing
Service type Substrate Seal Service treatment Identical
Integrity Insulation Aperture
Services
Bl ank seal ≤ 2.6m x 2.6m***
240 240 N/A N/A
150mm thick
150mm thick masonry
Copper pipe ≤ 42 High Strength 240 240 0mm 0mm
wal l 1000mm length of
Copper Pipe ≤ 108mm Compound 240 240 0mm 0mm
25mm H&V pipe
Steel pipe ≤ 168mm 240 240 0mm 0mm
section L/S
Steel pipe ≤ 219mm 240 240 0mm 0mm
HIGH STRNEGTH COMPOUND 150MM THICK - CABLES
Electrical cables ≤ Ø 21mm 240 120 0mm N/A
Ø 22mm - 50mm 240 120 0mm N/A
Ø 51mm - 80mm 240 120 0mm N/A
Cabl e tray ≤ 500mm (w) x 60mm (h) x
240 240 0mm N/A
1.5mm (t) 150mm thick
150mm thick masonry
Cable ladder ≤ 350mm (w) x 125mm (d) x High Strength N/A
wal l 240 120 0mm N/A
1.5mm (t) Compound
Tel ecomm cabl es ≤ Ø 100mm bundle 240 120 0mm N/A
Unsheathed cables ≤ Ø 24mm 240 60 0mm N/A
Steel or copper conduits ≤ Ø 16mm 240 240 0mm N/A
Plastic conduits ≤ Ø 16mm 240 180 0mm N/A
(V10/NOV22) 23
RIGID FLOOR - HIGH STRENGTH COMPOUND
Classification Spacing
Service type Substrate Seal Size Seal Service treatment
Integrity Insulation Aperture Services
Copper pipe ≤ Ø 107mm (1.5 - 14.2mm wall thickness) 50mm thick Rocklap H&V Pipe
Section, min. 500mm length to 60 15 100 100
topside of seal
Steel pipe ≤ Ø 115mm (3.5 - 14.2mm wall thickness) 50mm thick Rocklap H&V Pipe 120 120
100 100
Ø 116 - 160mm (5 - 14.2mm wall thickness) Section, min. 500mm length to 120 90
Electrical cables ≤ Ø 21mm 100mm thick 25mm thick Duct Wrap insulation,
Ø 22mm - 50mm 150mm thick Max. 1800mm min. 500mm l ength to topside of 120 60 100 100
High Strength
Ø 51mm - 80mm rigid floor x 1800mm seal
Compound
Unsheathed cables ≤ Ø 24mm
25mm thick Duct Wrap insulation,
min. 500mm l ength to topside of 120 120 100 100
seal
(V10/NOV22) 24
RIGID FLOOR - HIGH STRENGTH COMPOUND WITH UPSTAND
Service Classification Spacing
Service type Substrate Seal Size Seal
treatment Integrity Insulation Aperture Services
Telecomm cables ≤ Ø 100mm bundle 100mm thick
High Strength 25mm thick
Compound Duct Wrap
150mm thick Max. 1800mm with 50mm insulation,
120 120 100 100
rigid floor x 1800mm thick High min. 500mm
Strength length to
Compound topside of seal
upstand
(V10/NOV22) 25
TABLE TO BE UPDATED WHEN NEW ASSESSMENT COMPLETED
(V10/NOV22) 26
TABLE TO BE UPDATED WHEN NEW ASSESSMENT COMPLETED
(V10/NOV22) 27
(V10/NOV22) 28
DOUBLE 50MM ABALTIVE COATED BATT SOFTSEAL DEFLECTION HEAD 100MM WALL - NON COMBUSTIBLE PIPES
Classification Spacing
Service type Substrate Seal Service Treatment Identical
Integrity Insulation Aperture
Services
Blank seal ≤ 600 x 900
120 120 N/A N/A
N/A
≤ 1200 x 1200
120 90 N/A N/A
(V10/NOV22) 29
(V10/NOV22) 30
Flexible / rigid wall
Test Service separation
Service type (min. 100mm thick)
Standard
Integrity Insulation Aperture Services
PVC pipes Ø 32 - 50mm (1.8mm wall thickness) wall
Ø 55 - 63mm (2.3 - 3mm wall thickness)
Ø 75 - 82mm (3.1 - 4.8mm wall thickness)
Ø 90 - 110mm (4.2 - 7.4mm wall thickness) 120 120 EN N/A 200mm
Ø 125mm (6mm wall thickness)
Ø 140mm (6.1 - 7.5mm wall thickness)
Ø 160mm (6.2 - 9.5mm wall thickness)
PP pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 EN N/A 200mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.5 - 8mm wall thickness)
Ø 160mm (4 - 14.6mm wall thickness)
PE pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 EN N/A 200mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.9 - 5.8mm wall thickness)
Ø 160mm (4.9 - 9.5mm wall thickness)
(V10/NOV22) 31
Flexible / rigid wall
Test Service separation
Service type (min. 100mm thick)
Standard
Integrity Insulation Aperture Services
PVC pipes Ø 32 - 50mm (1.8mm wall thickness)
Ø 55 - 63mm (2.3 - 3mm wall thickness)
Ø 75 - 82mm (3.1 - 4.8mm wall thickness)
Ø 90 - 110mm (4.2 - 7.4mm wall thickness) 120 120 EN 50mm 0mm
Ø 125mm (6mm wall thickness)
Ø 140mm (6.1 - 7.5mm wall thickness)
Ø 160mm (6.2 - 9.5mm wall thickness)
PP pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 EN 50mm 0mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.5 - 8mm wall thickness)
Ø 160mm (4 - 14.6mm wall thickness)
PE pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 EN 50mm 0mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.9 - 5.8mm wall thickness)
Ø 160mm (4.9 - 9.5mm wall thickness)
(V10/NOV22) 32
Flexible / rigid wall
Test Service separation
Service type (min. 100mm thick)
Standard
Integrity Insulation Aperture Services
PVC pipes Ø 32 - 50mm (1.8mm wall thickness)
Ø 55 - 63mm (2.3 - 3mm wall thickness)
Ø 75 - 82mm (3.1 - 4.8mm wall thickness)
Ø 90 - 110mm (4.2 - 7.4mm wall thickness) 120 120 EN 50mm 0mm
Ø 125mm (6mm wall thickness)
Ø 140mm (6.1 - 7.5mm wall thickness)
Ø 160mm (6.2 - 9.5mm wall thickness)
PP pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 EN 50mm 0mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.5 - 8mm wall thickness)
Ø 160mm (4 - 14.6mm wall thickness)
PE pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 EN 50mm 0mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.9 - 5.8mm wall thickness)
Ø 160mm (4.9 - 9.5mm wall thickness)
(V10/NOV22) 33
Flexible / rigid wall
Test Service separation
Service type (min. 75mm thick)
Standard
Integrity Insulation Aperture Services
PVC pipes Ø 32 - 50mm (1.8mm wall thickness)
Ø 55 - 63mm (2.3 - 3mm wall thickness)
Ø 75 - 82mm (3.1 - 4.8mm wall thickness) BS EN 1366-
60 60 50mm 0mm
Ø 90 - 110mm (4.2 - 7.4mm wall thickness) 3:2009
Ø 125mm (6mm wall thickness)
Ø 140mm (6.1 - 7.5mm wall thickness)
PP pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
BS EN 1366-
Ø 90 - 110mm (2.7 - 10mm wall thickness) 60 60 50mm 0mm
3:2009
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.5 - 8mm wall thickness)
Ø 160mm (4 - 14.6mm wall thickness)
PE pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
BS EN 1366-
Ø 90 - 110mm (2.7 - 10mm wall thickness) 60 60 50mm 0mm
3:2009
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.9 - 5.8mm wall thickness)
Ø 160mm (4.9 - 9.5mm wall thickness)
(V10/NOV22) 34
Rigid floor
Test Service separation
Service type (min. 150mm thick)
Standard
Integrity Insulation Aperture Services
PVC pipes Ø 32 - 50mm (1.8mm wall thickness)
Ø 55 - 63mm (2.3 - 3mm wall thickness)
Ø 75 - 82mm (3.1 - 4.8mm wall thickness)
Ø 90 - 110mm (4.2 - 7.4mm wall thickness) 240 240 EN N/A 200mm
Ø 125mm (6mm wall thickness)
Ø 140mm (6.1 - 7.5mm wall thickness)
Ø 160mm (6.2 - 9.5mm wall thickness)
PP pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 240 240 EN N/A 200mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.5 - 8mm wall thickness)
Ø 160mm (4 - 14.6mm wall thickness)
PE pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 240 240 EN N/A 200mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.9 - 5.8mm wall thickness)
Ø 160mm (4.9 - 9.5mm wall thickness)
(V10/NOV22) 35
Rigid floor
Test Service separation
Service type (min. 150mm thick)
Standard
Integrity Insulation Aperture Services
PVC pipes Ø 32 - 50mm (1.8mm wall thickness)
Ø 55 - 63mm (2.3 - 3mm wall thickness)
Ø 75 - 82mm (3.1 - 4.8mm wall thickness)
Ø 90 - 110mm (4.2 - 7.4mm wall thickness) 120 120 EN N/A 200mm
Ø 125mm (6mm wall thickness)
Ø 140mm (6.1 - 7.5mm wall thickness)
Ø 160mm (6.2 - 9.5mm wall thickness)
HDPE pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 EN N/A 200mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.9 - 5.8mm wall thickness)
Ø 160mm (4.9 - 9.5mm wall thickness)
PP pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 EN N/A 200mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.5 - 8mm wall thickness)
Ø 160mm (4 - 14.6mm wall thickness)
(V10/NOV22) 36
Rigid floor
Test Service separation
Service type (min. 150mm thick)
Standard
Integrity Insulation Aperture Services
PVC pipes Ø 32 - 50mm (1.8mm wall thickness)
Ø 55 - 63mm (2.3 - 3mm wall thickness)
Ø 75 - 82mm (3.1 - 4.8mm wall thickness)
BS EN 1366-
Ø 90 - 110mm (4.2 - 7.4mm wall thickness) 120 120 0mm 0mm
3:2009
Ø 125mm (6mm wall thickness)
Ø 140mm (6.1 - 7.5mm wall thickness)
Ø 160mm (6.2 - 9.5mm wall thickness)
HDPE pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
BS EN 1366-
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 0mm 0mm
3:2009
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.9 - 5.8mm wall thickness)
Ø 160mm (4.9 - 9.5mm wall thickness)
PP pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
BS EN 1366-
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 0mm 0mm
3:2009
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.5 - 8mm wall thickness)
Ø 160mm (4 - 14.6mm wall thickness)
(V10/NOV22) 37
(V10/NOV22) 38
(V10/NOV22) 39
1) SLEEVED CPVC PIPE - LARGE ANNULAR GAP 2) SLEEVED CPVC PIPE - SMALL ANNULAR GAP ROCKWOOL Standard Detail:
1) SECTION 2) SECTION Supporting Evidence : WF 411297
Flexible wall Flexible wall Refer to Lubrizol / SPEARS CPVC Piping Systems
• min. 100mm thickness • min. 100mm thickness Compatible Product Finder for further information/evidence
• min. 2no. layers of plasterboard • min. 2no. layers of plasterboard
of compatibility.
ROCKWOOL High Expansion Sealant The supporting construction must be capable of achieving
• 20mm annular gap with min 25mm depth both sides of seal ROCKWOOL High Expansion Sealant the required fire rating of the proposed firestop.
cPVC Pipe & Sleeve cPVC Pipe & Sleeve • 20mm annular gap with min 25mm depth both sides of seal
• Ø89mm 150mm long cPVC sleeve • Ø89mm 150mm long cPVC sleeve
• Ø27mm cPVC pipe
24 • Ø60mm cPVC pipe 8 Aperture Size: Max. 600mm wide x 400mm high.
20
ROCKWOOL High Expansion
cPVC Pipe & Sleeve 100 Sealant
• Ø89mm 150mm long cPVC sleeve
• 20mm Annular gap with 100mm depth "fully filled"
• Ø73mm cPVC pipe
(V10/NOV22) 40
(V10/NOV22) 41
(V10/NOV22) 42
(V10/NOV22) 43
63mm Dia. PVC CONDUIT THROUGH 75mm 63mm Dia. PVC CONDUIT THROUGH 75mm ROCKWOOL Standard Detail:
FLEXIBLE WALL FLEXIBLE WALL Supporting Evidence : WF 411460 / WF 411469
EI 60 EI 60 (BS EN 1366-3:2009)
Flexible wall The supporting construction must be capable of achieving
• min. 75mm thick Flexible wall the required fire rating of the proposed firestop.
• min. 1no. board layers • min. 75mm thick
• Fire rated to at least the same fire rating as the firestop seal • min. 1no. board layers
• Fire rated to at least the same fire rating as the firestop seal
Flexible wall constructions must be installed in accordance
ROCKWOOL FIREPRO® High
12.5 Expansion Intumescent Sealant ROCKWOOL FIREPRO® High with the manufacturer's guidelines. The wall construction
20 • 20mm annular Expansion Intumescent Sealant
should be a minimum thickness of 75mm.
• min. 12.5mm depth • 20mm annular
• min. 12.5mm depth All service items should be adequately supported both
sides of the firestop to ensure that no load is transferred
onto the firestop seal.
Cable - Bundle Cable - Single Where possible a 20mm annular gap should be maintained
Note: • max. 8no. telecommunication cables
Note: • telecommunication cable
around the full circumference of the conduit.
Where conduit is tight to
opening point small gaps with PVC sleeve
Where conduit is tight to
opening point small gaps with
PVC sleeve
High Expansion Intumescent • max. Ø 63mm High Expansion Intumescent • max. Ø 63mm Applications in flexible wall constructions can be used in
Sealant Sealant • min. 125mm length
• min. 125mm length
• ROCKWOOL RWA45 packed around cables within sleeve masonry wall constructions.
• ROCKWOOL RWA45 packed around cables within sleeve
• min. 13mm deep ROCKWOOL FIREPRO® Acoustic Intumescent
75 • min. 13mm deep ROCKWOOL FIREPRO® Acoustic Intumescent
Sealant to seal within sleeve
Sealant to seal within sleeve Refer to relevant product datasheet for further installation
guidelines.
ROCKWOOL FIREPRO High ® ROCKWOOL FIREPRO® High
Expansion Intumescent Sealant Expansion Intumescent Sealant These products should only be utilised for applications as
20 • 20mm annular 20 • 20mm annular
• min. 12.5mm depth outlined in the relevant ROCKWOOL product data sheet
Ø83 • min. 12.5mm depth
Ø83 and in accordance with the relevant ROCKWOOL Fire
PVC sleeve PVC sleeve Resistance Testing. Additionally the product must be
• max. Ø 63mm
• max. Ø 63mm installed in accordance with the current ROCKWOOL
Note:
• min. 125mm length
Note: Ø63 • min. 125mm length
• ROCKWOOL RWA45 packed around cables within sleeve Ø63 • ROCKWOOL RWA45 packed around cables within sleeve guidelines.
Where conduit is tight to Where conduit is tight to • min. 13mm deep ROCKWOOL FIREPRO® Acoustic Intumescent
• min. 13mm deep ROCKWOOL FIREPRO® Acoustic Intumescent opening point small gaps with
opening point small gaps with Sealant to seal within sleeve
Sealant to seal within sleeve
High Expansion Intumescent High Expansion Intumescent For further information please visit www.rockwool.co.uk or
Sealant
Flexible wall
Sealant Flexible wall contact our Technical Solutions Team on 01656 868490.
• min. 75mm thick
ELEVATION - 63mm Dia. PVC CONDUIT
• min. 75mm thick
• min. 1no. board layers
ELEVATION - 63mm Dia. PVC CONDUIT • min. 1no. board layers
THROUGH 75mm FLEXIBLE WALL • Fire rated to at least the same fire rating as the firestop seal THROUGH 75mm FLEXIBLE WALL • Fire rated to at least the same fire rating as the firestop seal
EI 60 EI 60
Integrity Performance: Insulation Performance:
LINEAR ARRANGEMENT OF 63mm Dia. PVC LINEAR ARRANGEMENT OF 63mm Dia. PVC Scale: Date:
NTS NOV 20
CONDUITS THROUGH 75mm FLEXIBLE WALL CONDUITS THROUGH 75mm FLEXIBLE WALL
EI 60 EI 60 Sheet Size: Drawn By: Checked By:
A3 RW TECH L.HAM
The published fire ratings have been achieved by following the instructions set out above. Use of alternative components or deviations from the instructions in any way is likely to mean that the installation will not comply with the assessed rating. Rockwool Ltd. does not accept responsibility for the consequences of using
Rockwool products in applications or for purposes not authorised by Rockwool Ltd. Expert advice should be sought where such applications are contemplated.The information contained in this drawing is believed to be correct at the date of publication, and is based upon tested and certified solutions. The policy of Rockwool Drawing Number: Revision:
Ltd. is one of constant improvement. Installers should therefore ensure that they are working from the latest published drawings and instructions. Whilst Rockwool will endeavour to keep its publications up to date the accuracy of the information contained within this drawing may be affected by pertinent changes in the law or
regulatory requirements and alterations or amendments to the specification of Rockwool products. RWSD-HE-0110 B
(V10/NOV22) 44
63mm Dia. PVC SLEEVE PARTIAL PENETRATION 3 No. 34mm Dia. PVC SLEEVES PARTIAL PENETRATIONS ROCKWOOL Standard Detail:
75mm FLEXIBLE WALL 75mm FLEXIBLE WALL Supporting Evidence : WF 411469 (BS EN 1366-3:2009)
EI 90 EI 90/60
The supporting construction must be capable of achieving
the required fire rating of the proposed firestop.
Flexible wall Flexible wall
• min. 75mm thick • min. 75mm thick
• min. 1no. board layers • min. 1no. board layers Flexible wall constructions must be installed in accordance
• Fire rated to at least the same fire rating as the firestop seal • Fire rated to at least the same fire rating as the firestop seal with the manufacturer's guidelines. The wall construction
should be a minimum thickness of 75mm.
90 minutes Up to 90 minutes
Drawing Title:
Galvanized Spiral Duct cPVC Pipe Penetration ROCKWOOL FIREPRO® High Expansion Int. Sealant
• Max. 100mm diameter • 63mm diameter
75mm Flexible Wall - 1no. Board - Pipe & Partial Pens.
100mm Dia. GALV. SPIRAL DUCT THROUGH 63mm Dia. CPVC PIPE THROUGH Scale: Date:
75mm FLEXIBLE WALL 75mm FLEXIBLE WALL NTS NOV 20
E 90 (Integrity Only) EI 90 Sheet Size: Drawn By: Checked By:
A3 RW. TECH L.HAM
The published fire ratings have been achieved by following the instructions set out above. Use of alternative components or deviations from the instructions in any way is likely to mean that the installation will not comply with the assessed rating. Rockwool Ltd. does not accept responsibility for the consequences of using
Rockwool products in applications or for purposes not authorised by Rockwool Ltd. Expert advice should be sought where such applications are contemplated.The information contained in this drawing is believed to be correct at the date of publication, and is based upon tested and certified solutions. The policy of Rockwool Drawing Number: Revision:
Ltd. is one of constant improvement. Installers should therefore ensure that they are working from the latest published drawings and instructions. Whilst Rockwool will endeavour to keep its publications up to date the accuracy of the information contained within this drawing may be affected by pertinent changes in the law or
regulatory requirements and alterations or amendments to the specification of Rockwool products. RWSD-HE-0111 B
(V10/NOV22) 45
(V10/NOV22) 46
(V10/NOV22) 47
(V10/NOV22) 48
Insulated fie sleeve through single 50mm batt
Spacing Classification
Pipe Wall
Pipe Material Pipe Size (mm) Substrate Seal Closure Device Aperture Edge Service Separation
Thickness (mm) Integrity Insulation
Separation (mm) (mm)
PVC 40 - 160 1.8 - 9.5 50mm ablative
75mm thick PB / coated batt
HDPE 40 - 160 2.4 - 9.5 IFS - 150mm 0 0 30 30
Masonry wall 600mm (h) x
PP 40 - 160 1.8 - 9.1 900mm (w)
(V10/NOV22) 49
Insulated fire sleeve through double 50mm batt - Single sided installation
Spacing Classification
Pipe Wall
Pipe Material Pipe Size (mm) Substrate Seal Closure Device Aperture Edge Service Separation
Thickness (mm) Integrity Insulation
Separation (mm) (mm)
(V10/NOV22) 50
ROCKWOOL Standard Detail:
Supporting Evidence : WF 411471 (BS EN 1366-3:2009)
Combustible pipe through Solutions for flexible wall constructions can be used in
ROCKWOOL SoftSeal ROCKWOOL SoftSeal at 45 masonry constructions of the same minimum wall
Intumescent Sealant degree angle thickness (100mm Min.)
ROCKWOOL SoftSeal
applied to all abutments,
100 joints in batt and 300mm length of insulated fire 45° These products should only be utilised for applications as
perimeter of aperture sleeve 300 outlined in the relevant ROCKWOOL product data sheet
and in accordance with the relevant ROCKWOOL Fire
Resistance Testing. Additionally the product must be
Combustible Pipe installed in accordance with the current ROCKWOOL
100 guidelines.
100
Insulated Fire Sleeve through SoftSeal - Angled Pipes (45 degrees) Up to 120 Minutes Up to 120 Minutes
Spacing Classification
Pipe Wall
Pipe Material Pipe Size (mm) Substrate Seal Closure Device Aperture Edge Service Separation
Thickness (mm) Integrity Insulation
Separation (mm) (mm)
Scale: Date:
NTS NOV 20
(V10/NOV22) 51
ROCKWOOL Standard Detail:
Supporting Evidence : WF 411457 / WF 411460 / WF
ROCKWOOL INSULATED FIRE SLEEVE ROCKWOOL INSULATED FIRE SLEEVE 411464 / WF 411467 (BS EN 1366-3:2009)
THROUGH 100MM THICK WALL THROUGH 75MM THICK WALL
The supporting construction must be capable of achieving
the required fire rating of the proposed Firestop.
Fire rated flexible wall / ROCKWOOL Acoustic Fire rated flexible wall / ROCKWOOL Acoustic
plasterboard partition plasterboard partition Insulated Fire Sleeve to be minimum 150mm long through
Intumescent Sealant Intumescent Sealant wall.
to fill gaps up to 10mm to fill gaps up to 15mm
25 37.5
between insulated fire between insulated fire Solutions for flexible wall constructions can be used in
sleeve and substrate. sleeve and substrate. masonry constructions of the same minimum wall
Combustible and Minimum 12.5mm Combustible and Minimum 12.5mm thickness (75mm or 100mm)
non-combustible pipes to be depth non-combustible pipes to be depth
adequately supported on each adequately supported on each Core holes through walls to have a minimum separation of
150mm. For reduced separation please contact
side of the wall side of the wall
ROCKWOOL Technical.
50
ROCKWOOL Insulated Fire ROCKWOOL Insulated Fire
These products should only be utilised for applications as
Sleeve to project by min. Sleeve to project by min. outlined in the relevant ROCKWOOL product data sheet
25mm from each face of the 37.5mm from each face of the and in accordance with the relevant ROCKWOOL Fire
wall. Min 150mm total length. wall. Min 150mm total length. Resistance Testing. Additionally the product must be
installed in accordance with the current ROCKWOOL
100 75 guidelines.
(V10/NOV22) 52
ROCKWOOL Standard Detail:
Supporting Evidence : WF 423089 / WF 423090
(BS EN 1366-3:2009)
Scale: Date:
NTS NOV 20
(V10/NOV22) 53
ROCKWOOL Standard Detail:
Supporting Evidence : WF 416060
Combustible or non combustible Core holes through floors to have a minimum separation
pipes to be adequately of 150mm. For reduced separation please contact
supported on both side of the ROCKWOOL Technical.
floor slab
Min 150mm These products should only be utilised for applications as
>15 <15 outlined in the relevant ROCKWOOL product data sheet
concrete floor slab Annular gaps up to 15mm. and in accordance with the relevant ROCKWOOL Fire
Use 50mm depth RWA45 Resistance Testing. Additionally the product must be
backing with 20mm depth installed in accordance with the current ROCKWOOL
Gaps >15mm fill
150 ROCKWOOL Acoustic guidelines.
with ROCKWOOL
Intumescent Sealant
Standard or HS
For further information or alternative products please visit
Compound www.rockwool.co.uk or contact our Technical Solutions
Team on 01656 868490
150mm length of
insulated fire
sleeve
Insulated fire sleeve through 150mm AAC slab Up to 120 Minutes Up to 120 Minutes
Pipe Wall Thickness Classification
Pipe Material Pipe Size (mm) Substrate Closure Device Annular Gap
(mm) Integrity Insulation
PVC 40 - 160 1.8 - 9.5
15mm - sealed with
120
150mm Aerated 20mm deep AIS
HDPE 40 - 160 2.4 - 9.5 IFS - 150mm 180
concrete slab with 50mm RWA45 Pencoed, Bridgend,
backing South Wales CF35 6NY
PP 40 - 160 1.8 - 9.1 60
t: 01656 868490
[email protected]
Drawing Title:
Scale: Date:
NTS NOV 20
(V10/NOV22) 54
Oval insulated fire sleeve
Spacing Classification
Pipe Wall
Vent Material Vent Size (mm) Substrate Seal Closure Device Aperture Edge Service Separation
Thickness (mm) Integrity Insulation
Separation (mm) (mm)
Spacing Classification
Vent Material Vent Size (mm)Vent Wall Thickness (mm) Substrate Seal Closure Device
Aperture Edge Service Separation
Integrity Insulation
Separation (mm) (mm)
100mm thick PB / 100mm softseal 1200mm (h) x
PVC 204 x 60 2 0 0 60 60
Masonry wall 1200mm (w)
132mm thick PB /
PVC 110 x 54 1.5 - 1.7mm N/A OIFS - 150mm - 100 120 120
Masonry wall
132mm thick PB /
PVC 204 x 60 1.5 - 1.7mm N/A - 100 120 120
Masonry wall
PVC 110 x 54 1.5 - 1.7mm 50mm Ablative Coated Batt 100 100 60 60
PVC 204 x 60 1.5 - 1.7mm 50mm Ablative Coated Batt 100 100 60 60
(V10/NOV22) 55
Flexible
Flexible / rigid/wall
rigid wall Intumescent
Intumescent Thickness
Thickness
Service
Test Test Service separation
separation
Service
Service type type (min. (min.
100mm 100mm
thick)thick) Pipe Diameter
Pipe Diameter Intumescent
Intumescent Material
Material
Standard
Standard
Integrity
Integrity Insulation
Insulation Aperture
Aperture Services
Services Ø32 - Ø32
50mm - 50mm 40mm40mm (w) x 2mm
(w) x 2mm (t) (t)
PVC pipes
PVC pipes Ø 32 -Ø50mm
32 - 50mm
(1.8mm(1.8mm wall thickness)
wall thickness) 120 120 120 120 Ø51 - Ø51
82mm - 82mm 40mm40mm (w) x 4mm
(w) x 4mm (t) (t)
Ø 160mm
Ø 160mm (6.2mm (6.2mm wall thickness)
wall thickness) 90 90 90 90 Ø83 - Ø83
115mm- 115mm 40mm40mm (w) x 6mm
(w) x 6mm (t) (t)
EN EN N/A N/A 100mm 100mm
Ø 160mm
Ø 160mm (9.5mm (9.5mm wall thickness)
wall thickness) Ø116 Ø116
- 160mm- 160mm 40mm40mm (w) x 8mm
(w) x 8mm (t) (t)
120 120 120 120
Ø 200mm
Ø 200mm (7.7 - 9.6mm
(7.7 - 9.6mm wall thickness)
wall thickness) Ø161 Ø161
- 200mm- 200mm 40mm40mm (w) x 10mm
(w) x 10mm (t) (t)
PP pipes
PP pipes Ø 32 -Ø50mm
32 - 50mm
(2.9mm(2.9mm wall thickness)
wall thickness) 120 120 Ø201 Ø201
- 250mm- 250mm 40mm40mm (w) x 12mm
(w) x 12mm (t) (t)
Ø 160mm (4mm wall
Ø 160mm (4mm wall thickness) thickness) 90 90
Ø 160mm
Ø 160mm (14.6mm(14.6mm wall thickness)
wall thickness) 120 120
120 120 EN EN N/A N/A 100mm
100mm
Ø 200mm
Ø 200mm (4.9mm (4.9mm wall thickness)
wall thickness) 90 90
Ø 200mm
Ø 200mm (18.2mm(18.2mm wall thickness)
wall thickness) 120 120
Ø 250mm
Ø 250mm (10.1mm(10.1mm wall thickness)
wall thickness) 15 15
PE pipes
PE pipes Ø 32 -Ø50mm
32 - 50mm
(2.9mm(2.9mm wall thickness)
wall thickness) 120 120 120 120
Ø 160mm
Ø 160mm (9.5mm (9.5mm wall thickness)
wall thickness) 90 90 90 90 EN EN N/A N/A 100mm
100mm
Ø 200mm
Ø 200mm (18.4mm(18.4mm wall thickness)
wall thickness) 120 120 120 120
(V10/NOV22) 56
Rigid floor Intumescent Thickness
Test Service separat ion
Service t ype (min. 150mm thick) Pipe Diamet er Int umescent Mat erial
Standard
Int egrit y Insulation Aperture Services Ø32 - 50mm 40mm (w) x 2mm (t )
PVC pipes Ø 32 - 50mm (1.8mm wall thickness) 120 Ø51 - 82mm 40mm (w) x 4mm (t )
120
Ø 200mm (7.7mm wall thickness) 90 EN N/A 100mm Ø83 - 115mm 40mm (w) x 6mm (t )
Ø 200mm (9.6mm wall thickness) 60 60 Ø116 - 160mm 40mm (w) x 8mm (t )
PP pipes Ø 32 - 50mm (2.9mm wall thickness) 120 120 Ø161 - 200mm 40mm (w) x 10mm (t )
Ø 200mm (4.9mm wall thickness) 15 15 EN N/A 100mm
Ø 200mm (18.2mm wall thickness) 120 90
HDPE pipes Ø 32 - 50mm (2.9mm wall thickness) Rigid floor Intumescent Thickness
Ø 200mm (4.9mm wall thickness) 120 120 EN 150mm thick)
N/A Test
100mm Service separat ion
Service t ype (min. Pipe Diamet er Int umescent Mat erial
Ø 200mm (11.4mm wall thickness) Standard
Int egrit y Insulation Aperture Services Ø32 - 50mm 40mm (w) x 2mm (t )
PVC pipes Ø 32 - 50mm (1.8mm wall thickness) 120 Ø51 - 82mm 40mm (w) x 4mm (t )
120
Ø 200mm (7.7mm wall thickness) 90 EN N/A 100mm Ø83 - 115mm 40mm (w) x 6mm (t )
Ø 200mm (9.6mm wall thickness) 60 60 Ø116 - 160mm 40mm (w) x 8mm (t )
PP pipes Ø 32 - 50mm (2.9mm wall thickness) 120 120 Ø161 - 200mm 40mm (w) x 10mm (t )
Ø 200mm (4.9mm wall thickness) 15 15 EN N/A 100mm
Ø 200mm (18.2mm wall thickness) 120 90
HDPE pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 200mm (4.9mm wall thickness) 120 120 EN N/A 100mm
Ø 200mm (11.4mm wall thickness)
(V10/NOV22) 57
Pipe Size Wrap Thickness Layers
32-50 40mm (W) x 2mm (T) 1
51-82 40mm (W) x 4mm (T) 2
83-115 40mm (W) x 6mm (T) 3
116-160 40mm (W) x 8mm (T) 4
151-200 40mm (W) x 10mm (T) 5
201-250 40mm (W) x 12mm (T) 6
(V10/NOV22) 58
Pipe Size / Wall / Insulation Classification
Pipe Mat erial Wrap Layers
Pipe Size (mm) Wall Thickness (mm) Insulat ion Type / Size (mm) Int egrit y Insulation
13-25 Elastomeric (C/S - 2 No. 40mm (w) x 2mm
St eel or Copper 42 - 159 1.2 - 14.2 120 60
continuously sustained) (t)
13-25 Elastomeric (C/S - 2 No. 40mm (w) x 2mm
St eel or Copper 42 1 - 14.2 120 90
continuously sustained) (t)
25 - 40 Phenolic (C/S - 2 No. 40mm (w) x 2mm
St eel or Copper 42 - 108 1.2 - 14.2 120 60
continuously sustained) (t)
25 - 40 Phenolic (C/S - 2 No. 40mm (w) x 2mm
St eel or Copper 42 1 - 14.2 120 90
continuously sustained) (t)
50 Glass Fibre (C/S - cont inuously 2 No. 40mm (w) x 2mm
St eel or Copper 42 1 - 14.2 120 90
sustained) (t)
(V10/NOV22) 59
Pipe Size / Wall / Insulation Classification
Pipe Material Wrap Layers
Pipe Size (mm) Wall Thickness (mm) Insulation Type / Size (mm) Integrity Insulation
13 - 25 Elastomeric (C/S - 2 No. 40mm (w) x
Steel or Copper 42 - 159 1.2 - 14.2 120 60
continuously sustained) 2mm (t)
13 - 25 Elastomeric (C/S - 2 No. 40mm (w) x
Steel or Copper 42 1.2 - 14.2 120 90
continuously sustained) 2mm (t)
25 - 40 Phenolic (C/S - 2 No. 40mm (w) x
Steel or Copper 42 - 108 1.2 - 14.2 120 60
continuously sustained) 2mm (t)
25 - 40 Phenolic (C/S - 2 No. 40mm (w) x
Steel or Copper 42 1.2 - 14.2 120 90
continuously sustained) 2mm (t)
50 (30kg/m³) Glassfibre (C/S - 2 No. 40mm (w) x
Steel or Copper 42 1.2 - 14.2 120 90
continuously sustained) 2mm (t)
(V10/NOV22) 60
ROCKWOOL Pipe Wrap Roll to both sides of flexible or ridgid wall (Min 100mm thick)
Pipe Material Pipe Size & Wall Thickness (mm) Wrap Layers Annulus (mm) Classification
PVC 32 - 50 O/A Dia - 1.8mm Wall 1 No. 40mm (W) x 2mm (T) 4 EI 120
PVC 160 O/A Dia - 6.2 - 9.5mm Wall 4 No. 40mm (W) x 2mm (T) 10 EI 90
PVC 160 O/A Dia - 9.5mm Wall 4 No. 40mm (W) x 2mm (T) 10 EI 120
PVC 200 O/A Dia. 7.7 - 9.6mm Wall 5 No. 40mm (W) x 2mm(T) 12 EI120
PP 32 - 50 O/A Dia. - 2.9mm Wall 1 No. 40mm (W) x 2mm (T) 4 EI 120
PP 160 O/A Dia - 4mm Wall 5 No. 40mm (W) x 2mm (T) 10 E 120 (EI90)
PP 160 O/A Dia - 14.6mm Wall 4No. 40mm (W) x 2mm (T) 10 EI 120
PP 200 O/A Dia. - 4.9mm Wall 5 No. 40mm (W) x 2mm(T) 12 E 120 (EI90)
PP 200 O/A Dia. - 18.2mm Wall 5 No. 40mm (W) x 2mm(T) 12 EI 120
PP 250 O/A Dia. - 10.1mm Wall 6 No. 40mm (W) x 2mm(T) 14 E 120
PE 32 - 50 O/A Dia. - 2.9mm Wall 1 No. 40mm (W) x 2mm (T) 4 EI 120
PE 160 O/A Dia - 9.5mm Wall 4 No. 40mm (W) x 2mm (T) 10 EI 90
PP 200 O/A Dia. - 18.4mm Wall 5 No. 40mm (W) x 2mm(T) 12 EI 120
(V10/NOV22) 61
Pipe Size (mm) Wrap Thickness Layers
32-50 40mm (W) x 2mm (T) 1
51-82 40mm (W) x 4mm (T) 2
83-115 40mm (W) x 6mm (T) 3
116-150 40mm (W) x 8mm (T) 4
151-200 40mm (W) x 10mm (T) 5
ROCKWOOL FIREPRO Pipewrap Roll in rigid floor applications (min. 150mm thick) NOTES
Classification
Pipe material Pipe size & wall thickness (mm) Wrap layers (mm) Annulus
Integrity Insulation
PVC Ø 32-50 (1.8mm wall thickness) 2 no. 40 (w) x 2 (t) 4 120 120 UL-EU-01204-CPR
PVC Ø 200 (7.7mm wall thickness) 5 no. 40 (w) x 2 (t) 12 120 90
PVC Ø 200 (9.6mm wall thickness) 5 no. 40 (w) x 2 (t) 12 60 60
PP Ø 32-50 (2.9mm wall thickness) 2 no. 40 (w) x 2 (t) 4 120 120
PP Ø 200 (18.2mm wall thickness) 5 no. 40 (w) x 2 (t) 12 120 90
HDPE Ø 32-50 (2.9mm wall thickness) 2 no. 40 (w) x 2 (t) 4 120 120
HDPE Ø 200 (4.9mm wall thickness) 5 no. 40 (w) x 2 (t) 12 120 120
HDPE Ø 200 (11.4mm wall thickness) 5 no. 40 (w) x 2 (t) 12 120 120
(V10/NOV22) 62
Substrate Backing material Standard
thickness (mm) (mm) (mm) seal Integrity Insulation
20 12.5 Ø 20mm PE rod 120 120 EN
20 10 Ø 20mm PE rod ü 120 45 EN
Concrete wall /
100 30 15 Ø 30mm PE rod ü 120 30 EN
concrete wall
40 20 Ø 40mm PE rod ü 120 30 EN
50 25 Ø 50mm PE rod ü 120 60 EN
min. Substrate max. width min. Depth Single sided Performance (mins)
Substrate Backing material Standard
thickness (mm) (mm) (mm) seal Integrity Insulation
Concrete floor / 20 10 Ø 20mm PE rod ü 240 45 EN
150
concrete floor 50 25 Ø 50mm PE rod ü 240 90 EN
Concrete EN
Concrete EN
min. Substrate max. width min. Depth Single sided Performance (mins)
Substrate Backing material Standard
Concrete EN
thickness (mm)
min. Substrate
(mm)
max. width
(mm)
min. Depth
seal
Single sided
Integrity
PerformanceInsulation
(mins)
Substrate 20 12.5 Backing
Ø 20mmmaterial
PE rod 120 120 Standard
EN
thickness (mm) (mm) (mm) seal Integrity Insulation
min. Substrate max.20
20width min.10
Depth
12.5
Ø 20mm PE rod
Ø 20mmmaterial
PE rod üsided
Single 120
Performance
120
45
(mins)
120
EN
EN
Steel
Concrete wall /
Substrate
concrete wall
100 (mm)
thickness 30
(mm)
20
15
(mm)
10
Backing
Ø 30mm PE rod
Ø 20mm PE rod ü
seal
ü
120
Integrity
120
30
Insulation
45
Standard
EN
EN
Concrete wall / 40
20 20
12.5 ØØ 40mm
20mm PE
PE rod
rod ü 120
120 30
120 EN
EN
100 30 15 Ø 30mm PE rod ü 120 30 EN
concrete wall min. Substrate 50
20
max.40
width 25
10
min.20
Depth Ø 40mm
50mm PE rod
20mm PE rod Single
üsided 120
Performance 60
(mins)
45 EN
Concrete
Substrate
Concrete wall / EN
100 (mm)
thickness 30
(mm)
50 15
(mm)
25
Ø
Backing
ØØ 50mm
material
30mm PE
PE rod
rod
ü
seal
ü
120
120
Integrity
120
30
30
Insulation
60
EN
Standard
EN
EN
concrete wall ü
40
20 20
10 40mm PE rod
Ø 20mm ü 120 30
20 EN
Concrete wall /
Substrate min. Substrate max.30
width
50 min.15
Depth
25 Ø 30mm PE rod
50mmmaterial
Backing Singleüsided Performance
45
120 (mins)
30
60 EN
Standard
100
steel thickness (mm) (mm) (mm) seal Integrity Insulation
min. Substrate max.40
width min.20
Depth Ø 40mm PE rod Singleüsided 45 30
Performance (mins) EN
Substrate
Concrete floor / 20
50 12.5
10
25 Backing
Ø 50mmmaterial
Ø 20mm PE
PE rod
rod ü 120
240
45 120
45
30 Standard
EN
EN
Concrete
concretewall
Concrete
Concrete
floor
floor //
EN
thickness
150 (mm)
min. Substrate
(mm)
20
max.50
20width
(mm)
10
min.25
Depth
10
20mm PE rod
Ø 50mm
Ø 20mmmaterial
PE rod
seal
üsided
Single
Integrity
120
240
Performance
240
Insulation
45
90
(mins)
45
EN
EN
Substrate 100 (mm) 30 15 Backing
Ø 30mm PE rod ü 120 30 Standard
EN
150
thickness (mm) (mm) ü
seal Integrity Insulation
concretefloor
concrete wall 50 25 Ø 50mm PE rod ü 240 90 EN
Concrete floor
Substrate / min.
min. Substrate
Substrate max.40
max. width
20
width min.20
min. Depth
10
Depth ØØ 40mm PE
PE rod
20mmmaterial
Backing rod Singleüsided
Singleüsided 120
Performance
Performance
240 30
(mins)
(mins)
45 EN
EN
Standard
Substrate 150 50 25 Backing
Ø material Standard
concrete floor thickness
thickness (mm)
(mm) (mm)
50
(mm) (mm)
25
(mm) Ø 50mm
50mm PE
PE rod
rod seal
ü
seal
ü 120
Integrity
240
Integrity 60
Insulation
90
Insulation EN
EN
Concrete floor / 20
20 12.5
10 Ø 20mm
Ø 20mm PE
PE rod
rod ü 120
120 120
20 EN
EN
150 20 10 Ø 50mm
20mm PE
PE rod
rod ü 120 45 EN
steelwall /
Concrete 50 50 Ø ü 240 90 EN
100
min. Substrate max.30
width min.15
Depth Ø 30mm PE rod Singleüsided Performance
120 (mins)
30 EN
Substrate
concrete wall Backing material Standard
thickness (mm) 40
(mm) 20
(mm) Ø 40mm PE rod seal
ü 120
Integrity 30
Insulation EN
Steel
Concrete floor /
concrete floor
150
20
50
50
10
25
25
Ø 20mm
50mm PE rod
Ø 50mm PE rod
ü 240
120
240
45
60
90
EN
EN
Hardwood
Steel
ü
min. Substrate max. width min. Depth Single sided Performance (mins)
Substrate Backing material Performance (mins) Standard
Steel
Substrate
min. Substrate
thickness (mm)
min. Substrate
thickness (mm)
max. width
(mm)
max. width
(mm)
min. Depth
(mm)
min. Depth
(mm)
Backing material
Single sided
seal
Single sided
seal
Integrity
PerformanceInsulation
Integrity (mins)
Insulation
Standard
Substrate 20 10 Backing
Ø 20mmmaterial
PE rod ü 120 20 Standard
EN
Concrete floor / thickness (mm) (mm)
20 (mm)
10 Ø 20mm PE rod seal
ü Integrity
240 Insulation
45 EN
Concrete wall / 150
min. Substrate max.30
width min.15
Depth Ø 30mm PE rod üsided
Single 45
Performance 30
(mins) EN
concrete floor
Substrate 100 20
50 10
25 Ø 20mm PE rod
50mmmaterial
Backing ü 120
240 20
90 EN
Standard
steel thickness (mm) 40
(mm) 20
(mm) Ø 30mm
40mm PE
PE rod
rod seal
ü 45
Integrity 30
Insulation EN
Concrete wall / 30 15 Ø ü 45 30 EN
100 50
20 25
10 Ø 50mm
20mm PE rod ü 45
120 30
20 EN
steel 40 20 Ø 40mm PE rod ü 45 30 EN
Concrete wall / 30 15 Ø 50mm
30mm PE
PE rod
rod 45 30 EN
Steel
steel
100 50
40
25
20
Ø
Ø 40mm PE rod
üü
ü
45
45
30
30
EN
EN
min. Substrate max.50
width min.25
Depth Ø 50mm PE rod Singleüsided Performance
45 (mins)
30 EN
Substrate Backing material Performance (mins) Standard
min. Substrate
thickness (mm) max. width
(mm) min. Depth
(mm) Single
sealsided Integrity Insulation
Substrate min. Substrate max. width min. Depth Backing material Single sided Performance (mins) Standard
Substrate
Concrete floor / thickness (mm) (mm)
20 (mm)
10 Backing
Ø 20mmmaterial
PE rod seal
ü Integrity
120 Insulation
20 Standard
EN
thickness
150 (mm) (mm) (mm) seal Integrity Insulation
steel min. Substrate 20
50
max.20
width 10
50
min.10
Depth 20mm PE rod
Ø 50mm üsided
Single 120
240
Performance 20
90
(mins) EN
Steel
Concrete floor /
Substrate
Concrete wall / 150 (mm)
thickness 30
(mm) 15
(mm)
Ø 20mmmaterial
Backing PE rod
Ø 30mm PE rod ü
ü
seal
120
45
Integrity
20
30
Insulation
EN
Standard
EN
Softwood
steel
steelfloor /
Concrete
100 50
40
20
50
20
10
Ø 50mm PE rod
ØØ 40mm
20mm PE
PE rod
rod
ü
ü
ü
240
45
120
90
30
20
EN
EN
EN
150 max.50 min.25 Ø
steel
Substrate
min. Substrate width
50 Depth
50 Ø 50mm PE
PE rod
50mmmaterial
Backing rod Singleü
üsided 45
Performance
240 30
(mins)
90 EN
EN
Standard
min. Substrate
thickness (mm) max. width
(mm) min. Depth
(mm) Single sided
seal PerformanceInsulation
Integrity (mins)
Hardwood
Substrate
thickness (mm) (mm)
20 (mm)
10
Backing material
Ø 20mm PE rod seal
ü Integrity
120 Insulation
20
Standard
EN
Hardwood
Concrete wall /
Substrate
min. Substrate
100
20
max.30
width 10
min.15
Depth 20mm PE rod
Ø 30mm
Backing material
Singleüsided 30
Performance
45 15
(mins)
30 EN
Standard
steel thickness (mm) 30
(mm)
40 15
(mm)
20 30mm PE rod
Ø 40mm seal 30
Integrity
45 15
Insulation
30 EN
Hardwood
Concrete wall /
Concrete floor / 100 40
20
50 20
10
25 40mm PE rod
Ø 20mm
50mm
ü
ü 30
120
45 15
20
30 EN
softwood 150
steel 50 25
50 Ø 50mm PE rod ü 45
240 30
90 EN
50 50 Ø 50mm PE rod ü 45 45 EN
min. Substrate max. width min. Depth Single sided Performance (mins)
Substrate Backing material Standard
Plasterboard thickness (mm) (mm) (mm) seal Integrity Insulation
Hardwood
Concrete floor /
steel
150
20
50
10
50
Ø 20mm PE rod
Ø 50mm PE rod
ü 120
240
20
90
EN
EN
ü
min. Substrate max. width min. Depth Single sided Performance (mins)
Substrate Backing material Standard
thickness (mm) (mm) (mm) seal Integrity Insulation
Head of wall /
120 20 25 Steel head track 120 120 EN
concrete soffit
Softwood
Hardwood
Softwood
min.
min. Substrate
Substrate max.
max. width
width min.
min. Depth
Depth Single
Single sided
sided Performance
Performance (mins)
(mins)
Substrate Backing
Backing material Standard
Softwood
Substrate thickness
thickness (mm)
(mm)
min. Substrate
(mm)
(mm)
max. width
(mm)
(mm)
min. Depth
material seal
seal
Single sided
Integrity
PerformanceInsulation
Integrity Insulation
(mins)
Standard
Substrate 20 10 Backing
Ø 20mmmaterial
PE rod ü 30 15 Standard
EN
Flexible wall / thickness
120(mm) (mm)
20 (mm)
12.5 Ø 30mm
20mm PE
PE rod
rod seal Integrity
120 Insulation
120 EN
concrete
Concrete wall/
wall min. Substrate max.30
20width min.15
Depth
10
Ø
Ø 20mmmaterial
PE rod üsided
Single
ü
30
Performance
30
15
(mins)
15
EN
EN
Substrate Backing Standard
100 (mm)
thickness 40
(mm) 20
(mm) Ø 30mm
40mm PE
PE rod
rod seal
ü 30
Integrity 15
Insulation EN
softwood 30 15 Ø ü 30 15 EN
Concrete wall / 50
20 25
10 Ø 50mm
20mm PE rod ü 45
30 30
15 EN
100 40 20 Ø 40mm PE rod ü 30 15 EN
softwood 50
30 50
15 Ø 50mm
30mm PE rod ü 45
30 45
15 EN
Softwood
Concrete wall /
100
50
40
50
25
20
50
Ø 50mm
ØØ 50mm
PE rod
40mm PE
PE rod
rod
ü
ü
45
30
45
30
15
45
EN
EN
EN
softwood ü
Plasterboard min. Substrate
50
max.50
width
25
min.50
Depth
Ø 50mm PE rod ü
Singleüsided
45
Performance
30
(mins)
EN
Ø 50mmmaterial
PE rod 45 45 EN
Plasterboard
Substrate
thickness (mm) (mm) (mm)
Backing
seal Integrity Insulation
Standard
min. Substrate max.20
width min.10
Depth Ø 20mmmaterial
PE rod Singleüsided Performance
30 (mins)
15 EN
Substrate Backing Standard
Plasterboard
Softwood thickness (mm)
min. Substrate
(mm)
max.30
width
(mm)
min.15
Depth Ø 30mm PE rod seal
Singleüsided
Integrity
30
PerformanceInsulation
15
(mins) EN
Concrete
Head wall//
Substrate
of wall Backing material Standard
100(mm)
thickness
120 40
(mm)
20 20
(mm)
25 Steel headPEtrack
Ø 40mm rod seal
ü 30
Integrity
120 15
Insulation
120 EN
EN
softwood
concrete soffit Performance (mins)
Head of wall / min. Substrate
min. Substrate max.50
max. width
width min.25
min. Depth
Depth Ø 50mmmaterial
PE rod Single sided
Singleüsided 45
Performance 30
(mins) EN
Substrate
Substrate 120 (mm) 20 25 Backing
Backing
Steel material
head Standard
Standard
concrete soffit thickness
thickness (mm) (mm)
50
(mm) (mm)
50
(mm) Ø 50mm PEtrack
rod seal
seal
ü
120
Integrity
45
Integrity
120
Insulation
45
Insulation
EN
EN
Head of wall / 20 10 Ø 20mm
120 20 25 Steel headPEtrack
rod ü 30
120 15
120 EN
EN
concrete soffit min. Substrate max.30
width min.15
Depth Singleüsided Performance (mins)
Plasterboard
Substrate
Concrete wall / thickness
100(mm) (mm) (mm)
Ø 30mmmaterial
Backing PE rod
seal
30
Integrity
15
Insulation
EN
Standard
softwood min. Substrate max.40
width min.20
Depth Ø 40mm PE rod Singleüsided 30
Performance 15
(mins) EN
Substrate
Flexible wall / Backing material Standard
thickness
120 (mm) 50
(mm)
20 25
(mm)
12.5 Ø 20mm
Ø 50mm PE PE rod
rod seal
ü 45
Integrity
120 30
Insulation
120 EN
EN
min. Performance (mins)
concrete wall
Substrate
Flexible wall / min. Substrate
Substrate max. width
max.50
width min. Depth
min.50
Depth Backing
Ø 50mmmaterial
PE rod
Single
Single sided
üsided Performance
45 (mins)
45 Standard
EN
Substrate thickness
120 (mm) (mm)
20 (mm)
12.5 Backing
Ø 20mmmaterial
PE rod seal Integrity
120 Insulation
120 Standard
EN
concrete wall thickness (mm) (mm) (mm) seal Integrity Insulation
Head of wall
Flexible wall //
Plasterboard
concrete
concretesoffit
wall
120
120 20
20 25
12.5 Steel
Ø 20mmheadPEtrack
rod 120
120 120
120 EN
EN
min. Substrate max. width min. Depth Single sided Performance (mins)
Substrate Backing material Standard
thickness (mm)
min. Substrate (mm)
max. width (mm)
min. Depth seal
Single sided PerformanceInsulation
Integrity (mins)
Substrate Backing material Standard
Head of wall / thickness (mm) (mm) (mm) seal Integrity Insulation
120 20 25 Steel head track 120 120 EN
concrete soffit
Flexible wall /
120 20 12.5 Ø 20mm PE rod 120 120 EN
(V10/NOV22)
concrete wall
63
min. Substrate max. width min. Depth Single sided Performance (mins)
Substrate Backing material Standard
thickness (mm) (mm) (mm) seal Integrity Insulation
Flexible wall /
120 20 12.5 Ø 20mm PE rod 120 120 EN
concrete wall
(V10/NOV22) 64
(V10/NOV22) 65
(V10/NOV22) 66
Flexible / rigid wall
Test Service separation
Service type Backing material (min. 100mm thick)
Standard
Integrity Insulation Aperture Services
Blank seal ≤ 180mm x 180mm 120 120
Electrical cable ≤ Ø 21mm 120 120
Ø 22mm - 50mm 20mm thick 90 60
EN 10mm N/A
Telecomm cables ≤ Ø 100mm bundle ROCKWOOL RWA45 120 120
PVC conduit ≤ Ø 16mm 120 120
Copper / steel conduit ≤ Ø 16mm 120 15
(V10/NOV22) 67
(V10/NOV22) 68
Performance (mins) Performance (mins) Service separation
H&V Test
Service type Annular gap Locally Sustained Continuously Sustained minimum (mm)
Thickness Standard
Integrity Insulation Integrity Insulation Aperture Services
Copper pipe ≤ Ø 15mm
≤ 10mm
Steel pipe ≤ Ø 60mm
Copper pipe ≤ Ø 15mm 20mm 120 120 120 120
Steel pipe ≤ Ø 60mm 11 - 50mm
Copper pipe custer Ø 15 - 60mm
Copper pipe ≤ Ø 15mm 120
Ø 16mm - 108mm 120 60 120 120
≤ 10mm
Steel pipe ≤ Ø 114mm EN 0 0
90
Ø 114mm - 219mm 90 90 90
25mm
Copper pipe ≤ Ø 15mm 120
120
Ø 16mm - 108mm
11 - 50mm 120 90 120
Steel pipe ≤ Ø 114mm
90
Ø 114mm - 219mm 60
Copper pipe cluster Ø 15mm - 108mm 60
25mm ≤ 50mm 120 120 120
Steel pipe cluster Ø 15mm - 114mm 120
(V10/NOV22) 69
Sealant
Sleeve Pipe Seal Aperture Size Annular Gap Backer EI Rating Spacing
Depth
42 - 108mm 15 - 76mm Compound 440 x 330 14 - 47mm RWA45 15mm 120/10 0mm From Aperture Edge
42 - 108mm 15 - 76mm Double 50mm ACB 440 x 330 14 - 47mm RWA45 15mm 120/15 0mm From Aperture Edge
(V10/NOV22) 70
(V10/NOV22) 71
(V10/NOV22) 72
(V10/NOV22) 73
Integrity & Insulation
Wall Thickness
2A with 2B
100mm 2 hours
150mm 3 hours
200mm 4 hours
(V10/NOV22) 74
Fire Resistance Cavity Assessment/
Product SP Brackets Test Standard
Vertical Horizontal (mm) Certification
SP60 Firestop Slab EI60 EI60 50 - 300 50-100 SP/S | 101-300 SP/L BS 476 Part 20 CC 89697 Revision 8
SP120 Firestop Slab EI120 EI120 50 - 300 50-100 SP/S | 101-300 SP/L BS 476 Part 20 CC 89697 Revision 8
SP60 Firestop Slab E120, EI30 EI60 301 - 400 301-400 SP/L BS 476 Part 20
SP120 Firestop Slab E120, EI60 E120 301 - 400 301-400 SP/L BS 476 Part 20
SP60 Firestop Slab N/A EI60 50 - 300 50-100 SP/S | 101-300 SP/L BS EN 1366-4 Certifire CF5836
SP120 Firestop Slab N/A EI120 50 - 300 50-100 SP/S | 101-300 SP/L BS EN 1366-4 Certifire CF5836
SP Plus
(V10/NOV22) 75
(V10/NOV22) 76
Service separat ion
Performance (mins) Test
Service t ype minimum (mm) Notes
Standard
Int egrit y Insulation Aperture Services
≤ Ø 40mm (1.9mm - 3mm wall) 90 Insulat ed Fire Sleeve wrapped
PVC pipe 120
Ø 41mm - 110mm (4.2mm - 6.6mm wall) 60 around the pipes with 50mm
≤ Ø 40mm (2.4mm - 3.7mm wall) 90 projection to both sides of
HDPE pipe 120
Ø 41mm - 110mm (2.7mm - 10mm wall) 60 EN 0 100 t he seal.
(V10/NOV22) 77
November 2022
ROCKWOOL Limited
Pencoed
Bridgend
CF35 6NY
Tel: 01656 862 621
[email protected]
rockwool.com/uk