Fire Stopping Standard Details

Interested?
Fire Stopping For further information on

Standard Details ROCKWOOL FIREPRO®


products and solutions, contact
the Technical Solutions Team
on 01656 868 490 or
The ROCKWOOL FIREPRO® range of
email: [email protected].
products provides fire stopping and
fire resistance throughout the whole Visit www.rockwool.com/uk
construction process; intended to make to view our complete range of
buildings and their inhabitants safer in the products and services.
event of fire.
Beyond ROCKWOOL insulation’s inherent fire resistant
qualities, our specialist range of products help architects,
contractors and developers conform to current fire regulations.
Our range of fire resistance products cater for most general
purpose and specialty building applications:

▪ Structural protection
▪ Penetration seals
▪ Joints
▪ Cavity barriers
▪ Building services protection

(V10/NOV22) 2
Changelog
General changes Detail amendments

Detail references changed to include product reference Single 50mm batt


RWSD-ACB-0001 Performance limited at 60 minutes
double skin
Spacing guidelines removed - spacings now illustrated on relevant detail
RWSD-ACB-0101 Double 50mm batt Large aperture in masonry wall coverage omitted
New performance table format applied to all details including spacing

Supporting evidence reference changed to reflect new assessments Single sided double Cable insulation performance reduced to 60 minutes. Additional non
RWSD-ACB-0102
50mm batt combustible pipe and PVC conduit coverage added
Fire Stopping Guide Unlagged & lagged cable performance confirmed. Additional non
RWSD-ACB-0201 50mm batt face fix
Point 4) Note added on shaft walls combustible pipe coverage added
Double 50mm batt floor Cable performance without additional pattress added. Additional non
Point 5) Note on sandwich or composite walls added RWSD-ACB-0501
seal combustible pipe coverage added. Damper reference removed
Point 9) 400mm service support distance Single 60mm batt Damper reference removed. Scope enhanced in terms of cables, trunking
RWSD-ACB-1001
Point 10) Separation note added to reflect BS EN 1366-3:2021 double skin & non combustible pipes
Double 60mm batt Damper reference removed. Scope enhanced in terms of cables & non
Point 11) Clarification on cable carriers - any length in accordance with BS EN 1366-3:2021 RWSD-ACB-1101
double skin combustible pipes
Details omitted Unlagged & lagged cable performance confirmed. Additional non
RWSD-ACB-1201 60mm batt face fix
combustible pipe coverage added
SD-140 - L/I H&V Pipe lagging through batt seals
Additional requirements to u/s of steel. Increased scope in terms of seal
SD-141 - L/S H&V Pipe lagging through batt seals RWSD-ACB-1301 60mm batt HoW
height and length
SD-126 - 50mm ablative batt head of wall Damper note removed. Detail revised in line with current assessment -
RWSD-ACB-1501 60mm batt floor seal
cable coverage removed
Additional details
RWSD-SS-0101 Softseal linear joint Cavity width reduced inline with new assessment
RWSD-ACB-0002 - Single skin single 50mm batt

RWSD-ACB-0103 - Single skin double 50mm batt Single 50mm batt High
RWSD-HE-0001 Tracpipe coverage added
Expansion
RWSD-COM-1001 - High strength compound wall seal
Double 50mm batt High Flexible substrate removed, medium cable performance reduced to E 120
RWSD-HE-0050
RWSD-COM-1510 - High strength compound rigid floors - Cables Expansion EI 90 in line with current assessment. Small cables added EI 120

RWSD-COM-1511 - High strength compound floor seal - Cables with plinth / wrap RWSD-HE-0054 CPVC application range Error on single skin detail amended
RWSD-SS-0010 - Softseal deflection head High expansion sealant
RWSD-HE-0102 Armaflex details combined
RWSD-COL-0004 - Single skin single batt - Pipe collar CE 100mm wall
High expansion sealant
RWSD-COL-0503 - Double batt floor seal - Pipe collar CE RWSD-HE-0501 PVC pipe detail combined
double batt floor seal
RWSD-AIS-0110 - Single skin AIS cables Oval duct scope added for 100mm wall & single/double 50mm batt
RWSD-IFS-1003 Oval IFS
RWSD-AIS-0120 - Single skin AIS pipe penetrations applications
Face fix 50mm batt -
RWSD-SP-0001 - SP Slab linear joint seal data reinstated RWSD-PWR-0101 Table reduced - scope refined
PWR insulated pipes

(V10/NOV22) 3
Contents
Orientation
Page FIREPRO® product Application area Drawing no.
of use
7 Single 50mm Ablative Coated Batt - 100mm Wall Multiple Service Penetrations Wall Seal RWSD-ACB-0001
8 Single 50mm Ablative Coated Batt - 75mm Wall Multiple Service Penetrations Wall Seal RWSD-ACB-0002
9 Double 50mm Ablative Coated Batt Multiple Service Penetrations Wall Seal RWSD-ACB-0101
10 Double 50mm Ablative Coated Batt - Single Sided Install Multiple Service Penetrations Wall Seal RWSD-ACB-0102
11 Double 50mm Ablative Coated Batt - Single Skin 100mm Wall Multiple Service Penetrations Wall Seal RWSD-ACB-0103
12 Double 50mm Ablative Coated Batt - Timber Penetrations Timber Penetrations Wall Seal RWSD-ACB-0120
13 50mm Ablative Coated Batt - Face Fix Multiple Service Penetrations Wall Seal RWSD-ACB-0201
14 Double 50mm Ablative Coated Batt - Floor Seal Multiple Service Penetrations Floor Seal RWSD-ACB-0501
15 Single 60mm Ablative Coated Batt - 100mm Wall Multiple Service Penetrations Wall Seal RWSD-ACB-1001
16 Double 60mm Ablative Coated Batt Multiple Service Penetrations Wall Seal RWSD-ACB-1101
17 60mm Ablative Coated Batt - Face Fix Multiple Service Penetrations Wall Seal RWSD-ACB-1201
18 60mm Ablative Coated Batt - Head of Wall Head of Wall / Linear Joint Wall Seal RWSD-ACB-1301
19 Single 60mm Ablative Coated Batt - Floor Seal Multiple Service Penetrations Floor Seal RWSD-ACB-1501
20 Firestop Compound Multiple Service Penetrations Floor Seal RWSD-COM-0501
21 Firestop Compound - H&V Pipe Section Pipe Penetrations Floor Seal RWSD-COM-0503
22 Firestop Compound - Sleeved Services Pipe Penetrations Floor Seal RWSD-COM-0510
23 High Strength Compound Multiple Service Penetrations Wall Seal RWSD-COM-1001
24 High Strength Compound Multiple Service Penetrations Floor Seal RWSD-COM-1510
25 High Strength Compound Cable Penetrations Floor Seal RWSD-COM-1511
26 SoftSeal - 100mm Wall Multiple Service Penetrations Wall Seal RWSD-SS-0001
27 SoftSeal - Masonry Wall Multiple Service Penetrations Wall Seal RWSD-SS-0002
28 SoftSeal - 100mm Wall Pipe Penetrations Wall Seal RWSD-SS-0003
29 SoftSeal - Deflection Head with Double 50mm Ablative Coated Batt Multiple Service Penetrations Wall Seal RWSD-SS-0010
30 SoftSeal Linear Joint Floor Seal RWSD-SS-0101
31 Pipe Collar CE - 100mm Wall Pipe Penetrations Wall Seal RWSD-COL-0001
32 Pipe Collar CE - Double 50mm Ablative Coated Batt Pipe Penetrations Wall Seal RWSD-COL-0002
33 Pipe Collar CE - 50mm Ablative Coated Batt - Face Fix Pipe Penetrations Wall Seal RWSD-COL-0003
34 Pipe Collar CE - Single 50mm Ablative Coated Batt - 75mm Wall Pipe Penetrations Wall Seal RWSD-COL-0004
35 Pipe Collar CE - Floor Seal Pipe Penetrations Floor Seal RWSD-COL-0501
36 Pipe Collar CE - Profiled Metal Deck Pipe Penetrations Floor Seal RWSD-COL-0502
37 Pipe Collar CE - Double 50mm Ablative Coated Batt Pipe Penetrations Floor Seal RWSD-COL-0503
38 High Expansion Sealant - 50mm Ablative Coated Batt Pipe Penetrations Wall Seal RWSD-HE-0001

(V10/NOV22) 4
Page FIREPRO® product Application area Orientation of use Drawing no.
39 High Expansion Sealant - Double 50mm Ablative Coated Batt Multiple Service Penetrations Wall Seal RWSD-HE-0050
40 High Expansion Sealant - Sleeved CPVC Pipes Pipe Penetrations Wall Seal RWSD-HE-0051
41 High Expansion Sealant - CPVC Pipes Pipe Penetrations Wall Seal RWSD-HE-0054
42 High Expansion Sealant - 100mm Wall Pipe Penetrations Wall Seal RWSD-HE-0102
43 High Expansion Sealant - 120mm Wall Pipe Penetrations Wall Seal RWSD-HE-0103
44 High Expansion Sealant - 75mm Wall Conduits Wall Seal RWSD-HE-0110
45 High Expansion Sealant - 75mm Wall Pipe Penetrations / Conduits Wall Seal RWSD-HE-0111
46 High Expansion Sealant - Double 50mm Ablative Coated Batt Multiple Service Penetrations Floor Seal RWSD-HE-0501
47 High Expansion Sealant - 150mm Floor Sealed Both Side Multiple Service Penetrations Floor Seal RWSD-HE-0601
48 High Expansion Sealant - 150mm Floor Sealed Top Side Multiple Service Penetrations Floor Seal RWSD-HE-0602
49 Insulated Fire Sleeve - Ablative Coated Batt Seals Pipe Penetrations Wall Seal RWSD-IFS-0001
50 Insulated Fire Sleeve - Ablative Coated Batt Single Sided Pipe Penetrations Wall Seal RWSD-IFS-0002
51 Insulated Fire Sleeve - Angled Pipes (SoftSeal) Pipe Penetrations Wall Seal RWSD-IFS-0003
52 Insulated Fire Sleeve - Flexible Walls Pipe Penetrations Wall Seal RWSD-IFS-0101
53 Insulated Fire Sleeve - Double 50mm Ablative Coated Batt Pipe Penetrations Floor Seal RWSD-IFS-0501
54 Insulated Fire Sleeve - 150mm Floor Pipe Penetrations Floor Seal RWSD-IFS-0601
55 Oval Insulated Fire Sleeve -Flexible Wall / Softseal Oval Duct Penetrations Wall Seal RWSD-IFS-1003
56 Pipe Wrap CE - 100mm Wall Pipe Penetrations Wall Seal RWSD-PW-0001
57 Pipe Wrap CE - 150mm Floor Pipe Penetrations Floor Seal RWSD-PW-0501
58 Pipe Wrap Roll - Double 50mm Ablative Coated Batt Pipe Penetrations Wall Seal RWSD-PWR-0001
59 Pipe Wrap Roll - Double 50mm Ablative Coated Batt Insulated Pipe Penetrations Wall Seal RWSD-PWR-0002
60 Pipe Wrap Roll - Face Fix 50mm Ablative Coated Batt Insulated Pipe Penetrations Wall Seal RWSD-PWR-0101
61 Pipe Wrap Roll - 100mm Wall Pipe Penetrations Wall Seal RWSD-PWR-0201
62 Pipe Wrap Roll - 150mm Floor Pipe Penetrations Floor Seal RWSD-PWR-0502
63 Acoustic Intumescent Sealant Linear Joint Seals Wall & Floor Seals RWSD-AIS-0001
64 Acoustic Intumescent Sealant - 75mm Wall Sleeved Services / Cables Wall Seal RWSD-AIS-0101
65 Acoustic Intumescent Sealant - 75mm Wall Cable Penetrations Wall Seal RWSD-AIS-0110
66 Acoustic Intumescent Sealant - 75mm Wall Pipe Penetrations Wall Seal RWSD-AIS-0120
67 Acoustic Intumescent Sealant - 100mm Wall Cable Penetrations Wall seal RWSD-AIS-0210
68 Acoustic Intumescent Sealant - 100mm Wall Cables / Pipe Penetrations Wall Seal RWSD-AIS-0220
69 Acoustic Intumescent Sealant - 100mm Wall H&V Lagged Pipe Penetrations Wall Seal RWSD-AIS-0221
70 Acoustic Intumescent Sealant - Masonry Wall Sleeved Services Pipes Wall Seal RWSD-AIS-0301
71 Ablative Coated Batt with EZ Path EZ Path Cable Transit Wall Seal RWSD-EZP-0001
72 Ablative Coated Batt with EZ Path & Cover Plate EZ Path Cable Transit Wall Seal RWSD-EZP-0002
73 Firestop Compound with EZ Path EZ Path Cable Transit Floor Seal RWSD-EZP-0501
74 Linear & Trapezoidal Fire Stops Linear Joint Seals Wall Seal RWSD-LTF-0001
75 SP Firestop Systems Linear Joint Seal Wall & Floor Seal RWSD-SP-0001
76 SP Firestop Systems - Masonry Support Angle Penetration Linear Joint Seal Floor Seal RWSD-SP-0101
77 SP Firestop Systems SP Plus Penetrations Linear Joint Seal - Pipe Penetrations Floor Seal RWSD-SP-0102

5
ROCKWOOL® Fire Stopping Guide
1. ROCKWOOL will not support the mixing of different fire protection manufacturers systems/products of any type in line with ASFP
recommendations (ASFP Advisory Note 6), unless proven by fire testing at an accredited fire test laboratory.
2. ROCKWOOL products should be installed in accordance with the relevant product data sheet and within the field of application identified
within the standard details. For applications that fall outside of the parameters identified in the standard details or data sheets please contact
ROCKWOOL for further guidance.
3. Some on-site applications may be outside the scope of the standard detail pack. Please contact ROCKWOOL in these instances as we may be
able to offer a manufacturer technical evaluation. Technical evaluations are an appraisal of the likely performance of the installed ROCKWOOL
products in that application when subjected to a fire resistance test. They are offered in lieu of direct formal testing and are based upon
ROCKWOOL’s experiences of product performance during fire resistance testing. For this reason, before installation, technical evaluations
used on-site should be reviewed and accepted by Building Control and/or the scheme Fire Officer or the overseeing body for the project.
ROCKWOOL have adopted the processes outlined in the PFPF guide to manage the conflict of interest inherent with a manufacturers technical
evaluation compared to an assessment developed by UKAS accredited third party, allowing for a clear a rigorous examination of the proposal
by the approving body
4. All openings for penetrations within the dry lining system shall be framed and lined. As a reflection of the fire test standard, all partitions are
based upon single-skin, or double-skin flexible wall constructions. Shaft walls are not covered by standard flexible wall constructions and
should be treated independently. For the interchangeability of tested wall types please refer to ASFP Advisory Note 15. Face-fix options, with
ROCKWOOL Ablative Coated Batt, are available, but please check for its suitability against the site conditions.
5. For solutions in sandwich panel or composite wall constructions please contact ROCKWOOL technical.
6. Design of the opening for penetrations, and its fire stopping, should correspond to the integrity and insulation requirements of the host wall or
floor, unless leniency on the insulation rating is provided by the fire officer or overseeing body via a derogation.
7. Under the CPR it is a requirement that fire dampers are CE marked and as such that they are installed (and fire stopped) in line with the
relevant damper manufacturer’s installation guides. Damper manufacturers can now provide a tested fire stopping solution for sealing
around their damper systems. Therefore, ROCKWOOL’s default position is to guide the Client and/or Installer to contact the relevant damper
manufacturer for its tested and certified fire stopping solution.
8. Services of different types can pass through the same penetration seal, with the exception of ducts and dampers which should pass exclusively
through its own opening, as per the EN test guidance. Where services of different types pass through the same opening (i.e. a duct passes
through the same opening as a pipe) please contact ROCKWOOL.
9. Service support positions should be installed as a reflection of the fire test as per industry and ASFP guidance (ASFP Advisory Note 8). Support
for services passing through walls should be within 400mm on each side. Services passing through floors should be supported above the floor.
10. With reference to penetration spacings, please refer to the performance tables within the relevant ROCKWOOL standard detail. If no
dimension is given, for service or aperture separation, then the separation is 100mm in line with BS EN 1366-3:2021.
11. In line with BS EN 1366-3:2021 steel cable carriers, ladders and/or trays can be any width. Please refer to the relevant standard detail for the
limiting performance of cable trays, ladders and cables.

(V10/NOV22) 6
SINGLE 50MM ABALTIVE COATED BATT 100MM WALL
Classification Spacing
Service type Substrate Seal Service treatment Identical
Integrity Insulation Aperture
Services
Bl ank seal ≤ 1200 x 1200 60 60 N/A N/A
Electrical cables ≤ Ø ≤15mm 60 60 55mm 0mm
Ø 16mm - 21mm 60 30 55mm 0mm
Ø 22mm - 50mm 60 60 55mm 0mm
Ø 51mm - 80mm 60 30 0mm 0mm
Electrical cables Ø 16mm - 21mm
Additional pattress to both 60 60 55mm 0mm
faces
Ø 51mm - 80mm 60 60 0mm 0mm
Cabl e tray ≤ 500mm (w) x 60mm (h) x 100mm Flexible 1no, 50mm
60 30 55mm 0mm
1.5mm (t) Wall Construction Abl ative
Cable ladder ≤ 350mm (w) x 125mm (d) x or Masonry Wal l Coated Batt
60 60 0mm 0mm
1.5mm (t)
Tel ecomm cabl es ≤ Ø 100mm bundle 60 60 55mm 0mm
Unsheathed cables ≤ Ø 24mm 60 30 55mm 0mm
Steel or copper conduits ≤ Ø 16mm 60 - 55mm 0mm
Plastic conduits ≤ Ø 16mm 60 30 55mm 0mm
Steel pipe ≤ 219mm 1000mm length of 25mm H&V 60 60 0mm 0mm
Copper pipe ≤ 159mm pipe section (L/S) 60 60 0mm 0mm
Copper & Steel pipes ≤ 159mm 60 - 0mm 100mm

(V10/NOV22) 7
SINGLE 50MM ABALTIVE COATED BATT 75MM WALL - PIPE PENETRATIONS

Classification Spacing
Service type Substrate Seal Service Treatment
Identical
Integrity Insulation Aperture
Services
Bl ank seal ≤ 1200 x 1200 30 30 N/A N/A
N/A
≤ 600 x 900 60 60 N/A N/A
Steel pipe ≤ 219mm 60 60 0mm 0mm
Copper pipe ≤ 159mm 75mm thick flexible wall 1000mm length of 25mm H&V pipe
50mm Ablative Coated Batt 60 60 0mm 0mm
construction section L/S
Copper pipe ≤ 42mm 60 60 0mm 0mm
Copper & Steel pipe ≤ 159mm N/A 60 - 0mm 100mm
CPVC ≤ 73mm x 11mm High Expansion Sealant 20mm annular -
60 60 40mm 70mm
full depth (50mm)
SINGLE 50MM ABALTIVE COATED BATT 75MM WALL - CABLES
Electrical cables ≤ Ø ≤21mm 30 30 0mm 0mm
≤ Ø 22-50mm 30 30 0mm 0mm
≤ Ø 51 - 80mm 30 30 0mm 0mm
Perforated Tray ≤ 500mm (w) x 25mm (d) x
30 30 0mm 0mm
1.0mm (t)
Cable ladder ≤ 350mm (w) x 125mm (d) x N/A 30 30 0mm 0mm
1.5mm (t)
Tel ecomm cabl es ≤ Ø 100mm bundle 75mm thick flexible wall
50mm Ablative Coated Batt 30 30 0mm 0mm
construction
Unsheathed cables ≤ Ø 24mm 30 30 0mm 0mm
PVC conduits ≤ Ø 16mm 30 30 0mm 0mm
Copper Conduits ≤ Ø 16mm 30 - 0mm 0mm
Steel Trunking ≤ 150mm x 150mm 60 60 0mm 100mm
300mm length full depth RWA45 (45
≤ 300mm x 150mm kg/m3) stonewool positioned centrally
to the seal 60 30 0mm 100mm

(V10/NOV22) 8
DOUBLE 50MM ABALTIVE COATED BATT 100MM WALL - NON COMBUSTIBLE PIPES
Classification Spacing
Service type Substrate Seal Service Treatment Identical
Integrity Insulation Aperture
Services
Bl ank seal ≤ 1200 x 900 100mm Flexible Wall 120 120 N/A N/A
Construction or Masonry
≤ 2600 x 2600 N/A 90 90 N/A N/A
Wal l
≤ 1100 x 1100 150mm Masonry Wall 120 120 N/A N/A
Steel pipe ≤ 168mm 1000mm length of 40mm H&V 120 120 0mm 0mm
Copper pipe ≤ 108mm pipe section L/S 120 120 0mm 0mm
≤ 168mm
Steel pipe 100mm Flexible Wall 120 90 0mm 0mm
Construction or Masonry 2 No. 50mm
1000mm length of 25mm H&V
≤ 108mm Abl ative Coated
Copper pipe Wal l pipe section L/S 120 90 0mm 0mm
Batts
Copper pipe ≤ 42 120 120 100mm 100mm
Steel pipes ≤ 219mm N/A 120 15 0mm 100mm
Steel pipe ≤ 610mm 1000mm length of 40mm H&V
180 60 0mm 100mm
pipe section L/S
Steel pipe ≤ 610mm 100mm Masonry Wall
N/A 180 15 0mm 100mm
Construction
Steel pipe ≤ 324mm 300mm length of Ablative Liquid 120 45 100mm 100mm
Copper pipe ≤ 159mm 2mm DFT (L/S) 120 15 100mm 100mm
DOUBLE 50MM ABALTIVE COATED BATT 100MM WALL - CABLES
Electrical cables ≤ Ø ≤21mm 120 90 0mm 0mm
≤ Ø 22-50mm 120 60 0mm 0mm
≤ Ø 51 - 80mm 90 60 0mm 0mm
Perforated Tray ≤ 500mm (w) x 60mm (d) x
1.0mm (t) 120 90 0mm 0mm

Cable ladder ≤ 350mm (w) x 125mm (d) 100mm Flexible Wall


x 1.5mm (t) Construction or Masonry N/A 90 90 0mm 0mm
Wal l
Tel ecomm cabl es ≤ Ø 100mm bundle 120 90 0mm 0mm
Unsheathed cables ≤ Ø 24mm
2 No. 50mm 120 45 0mm 0mm
Abl ative Coated
PVC conduits ≤ Ø 16mm Batts 120 90 0mm 0mm
Copper Conduits ≤ Ø 16mm 120 15 0mm 0mm
Electrical cables ≤ Ø ≤21mm 120 120 100mm 0mm
≤ Ø 22mm - 80mm 120 90 100mm 0mm
Cabl e tray ≤ 500mm (w) x 60mm (h) x
1.5mm (t) 120 120 100mm 0mm
40mm thick 45kg/m3 stonewool
150mm Masonry Wall
Cable ladder ≤ 350mm (w) x 125mm (d) lagging (RWA45) L/I 300mm
x 1.5mm (t) 120 120 100mm 0mm

Tel ecomm cabl es ≤ Ø 100mm bundle 120 120 100mm 0mm


Unsheathed cables ≤ Ø 24mm 120 120 100mm 0mm

(V10/NOV22) 9
DOUBLE 50MM ABALTIVE COATED BATT 100MM WALL - SINGLE SIDED INSTALL
Classi fi cati on Spacing
Servi ce type Substrate Seal Servi ce Treatment Identical
Integrity Insulation Aperture
Servi ces
Blank seal ≤ 1200 x 600 120 90 N/A N/A
Electrical cables ≤ Ø ≤21mm 120 60 0mm 0mm
≤ Ø 22-50mm 120 60 0mm 0mm
≤ Ø 51 - 80mm 90 60 0mm 0mm
Perforated Tray ≤ 500 x 60 x 1.0mm 120 60 0mm 0mm
Cable ladder ≤ 350mm (w) x 125mm (d)
N/A 90 90 0mm 0mm
x 1.5mm (t)
Telecomm cables ≤ Ø 100mm bundle 120 90 0mm 0mm
Unsheathed cables ≤ Ø 24mm 120 45 0mm 0mm
PVC conduits ≤ Ø 16mm
120 90 0mm 0mm

Copper Conduits ≤ Ø 16mm 120 15 0mm 0mm

Steel ≤ 168mm 120 120 0mm 0mm

1000mm length of 40mm H&V pipe


Copper ≤ 42 120 120 0mm 0mm
secti on L/S

Copper ≤ 108mm 100mm Flexible Wall 2 No. 50mm Ablative 120 90 0mm 0mm
Construction or Coated Batts (Single
Masonry Wall sided install) 1000mm length of 40mm H&V pipe
Copper ≤ 108mm 120 120 0mm 0mm
secti on C/S

Steel ≤ 168mm 120 60 0mm 0mm

1000mm length of 25mm H&V pipe


Copper ≤ 42mm 120 90 0mm 0mm
secti on L/S

Copper ≤ 108mm 120 30 0mm 0mm

Steel ≤ 60mm 120 120 0mm 100mm


1000mm length of 20mm H&V pipe
secti on L/S
Copper ≤ 15mm 120 120 0mm 100mm

Copper ≤ 159mm 120 - 0mm 100mm


N/A
Steel ≤ 219mm 120 15 0mm 100mm
63mm - 5 No. small High expansion sealant - 20mm
Pvc flexible conduit ≤ 90 90 0mm 0mm
½ cables ≤21mm annular 100mm depth
100mm x 100mm - with
300mm length of 45 Kg/m³
Steel trunking ≤ 100mm cable bundle 120 90 0mm 100mm
stonewool
(≤21mm)

WF 385718 - sealed non fi re si de


DOUBLE 50MM ABALTIVE COATED BATT 100MM WALL - CABLES
Electrical cables ≤ Ø ≤21mm 120 30 0mm
≤ Ø 22-50mm 120 60 0mm

(V10/NOV22)
Soli d Tray
≤ Ø 51 - 80mm
500
120
120
60
60
0mm
0mm 10
Perforated Tray ≤ 500 x 25 x 1.0mm 100mm Flexible Wall 120 60 0mm
2 No. 50mm ablative
Cable ladder ≤ 350mm (w) x 125mm (d) Construction or N/A
Coated Batts 120 90 0mm
x 1.5mm (t) Masonry Wall
Telecomm cables ≤ Ø 100mm bundle 120 90 0mm
Unsheathed cables ≤ Ø 24mm 120 60 0mm
DOUBLE 50MM ABALTIVE COATED BATT SINGLE SKIN 100MM WALL - NON COMBUSTIBLE PIPES

Classi fi cati on Spacing


Servi ce type Substrate Seal Servi ce Treatment
Identical
Integrity Insulation Aperture
Servi ces
Blank seal ≤ 1200 x 1200 N/A 60 60 N/A N/A
≤ 168mm
Steel pi pe 60 60 0mm 0mm
100mm Flexible Wall 2 No. 50mm Ablative Coated 1000mm length of 25mm H&V pipe
Copper pipe ≤ 108mm 60 60 0mm 0mm
Construction or Masonry Wall Batts secti on L/S
Copper pipe ≤ 42 60 60 100mm 100mm
Steel pi pes ≤ 219mm N/A 60 15 0mm 100mm

DOUBLE 50MM ABALTIVE COATED BATT SINGLE SKIN 100MM WALL - CABLES
Electrical cables ≤ Ø ≤21mm 60 60 0mm 0mm
≤ Ø 22-50mm 60 60 0mm 0mm
≤ Ø 51 - 80mm 60 60 0mm 0mm
Perforated Tray ≤ 500mm (w) x 25mm (d) x 1.0mm
(t) 60 60 0mm 0mm

Cable ladder ≤ 350mm (w) x 125mm (d) x 1.5mm


N/A 60 60 0mm 0mm
(t)
Telecomm cables ≤ Ø 100mm bundle 100mm Flexible Wall 2 No. 50mm Ablative Coated 60 60 0mm 0mm
Unsheathed cables ≤ Ø 24mm Construction or Masonry Wall Batts
60 45 0mm 0mm
PVC conduits ≤ Ø 16mm 60 60 0mm 0mm
Copper Conduits ≤ Ø 16mm
60 15 0mm 0mm

Steel Trunking ≤ 100mm x 100mm (Small Cables


≤21mm) 300mm length full depth of RWA45
(45 kg/m3) positioned centrally to 60 60 0mm 30mm
seal

(V10/NOV22) 11
(V10/NOV22) 12
DOUBLE 50MM ABALTIVE COATED BATT FACE FIX
Classification Spacing
Service type Substrate Seal Service Treatment
Integrity Insulation Aperture Identical Services
Blank seal ≤ 1000 x 1000 120 120 N/A N/A
Electrical cables ≤ Ø ≤21mm 120 90 0mm 0mm
≤ Ø 22-50mm 120 60 0mm 0mm
≤ Ø 51 - 80mm 90 60 0mm 0mm
Perforated Tray ≤ 500 mm (w) x 25mm (h) x
120 90 0mm 0mm
1.0mm (t)
N/A
Cable ladder ≤ 350mm (w) x 125mm (d) x
90 90 0mm 0mm
1.5mm (t)
Telecomm cables ≤ Ø 100mm bundle 120 90 0mm 0mm
Unsheathed cables ≤ Ø 24mm 120 45 0mm 0mm
PVC conduits ≤ Ø 16mm 120 90 0mm 0mm
Copper Conduits ≤ Ø 16mm 120 15 0mm 0mm
Electrical cables ≤ Ø ≤80mm 120 120 100mm 0mm
Cable tray ≤ 500mm (w) x 60mm (h) x 100mm Flexible Wall
120 120 100mm 0mm
1.5mm (t) Construction or Masonry
Cable ladder ≤ 350mm (w) x 125mm (d) x Wall 40mm thick 45kg/m3 120 120 100mm 0mm
1.5mm (t) stonewool lagging
Telecomm cables ≤ Ø 100mm bundle 2 No. 50mm Ablative (RWA45) L/I 300mm 120 120 100mm 0mm
Steel or copper conduits ≤ Ø 16mm Coated Batts Face Fixed 120 120 100mm 0mm
Plastic conduits ≤ Ø 16mm 120 120 100mm 0mm
Unsheathed cables ≤ Ø 24mm 120 120 100mm 0mm
Steel pipe ≤ 168mm 120 120 0mm 0mm
1000mm length of 40mm
Copper pipe ≤ 108mm H&V pipe section L/S 120 120 0mm 0mm
Steel pipes ≤ 219mm N/A 120 15 0mm 0mm
Steel pipe ≤ 168mm 90 60 0mm 0mm
≤ 108mm 1000mm length of 25mm
Copper pipe 90 30 0mm 0mm
H&V pipe section L/S
Copper pipe ≤ 42 120 120 100mm 100mm
Steel pipe ≤ 610mm
1000mm length of 40mm
180 60 0mm 100mm
H&V pipe section L/S
Steel pipe ≤ 610mm 100mm Masonry Wall
N/A 180 15 0mm 100mm
Construction
Steel pipe ≤ 324mm 120 45 100mm 100mm
300mm length of Ablative
Copper pipe ≤ 159mm Liquid 2mm DFT (L/S) 120 20 100mm 100mm

(V10/NOV22) 13
DOUBLE 50MM ABALTIVE COATED BATT 150MM FLOOR
Classification Spacing
Service type Substrate Seal Service treatment Identical
Integrity Insulation Aperture
Services
Blank seal ≤ 1600 x 1100
120 120 N/A N/A
Electrical cables ≤ Ø ≤15mm 120 90 60mm 0mm
Ø 16mm - 21mm 120 30 60mm 0mm
Ø 22mm - 50mm 120 30 60mm 0mm
Ø 51mm - 80mm 120 30 60mm 0mm
Cable tray ≤ 500mm (w) x 60mm (h) x 1.5mm N/A
120 60 60mm 0mm
(t)
Cable ladder ≤ 350mm (w) x 125mm (d) x
120 60 60mm 0mm
1.5mm (t)
Telecomm cables ≤ Ø 100mm bundle 120 120 60mm 0mm
Steel or copper conduits ≤ Ø 16mm 120 - 60mm 0mm
Plastic conduits ≤ Ø 16mm 2no, 50mm Ablative 120 90 60mm 0mm
Electrical cables Ø ≤15mm Coated Batt 120 120 60mm 0mm
Ø 16mm - 80mm 150mm Concrete 120 60 60mm 0mm
Cable tray ≤ 500mm (w) x 60mm (h) x 1.5mm Floor (800 kg/m3)
Additional 50mm pattress to both faces 120 90 60mm 0mm
(t)
of batt
Cable ladder ≤ 350mm (w) x 125mm (d) x
120 90 60mm 0mm
1.5mm (t)
Unsheathed cables ≤ Ø 17mm 120 90 60mm 0mm
Copper or steel pipe ≤ Ø 42mm 120 120 0mm 0mm
Copper or steel pipe ≤ Ø 108mm 25mm thick H&V pipe section 1000mm 120 120 0mm 0mm
Steel pipe ≤ Ø 168mm length L/S 120 120 0mm 0mm
Steel pipe ≤ Ø 219mm 120 90 0mm 100mm
Steel pipe ≤ Ø 219mm 40mm thick H&V pipe section 1000mm
120 120 0mm 100mm
length L/S
Steel or Copper pipe ≤ 42mm 40mm thick 40 Kg/m3 stonewool
**700mm x 1100mm
(RWA45) lagging 300mm both sides of 120 120 100mm 100mm
Max void**
seal L/I

(V10/NOV22) 14
SINGLE 60MM ABALTIVE COATED BATT 100MM WALL
Classi fi cati on Spacing
Servi ce type Substrate Seal Servi ce treatment Identical
Integrity Insulation Aperture
Servi ces
Blank seal ≤ 1200mm x 600mm 100mm Flexible Wall N/A 120 120 N/A N/A
≤ 2.6m x 2.6m Construction or N/A 120 90 N/A N/A
≤ 1200 x 1200 Masonry Wall N/A 60 60 N/A N/A
Electrical cables ≤ Ø ≤21mm N/A 120 60 0mm 0mm
Ø 22mm - 50mm N/A 120 60 0mm 0mm
Ø 51mm - 80mm N/A 60 60 0mm 0mm
150mm masonry wall
Telecomm cables ≤ Ø 100mm bundle N/A 60 60 0mm 0mm
Cable ladder ≤ 350mm (w) x 125mm (d) x
N/A 120 60 0mm 0mm
1.5mm (t)
Electrical cables ≤ Ø ≤21mm N/A 90 60 0mm 0mm
Ø 22mm - 50mm N/A 60 60 55mm 0mm
Ø 51mm - 80mm N/A 60 30 0mm 0mm
Ø 51mm - 80mm
Additional pattress to both faces 60 60 0mm 0mm
Cable tray ≤ 500mm (w) x 60mm (h) x 1no, 60mm Ablative
Coated Batt N/A 60 30 0mm 0mm
1.5mm (t)
Cable ladder ≤ 350mm (w) x 125mm (d) x N/A 60 30 0mm 0mm
Telecomm cables ≤ Ø 100mm bundle N/A 60 30 0mm 0mm
Unsheathed cables ≤ Ø 24mm 100mm Flexible Wall N/A 60 30 0mm 0mm
Steel or copper conduits ≤ Ø 16mm Construction or N/A 90 - 0mm 0mm
Plastic conduits ≤ Ø 16mm Masonry Wall N/A 90 60 0mm 0mm
Steel trunking ≤ 300mm x 150mm x 1mm
(Small cables ≤ 21mm or 300mm length of 45Kg/m3
100mm bundle) stonewool (RWA45) positioned 120 30 100mm 100mm
centrally to the seal

Steel pi pe ≤ 219mm 1000mm length of 25mm H&V 60 60 0mm 0mm


Copper pipe ≤ 159mm pi pe secti on (L/S) 60 60 0mm 0mm
Copper pipe ≤ 108mm N/A 120 - 100mm 100mm
Steel pi pe ≤ 168mm N/A 120 - 100mm 100mm

(V10/NOV22) 15
DOUBLE 60MM ABALTIVE COATED BATT 120MM WALL - NON COMBUSTIBLE PIPES
Classification Spacing
Service type Substrate Seal Service Treatment Identical
Integrity Insulation Aperture
Services
Bl ank seal ≤ 1200 x 900 100mm Flexible 120 120 N/A N/A
≤ 2600 x 2600 Wal l 90 90 N/A N/A
N/A
≤ 1100 x 1100 150mm Masonry
120 120 N/A N/A
Wal l
Steel pipe ≤ 168mm 1000mm length of 120 120 0mm 0mm
Copper pipe ≤ 108mm 100mm Flexible 40mm H&V pipe 120 120 0mm 0mm
Steel pipe ≤ 168mm Wal l 1000mm length of 90 60 0mm 0mm
Copper pipe ≤ 108mm Construction or 2 No. 60mm 25mm H&V pipe 90 30 0mm 0mm
Copper pipe ≤ 42 Masonry Wal l abl ative Coated section L/S 120 120 100mm 100mm
Batts
Steel pipes ≤ 219mm N/A 120 15 0mm 100mm
Steel pipe ≤ 610mm 1000mm length of
40mm H&V pipe 120 60 0mm 100mm
100mm Masonry
section L/S
Wal l
Steel pipe ≤ 610mm Construction N/A 120 15 0mm 100mm
Steel pipe ≤ 324mm 300mm length of 120 45 100mm 100mm
Copper pipe ≤ 159mm Ablative Liquid 2mm 120 15 100mm 100mm
DOUBLE 60MM ABALTIVE COATED BATT 120MM WALL - CABLES
Electrical cables ≤ Ø ≤21mm 120 90 0mm 0mm
≤ Ø 22-50mm 120 60 0mm 0mm
≤ Ø 51 - 80mm 90 60 0mm 0mm
Perforated Tray ≤ 500 x 25 x 1.0mm 100mm Flexible 120 90 0mm 0mm
Cable ladder ≤ 350mm (w) x 125mm (d) Wal l
x 1.5mm (t) N/A 90 90 0mm 0mm
Construction or
Tel ecomm cabl es ≤ Ø 100mm bundle Masonry Wal l 120 90 0mm 0mm
Unsheathed cables ≤ Ø 24mm 120 45 0mm 0mm
PVC conduits ≤ Ø 16mm 2 No. 60mm 120 90 0mm 0mm
Copper Conduits ≤ Ø 16mm abl ative Coated 120 15 0mm 0mm
Electrical cables ≤ Ø ≤21mm Batts 120 120 100mm 0mm
≤ Ø 22mm - 80mm 120 90 100mm 0mm
Cabl e tray ≤ 500mm (w) x 60mm (h) x
1.5mm (t) 40mm thick 45kg/m3 120 120 100mm 0mm
150mm Masonry
stonewool l agging
Cable ladder ≤ 350mm (w) x 125mm (d) Wal l
(RWA45) L/I 300mm 120 120 100mm 0mm
x 1.5mm (t)
Tel ecomm cabl es ≤ Ø 100mm bundle 120 120 100mm 0mm
Unsheathed cables ≤ Ø 24mm 120 120 100mm 0mm

(V10/NOV22) 16
DOUBLE 60MM ABALTIVE COATED BATT FACE FIX
Classification Spacing
Service type Substrate Seal Service Treatment Identical
Integrity Insulation Aperture
Services
Blank seal ≤ 1000 x 1000 120 120 N/A N/A
Electrical cables ≤ Ø ≤21mm 120 90 0mm 0mm
≤ Ø 22-50mm 120 60 0mm 0mm
≤ Ø 51 - 80mm 90 60 0mm 0mm
Perforated Tray ≤ 500 mm (w) x 25mm (h) x
120 90 0mm 0mm
1.0mm (t)
N/A
Cable ladder ≤ 350mm (w) x 125mm (d)
90 90 0mm 0mm
x 1.5mm (t)
Telecomm cables ≤ Ø 100mm bundle 120 90 0mm 0mm
Unsheathed cables ≤ Ø 24mm 120 45 0mm 0mm
PVC conduits ≤ Ø 16mm 120 90 0mm 0mm
Copper Conduits ≤ Ø 16mm 120 15 0mm 0mm
Electrical cables ≤ Ø ≤80mm 120 120 100mm 0mm
Cable tray ≤ 500mm (w) x 60mm (h) x
100mm Flexible Wall 120 120 100mm 0mm
1.5mm (t)
Construction or
Cable ladder ≤ 350mm (w) x 125mm (d) 40mm thick 45kg/m3
Masonry Wall 120 120 100mm 0mm
x 1.5mm (t) stonewool lagging (RWA45)
Telecomm cables ≤ Ø 100mm bundle L/I 300mm 120 120 100mm 0mm
Steel or copper conduits ≤ Ø 16mm 2 No. 60mm Ablative 120 120 100mm 0mm
Plastic conduits ≤ Ø 16mm Coated Batts Face Fixed
120 120 100mm 0mm
Unsheathed cables ≤ Ø 24mm 120 120 100mm 0mm
≤ 168mm
Steel pipe 120 120 0mm 0mm
1000mm length of 40mm
≤ 108mm H&V pipe section L/S
Copper pipe 120 120 0mm 0mm

Steel pipes ≤ 219mm N/A 120 15 0mm 0mm


Steel pipe ≤ 168mm 90 60 0mm 0mm
Copper pipe ≤ 108mm 1000mm length of 25mm 90 30 0mm 0mm
Copper pipe ≤ 42 H&V pipe section L/S
120 120 100mm 100mm
Steel pipe ≤ 610mm
1000mm length of 40mm
180 60 0mm 100mm
H&V pipe section L/S

Steel pipe ≤ 610mm 100mm Masonry Wall N/A 180 15 0mm 100mm
Construction
Steel pipe ≤ 324mm 120 45 100mm 100mm
Copper pipe ≤ 159mm 300mm length of Ablative
Liquid 2mm DFT (L/S) 120 20 100mm 100mm

(V10/NOV22) 17
(V10/NOV22) 18
SINGLE 60MM ABALTIVE COATED BATT 150MM FLOOR
Classification Spacing
Service type Substrate Seal Service treatment Identical
Integrity Insulation Aperture
Services
Blank seal ≤ 1200 x 600 240 120 N/A N/A
Steel pipe ≤ 168mm 1no, 60mm 240 - 100mm 100mm
150mm Concrete
Copper pipe ≤ 108mm Ablative 240 - 100mm 100mm
Floor (800 kg/m3)
Steel pipe ≤ 168mm Coated Batt 40mm thick H&V pipe section 240 120 100mm 100mm
Copper pipe ≤ 108mm L/I & L/S 240 120 100mm 100mm

(V10/NOV22) 19
60 Minutes 90 Minutes 120 Minutes 240 Minutes
Service type
Integrity Insulation Integrity Insulation Integrity Insulation Integrity Insulation
75mm Blank seal up to 500 mm x 500 mm* ü ü ü ü ü ü
100mm Blank seal up to 750 mm x 750 mm* ü ü ü ü ü ü ü ü
75mm Seal with services no reinforcement - 500mm x any length* ü ü ü ü ü ü
100mm Seal with services, Simply Reinforced - 1500mm x any length* ü ü ü ü ü ü ü ü
Cable Tray ≤ 500mm x 50mm ü ü ü ü ü ü
Bunched cables ≤100 mm ü ü ü ü
Electrical cables up to 21mm ü ü ü ü ü ü
Electrical cables 21mm - 50mm ü ü ü ü ü
Electrical cables 51mm - 80mm ü ü ü ü
Steel pipes ≤165 Unlagged ü ü ü ü
Steel pipes ≤165 lagged with Fire Tube ü ü ü ü ü ü ü
Copper pipes ≤ 108 mm lagged with Fire Tube ü ü ü ü ü ü ü
Copper pipes ≤ 108 mm unlagged ü ü ü ü
≤160mm PVC, uPVC, PP, MDPE & HDPE pipe Rockwool Pipe Wrap ü ü ü ü ü ü
* Load bearing performance in line with BS6399 for workspaces and cupboards

(V10/NOV22) 20
Service Substrate Supporting Performance
Penetration Type/Size (mm) Formation Insulation Thickness (mm) Seal
Separation Separation construction Integrity Insulation
Copper 42 150mm thick 240 120
40mm H&V pipe lagging - 500mm to top 100mm thick ROCKWOOL Standard 0mm 0mm
Copper 43 - 159 Cluster AAC concrete 120 45
of slab only Compound (From lagging) (From lagging)
Steel < 219 slab (650 kg/m³) 240 120

(V10/NOV22) 21
Penetration Type/Size Service Substrate Supporting Performance
Formation Insulation Thickness (mm) Seal
(mm) Separation Separation construction Integrity Insulation
40mm H&V pipe section -
0mm 0mm 150mm thick AAC
Steel < 219 Single 1000mm length through the 100mm thick ROCKWOOL 120 120
(Between (Between concrete slab (650
seal (L/S) Standard Compound
sleeves) sleeves) kg/m³)
Steel < 219 Single N/A 120 15

(V10/NOV22) 22
HIGH STRENGTH COMPOUND 150MM THICK
Classification Spacing
Service type Substrate Seal Service treatment Identical
Integrity Insulation Aperture
Services
Bl ank seal ≤ 2.6m x 2.6m***
240 240 N/A N/A
150mm thick
150mm thick masonry
Copper pipe ≤ 42 High Strength 240 240 0mm 0mm
wal l 1000mm length of
Copper Pipe ≤ 108mm Compound 240 240 0mm 0mm
25mm H&V pipe
Steel pipe ≤ 168mm 240 240 0mm 0mm
section L/S
Steel pipe ≤ 219mm 240 240 0mm 0mm
HIGH STRNEGTH COMPOUND 150MM THICK - CABLES
Electrical cables ≤ Ø 21mm 240 120 0mm N/A
Ø 22mm - 50mm 240 120 0mm N/A
Ø 51mm - 80mm 240 120 0mm N/A
Cabl e tray ≤ 500mm (w) x 60mm (h) x
240 240 0mm N/A
1.5mm (t) 150mm thick
150mm thick masonry
Cable ladder ≤ 350mm (w) x 125mm (d) x High Strength N/A
wal l 240 120 0mm N/A
1.5mm (t) Compound
Tel ecomm cabl es ≤ Ø 100mm bundle 240 120 0mm N/A
Unsheathed cables ≤ Ø 24mm 240 60 0mm N/A
Steel or copper conduits ≤ Ø 16mm 240 240 0mm N/A
Plastic conduits ≤ Ø 16mm 240 180 0mm N/A

(V10/NOV22) 23
RIGID FLOOR - HIGH STRENGTH COMPOUND
Classification Spacing
Service type Substrate Seal Size Seal Service treatment
Integrity Insulation Aperture Services
Copper pipe ≤ Ø 107mm (1.5 - 14.2mm wall thickness) 50mm thick Rocklap H&V Pipe
Section, min. 500mm length to 60 15 100 100
topside of seal
Steel pipe ≤ Ø 115mm (3.5 - 14.2mm wall thickness) 50mm thick Rocklap H&V Pipe 120 120
100 100
Ø 116 - 160mm (5 - 14.2mm wall thickness) Section, min. 500mm length to 120 90
Electrical cables ≤ Ø 21mm 100mm thick 25mm thick Duct Wrap insulation,
Ø 22mm - 50mm 150mm thick Max. 1800mm min. 500mm l ength to topside of 120 60 100 100
High Strength
Ø 51mm - 80mm rigid floor x 1800mm seal
Compound
Unsheathed cables ≤ Ø 24mm
25mm thick Duct Wrap insulation,
min. 500mm l ength to topside of 120 120 100 100
seal

(V10/NOV22) 24
RIGID FLOOR - HIGH STRENGTH COMPOUND WITH UPSTAND
Service Classification Spacing
Service type Substrate Seal Size Seal
treatment Integrity Insulation Aperture Services
Telecomm cables ≤ Ø 100mm bundle 100mm thick
High Strength 25mm thick
Compound Duct Wrap
150mm thick Max. 1800mm with 50mm insulation,
120 120 100 100
rigid floor x 1800mm thick High min. 500mm
Strength length to
Compound topside of seal
upstand

(V10/NOV22) 25
TABLE TO BE UPDATED WHEN NEW ASSESSMENT COMPLETED

60 Minutes 90 Minutes 120 Minutes


Service type
Integrity Insulation Integrity Insulation Integrity Insulation
Blank seal up to 800 mm x 800mm ü ü ü ü ü ü
Blank seal within 2 x 50mm ROCKWOOL Ablative Batt picture frame 800mm x 430mm ü ü ü ü ü ü
Electrical cables 21mm-50mm diameter ü ü ü ü
Electrical cables 51mm-80mm diameter ü ü ü
Cable tray and ladders ü ü ü ü
Bunched cables ≤100 mm ü ü ü ü ü ü
Unsheathed electrical cables ≤24 mm ü ü ü
Steel or copper conduits ≤16 mm ü ü ü
Steel pipes ≤160 mm diameter ü ü ü ü
Steel or copper pipes ≤40 mm ü ü ü ü ü ü
All services insulated with RWA45 40mm thick, 200mm either side of seal.
Please contact ROCKWOOL Technical department for the protection of plastic pipes

(V10/NOV22) 26
TABLE TO BE UPDATED WHEN NEW ASSESSMENT COMPLETED

60 Minutes 90 Minutes 120 Minutes


Service type
Integrity Insulation Integrity Insulation Integrity Insulation
Blank seal up to 1200 mm x 730mm ü ü ü ü ü ü
Blank seal within 2 x 50mm ROCKWOOL Ablative Batt picture frame 900mm x 530mm ü ü ü ü ü ü
Electrical cables ≤21mm diameter ü ü ü ü ü ü
Electrical cables 22mm-50mm diameter ü ü ü
Electrical cables 51mm-80mm diameter ü ü
Cable tray and ladders ü ü ü
Bunched cables ≤100 mm ü ü ü ü ü ü
Unsheathed electrical cables ≤24 mm ü ü ü ü ü ü
Steel or copper conduits ≤16 mm ü ü ü ü ü ü
Steel pipe 161mm - 200mm diameter ü 30 ü
Steel pipes ≤160 mm diameter ü ü ü ü ü ü
Steel or copper pipes ≤40 mm ü ü ü ü ü ü
All services insulated with RWA45 40mm thick, 200mm either side of seal.
Please contact ROCKWOOL Technical department for the protection of plastic pipes

(V10/NOV22) 27
(V10/NOV22) 28
DOUBLE 50MM ABALTIVE COATED BATT SOFTSEAL DEFLECTION HEAD 100MM WALL - NON COMBUSTIBLE PIPES
Classification Spacing
Service type Substrate Seal Service Treatment Identical
Integrity Insulation Aperture
Services
Blank seal ≤ 600 x 900
120 120 N/A N/A
N/A
≤ 1200 x 1200
120 90 N/A N/A

Steel Pipe ≤ 219mm 120 90


50mm soffit
Copper Pipe ≤ 159mm Double batt seal with 1000mm length of 25mm H&V 90 30 0mm
100mm thick flexible wall 0mm side
≤ 42mm SoftSeal deflection pipe section L/S 120 120
construction
Copper Pipe 108mm Head 120 120 0mm 100mm
Perforated Tray ≤ 500mm (w) x 25mm (d) x
N/A 120 60 100mm 100mm
1.0mm (t)
Telecomm cables ≤ Ø 100mm bundle High Expansion sealant 20mm
Annular / Min. 25mm depth to 120 120 100mm 100mm
both faces

(V10/NOV22) 29
(V10/NOV22) 30
Flexible / rigid wall
Test Service separation
Service type (min. 100mm thick)
Standard
Integrity Insulation Aperture Services
PVC pipes Ø 32 - 50mm (1.8mm wall thickness) wall
Ø 55 - 63mm (2.3 - 3mm wall thickness)
Ø 75 - 82mm (3.1 - 4.8mm wall thickness)
Ø 90 - 110mm (4.2 - 7.4mm wall thickness) 120 120 EN N/A 200mm
Ø 125mm (6mm wall thickness)
Ø 140mm (6.1 - 7.5mm wall thickness)
Ø 160mm (6.2 - 9.5mm wall thickness)
PP pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 EN N/A 200mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.5 - 8mm wall thickness)
Ø 160mm (4 - 14.6mm wall thickness)
PE pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 EN N/A 200mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.9 - 5.8mm wall thickness)
Ø 160mm (4.9 - 9.5mm wall thickness)

(V10/NOV22) 31
Flexible / rigid wall
Test Service separation
Service type (min. 100mm thick)
Standard
Integrity Insulation Aperture Services
PVC pipes Ø 32 - 50mm (1.8mm wall thickness)
Ø 55 - 63mm (2.3 - 3mm wall thickness)
Ø 75 - 82mm (3.1 - 4.8mm wall thickness)
Ø 90 - 110mm (4.2 - 7.4mm wall thickness) 120 120 EN 50mm 0mm
Ø 125mm (6mm wall thickness)
Ø 140mm (6.1 - 7.5mm wall thickness)
Ø 160mm (6.2 - 9.5mm wall thickness)
PP pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 EN 50mm 0mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.5 - 8mm wall thickness)
Ø 160mm (4 - 14.6mm wall thickness)
PE pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 EN 50mm 0mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.9 - 5.8mm wall thickness)
Ø 160mm (4.9 - 9.5mm wall thickness)

(V10/NOV22) 32
Flexible / rigid wall
Test Service separation
Service type (min. 100mm thick)
Standard
Integrity Insulation Aperture Services
PVC pipes Ø 32 - 50mm (1.8mm wall thickness)
Ø 55 - 63mm (2.3 - 3mm wall thickness)
Ø 75 - 82mm (3.1 - 4.8mm wall thickness)
Ø 90 - 110mm (4.2 - 7.4mm wall thickness) 120 120 EN 50mm 0mm
Ø 125mm (6mm wall thickness)
Ø 140mm (6.1 - 7.5mm wall thickness)
Ø 160mm (6.2 - 9.5mm wall thickness)
PP pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 EN 50mm 0mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.5 - 8mm wall thickness)
Ø 160mm (4 - 14.6mm wall thickness)
PE pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 EN 50mm 0mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.9 - 5.8mm wall thickness)
Ø 160mm (4.9 - 9.5mm wall thickness)

(V10/NOV22) 33
Flexible / rigid wall
Test Service separation
Service type (min. 75mm thick)
Standard
Integrity Insulation Aperture Services
PVC pipes Ø 32 - 50mm (1.8mm wall thickness)
Ø 55 - 63mm (2.3 - 3mm wall thickness)
Ø 75 - 82mm (3.1 - 4.8mm wall thickness) BS EN 1366-
60 60 50mm 0mm
Ø 90 - 110mm (4.2 - 7.4mm wall thickness) 3:2009
Ø 125mm (6mm wall thickness)
Ø 140mm (6.1 - 7.5mm wall thickness)
PP pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
BS EN 1366-
Ø 90 - 110mm (2.7 - 10mm wall thickness) 60 60 50mm 0mm
3:2009
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.5 - 8mm wall thickness)
Ø 160mm (4 - 14.6mm wall thickness)
PE pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
BS EN 1366-
Ø 90 - 110mm (2.7 - 10mm wall thickness) 60 60 50mm 0mm
3:2009
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.9 - 5.8mm wall thickness)
Ø 160mm (4.9 - 9.5mm wall thickness)

(V10/NOV22) 34
Rigid floor
Test Service separation
Service type (min. 150mm thick)
Standard
Integrity Insulation Aperture Services
PVC pipes Ø 32 - 50mm (1.8mm wall thickness)
Ø 55 - 63mm (2.3 - 3mm wall thickness)
Ø 75 - 82mm (3.1 - 4.8mm wall thickness)
Ø 90 - 110mm (4.2 - 7.4mm wall thickness) 240 240 EN N/A 200mm
Ø 125mm (6mm wall thickness)
Ø 140mm (6.1 - 7.5mm wall thickness)
Ø 160mm (6.2 - 9.5mm wall thickness)
PP pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 240 240 EN N/A 200mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.5 - 8mm wall thickness)
Ø 160mm (4 - 14.6mm wall thickness)
PE pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 240 240 EN N/A 200mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.9 - 5.8mm wall thickness)
Ø 160mm (4.9 - 9.5mm wall thickness)

(V10/NOV22) 35
Rigid floor
Test Service separation
Service type (min. 150mm thick)
Standard
Integrity Insulation Aperture Services
PVC pipes Ø 32 - 50mm (1.8mm wall thickness)
Ø 55 - 63mm (2.3 - 3mm wall thickness)
Ø 75 - 82mm (3.1 - 4.8mm wall thickness)
Ø 90 - 110mm (4.2 - 7.4mm wall thickness) 120 120 EN N/A 200mm
Ø 125mm (6mm wall thickness)
Ø 140mm (6.1 - 7.5mm wall thickness)
Ø 160mm (6.2 - 9.5mm wall thickness)
HDPE pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 EN N/A 200mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.9 - 5.8mm wall thickness)
Ø 160mm (4.9 - 9.5mm wall thickness)
PP pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 EN N/A 200mm
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.5 - 8mm wall thickness)
Ø 160mm (4 - 14.6mm wall thickness)

(V10/NOV22) 36
Rigid floor
Test Service separation
Service type (min. 150mm thick)
Standard
Integrity Insulation Aperture Services
PVC pipes Ø 32 - 50mm (1.8mm wall thickness)
Ø 55 - 63mm (2.3 - 3mm wall thickness)
Ø 75 - 82mm (3.1 - 4.8mm wall thickness)
BS EN 1366-
Ø 90 - 110mm (4.2 - 7.4mm wall thickness) 120 120 0mm 0mm
3:2009
Ø 125mm (6mm wall thickness)
Ø 140mm (6.1 - 7.5mm wall thickness)
Ø 160mm (6.2 - 9.5mm wall thickness)
HDPE pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
BS EN 1366-
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 0mm 0mm
3:2009
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.9 - 5.8mm wall thickness)
Ø 160mm (4.9 - 9.5mm wall thickness)
PP pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 55 - 63mm (2.9- 4.4mm wall thickness)
Ø 75 - 82mm (2.8- 6.7mm wall thickness)
BS EN 1366-
Ø 90 - 110mm (2.7 - 10mm wall thickness) 120 120 0mm 0mm
3:2009
Ø 125mm (3.1mm wall thickness)
Ø 140mm (3.5 - 8mm wall thickness)
Ø 160mm (4 - 14.6mm wall thickness)

(V10/NOV22) 37
(V10/NOV22) 38
(V10/NOV22) 39
1) SLEEVED CPVC PIPE - LARGE ANNULAR GAP 2) SLEEVED CPVC PIPE - SMALL ANNULAR GAP ROCKWOOL Standard Detail:
1) SECTION 2) SECTION Supporting Evidence : WF 411297

Flexible wall Flexible wall Refer to Lubrizol / SPEARS CPVC Piping Systems
• min. 100mm thickness • min. 100mm thickness Compatible Product Finder for further information/evidence
• min. 2no. layers of plasterboard • min. 2no. layers of plasterboard
of compatibility.

ROCKWOOL High Expansion Sealant The supporting construction must be capable of achieving
• 20mm annular gap with min 25mm depth both sides of seal ROCKWOOL High Expansion Sealant the required fire rating of the proposed firestop.
cPVC Pipe & Sleeve cPVC Pipe & Sleeve • 20mm annular gap with min 25mm depth both sides of seal
• Ø89mm 150mm long cPVC sleeve • Ø89mm 150mm long cPVC sleeve
• Ø27mm cPVC pipe
24 • Ø60mm cPVC pipe 8 Aperture Size: Max. 600mm wide x 400mm high.

The flexible wall construction must be installed in


accordance with the manufacturer's guidelines with the
aperture being fully framed and lined out. The wall
50 50 construction should also be minimum 100mm thickness.
ROCKWOOL High Expansion Sealant ROCKWOOL High Expansion Sealant
• Fill annular gap between sleeve & pipe with 50mm depth to both • Fill annular gap between sleeve & pipe with 50mm depth to
sides of seal both sides of seal All service items should be adequately supported either
• PE backing rod between sleeve and pipe for depth control • PE backing rod between sleeve and pipe for depth control side of the firestop to ensure that no load is transferred
onto the seal.
ROCKWOOL Ablative Coated Batt ROCKWOOL Ablative Coated Batt
• 50mm thickness • 50mm thickness Please refer to the relevant product datasheet for further
• Installed in 2no. layer within the aperture • Installed in 2no. layer within the aperture installation guidance.
• Edges of the batt to be buttered with Acoustic Intumescent Sealant • Edges of the batt to be buttered with Acoustic Intumescent Sealant
• All batt-to-batt and batt-to-substrate joints to be sealed with Acoustic • All batt-to-batt and batt-to-substrate joints to be sealed with Acoustic
Intumescent Sealant Intumescent Sealant These products should only be utilised for applications as
1) ELEVATION 2) ELEVATION
outlined in the relevant ROCKWOOL product datasheet
Ø89 Ø89 Ø60 and in accordance with the relevant ROCKWOOL Fire
Ø27 Resistance Testing. Additionally the product must be
installed in accordance with the current ROCKWOOL
cPVC Pipe & Sleeve ROCKWOOL HE Sealant cPVC Pipe & Sleeve ROCKWOOL HE Sealant guidelines. For further information please visit
• Ø89mm 150mm long cPVC sleeve 20 • 20mm annular gap with min 25mm depth
• Ø89mm 150mm long cPVC sleeve 20 • 20mm annular gap with min 25mm depth
www.rockwool.co.uk or contact our Technical Solutions
• Ø27mm cPVC pipe
24 • Ø60mm cPVC pipe
Team on 01656 868490.
8

3) SLEEVED CPVC PIPE - NO ANNULAR GAP


3) ELEVATION
3) SECTION
Ø89 Ø73
Integrity Performance: Insulation Performance:
Flexible wall cPVC Pipe & Sleeve
• min. 100mm thickness • Ø89mm 150mm long cPVC sleeve ROCKWOOL High Expansion 120 minutes 120 minutes
• min. 2no. layers of plasterboard • Ø73mm cPVC pipe
Sealant
• 20mm annular gap full depth "fully filled"

20
ROCKWOOL High Expansion
cPVC Pipe & Sleeve 100 Sealant
• Ø89mm 150mm long cPVC sleeve
• 20mm Annular gap with 100mm depth "fully filled"
• Ø73mm cPVC pipe

150 0 Pencoed, Bridgend,


South Wales CF35 6NY
t: 01656 868490
[email protected]
20 ROCKWOOL High Expansion Sealant ROCKWOOL High
• Small gaps between pipe & sleeve "pointed" with a bead of sealant
SPACING Expansion Sealant Drawing Title:
• Where sleeve is tight to aperture fill gaps
150mm BETWEEN SLEEVES with HE sealant to required minimum depth HIGH EXPANSION INTUMESCENT SEALANT
0mm TO APERTURE EDGE cPVC pipes with cPVC sleeves
ROCKWOOL Ablative Coated Batt
• 50mm thickness
• Installed in 2no. layer within the aperture
PERFORMANCE: EI 120
• Edges of the batt to be buttered with Acoustic Intumescent Sealant cPVC PIPE WITH 150mm LENGTH cPVC SLEEVE THROUGH ABLATIVE Scale:
NTS
Date:
OCT 20
• All batt-to-batt and batt-to-substrate joints to be sealed with Acoustic
Intumescent Sealant COATED BATT - TREATED WITH HIGH EXPANSION SEALANT
Sheet Size: Drawn By: Checked By:
A3 S. HIRONS L.HAM
The published fire ratings have been achieved by following the instructions set out above. Use of alternative components or deviations from the instructions in any way is likely to mean that the installation will not comply with the assessed rating. Rockwool Ltd. does not accept responsibility for the consequences of using
Rockwool products in applications or for purposes not authorised by Rockwool Ltd. Expert advice should be sought where such applications are contemplated.The information contained in this drawing is believed to be correct at the date of publication, and is based upon tested and certified solutions. The policy of Rockwool Drawing Number: Revision:
Ltd. is one of constant improvement. Installers should therefore ensure that they are working from the latest published drawings and instructions. Whilst Rockwool will endeavour to keep its publications up to date the accuracy of the information contained within this drawing may be affected by pertinent changes in the law or
regulatory requirements and alterations or amendments to the specification of Rockwool products. RWSD-HE-0051 B

(V10/NOV22) 40
(V10/NOV22) 41
(V10/NOV22) 42
(V10/NOV22) 43
63mm Dia. PVC CONDUIT THROUGH 75mm 63mm Dia. PVC CONDUIT THROUGH 75mm ROCKWOOL Standard Detail:
FLEXIBLE WALL FLEXIBLE WALL Supporting Evidence : WF 411460 / WF 411469
EI 60 EI 60 (BS EN 1366-3:2009)
Flexible wall The supporting construction must be capable of achieving
• min. 75mm thick Flexible wall the required fire rating of the proposed firestop.
• min. 1no. board layers • min. 75mm thick
• Fire rated to at least the same fire rating as the firestop seal • min. 1no. board layers
• Fire rated to at least the same fire rating as the firestop seal
Flexible wall constructions must be installed in accordance
ROCKWOOL FIREPRO® High
12.5 Expansion Intumescent Sealant ROCKWOOL FIREPRO® High with the manufacturer's guidelines. The wall construction
20 • 20mm annular Expansion Intumescent Sealant
should be a minimum thickness of 75mm.
• min. 12.5mm depth • 20mm annular
• min. 12.5mm depth All service items should be adequately supported both
sides of the firestop to ensure that no load is transferred
onto the firestop seal.
Cable - Bundle Cable - Single Where possible a 20mm annular gap should be maintained
Note: • max. 8no. telecommunication cables
Note: • telecommunication cable
around the full circumference of the conduit.
Where conduit is tight to
opening point small gaps with PVC sleeve
Where conduit is tight to
opening point small gaps with
PVC sleeve
High Expansion Intumescent • max. Ø 63mm High Expansion Intumescent • max. Ø 63mm Applications in flexible wall constructions can be used in
Sealant Sealant • min. 125mm length
• min. 125mm length
• ROCKWOOL RWA45 packed around cables within sleeve masonry wall constructions.
• ROCKWOOL RWA45 packed around cables within sleeve
• min. 13mm deep ROCKWOOL FIREPRO® Acoustic Intumescent
75 • min. 13mm deep ROCKWOOL FIREPRO® Acoustic Intumescent
Sealant to seal within sleeve
Sealant to seal within sleeve Refer to relevant product datasheet for further installation
guidelines.
ROCKWOOL FIREPRO High ® ROCKWOOL FIREPRO® High
Expansion Intumescent Sealant Expansion Intumescent Sealant These products should only be utilised for applications as
20 • 20mm annular 20 • 20mm annular
• min. 12.5mm depth outlined in the relevant ROCKWOOL product data sheet
Ø83 • min. 12.5mm depth
Ø83 and in accordance with the relevant ROCKWOOL Fire
PVC sleeve PVC sleeve Resistance Testing. Additionally the product must be
• max. Ø 63mm
• max. Ø 63mm installed in accordance with the current ROCKWOOL
Note:
• min. 125mm length
Note: Ø63 • min. 125mm length
• ROCKWOOL RWA45 packed around cables within sleeve Ø63 • ROCKWOOL RWA45 packed around cables within sleeve guidelines.
Where conduit is tight to Where conduit is tight to • min. 13mm deep ROCKWOOL FIREPRO® Acoustic Intumescent
• min. 13mm deep ROCKWOOL FIREPRO® Acoustic Intumescent opening point small gaps with
opening point small gaps with Sealant to seal within sleeve
Sealant to seal within sleeve
High Expansion Intumescent High Expansion Intumescent For further information please visit www.rockwool.co.uk or
Sealant
Flexible wall
Sealant Flexible wall contact our Technical Solutions Team on 01656 868490.
• min. 75mm thick
ELEVATION - 63mm Dia. PVC CONDUIT
• min. 75mm thick
• min. 1no. board layers
ELEVATION - 63mm Dia. PVC CONDUIT • min. 1no. board layers

THROUGH 75mm FLEXIBLE WALL • Fire rated to at least the same fire rating as the firestop seal THROUGH 75mm FLEXIBLE WALL • Fire rated to at least the same fire rating as the firestop seal

EI 60 EI 60
Integrity Performance: Insulation Performance:

Flexible wall 60 minutes 60 minutes


• min. 75mm thick
Note: • min. 1no. board layers
• Fire rated to at least the same fire rating as the firestop seal
ROCKWOOL FIREPRO® High
Where conduit is tight to
opening point small gaps with Note:
High Expansion Intumescent PVC Conduits Expansion Intumescent Sealant
Sealant 75 75 • max. Ø 63mm
Where conduit is tight to
opening point small gaps with 229
High Expansion Intumescent • 20mm annular
20 20
• min. 225mm length
• ROCKWOOL RWA45 packed around cables within sleeve Sealant • min. 12.5mm depth
• min. 13mm deep ROCKWOOL FIREPRO® Acoustic Intumescent Pencoed, Bridgend,
PVC conduits (Linear arrangement)
Sealant to seal within sleeve
20 • max. Ø 63mm - in linear arrangement South Wales CF35 6NY
83 • min. 225mm length
t: 01656 868490
• ROCKWOOL RWA45 packed around cables within sleeve

12.5 • min. 13mm deep ROCKWOOL FIREPRO® Acoustic Intumescent [email protected]


Cable - Bundle Sealant to seal within sleeve

• max. 7no. telecommunication cables Ø63


Drawing Title:
ROCKWOOL FIREPRO® High Flexible wall
ROCKWOOL FIREPRO® High Expansion Int. Sealant
Expansion Intumescent Sealant • min. 75mm thick
• min. 1no. board layers 75mm Flexible Wall - 1no. Board - Conduit Penetrations
• 20mm annular • Fire rated to at least the same fire rating as the firestop seal
75 • min. 12.5mm depth

LINEAR ARRANGEMENT OF 63mm Dia. PVC LINEAR ARRANGEMENT OF 63mm Dia. PVC Scale: Date:
NTS NOV 20
CONDUITS THROUGH 75mm FLEXIBLE WALL CONDUITS THROUGH 75mm FLEXIBLE WALL
EI 60 EI 60 Sheet Size: Drawn By: Checked By:
A3 RW TECH L.HAM
The published fire ratings have been achieved by following the instructions set out above. Use of alternative components or deviations from the instructions in any way is likely to mean that the installation will not comply with the assessed rating. Rockwool Ltd. does not accept responsibility for the consequences of using
Rockwool products in applications or for purposes not authorised by Rockwool Ltd. Expert advice should be sought where such applications are contemplated.The information contained in this drawing is believed to be correct at the date of publication, and is based upon tested and certified solutions. The policy of Rockwool Drawing Number: Revision:
Ltd. is one of constant improvement. Installers should therefore ensure that they are working from the latest published drawings and instructions. Whilst Rockwool will endeavour to keep its publications up to date the accuracy of the information contained within this drawing may be affected by pertinent changes in the law or
regulatory requirements and alterations or amendments to the specification of Rockwool products. RWSD-HE-0110 B

(V10/NOV22) 44
63mm Dia. PVC SLEEVE PARTIAL PENETRATION 3 No. 34mm Dia. PVC SLEEVES PARTIAL PENETRATIONS ROCKWOOL Standard Detail:
75mm FLEXIBLE WALL 75mm FLEXIBLE WALL Supporting Evidence : WF 411469 (BS EN 1366-3:2009)
EI 90 EI 90/60
The supporting construction must be capable of achieving
the required fire rating of the proposed firestop.
Flexible wall Flexible wall
• min. 75mm thick • min. 75mm thick
• min. 1no. board layers • min. 1no. board layers Flexible wall constructions must be installed in accordance
• Fire rated to at least the same fire rating as the firestop seal • Fire rated to at least the same fire rating as the firestop seal with the manufacturer's guidelines. The wall construction
should be a minimum thickness of 75mm.

All service items should be adequately supported both


Sleeved Cable (Single) Sleeved Cable (Linear arrangement) sides of the firestop to ensure that no load is transferred
• max. Ø63mm PVC sleeve • max. Ø34mm Century Hose sleeve
• min. 100mm length within wall • min. 100mm length within wall
onto the firestop seal.
• Partial penetration into the flexible wall • Partial penetration into the flexible wall
• Conduit sleeving telecommunication cable • Conduit sleeving telecommunication cable For further guidance on partial pipe penetrations refer to
• End of conduit plugged with RAW45 & 13mm depth of AIS • End of conduit plugged with RAW45 & 13mm depth of AIS
ASFP advisory note 13.
®
ROCKWOOL FIREPRO High
ROCKWOOL FIREPRO® High Expansion Intumescent Sealant
Refer to relevant product datasheet for further installation
Expansion Intumescent Sealant guidelines.
• 20mm annular
• 20mm annular • min. 12.5mm depth
75 • min. 12.5mm depth 75 These products should only be utilised for applications as
Flexible wall outlined in the relevant ROCKWOOL product data sheet
• min. 75mm thick and in accordance with the relevant ROCKWOOL Fire
Flexible wall • min. 1no. board layers
• Fire rated to at least the same fire rating as the firestop seal Resistance Testing. Additionally the product must be
• min. 75mm thick
installed in accordance with the current ROCKWOOL
83 • min. 1no. board layers
Sleeved Cable (Linear arrangement) guidelines.
• Fire rated to at least the same fire rating as the firestop seal 142
20 20 • max. Ø34mm Century Hose sleeve

Sleeved Cable (Single)


• min. 100mm length within wall
For further information please visit www.rockwool.co.uk or
• Partial penetration into the flexible wall
83 • max. Ø63mm PVC sleeve 55 • Conduit sleeving telecommunication cable contact our Technical Solutions Team on 01656 868490.
• min. 100mm length within wall • End of conduit plugged with RAW45 & 13mm depth of AIS
• Partial penetration into the flexible wall 20
Ø63
• Conduit sleeving telecommunication cable
• End of conduit plugged with RAW45 & 13mm depth of AIS
3No. Ø34
ROCKWOOL FIREPRO High ® ROCKWOOL FIREPRO® High
ELEVATION ELEVATION
Expansion Intumescent Sealant Expansion Intumescent Sealant
63mm Dia. PVC SLEEVE • 20mm annular
3 No. 34mm Dia. PVC SLEEVE • 20mm annular
PARTIAL PENETRATION • min. 12.5mm depth PARTIAL PENETRATION • min. 12.5mm depth

EI 90 EI 90/60 Integrity Performance: Insulation Performance:

90 minutes Up to 90 minutes

Flexible wall Flexible wall


• min. 75mm thick • min. 75mm thick
• min. 1no. board layers • min. 1no. board layers
• Fire rated to at least the same fire rating as the firestop seal • Fire rated to at least the same fire rating as the firestop seal

ROCKWOOL FIREPRO® High ROCKWOOL FIREPRO® High


Expansion Intumescent Sealant Expansion Intumescent Sealant Pencoed, Bridgend,
• 10mm annular • 20mm annular
• Min. 12.5mm depth • Min. 12.5mm depth South Wales CF35 6NY
• RWA45 backing material • RWA45 backing material
t: 01656 868490
[email protected]

Drawing Title:
Galvanized Spiral Duct cPVC Pipe Penetration ROCKWOOL FIREPRO® High Expansion Int. Sealant
• Max. 100mm diameter • 63mm diameter
75mm Flexible Wall - 1no. Board - Pipe & Partial Pens.

100mm Dia. GALV. SPIRAL DUCT THROUGH 63mm Dia. CPVC PIPE THROUGH Scale: Date:
75mm FLEXIBLE WALL 75mm FLEXIBLE WALL NTS NOV 20
E 90 (Integrity Only) EI 90 Sheet Size: Drawn By: Checked By:
A3 RW. TECH L.HAM
The published fire ratings have been achieved by following the instructions set out above. Use of alternative components or deviations from the instructions in any way is likely to mean that the installation will not comply with the assessed rating. Rockwool Ltd. does not accept responsibility for the consequences of using
Rockwool products in applications or for purposes not authorised by Rockwool Ltd. Expert advice should be sought where such applications are contemplated.The information contained in this drawing is believed to be correct at the date of publication, and is based upon tested and certified solutions. The policy of Rockwool Drawing Number: Revision:
Ltd. is one of constant improvement. Installers should therefore ensure that they are working from the latest published drawings and instructions. Whilst Rockwool will endeavour to keep its publications up to date the accuracy of the information contained within this drawing may be affected by pertinent changes in the law or
regulatory requirements and alterations or amendments to the specification of Rockwool products. RWSD-HE-0111 B

(V10/NOV22) 45
(V10/NOV22) 46
(V10/NOV22) 47
(V10/NOV22) 48
Insulated fie sleeve through single 50mm batt
Spacing Classification
Pipe Wall
Pipe Material Pipe Size (mm) Substrate Seal Closure Device Aperture Edge Service Separation
Thickness (mm) Integrity Insulation
Separation (mm) (mm)
PVC 40 - 160 1.8 - 9.5 50mm ablative
75mm thick PB / coated batt
HDPE 40 - 160 2.4 - 9.5 IFS - 150mm 0 0 30 30
Masonry wall 600mm (h) x
PP 40 - 160 1.8 - 9.1 900mm (w)

Insulated fie sleeve through double 50mm batt


Spacing Classification
Pipe Wall
Pipe Material Pipe Size (mm) Substrate Seal Closure Device Aperture Edge Service Separation
Thickness (mm) Integrity Insulation
Separation (mm) (mm)

PVC 40 - 160 1.8 - 9.5 Double 50mm


100mm thick PB / ablative coated
IFS - 150mm 25 / 50 30 / 50 120 120
Masonry wall batt 600mm (h) x
HDPE 40 - 160 2.4 - 9.5 900mm (w)

(V10/NOV22) 49
Insulated fire sleeve through double 50mm batt - Single sided installation
Spacing Classification
Pipe Wall
Pipe Material Pipe Size (mm) Substrate Seal Closure Device Aperture Edge Service Separation
Thickness (mm) Integrity Insulation
Separation (mm) (mm)

PVC 40 - 110 1.8 - 6.6 Double 50mm


100mm thick PB / ablative coated
IFS - 150mm 0 0 120 120
Masonry wall batt 600mm (h) x
HDPE 40 - 110 2.4 - 6.6 900mm (w)

(V10/NOV22) 50
ROCKWOOL Standard Detail:
Supporting Evidence : WF 411471 (BS EN 1366-3:2009)

The supporting construction must be capable of achieving


ROCKWOOL INSULATED FIRE SLEEVE IN the required fire rating of the proposed Firestop.
SOFTSEAL - SECTION DETAIL ROCKWOOL INSULATED FIRE SLEEVE IN
All service items should be adequately supported either
SOFTSEAL @ 45 degrees - PLAN DETAIL
side of seal - min 350mm from face of batt seal.
Fire rated flexible wall /
plasterboard partition Insulated Fire Sleeve to be minimum 300mm long through
SoftSeal batt.

Combustible pipe through Solutions for flexible wall constructions can be used in
ROCKWOOL SoftSeal ROCKWOOL SoftSeal at 45 masonry constructions of the same minimum wall
Intumescent Sealant degree angle thickness (100mm Min.)
ROCKWOOL SoftSeal
applied to all abutments,
100 joints in batt and 300mm length of insulated fire 45° These products should only be utilised for applications as
perimeter of aperture sleeve 300 outlined in the relevant ROCKWOOL product data sheet
and in accordance with the relevant ROCKWOOL Fire
Resistance Testing. Additionally the product must be
Combustible Pipe installed in accordance with the current ROCKWOOL
100 guidelines.

For further information or alternative products please visit


ROCKWOOL Insulated Fire www.rockwool.co.uk or contact our Technical Solutions
ROCKWOOL SoftSeal Min 100mm thick Team on 01656 868490
Sleeve - 300mm long stud wall
intumescent sealant
ROCKWOOL
SoftSeal

100

Insulated Fire Sleeve Performance Tables:


Integrity Performance: Insulation Performance:

Insulated Fire Sleeve through SoftSeal - Angled Pipes (45 degrees) Up to 120 Minutes Up to 120 Minutes
Spacing Classification
Pipe Wall
Pipe Material Pipe Size (mm) Substrate Seal Closure Device Aperture Edge Service Separation
Thickness (mm) Integrity Insulation
Separation (mm) (mm)

PVC 40 - 110 1.8 - 6.6


0
Pencoed, Bridgend,
HDPE 40 - 110 2.4 - 6.6
100mm thick PB /
100mm softseal South Wales CF35 6NY
1200mm (h) x IFS - 300mm 0 120 120 t: 01656 868490
Masonry wall
1200mm (w)
PVC < 160 < 9.5 [email protected]
35
HDPE < 160 < 9.5 Drawing Title:

FirePro Insulated Fire Sleeve:


SoftSeal - Angled Pipes

Scale: Date:
NTS NOV 20

Sheet Size: Drawn By: Checked By:


A3 RW TECH L.HAM
The published fire ratings have been achieved by following the instructions set out above. Use of alternative components or deviations from the instructions in any way is likely to mean that the installation will not comply with the assessed rating. Rockwool Ltd. does not accept responsibility for the consequences of using
Rockwool products in applications or for purposes not authorised by Rockwool Ltd. Expert advice should be sought where such applications are contemplated.The information contained in this drawing is believed to be correct at the date of publication, and is based upon tested and certified solutions. The policy of Rockwool Drawing Number: Revision:
Ltd. is one of constant improvement. Installers should therefore ensure that they are working from the latest published drawings and instructions. Whilst Rockwool will endeavour to keep its publications up to date the accuracy of the information contained within this drawing may be affected by pertinent changes in the law or
regulatory requirements and alterations or amendments to the specification of Rockwool products. RWSD-IFS-0003 B

(V10/NOV22) 51
ROCKWOOL Standard Detail:
Supporting Evidence : WF 411457 / WF 411460 / WF
ROCKWOOL INSULATED FIRE SLEEVE ROCKWOOL INSULATED FIRE SLEEVE 411464 / WF 411467 (BS EN 1366-3:2009)
THROUGH 100MM THICK WALL THROUGH 75MM THICK WALL
The supporting construction must be capable of achieving
the required fire rating of the proposed Firestop.
Fire rated flexible wall / ROCKWOOL Acoustic Fire rated flexible wall / ROCKWOOL Acoustic
plasterboard partition plasterboard partition Insulated Fire Sleeve to be minimum 150mm long through
Intumescent Sealant Intumescent Sealant wall.
to fill gaps up to 10mm to fill gaps up to 15mm
25 37.5
between insulated fire between insulated fire Solutions for flexible wall constructions can be used in
sleeve and substrate. sleeve and substrate. masonry constructions of the same minimum wall
Combustible and Minimum 12.5mm Combustible and Minimum 12.5mm thickness (75mm or 100mm)
non-combustible pipes to be depth non-combustible pipes to be depth
adequately supported on each adequately supported on each Core holes through walls to have a minimum separation of
150mm. For reduced separation please contact
side of the wall side of the wall
ROCKWOOL Technical.
50
ROCKWOOL Insulated Fire ROCKWOOL Insulated Fire
These products should only be utilised for applications as
Sleeve to project by min. Sleeve to project by min. outlined in the relevant ROCKWOOL product data sheet
25mm from each face of the 37.5mm from each face of the and in accordance with the relevant ROCKWOOL Fire
wall. Min 150mm total length. wall. Min 150mm total length. Resistance Testing. Additionally the product must be
installed in accordance with the current ROCKWOOL
100 75 guidelines.

For further information or alternative products please visit


www.rockwool.co.uk or contact our Technical Solutions
Insulated Fire Sleeve Performance Tables: Team on 01656 868490

Insulated fire sleeve through 100mm PB/Masonry Wall


Pipe Wall Classification
Pipe Material Pipe Size (mm) Substrate Closure Device Annular Gap
Thickness (mm) Integrity Insulation

PVC 40 - 160 1.8 - 9.5


120 120
HDPE 40 - 160 2.4 - 9.5
PP 40 - 110 1.8 - 6.3 100mm thick PB / 10mm max 25mm
IFS - 150mm Integrity Performance: Insulation Performance:
PP 160 4 Masonry depth
90 60
PP 160 9.1 Up to 120 Minutes Up to 120 Minutes

Steel ≤168 4 120 15


Cable Bundle with insulated fire sleeve
100mm thick PB / 5mm max
110mm Dia. Data Cable Bundle IFS - 150mm 60 60
Masonry 12.5mm depth
Pencoed, Bridgend,
South Wales CF35 6NY
Insulated fire sleeve through 75mm PB/Masonry Wall
t: 01656 868490
Wall Thickness Classification
Pipe Material Pipe Size (mm)
(mm)
Substrate Closure Device Annular Gap
Integrity Insulation
[email protected]
PVC 40 - 160 1.8 - 9.5
100mm thick PB / 15mm max
HDPE 40 - 160 2.4 - 9.5 IFS - 150mm 60 60 Drawing Title:
Masonry 12.5mm depth
PP 40 - 160 1.8 - 9.1 FirePro Insulated Fire Sleeve:
Cable Bundle with insulated fire sleeve Penetration Seal through Wall (75mm & 100mm thick)
100mm thick PB / 5mm max
110mm Dia. Data Cable Bundle IFS - 150mm 60 60
Masonry 12.5mm depth
Scale: Date:
NTS NOV 20

Sheet Size: Drawn By: Checked By:


A3 RW TECH L. HAM
The published fire ratings have been achieved by following the instructions set out above. Use of alternative components or deviations from the instructions in any way is likely to mean that the installation will not comply with the assessed rating. Rockwool Ltd. does not accept responsibility for the consequences of using
Rockwool products in applications or for purposes not authorised by Rockwool Ltd. Expert advice should be sought where such applications are contemplated.The information contained in this drawing is believed to be correct at the date of publication, and is based upon tested and certified solutions. The policy of Rockwool Drawing Number: Revision:
Ltd. is one of constant improvement. Installers should therefore ensure that they are working from the latest published drawings and instructions. Whilst Rockwool will endeavour to keep its publications up to date the accuracy of the information contained within this drawing may be affected by pertinent changes in the law or
regulatory requirements and alterations or amendments to the specification of Rockwool products. RWSD-IFS-0101 B

(V10/NOV22) 52
ROCKWOOL Standard Detail:
Supporting Evidence : WF 423089 / WF 423090
(BS EN 1366-3:2009)

The supporting construction must be capable of achieving


the required fire rating of the proposed Firestop.

All service items should be adequately supported either


side of seal.
ROCKWOOL INSULATED FIRE SLEEVE IN DOUBLE ROCKWOOL INSULATED FIRE SLEEVE IN DOUBLE
BATT FLOOR SEAL - SECTION BATT FLOOR SEAL - SEPARATION PLAN Insulated Fire Sleeve to be minimum 150mm long through
double batt seal.
2 No. 50mm Abaltive 0 (Sleeve to substrate) 0 (Between sleeves)
Batt sealed from top These products should only be utilised for applications as
Combustible pipe penetration
outlined in the relevant ROCKWOOL product data sheet
side only
and in accordance with the relevant ROCKWOOL Fire
Resistance Testing. Additionally the product must be
installed in accordance with the current ROCKWOOL
Concrete floor 25 guidelines.
150 Timber floor with
slab 25 50
exposed timber to For further information or alternative products please visit
perimeter of seal. Ø160 www.rockwool.co.uk or contact our Technical Solutions
120 22mm floor board Team on 01656 868490
ROCKWOOL Insulated Fire 47 x 198 timber joists at
Sleeve positioned centrally 600mm c/c
to the batt seal 15mm plasterboard lining

Insulated Fire Sleeve Performance Tables:


Integrity Performance: Insulation Performance:

Insulated fie sleeve through double 50mm batt Up to 90 Minutes Up to 90 Minutes


Spacing Classification
Pipe Wall
Pipe Material Pipe Size (mm) Substrate Seal Closure Device Aperture Edge Service Separation
Thickness (mm) Integrity Insulation
Separation (mm) (mm)

PVC 40 - 160 1.8 - 9.5 Double 50mm


ablative batt seal
HDPE 40 - 160 2.4 - 9.5 0 0 (Linear) 60 60 Pencoed, Bridgend,
1600mm x
PP 40 - 160 1.8 - 9.1 1100mm South Wales CF35 6NY
Timber Floor
Rehau (PEX) 40 5.5 Construction
IFS - 150mm 0 n/a 90 90 t: 01656 868490
DN50 (66mm Double 50mm [email protected]
Tracpipe 6 ablative batt seal 0 n/a 90 90
od)
1100mm x
PVC/HDPE/PP 40 1.8 - 3.7 700mm 0 0 (Linear) 90 90 Drawing Title:

FirePro Insulated Fire Sleeve:


Double 50mm Ablative Coated Batt Floor Seal

Scale: Date:
NTS NOV 20

Sheet Size: Drawn By: Checked By:


A3 RW TECH L.HAM
The published fire ratings have been achieved by following the instructions set out above. Use of alternative components or deviations from the instructions in any way is likely to mean that the installation will not comply with the assessed rating. Rockwool Ltd. does not accept responsibility for the consequences of using
Rockwool products in applications or for purposes not authorised by Rockwool Ltd. Expert advice should be sought where such applications are contemplated.The information contained in this drawing is believed to be correct at the date of publication, and is based upon tested and certified solutions. The policy of Rockwool Drawing Number: Revision:
Ltd. is one of constant improvement. Installers should therefore ensure that they are working from the latest published drawings and instructions. Whilst Rockwool will endeavour to keep its publications up to date the accuracy of the information contained within this drawing may be affected by pertinent changes in the law or
regulatory requirements and alterations or amendments to the specification of Rockwool products. RWSD-IFS-0501 B

(V10/NOV22) 53
ROCKWOOL Standard Detail:
Supporting Evidence : WF 416060

The supporting construction must be capable of achieving


the required fire rating of the proposed Firestop.

Insulated Fire Sleeve to be minimum 150mm long through


floor. For floor thickness less than 150mm please contact
ROCKWOOL technical.

Combustible or non combustible Core holes through floors to have a minimum separation
pipes to be adequately of 150mm. For reduced separation please contact
supported on both side of the ROCKWOOL Technical.
floor slab
Min 150mm These products should only be utilised for applications as
>15 <15 outlined in the relevant ROCKWOOL product data sheet
concrete floor slab Annular gaps up to 15mm. and in accordance with the relevant ROCKWOOL Fire
Use 50mm depth RWA45 Resistance Testing. Additionally the product must be
backing with 20mm depth installed in accordance with the current ROCKWOOL
Gaps >15mm fill
150 ROCKWOOL Acoustic guidelines.
with ROCKWOOL
Intumescent Sealant
Standard or HS
For further information or alternative products please visit
Compound www.rockwool.co.uk or contact our Technical Solutions
Team on 01656 868490
150mm length of
insulated fire
sleeve

Insulated Fire Sleeve Performance Tables:


Integrity Performance: Insulation Performance:

Insulated fire sleeve through 150mm AAC slab Up to 120 Minutes Up to 120 Minutes
Pipe Wall Thickness Classification
Pipe Material Pipe Size (mm) Substrate Closure Device Annular Gap
(mm) Integrity Insulation
PVC 40 - 160 1.8 - 9.5
15mm - sealed with
120
150mm Aerated 20mm deep AIS
HDPE 40 - 160 2.4 - 9.5 IFS - 150mm 180
concrete slab with 50mm RWA45 Pencoed, Bridgend,
backing South Wales CF35 6NY
PP 40 - 160 1.8 - 9.1 60
t: 01656 868490
[email protected]

Drawing Title:

FirePro Insulated Fire Sleeve:


Penetration Seal through Floor

Scale: Date:
NTS NOV 20

Sheet Size: Drawn By: Checked By:


A3 RW TECH L.HAM
The published fire ratings have been achieved by following the instructions set out above. Use of alternative components or deviations from the instructions in any way is likely to mean that the installation will not comply with the assessed rating. Rockwool Ltd. does not accept responsibility for the consequences of using
Rockwool products in applications or for purposes not authorised by Rockwool Ltd. Expert advice should be sought where such applications are contemplated.The information contained in this drawing is believed to be correct at the date of publication, and is based upon tested and certified solutions. The policy of Rockwool Drawing Number: Revision:
Ltd. is one of constant improvement. Installers should therefore ensure that they are working from the latest published drawings and instructions. Whilst Rockwool will endeavour to keep its publications up to date the accuracy of the information contained within this drawing may be affected by pertinent changes in the law or
regulatory requirements and alterations or amendments to the specification of Rockwool products. RWSD-IFS-0601 B

(V10/NOV22) 54
Oval insulated fire sleeve
Spacing Classification
Pipe Wall
Vent Material Vent Size (mm) Substrate Seal Closure Device Aperture Edge Service Separation
Thickness (mm) Integrity Insulation
Separation (mm) (mm)

100mm thick PB / 100mm softseal 1200mm (h) x


PVC 204 x 60 2 IFS - 150mm 0 0 60 60
Masonry wall 1200mm (w)

Oval insulated fire sleeve (EN)

Spacing Classification
Vent Material Vent Size (mm)Vent Wall Thickness (mm) Substrate Seal Closure Device
Aperture Edge Service Separation
Integrity Insulation
Separation (mm) (mm)
100mm thick PB / 100mm softseal 1200mm (h) x
PVC 204 x 60 2 0 0 60 60
Masonry wall 1200mm (w)

132mm thick PB /
PVC 110 x 54 1.5 - 1.7mm N/A OIFS - 150mm - 100 120 120
Masonry wall

132mm thick PB /
PVC 204 x 60 1.5 - 1.7mm N/A - 100 120 120
Masonry wall

Oval insulated fire sleeve (BS)


Spacing Classification
Vent Wall
Vent Material Vent Size (mm) Substrate Seal Closure Device Aperture Edge Service Separation
Thickness (mm) Integrity Insulation
Separation (mm) (mm)

PVC 110 x 54 1.5 - 1.7mm 50mm Ablative Coated Batt 100 100 60 60

PVC 204 x 60 1.5 - 1.7mm 50mm Ablative Coated Batt 100 100 60 60

PVC 220 x 90 1.8 50mm Ablative Coated Batt 100 100 60 60


100mm PB / Masonry wall OIFS - 150mm
Double 50mm ablative Coated
PVC 110 x 54 1.5 - 1.7mm 100 100 120 120
Batt

Double 50mm ablative Coated


PVC 205 x 60 1.5 - 1.7mm 100 100 120 120
Batt

Double 50mm ablative Coated


PVC 220 x 90 1.8 100 100 60 60
Batt

(V10/NOV22) 55
Flexible
Flexible / rigid/wall
rigid wall Intumescent
Intumescent Thickness
Thickness
Service
Test Test Service separation
separation
Service
Service type type (min. (min.
100mm 100mm
thick)thick) Pipe Diameter
Pipe Diameter Intumescent
Intumescent Material
Material
Standard
Standard
Integrity
Integrity Insulation
Insulation Aperture
Aperture Services
Services Ø32 - Ø32
50mm - 50mm 40mm40mm (w) x 2mm
(w) x 2mm (t) (t)
PVC pipes
PVC pipes Ø 32 -Ø50mm
32 - 50mm
(1.8mm(1.8mm wall thickness)
wall thickness) 120 120 120 120 Ø51 - Ø51
82mm - 82mm 40mm40mm (w) x 4mm
(w) x 4mm (t) (t)
Ø 160mm
Ø 160mm (6.2mm (6.2mm wall thickness)
wall thickness) 90 90 90 90 Ø83 - Ø83
115mm- 115mm 40mm40mm (w) x 6mm
(w) x 6mm (t) (t)
EN EN N/A N/A 100mm 100mm
Ø 160mm
Ø 160mm (9.5mm (9.5mm wall thickness)
wall thickness) Ø116 Ø116
- 160mm- 160mm 40mm40mm (w) x 8mm
(w) x 8mm (t) (t)
120 120 120 120
Ø 200mm
Ø 200mm (7.7 - 9.6mm
(7.7 - 9.6mm wall thickness)
wall thickness) Ø161 Ø161
- 200mm- 200mm 40mm40mm (w) x 10mm
(w) x 10mm (t) (t)
PP pipes
PP pipes Ø 32 -Ø50mm
32 - 50mm
(2.9mm(2.9mm wall thickness)
wall thickness) 120 120 Ø201 Ø201
- 250mm- 250mm 40mm40mm (w) x 12mm
(w) x 12mm (t) (t)
Ø 160mm (4mm wall
Ø 160mm (4mm wall thickness) thickness) 90 90
Ø 160mm
Ø 160mm (14.6mm(14.6mm wall thickness)
wall thickness) 120 120
120 120 EN EN N/A N/A 100mm
100mm
Ø 200mm
Ø 200mm (4.9mm (4.9mm wall thickness)
wall thickness) 90 90
Ø 200mm
Ø 200mm (18.2mm(18.2mm wall thickness)
wall thickness) 120 120
Ø 250mm
Ø 250mm (10.1mm(10.1mm wall thickness)
wall thickness) 15 15
PE pipes
PE pipes Ø 32 -Ø50mm
32 - 50mm
(2.9mm(2.9mm wall thickness)
wall thickness) 120 120 120 120
Ø 160mm
Ø 160mm (9.5mm (9.5mm wall thickness)
wall thickness) 90 90 90 90 EN EN N/A N/A 100mm
100mm
Ø 200mm
Ø 200mm (18.4mm(18.4mm wall thickness)
wall thickness) 120 120 120 120

(V10/NOV22) 56
Rigid floor Intumescent Thickness
Test Service separat ion
Service t ype (min. 150mm thick) Pipe Diamet er Int umescent Mat erial
Standard
Int egrit y Insulation Aperture Services Ø32 - 50mm 40mm (w) x 2mm (t )
PVC pipes Ø 32 - 50mm (1.8mm wall thickness) 120 Ø51 - 82mm 40mm (w) x 4mm (t )
120
Ø 200mm (7.7mm wall thickness) 90 EN N/A 100mm Ø83 - 115mm 40mm (w) x 6mm (t )
Ø 200mm (9.6mm wall thickness) 60 60 Ø116 - 160mm 40mm (w) x 8mm (t )
PP pipes Ø 32 - 50mm (2.9mm wall thickness) 120 120 Ø161 - 200mm 40mm (w) x 10mm (t )
Ø 200mm (4.9mm wall thickness) 15 15 EN N/A 100mm
Ø 200mm (18.2mm wall thickness) 120 90
HDPE pipes Ø 32 - 50mm (2.9mm wall thickness) Rigid floor Intumescent Thickness
Ø 200mm (4.9mm wall thickness) 120 120 EN 150mm thick)
N/A Test
100mm Service separat ion
Service t ype (min. Pipe Diamet er Int umescent Mat erial
Ø 200mm (11.4mm wall thickness) Standard
Int egrit y Insulation Aperture Services Ø32 - 50mm 40mm (w) x 2mm (t )
PVC pipes Ø 32 - 50mm (1.8mm wall thickness) 120 Ø51 - 82mm 40mm (w) x 4mm (t )
120
Ø 200mm (7.7mm wall thickness) 90 EN N/A 100mm Ø83 - 115mm 40mm (w) x 6mm (t )
Ø 200mm (9.6mm wall thickness) 60 60 Ø116 - 160mm 40mm (w) x 8mm (t )
PP pipes Ø 32 - 50mm (2.9mm wall thickness) 120 120 Ø161 - 200mm 40mm (w) x 10mm (t )
Ø 200mm (4.9mm wall thickness) 15 15 EN N/A 100mm
Ø 200mm (18.2mm wall thickness) 120 90
HDPE pipes Ø 32 - 50mm (2.9mm wall thickness)
Ø 200mm (4.9mm wall thickness) 120 120 EN N/A 100mm
Ø 200mm (11.4mm wall thickness)

(V10/NOV22) 57
Pipe Size Wrap Thickness Layers
32-50 40mm (W) x 2mm (T) 1
51-82 40mm (W) x 4mm (T) 2
83-115 40mm (W) x 6mm (T) 3
116-160 40mm (W) x 8mm (T) 4
151-200 40mm (W) x 10mm (T) 5
201-250 40mm (W) x 12mm (T) 6

Insulation Thickness Supporting Substrate Performance Notes T


Penetration Type/Size (mm) Seal Service Treatment Service Separation
(mm) construction Separation Integrity Insulation
40mm 1.8mm - 3.7mm 120 120 WF 405625
PVC
125mm 4.8mm - 7.4mm Double 50mm 120 120 WF 405625
40mm 2.9mm - 6.9mm 150mm thick masonry ROCKWOOL Ablative ROCKWOOL Pipe Wrap 100mm (Between 120 120 Improved separation and flexible wall coverage available from WF 411454 WF 405625
PP 100mm
125mm 3.1mm - 17.1mm wall (650 kg/m³) Coated Batt - 1100mm Roll sleeves) 120 120 (report yet to be finalised) WF 405625
40mm 2.9mm - 4.6mm x 800mm 120 120 WF 405625
HDPE
125mm 3.1mm - 11.4mm 120 120 WF 405625

(V10/NOV22) 58
Pipe Size / Wall / Insulation Classification
Pipe Mat erial Wrap Layers
Pipe Size (mm) Wall Thickness (mm) Insulat ion Type / Size (mm) Int egrit y Insulation
13-25 Elastomeric (C/S - 2 No. 40mm (w) x 2mm
St eel or Copper 42 - 159 1.2 - 14.2 120 60
continuously sustained) (t)
13-25 Elastomeric (C/S - 2 No. 40mm (w) x 2mm
St eel or Copper 42 1 - 14.2 120 90
continuously sustained) (t)
25 - 40 Phenolic (C/S - 2 No. 40mm (w) x 2mm
St eel or Copper 42 - 108 1.2 - 14.2 120 60
continuously sustained) (t)
25 - 40 Phenolic (C/S - 2 No. 40mm (w) x 2mm
St eel or Copper 42 1 - 14.2 120 90
continuously sustained) (t)
50 Glass Fibre (C/S - cont inuously 2 No. 40mm (w) x 2mm
St eel or Copper 42 1 - 14.2 120 90
sustained) (t)

Pipe Mat erial Pipe Size / Wall / Insulation Classification


Wrap Layers
Pipe Size (mm) Wall Thickness (mm) Insulat ion Type / Size (mm) Int egrit y Insulation
25 Phenolic (C/S - continuously 3 No. 40mm (w) x 2mm
Pvc 40 1.9 120 90
sustained) (t)
15 Phenolic (C/S - continuously 3 No. 40mm (w) x 2mm
Pvc 40 3 120 90
sustained) (t)
25 Phenolic (C/S - continuously 5 No. 40mm (w) x 2mm
Pvc 110 4.2 120 120
sustained) (t)
20 Phenolic (C/S - continuously 5 No. 40mm (w) x 2mm
Pvc 110 6.6 120 90
sustained) (t)
32 Elast omeric (C/S - 3 No. 40mm (w) x 2mm
Pvc 40 1.9 120 120
continuously sustained) (t)
9 Elastomeric (C/S - continuously 3 No. 40mm (w) x 2mm
PVC 40 3 120 120
sustained) (t)
32 Elast omeric (C/S - 5 No. 40mm (w) x 2mm
PVC 110 4.2 120 120
continuously sustained) (t)
13 Elast omeric (C/S - 5 No. 40mm (w) x 2mm
PVC 110 6.6 120 120
continuously sustained) (t)

(V10/NOV22) 59
Pipe Size / Wall / Insulation Classification
Pipe Material Wrap Layers
Pipe Size (mm) Wall Thickness (mm) Insulation Type / Size (mm) Integrity Insulation
13 - 25 Elastomeric (C/S - 2 No. 40mm (w) x
Steel or Copper 42 - 159 1.2 - 14.2 120 60
continuously sustained) 2mm (t)
13 - 25 Elastomeric (C/S - 2 No. 40mm (w) x
Steel or Copper 42 1.2 - 14.2 120 90
continuously sustained) 2mm (t)
25 - 40 Phenolic (C/S - 2 No. 40mm (w) x
Steel or Copper 42 - 108 1.2 - 14.2 120 60
continuously sustained) 2mm (t)
25 - 40 Phenolic (C/S - 2 No. 40mm (w) x
Steel or Copper 42 1.2 - 14.2 120 90
continuously sustained) 2mm (t)
50 (30kg/m³) Glassfibre (C/S - 2 No. 40mm (w) x
Steel or Copper 42 1.2 - 14.2 120 90
continuously sustained) 2mm (t)

(V10/NOV22) 60
ROCKWOOL Pipe Wrap Roll to both sides of flexible or ridgid wall (Min 100mm thick)

Pipe Material Pipe Size & Wall Thickness (mm) Wrap Layers Annulus (mm) Classification
PVC 32 - 50 O/A Dia - 1.8mm Wall 1 No. 40mm (W) x 2mm (T) 4 EI 120
PVC 160 O/A Dia - 6.2 - 9.5mm Wall 4 No. 40mm (W) x 2mm (T) 10 EI 90
PVC 160 O/A Dia - 9.5mm Wall 4 No. 40mm (W) x 2mm (T) 10 EI 120
PVC 200 O/A Dia. 7.7 - 9.6mm Wall 5 No. 40mm (W) x 2mm(T) 12 EI120
PP 32 - 50 O/A Dia. - 2.9mm Wall 1 No. 40mm (W) x 2mm (T) 4 EI 120
PP 160 O/A Dia - 4mm Wall 5 No. 40mm (W) x 2mm (T) 10 E 120 (EI90)
PP 160 O/A Dia - 14.6mm Wall 4No. 40mm (W) x 2mm (T) 10 EI 120
PP 200 O/A Dia. - 4.9mm Wall 5 No. 40mm (W) x 2mm(T) 12 E 120 (EI90)
PP 200 O/A Dia. - 18.2mm Wall 5 No. 40mm (W) x 2mm(T) 12 EI 120
PP 250 O/A Dia. - 10.1mm Wall 6 No. 40mm (W) x 2mm(T) 14 E 120
PE 32 - 50 O/A Dia. - 2.9mm Wall 1 No. 40mm (W) x 2mm (T) 4 EI 120
PE 160 O/A Dia - 9.5mm Wall 4 No. 40mm (W) x 2mm (T) 10 EI 90
PP 200 O/A Dia. - 18.4mm Wall 5 No. 40mm (W) x 2mm(T) 12 EI 120

(V10/NOV22) 61
Pipe Size (mm) Wrap Thickness Layers
32-50 40mm (W) x 2mm (T) 1
51-82 40mm (W) x 4mm (T) 2
83-115 40mm (W) x 6mm (T) 3
116-150 40mm (W) x 8mm (T) 4
151-200 40mm (W) x 10mm (T) 5

ROCKWOOL FIREPRO Pipewrap Roll in rigid floor applications (min. 150mm thick) NOTES
Classification
Pipe material Pipe size & wall thickness (mm) Wrap layers (mm) Annulus
Integrity Insulation
PVC Ø 32-50 (1.8mm wall thickness) 2 no. 40 (w) x 2 (t) 4 120 120 UL-EU-01204-CPR
PVC Ø 200 (7.7mm wall thickness) 5 no. 40 (w) x 2 (t) 12 120 90
PVC Ø 200 (9.6mm wall thickness) 5 no. 40 (w) x 2 (t) 12 60 60
PP Ø 32-50 (2.9mm wall thickness) 2 no. 40 (w) x 2 (t) 4 120 120
PP Ø 200 (18.2mm wall thickness) 5 no. 40 (w) x 2 (t) 12 120 90
HDPE Ø 32-50 (2.9mm wall thickness) 2 no. 40 (w) x 2 (t) 4 120 120
HDPE Ø 200 (4.9mm wall thickness) 5 no. 40 (w) x 2 (t) 12 120 120
HDPE Ø 200 (11.4mm wall thickness) 5 no. 40 (w) x 2 (t) 12 120 120

(V10/NOV22) 62
Substrate Backing material Standard
thickness (mm) (mm) (mm) seal Integrity Insulation
20 12.5 Ø 20mm PE rod 120 120 EN
20 10 Ø 20mm PE rod ü 120 45 EN
Concrete wall /
100 30 15 Ø 30mm PE rod ü 120 30 EN
concrete wall
40 20 Ø 40mm PE rod ü 120 30 EN
50 25 Ø 50mm PE rod ü 120 60 EN

min. Substrate max. width min. Depth Single sided Performance (mins)
Substrate Backing material Standard
thickness (mm) (mm) (mm) seal Integrity Insulation
Concrete floor / 20 10 Ø 20mm PE rod ü 240 45 EN
150
concrete floor 50 25 Ø 50mm PE rod ü 240 90 EN

Concrete EN
Concrete EN
min. Substrate max. width min. Depth Single sided Performance (mins)
Substrate Backing material Standard
Concrete EN
thickness (mm)
min. Substrate
(mm)
max. width
(mm)
min. Depth
seal
Single sided
Integrity
PerformanceInsulation
(mins)
Substrate 20 12.5 Backing
Ø 20mmmaterial
PE rod 120 120 Standard
EN
thickness (mm) (mm) (mm) seal Integrity Insulation
min. Substrate max.20
20width min.10
Depth
12.5
Ø 20mm PE rod
Ø 20mmmaterial
PE rod üsided
Single 120
Performance
120
45
(mins)
120
EN
EN
Steel
Concrete wall /
Substrate
concrete wall
100 (mm)
thickness 30
(mm)
20
15
(mm)
10
Backing
Ø 30mm PE rod
Ø 20mm PE rod ü
seal
ü
120
Integrity
120
30
Insulation
45
Standard
EN
EN
Concrete wall / 40
20 20
12.5 ØØ 40mm
20mm PE
PE rod
rod ü 120
120 30
120 EN
EN
100 30 15 Ø 30mm PE rod ü 120 30 EN
concrete wall min. Substrate 50
20
max.40
width 25
10
min.20
Depth Ø 40mm
50mm PE rod
20mm PE rod Single
üsided 120
Performance 60
(mins)
45 EN
Concrete
Substrate
Concrete wall / EN
100 (mm)
thickness 30
(mm)
50 15
(mm)
25
Ø
Backing
ØØ 50mm
material
30mm PE
PE rod
rod
ü
seal
ü
120
120
Integrity
120
30
30
Insulation
60
EN
Standard
EN
EN
concrete wall ü
40
20 20
10 40mm PE rod
Ø 20mm ü 120 30
20 EN
Concrete wall /
Substrate min. Substrate max.30
width
50 min.15
Depth
25 Ø 30mm PE rod
50mmmaterial
Backing Singleüsided Performance
45
120 (mins)
30
60 EN
Standard
100
steel thickness (mm) (mm) (mm) seal Integrity Insulation
min. Substrate max.40
width min.20
Depth Ø 40mm PE rod Singleüsided 45 30
Performance (mins) EN
Substrate
Concrete floor / 20
50 12.5
10
25 Backing
Ø 50mmmaterial
Ø 20mm PE
PE rod
rod ü 120
240
45 120
45
30 Standard
EN
EN
Concrete
concretewall
Concrete
Concrete
floor
floor //
EN
thickness
150 (mm)
min. Substrate
(mm)
20
max.50
20width
(mm)
10
min.25
Depth
10
20mm PE rod
Ø 50mm
Ø 20mmmaterial
PE rod
seal
üsided
Single
Integrity
120
240
Performance
240
Insulation
45
90
(mins)
45
EN
EN
Substrate 100 (mm) 30 15 Backing
Ø 30mm PE rod ü 120 30 Standard
EN
150
thickness (mm) (mm) ü
seal Integrity Insulation
concretefloor
concrete wall 50 25 Ø 50mm PE rod ü 240 90 EN
Concrete floor
Substrate / min.
min. Substrate
Substrate max.40
max. width
20
width min.20
min. Depth
10
Depth ØØ 40mm PE
PE rod
20mmmaterial
Backing rod Singleüsided
Singleüsided 120
Performance
Performance
240 30
(mins)
(mins)
45 EN
EN
Standard
Substrate 150 50 25 Backing
Ø material Standard
concrete floor thickness
thickness (mm)
(mm) (mm)
50
(mm) (mm)
25
(mm) Ø 50mm
50mm PE
PE rod
rod seal
ü
seal
ü 120
Integrity
240
Integrity 60
Insulation
90
Insulation EN
EN
Concrete floor / 20
20 12.5
10 Ø 20mm
Ø 20mm PE
PE rod
rod ü 120
120 120
20 EN
EN
150 20 10 Ø 50mm
20mm PE
PE rod
rod ü 120 45 EN
steelwall /
Concrete 50 50 Ø ü 240 90 EN
100
min. Substrate max.30
width min.15
Depth Ø 30mm PE rod Singleüsided Performance
120 (mins)
30 EN
Substrate
concrete wall Backing material Standard
thickness (mm) 40
(mm) 20
(mm) Ø 40mm PE rod seal
ü 120
Integrity 30
Insulation EN
Steel
Concrete floor /
concrete floor
150
20
50
50
10
25
25
Ø 20mm
50mm PE rod
Ø 50mm PE rod
ü 240
120
240
45
60
90
EN
EN
Hardwood
Steel
ü

min. Substrate max. width min. Depth Single sided Performance (mins)
Substrate Backing material Performance (mins) Standard
Steel
Substrate
min. Substrate
thickness (mm)
min. Substrate
thickness (mm)
max. width
(mm)
max. width
(mm)
min. Depth
(mm)
min. Depth
(mm)
Backing material
Single sided
seal
Single sided
seal
Integrity
PerformanceInsulation
Integrity (mins)
Insulation
Standard
Substrate 20 10 Backing
Ø 20mmmaterial
PE rod ü 120 20 Standard
EN
Concrete floor / thickness (mm) (mm)
20 (mm)
10 Ø 20mm PE rod seal
ü Integrity
240 Insulation
45 EN
Concrete wall / 150
min. Substrate max.30
width min.15
Depth Ø 30mm PE rod üsided
Single 45
Performance 30
(mins) EN
concrete floor
Substrate 100 20
50 10
25 Ø 20mm PE rod
50mmmaterial
Backing ü 120
240 20
90 EN
Standard
steel thickness (mm) 40
(mm) 20
(mm) Ø 30mm
40mm PE
PE rod
rod seal
ü 45
Integrity 30
Insulation EN
Concrete wall / 30 15 Ø ü 45 30 EN
100 50
20 25
10 Ø 50mm
20mm PE rod ü 45
120 30
20 EN
steel 40 20 Ø 40mm PE rod ü 45 30 EN
Concrete wall / 30 15 Ø 50mm
30mm PE
PE rod
rod 45 30 EN
Steel
steel
100 50
40
25
20
Ø
Ø 40mm PE rod
üü
ü
45
45
30
30
EN
EN
min. Substrate max.50
width min.25
Depth Ø 50mm PE rod Singleüsided Performance
45 (mins)
30 EN
Substrate Backing material Performance (mins) Standard
min. Substrate
thickness (mm) max. width
(mm) min. Depth
(mm) Single
sealsided Integrity Insulation
Substrate min. Substrate max. width min. Depth Backing material Single sided Performance (mins) Standard
Substrate
Concrete floor / thickness (mm) (mm)
20 (mm)
10 Backing
Ø 20mmmaterial
PE rod seal
ü Integrity
120 Insulation
20 Standard
EN
thickness
150 (mm) (mm) (mm) seal Integrity Insulation
steel min. Substrate 20
50
max.20
width 10
50
min.10
Depth 20mm PE rod
Ø 50mm üsided
Single 120
240
Performance 20
90
(mins) EN
Steel
Concrete floor /
Substrate
Concrete wall / 150 (mm)
thickness 30
(mm) 15
(mm)
Ø 20mmmaterial
Backing PE rod
Ø 30mm PE rod ü
ü
seal
120
45
Integrity
20
30
Insulation
EN
Standard
EN
Softwood
steel
steelfloor /
Concrete
100 50
40
20
50
20
10
Ø 50mm PE rod
ØØ 40mm
20mm PE
PE rod
rod
ü
ü
ü
240
45
120
90
30
20
EN
EN
EN
150 max.50 min.25 Ø
steel
Substrate
min. Substrate width
50 Depth
50 Ø 50mm PE
PE rod
50mmmaterial
Backing rod Singleü
üsided 45
Performance
240 30
(mins)
90 EN
EN
Standard
min. Substrate
thickness (mm) max. width
(mm) min. Depth
(mm) Single sided
seal PerformanceInsulation
Integrity (mins)
Hardwood
Substrate
thickness (mm) (mm)
20 (mm)
10
Backing material
Ø 20mm PE rod seal
ü Integrity
120 Insulation
20
Standard
EN
Hardwood
Concrete wall /
Substrate
min. Substrate
100
20
max.30
width 10
min.15
Depth 20mm PE rod
Ø 30mm
Backing material
Singleüsided 30
Performance
45 15
(mins)
30 EN
Standard
steel thickness (mm) 30
(mm)
40 15
(mm)
20 30mm PE rod
Ø 40mm seal 30
Integrity
45 15
Insulation
30 EN
Hardwood
Concrete wall /
Concrete floor / 100 40
20
50 20
10
25 40mm PE rod
Ø 20mm
50mm
ü
ü 30
120
45 15
20
30 EN
softwood 150
steel 50 25
50 Ø 50mm PE rod ü 45
240 30
90 EN
50 50 Ø 50mm PE rod ü 45 45 EN
min. Substrate max. width min. Depth Single sided Performance (mins)
Substrate Backing material Standard
Plasterboard thickness (mm) (mm) (mm) seal Integrity Insulation
Hardwood
Concrete floor /
steel
150
20
50
10
50
Ø 20mm PE rod
Ø 50mm PE rod
ü 120
240
20
90
EN
EN
ü
min. Substrate max. width min. Depth Single sided Performance (mins)
Substrate Backing material Standard
thickness (mm) (mm) (mm) seal Integrity Insulation
Head of wall /
120 20 25 Steel head track 120 120 EN
concrete soffit
Softwood
Hardwood
Softwood
min.
min. Substrate
Substrate max.
max. width
width min.
min. Depth
Depth Single
Single sided
sided Performance
Performance (mins)
(mins)
Substrate Backing
Backing material Standard
Softwood
Substrate thickness
thickness (mm)
(mm)
min. Substrate
(mm)
(mm)
max. width
(mm)
(mm)
min. Depth
material seal
seal
Single sided
Integrity
PerformanceInsulation
Integrity Insulation
(mins)
Standard
Substrate 20 10 Backing
Ø 20mmmaterial
PE rod ü 30 15 Standard
EN
Flexible wall / thickness
120(mm) (mm)
20 (mm)
12.5 Ø 30mm
20mm PE
PE rod
rod seal Integrity
120 Insulation
120 EN
concrete
Concrete wall/
wall min. Substrate max.30
20width min.15
Depth
10
Ø
Ø 20mmmaterial
PE rod üsided
Single
ü
30
Performance
30
15
(mins)
15
EN
EN
Substrate Backing Standard
100 (mm)
thickness 40
(mm) 20
(mm) Ø 30mm
40mm PE
PE rod
rod seal
ü 30
Integrity 15
Insulation EN
softwood 30 15 Ø ü 30 15 EN
Concrete wall / 50
20 25
10 Ø 50mm
20mm PE rod ü 45
30 30
15 EN
100 40 20 Ø 40mm PE rod ü 30 15 EN
softwood 50
30 50
15 Ø 50mm
30mm PE rod ü 45
30 45
15 EN
Softwood
Concrete wall /
100
50
40
50
25
20
50
Ø 50mm
ØØ 50mm
PE rod
40mm PE
PE rod
rod
ü
ü
45
30
45
30
15
45
EN
EN
EN
softwood ü
Plasterboard min. Substrate
50
max.50
width
25
min.50
Depth
Ø 50mm PE rod ü
Singleüsided
45
Performance
30
(mins)
EN
Ø 50mmmaterial
PE rod 45 45 EN
Plasterboard
Substrate
thickness (mm) (mm) (mm)
Backing
seal Integrity Insulation
Standard
min. Substrate max.20
width min.10
Depth Ø 20mmmaterial
PE rod Singleüsided Performance
30 (mins)
15 EN
Substrate Backing Standard
Plasterboard
Softwood thickness (mm)
min. Substrate
(mm)
max.30
width
(mm)
min.15
Depth Ø 30mm PE rod seal
Singleüsided
Integrity
30
PerformanceInsulation
15
(mins) EN
Concrete
Head wall//
Substrate
of wall Backing material Standard
100(mm)
thickness
120 40
(mm)
20 20
(mm)
25 Steel headPEtrack
Ø 40mm rod seal
ü 30
Integrity
120 15
Insulation
120 EN
EN
softwood
concrete soffit Performance (mins)
Head of wall / min. Substrate
min. Substrate max.50
max. width
width min.25
min. Depth
Depth Ø 50mmmaterial
PE rod Single sided
Singleüsided 45
Performance 30
(mins) EN
Substrate
Substrate 120 (mm) 20 25 Backing
Backing
Steel material
head Standard
Standard
concrete soffit thickness
thickness (mm) (mm)
50
(mm) (mm)
50
(mm) Ø 50mm PEtrack
rod seal
seal
ü
120
Integrity
45
Integrity
120
Insulation
45
Insulation
EN
EN
Head of wall / 20 10 Ø 20mm
120 20 25 Steel headPEtrack
rod ü 30
120 15
120 EN
EN
concrete soffit min. Substrate max.30
width min.15
Depth Singleüsided Performance (mins)
Plasterboard
Substrate
Concrete wall / thickness
100(mm) (mm) (mm)
Ø 30mmmaterial
Backing PE rod
seal
30
Integrity
15
Insulation
EN
Standard
softwood min. Substrate max.40
width min.20
Depth Ø 40mm PE rod Singleüsided 30
Performance 15
(mins) EN
Substrate
Flexible wall / Backing material Standard
thickness
120 (mm) 50
(mm)
20 25
(mm)
12.5 Ø 20mm
Ø 50mm PE PE rod
rod seal
ü 45
Integrity
120 30
Insulation
120 EN
EN
min. Performance (mins)
concrete wall
Substrate
Flexible wall / min. Substrate
Substrate max. width
max.50
width min. Depth
min.50
Depth Backing
Ø 50mmmaterial
PE rod
Single
Single sided
üsided Performance
45 (mins)
45 Standard
EN
Substrate thickness
120 (mm) (mm)
20 (mm)
12.5 Backing
Ø 20mmmaterial
PE rod seal Integrity
120 Insulation
120 Standard
EN
concrete wall thickness (mm) (mm) (mm) seal Integrity Insulation
Head of wall
Flexible wall //
Plasterboard
concrete
concretesoffit
wall
120
120 20
20 25
12.5 Steel
Ø 20mmheadPEtrack
rod 120
120 120
120 EN
EN

min. Substrate max. width min. Depth Single sided Performance (mins)
Substrate Backing material Standard
thickness (mm)
min. Substrate (mm)
max. width (mm)
min. Depth seal
Single sided PerformanceInsulation
Integrity (mins)
Substrate Backing material Standard
Head of wall / thickness (mm) (mm) (mm) seal Integrity Insulation
120 20 25 Steel head track 120 120 EN
concrete soffit
Flexible wall /
120 20 12.5 Ø 20mm PE rod 120 120 EN

(V10/NOV22)
concrete wall
63
min. Substrate max. width min. Depth Single sided Performance (mins)
Substrate Backing material Standard
thickness (mm) (mm) (mm) seal Integrity Insulation
Flexible wall /
120 20 12.5 Ø 20mm PE rod 120 120 EN
concrete wall
(V10/NOV22) 64
(V10/NOV22) 65
(V10/NOV22) 66
Flexible / rigid wall
Test Service separation
Service type Backing material (min. 100mm thick)
Standard
Integrity Insulation Aperture Services
Blank seal ≤ 180mm x 180mm 120 120
Electrical cable ≤ Ø 21mm 120 120
Ø 22mm - 50mm 20mm thick 90 60
EN 10mm N/A
Telecomm cables ≤ Ø 100mm bundle ROCKWOOL RWA45 120 120
PVC conduit ≤ Ø 16mm 120 120
Copper / steel conduit ≤ Ø 16mm 120 15

(V10/NOV22) 67
(V10/NOV22) 68
Performance (mins) Performance (mins) Service separation
H&V Test
Service type Annular gap Locally Sustained Continuously Sustained minimum (mm)
Thickness Standard
Integrity Insulation Integrity Insulation Aperture Services
Copper pipe ≤ Ø 15mm
≤ 10mm
Steel pipe ≤ Ø 60mm
Copper pipe ≤ Ø 15mm 20mm 120 120 120 120
Steel pipe ≤ Ø 60mm 11 - 50mm
Copper pipe custer Ø 15 - 60mm
Copper pipe ≤ Ø 15mm 120
Ø 16mm - 108mm 120 60 120 120
≤ 10mm
Steel pipe ≤ Ø 114mm EN 0 0
90
Ø 114mm - 219mm 90 90 90
25mm
Copper pipe ≤ Ø 15mm 120
120
Ø 16mm - 108mm
11 - 50mm 120 90 120
Steel pipe ≤ Ø 114mm
90
Ø 114mm - 219mm 60
Copper pipe cluster Ø 15mm - 108mm 60
25mm ≤ 50mm 120 120 120
Steel pipe cluster Ø 15mm - 114mm 120

(V10/NOV22) 69
Sealant
Sleeve Pipe Seal Aperture Size Annular Gap Backer EI Rating Spacing
Depth
42 - 108mm 15 - 76mm Compound 440 x 330 14 - 47mm RWA45 15mm 120/10 0mm From Aperture Edge
42 - 108mm 15 - 76mm Double 50mm ACB 440 x 330 14 - 47mm RWA45 15mm 120/15 0mm From Aperture Edge

(V10/NOV22) 70
(V10/NOV22) 71
(V10/NOV22) 72
(V10/NOV22) 73
Integrity & Insulation
Wall Thickness
2A with 2B
100mm 2 hours
150mm 3 hours
200mm 4 hours

(V10/NOV22) 74
Fire Resistance Cavity Assessment/
Product SP Brackets Test Standard
Vertical Horizontal (mm) Certification

SP60 Firestop Slab EI60 EI60 50 - 300 50-100 SP/S | 101-300 SP/L BS 476 Part 20 CC 89697 Revision 8

SP120 Firestop Slab EI120 EI120 50 - 300 50-100 SP/S | 101-300 SP/L BS 476 Part 20 CC 89697 Revision 8

SP60 Firestop Slab E120, EI30 EI60 301 - 400 301-400 SP/L BS 476 Part 20

SP120 Firestop Slab E120, EI60 E120 301 - 400 301-400 SP/L BS 476 Part 20

Fire performance with +/- 3%

SP60 Firestop Slab N/A EI60 50 - 300 50-100 SP/S | 101-300 SP/L BS EN 1366-4 Certifire CF5836

SP120 Firestop Slab N/A EI120 50 - 300 50-100 SP/S | 101-300 SP/L BS EN 1366-4 Certifire CF5836

SP Plus

SP Plus EI120 EI120 50 - 600mm SP/XL BS EN 1366-4 Certifire CF5836

SP Plus N/A EI60 50 - 1000mm SP/XL BS EN 1366-4 Certifire CF5836

(V10/NOV22) 75
(V10/NOV22) 76
Service separat ion
Performance (mins) Test
Service t ype minimum (mm) Notes
Standard
Int egrit y Insulation Aperture Services
≤ Ø 40mm (1.9mm - 3mm wall) 90 Insulat ed Fire Sleeve wrapped
PVC pipe 120
Ø 41mm - 110mm (4.2mm - 6.6mm wall) 60 around the pipes with 50mm
≤ Ø 40mm (2.4mm - 3.7mm wall) 90 projection to both sides of
HDPE pipe 120
Ø 41mm - 110mm (2.7mm - 10mm wall) 60 EN 0 100 t he seal.

St eel or copper H&V Pipe Section installed


≤ Ø 108 mm 120 30
pipe 1m centrally through the seal.

(V10/NOV22) 77
November 2022

ROCKWOOL Limited
Pencoed
Bridgend
CF35 6NY
Tel: 01656 862 621
[email protected]
rockwool.com/uk