ECL310 Manual
ECL310 Manual
5.0 Settings........................................................... 61
5.1 Introduction to Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
5.2 Flow temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
5.3 Room limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
5.4 Return limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
5.5 Flow / power limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
5.6 Optimization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
5.7 Control parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
5.8 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
5.9 Heat cut-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
5.10 Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
5.11 Alarm overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
5.12 Anti-bacteria. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
5.13 Water meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Together with the ECL Comfort 310, the additional Internal I/O
module ECA 32 (order code no. 087H3202) can be used for extra
data communication to SCADA:
• Temperature, Pt 1000 (default)
• 0 - 10 volt signals
The set-up of input type can be done by means of the Danfoss
Software "ECL Tool".
The B-types have no display and dial. The B-types are operated by
means of the Remote Control unit ECA 30 / 31:
• ECA 30 (087H3200)
• ECA 31 (087H3201)
Safety Note
To avoid injury of persons and damages to the device, it is absolutely
necessary to read and observe these instructions carefully.
Progress bar
During update:
• Do not remove the KEY
If the key is removed before the hour-glass is shown, you have
to start afresh.
• Do not disconnect the power
If the power is interrupted when the hour-glass is shown, the
controller will not work.
12174 1 2 174
- Circuit 2 Parameter no.
Disposal Note
This product should be dismantled and its components
sorted, if possible, in various groups before recycling
or disposal.
Always follow the local disposal regulations.
2.0 Installation
87H2097.11
S1
Da nfos s
The applications are very flexible. These are the basic principles: A1
S3
Heating (circuit 2 in A376.1, A376.2, A376.3, A376.9, A376.10) List of components: A376 in general, pumps and actuators
This circuit works after same principles as circuit 1.
P1 DHW circulation pump, circuit 3
The flow temperature sensor S9 is the most important sensor. P2 Heating circulation pump, circuit 1
By means of a week schedule (up to 3 ‘Comfort’ periods / day), P3 A376.1, A376.2, A376.3, A376.9, A376.10:
heating circuit 2 can be in ‘Comfort’ or ‘Saving’ mode (two different Heating circulation pump, circuit 2
temperature values for desired room temperature). The motorized A376.4: DHW circulation pump, circuit 2
control valve M3 controls the circuit.
M1 Motorized control valve, circuit 3
The return temperature (S10) enables limitation as described M2 Motorized control valve, circuit 1
previously.
M3 Motorized control valve, circuit 2
A connected flow or energy meter based on M-bus signal can limit A1 Alarm
the flow or energy to a set maximum value. Furthermore, the
limitation can be in relation to the outdoor temperature. Typically,
the lower the outdoor temperature, the higher the accepted flow / A376.1 example a:
power. ECL 310
87H2097.11
S1
Da nfos s
The circulation pump (P3) is ON at heat demand or at frost A1
protection. S3
S2
P2 1
The heating can be switched OFF when the outdoor temperature is M2
S5
higher than a selectable value.
S9
87H2098.11
S1
heating demand can be arranged.
Da nfos s
A1
S3
S2
P2 1
M2
S5
M3
S9
S7
P3 2
S10
S4
M1 3
S6
P1
87H2099.11
S1
Da nfos s
A1
If the measured DHW temperature (S4 / S9) is lower than the S3
desired DHW temperature, the motorized control valve (M1 / M3) is (S2)
P3 2
The return temperature (S6 / S10) can be limited to a fixed value. M3
S10
A376.9, A376.10: S7 S4
The return temperature S6 can measure, for monitoring purpose,
the return temperature on the secondary side. An alternative M1 3
position for S6 can be in the return on the primary side in order to S6
87H2100.11
S1
or ‘Saving’ mode (two values for the desired DHW temperature).
Da nfos s
A1
If the desired DHW temperature cannot be reached, the heating A376.3 example a:
circuit can be closed gradually to allow more energy to the DHW
circuit. ECL 310
87H2101.11
S1
Da nfos s
A1
An anti-bacteria function is available for activation on selected + ECA 32
P2 1
The outdoor temperature (S1) is used to protect the circulation A
M2
S5
circuit(s) against frost.
S9
S7
P3 2
M3
A S10
S4
M1 3
A S6
P1
87H1430.11
S1
Da nfos s
Schedule in "Common controller" is connected to the output O1 A1
and can be used for various issues.
S3
S2
P2 1
M2
Heating circuits 1 and 2: S5
• The secondary return temperatures (S2 and S10) are used for
M3 2
monitoring only. S10
• The pressure measurings, 0-10 volt (S7 and S14,) are used to S7 S4
P3
S8
P1
DHW circuit 3:
• The return temperature S6 can measure, for monitoring
purpose, the return temperature on the secondary side. An A376.9 example a:
alternative position for S6 can be in the return on the primary
side in order to limit the return temperature to a fixed value.
All circuits:
A376.9 example b:
• The temperatures (S11 and S12) are used for monitoring only. ECL 310
87H2104.11
S1 S8 S15 S16
Da nfos s
• The switch inputs (S8, S15 and S16) are related to the circuits + ECA 32
A1
Application A376.10
The application A376.10 is similar to the A376.9. S 11
M3
S9
The application A376.10 requires the internal I/O module ECA 32.
S11 and S12 measure supply flow and return pressures for S14
P3
2
S12 S10
monitoring.
S13 measures return temperature.
S14 measures pressure. S4
A376.10 example a:
Application: Relay:
A376.1, A376.2, A376.3, A376.4 Relay 6
A376.9, A376.10 Relay 4
See the Mounting Guide (delivered with the application key) for
application examples and electrical connections.
Circuit 1 can act as master and the remaining circuits can act as
slaves.
When the A376 has been uploaded with the subtypes A376.1,
A376.2, A376.3 and A376.4, the ECL Comfort controller starts
in Manual mode. This can be used for checking the controlled
components for correct functionality.
The subtypes A376.9 and A376.10 start, after upload, in Scheduled
mode.
See the Mounting Guide (delivered with the application key) for
application types / sub-types.
When a heating or DHW circuit should not send its heat demand
to circuit 1 or the master:
MENU \ Settings \ Application: 'Send desired T' (ID 1x500): OFF
2.3 Mounting
For easy access, you should mount the ECL Comfort controller near
the system. Select one of the following methods using the same
base part (code no. 087H3220):
• Mounting on a wall
• Mounting on a DIN rail (35 mm)
ECL Comfort 210 can be mounted in an ECL Comfort 310 base part
(for future upgrade).
If the controller is not securely locked into the base part, there is a risk
that the controller during operation can unlock from the base and the
base with terminals (and also the 230 V a.c. connections) are exposed.
To prevent injuries to persons, always make sure that the controller
is securely locked into its base. If this is not the case, the controller
should not be operated!
The easy way to lock the controller to its base or unlock it is to use a
screw driver as lever.
Mounting on a wall
Mount the base part on a wall with a smooth surface. Establish the
electrical connections and position the controller in the base part.
Secure the controller with the locking pin.
The easy way to lock the controller to its base or unlock it is to use a
screw driver as lever.
Before removing the ECL Comfort controller from the base part, ensure
that the supply voltage is disconnected.
Mounting on a wall
Mount the base part of the ECA 30 / 31 on a wall with a smooth
surface. Establish the electrical connections. Place the ECA 30 /
31 in the base part.
Mounting in a panel
Mount the ECA 30 in a panel using the ECA 30 frame kit (order code
no. 087H3236). Establish the electrical connections. Secure the
frame with the clamp. Place the ECA 30 in the base part. The ECA
30 can be connected to an external room temperature sensor.
Make sure that the surface of the pipe is clean and even where
the sensor is mounted.
Return temperature sensor (ESMU, ESM-11 or ESMC)
The return temperature sensor should always be placed so that it
measures a representative return temperature.
ESMU and ESMB-12: Using a sensor pocket to protect the sensor will,
however, result in a slower temperature measurement.
Pt 1000 temperature sensor (IEC 751B, 1000 Ω / 0 °C) Relationship between temperature and ohmic value:
Ω
°C Ω 1600
-50 803
1500
-40 843
-30 882
-20 922 1400
-10 961
0 1000
1300
10 1039
20 1078
30 1117 1200
40 1155
50 1194 1100
60 1232
70 1271
80 1309 1000
90 1347
100 1385 900
110 1423
120 1461
800
130 1498
140 1535
150 1573 °C
-50 -25 0 25 50 75 100 125 150
Safety Note
Necessary assembly, start-up, and maintenance work must be
performed by qualified and authorized personnel only.
See also the Mounting Guide (delivered with the application key)
for application specific connections.
See also the Mounting Guide (delivered with the application key)
for application specific connections.
See also the Mounting Guide (delivered with the application key)
for application specific connections.
See the Mounting Guide (delivered with the application key) for
sensor and input connections.
Sen- Description Recomm. type * If the outdoor temperature sensor is not connected or the
sor cable is short-circuited, the controller assumes that the
outdoor temperature is 0 (zero) °C.
S1 Outdoor temperature sensor * ESMT
** Only for room temperature sensor connection. The room
temperature signal can also be available from a Remote
S2 A376.1, A376.2, A376.3, A376.4: ESM-10 Control Unit (ECA 30 / 31). See the Mounting Guide (delivered
Room temperature sensor ** with the application key) for specific connections.
Alternative: ECA 30 / 31
*** The flow temperature sensor must always be connected
A376.9, A376.10: ESM-11 / ESMB / in order to have the desired functionality. If the sensor is
Return temperature sensor ESMC / ESMU not connected or the cable is short-circuited, the motorized
(heating, secondary side) control valve closes (safety function).
(S2) A376.2: ESM-10
Room temperature sensor **
Alternative: ECA 30 / 31
S3 Flow temperature sensor *** ESM-11 / ESMB /
(heating) ESMC / ESMU
S4 Flow temperature sensor *** ESM-11 / ESMB /
(DHW) ESMC / ESMU
S5 Return temperature sensor ESM-11 / ESMB /
(heating) ESMC / ESMU
S6 A376.1, A376.2, A376.3, A376.4: ESM-11 / ESMB /
Return temperature sensor ESMC / ESMU
(DHW)
A376.9, A376.10: ESM-11 / ESMB /
Return temperature sensor ESMC / ESMU
(DHW), for monitoring
(S6) A376.9, A376.10: ESM-11 / ESMB /
Return temperature sensor, ESMC / ESMU
(DHW), alternative position.
S7 A376.1, A376.3: ESM-10
Room temperature sensor **
Alternative: ECA 30 / 31
A376.2, A376.4: ESM-11 / ESMB /
Supply flow temperature sensor ESMC / ESMU
A376.9, A376.10:
Pressure transmitter, 0 - 10 V or
4 - 20 mA
S8 A376.2, A376.4:
Flow switch
A376.9, A376.10:
Alarm contact / switch
S9 Flow temperature sensor *** ESM-11 / ESMB /
(heating) ESMC / ESMU
S10 A376.1, A376.2, A376.3, A376.4: ESM-11 / ESMB /
Return temperature sensor ESMC / ESMU
(heating)
A376.9, A376.10: ESM-11 / ESMB /
Return temperature sensor, for ESMC / ESMU
monitoring
See the Mounting Guide (delivered with the application key) for
sensor and input connections.
ECA 32:
Total cable length: Max. 200 m (all sensors incl. internal ECL 485
communication bus).
Cable lengths of more than 200 m may cause noise sensibility (EMC).
The ECL 485 communication bus is not compatible with the ECL
bus in ECL Comfort 110, 200, 300 and 301!
Total cable length: Max. 200 m (all sensors incl. internal ECL 485
communication bus).
Cable lengths of more than 200 m may cause noise sensibility (EMC).
Progress bar
During update:
• Do not remove the KEY
If the key is removed before the hour-glass is shown, you have
to start afresh.
• Do not disconnect the power
If the power is interrupted when the hour-glass is shown, the
controller will not work.
If the ECL Application Key is not suitable for the controller, a "cross"
is displayed over the ECL Application Key-symbol.
Go to ‘Aut. daylight’
Choose whether ‘Aut. daylight´ *
YES or NO
should be active or not
The application is installed, and the controller resets and starts up.
B
The ECL Application key contains changed system settings:
Push the dial repeatedly.
’NO’: Only factory settings from the ECL Application Key will
be copied to the controller.
’YES*: Special system settings (differing from the factory
settings) will be copied to the controller.
‘NO: Only factory settings from the ECL Application Key will
be copied to the controller.
‘YES*: Special user settings (differing from the factory settings)
will be copied to the controller.
(Example):
The "i" in the upper right corner indicates that - besides the factory
settings - the subtype also contains special user / systems settings.
Confirm
Choose the circuit selector at the top
right corner in the display
Confirm
Confirm
Confirm
Confirm
Choose the circuit selector at the top
right corner in the display
Confirm
Confirm
Go to ‘Key functions’
Confirm
Choose ‘Copy’
Confirm
Choose ‘To’.
*
‘ECL’ or ‘KEY’ will be indicated. Choose
’ECL’ or ‘KEY’.
’ECL’ or KEY’
Push the dial repeatedly to choose
copy direction
Choose ‘System settings’ or ‘User **
settings’ ‘NO’ or ‘YES’
Push the dial repeatedly to choose
‘Yes’ or ‘No’ in ‘Copy’. Push to confirm.
Choose ‘Start copying’
The Application Key or the controller
is updated with special system or user
settings.
*
‘ECL’: Data will be copied from the Application Key to the
ECL Controller.
‘KEY’: Data will be copied from the ECL Controller to the
Application Key.
**
‘NO’: The settings from the ECL controller will not be copied
to the Application Key or to the ECL Comfort controller.
‘YES’: Special settings (differing from the factory settings) will
be copied to the Application Key or to the ECL Comfort
controller. If YES can not be chosen, there are no special
settings to be copied.
General principles
When the controller is connected and operating, you can check
and adjust all or some of the basic settings. The new settings can
be stored on the Key. Factory settings can always be restored.
How to store factory setting in the controller from the Make a note of new settings in the 'Settings overview' table.
Application Key?
Please read the paragraph concerning Application Key, Situation
1: The controller is new from the factory, the ECL Application Key
is not inserted.
Do not remove the ECL Application Key while copying. The data on
How to store personal settings from the controller to the Key? the ECL Application Key can be damaged!
Please read the paragraph concerning Application Key, Situation 3:
A copy of the controllers settings is needed for configuring another
controller
Make sure that the correct power supply is connected to terminals 9 and 10 (230 V or 24 V).
Check that the required controlled components (actuator, pump etc.) are connected to the correct terminals.
Check that all sensors / signals are connected to the correct terminals (see 'Electrical connections').
Is the ECL Application Key inserted (see 'Inserting the Application Key').
Does the ECL Comfort controller contain an existing application (see 'Inserting the Application Key').
Is the time & date set correctly (see 'Time & Date' in 'Common controller settings').
Check that all settings in the controller (see 'Settings overview') are set or that the factory settings comply with your
requirements.
Choose manual operation (see 'Manual control'). Check that valves open and close, and that required controlled
components (pump etc.) start and stop when operated manually.
Check that the temperatures / signals shown in the display match the actual connected components.
Having completed the manual operation check, choose controller mode (scheduled, comfort, saving or frost protection).
Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, circuit 1, Heating
Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, circuit 1, Heating continued
Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, circuit 1, Heating continued
Parallel priority ( ( ( (
Holiday ( ( ( ( ( (
Ext. override ( ( ( ( ( (
ECA override ( ( (
Boost ( ( ( ( ( (
Ramp ( ( ( ( ( (
Slave, demand ( ( ( ( ( (
Heating cut-out ( ( ( ( ( (
DHW priority ( ( ( ( ( (
SCADA offset ( ( ( ( ( (
Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, circuit 2, Heating
Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, circuit 2, Heating continued
Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, circuit 2, Heating continued
Parallel priority ( ( (
Holiday ( ( ( ( (
Ext. override ( ( ( ( (
ECA override ( (
Boost ( ( ( ( (
Ramp ( ( ( ( (
Heating cut-out ( ( ( ( (
DHW priority ( ( ( ( (
SCADA offset ( ( ( ( (
Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, DHW
Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, DHW continued
Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, DHW continued
Holiday ( ( ( ( ( (
Ext. override ( ( ( ( ( (
Anti-bacteria ( ( ( ( ( (
SCADA offset ( ( ( ( ( (
Log 1, 2 & 3 (sensors) Log today Outdoor T Outdoor T DHW flow & des.
Log yesterday Heating flow & des. Heating flow & des. DHW return T
Log 2 days Heat return T & limit Heat return T & limit Supply T
Log 4 days Room T Room T
Log 1, 2 & 3 (sensors) Log today Outdoor T Outdoor T DHW flow & des.
Log yesterday Heating flow & des. Heating flow & des. DHW return T
Log 2 days Heat return T & limit Heat return T & limit
Log 4 days Room T Room T
Log 1, 2 & 3 (sensors) Log today Outdoor T DHW flow & des. DHW flow & des.
Log yesterday Heating flow & des. DHW return T DHW return T
Log 2 days Heat return T & limit Supply T
Log 4 days Room T
The dial has a built-in accellerator. The faster you turn the dial, the
faster it reaches the limits of any wide setting range.
The position indicator in the display ( ) will always show you where
you are.
Confirm
Choose the circuit selector at the top
right corner in the display
Confirm
Confirm
Dependent on chosen display, the overview displays for the DHW Example of overview display with
circuit inform you about: Influence indication:
• actual DHW temperature (50.3)
• controller mode ( )
• desired DHW temperature (50 °C)
• comfort schedule of the current day(0 - 12 - 24)
• state of the controlled components (M1, P1)
• actual DHW temperature (50 °C), (desired DHW temperature (50))
• return temperature (- - °C) (limitation temperature (30))
Confirm
Confirm
Confirm
Confirm
Cooling mode
Heating circuit
Display example:
49 °C Flow temperature
(31) Desired flow temperature
24 °C Return temperature
(50) Return temperature limitation
50 °C Flow temperature
(50) Desired flow temperature
-- Return temperature: sensor not connected
(30) Return temperature limitation
Input overview
Arrow-down:
The parameter in question reduces the desired flow temperature.
Arrow-up:
The parameter in question increases the desired flow temperature.
Double-arrow:
The parameter in question creates an override (e.g. Holiday).
Straight line:
No active influence.
Confirm
Controlled components Circuit selector
Choose manual mode
Confirm
Choose pump
Confirm
Confirm valve mode When manual control is selected for one circuit, it is automatically
selected for all circuits!
To leave manual control, use the mode selector to select the
desired mode. Push the dial.
3.7 Schedule
This section describes the schedule in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application
related. They might differ from the displays in your application.
In some applications, however, there might be more than one
schedule. Additional schedules can be found in ‘Common
controller settings’.
The schedule will day-by-day show you the start and stop times of
your comfort periods (heating / DHW circuits).
Confirm
You can set max. 3 comfort periods a day. You can delete a comfort
period by setting start and stop times to the same value.
The start and stop times can be set in half-hourly (30 min. ) intervals.
5.0 Settings
The note "See Appendix …" refers to the Appendix at the end
of this Installation Guide, where parameter's setting ranges and
factory settings are listed.
The navigation hints (for example MENU > Settings > Return limit
… ) cover multiple subtypes.
values. 60
A
40
The shown value for the heat curve is an average value (slope),
based on the actual settings. 20
Heat curve
Circuit Setting range Factory setting
1 0.1 ... 4.0 1.0
When the slope of the heat curve is changed by means of the slope
value, the common point for all heat curves will be a desired flow
temperature = 24.6 °C at an outdoor temperature = 20 °C
The heat curves represent the desired flow temperature at different outdoor temperatures and at a desired room temperature of 20 °C.
110
1.4
100
90
1.0
80
70
0.6
60
50
40 0.2
30
20
10
The small arrows ( ) indicate 6 different outdoor temperature values at which you can change the heat curve.
Temp. min. (duct / flow / inlet temp. limit, min.) 1x177 ‘Temp. min.’ is overruled if 'Total stop' is active in Saving mode or
'Cut-out' is active.
Circuit Setting range Factory setting
‘Temp. min.’ can be overruled by the influence from the return
All * * temperature limitation (see 'Priority').
Set the min. duct / flow / inlet temperature for the system. The
desired duct / flow / inlet temperature will not be lower than this The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.
setting. Adjust the factory setting, if required.
Temp. max. (duct / flow / inlet temp. limit, max.) 1x178 The setting of ‘heat curve’ is possible for heating circuits only.
Circuit Setting range Factory setting
All * *
* See Appendix “Parameter ID overview” The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.
Set the max. flow / duct / inlet temperature for the system. The
desired temperature will not be higher than this setting. Adjust
the factory setting, if required.
If the duct / room temperature is higher than the desired value, the
desired flow temperature can be reduced.
Use this influence type to avoid a too high duct / room temperature.
The controller will allow for free heat gains, i.e. solar radiation or
heat from a fire place etc.
If the duct / room temperature is lower than the desired value, the
desired flow temperature can be increased.
Use this influence type to avoid a too low duct / room temperature.
This could e.g. be caused by windy surroundings.
A typical setting will be -4.0 for 'Infl. -max.' and 4.0 for 'Infl. -min.'
Adapt. time (adaption time) 1x015 If your application key has a heat curve setting:
Circuit Setting range Factory setting The adaptation function can correct the desired room temperature
with max. 8 K x heat curve slope value.
All * *
Controls how fast the actual room / duct temperature adapts to the desired
room / duct temperature (I control).
* See Appendix “Parameter ID overview” The ‘Infl. - max.’ and 'Infl. - min.' determine how much the room / duct
temperature should influence the desired flow / duct temperature.
0.0: No influence
-2.0: Minor influence
-5.0: Medium influence
-9.9: Maximum influence
If the ‘Infl.’ factor is too high and / or the ‘Adapt. time’ too low, there is
a risk of unstable control.
The controller automatically changes the desired flow temperature ‘Infl. - max.’ > 0
to obtain an acceptable return temperature when the return Return temperature
temperature falls below or gets higher than the set limit.
‘Infl. - max.’ < 0
This limitation is based on a PI regulation where P ('Infl.' factor)
responds quickly to deviations and I ('Adapt. time') responds ‘Infl. - min.’ < 0
slower and over time removes the small offsets between the
desired and actual values. This is done by changing the desired
flow temperature.
If the ‘Infl.’ factor is too high and / or the ‘Adapt. time’ too low, there is
a risk of unstable control.
T = Temperature
Y = Temperature
X = Time
# 1 # = Return temperature
# 2 # = Return temperature limit
# 3 # = Desired flow temperature
# 4 # = Action point
T = Temperature
Y = Temperature
X = Time
# 1 # = Return temperature
# 2 # = Return temperature limit
# 3 # = Desired flow temperature
# 4 # = Action point
Override mode
When ECL Comfort is in Scheduled mode, a contact (switch) signal can
be applied to an input in order to override to Comfort, Saving, Frost
Protection or Constant temperature. As long as the contact (switch)
signal is applied, the override is active.
Notes:
• The master circuit must be set to react on the desired flow temperature
in the slave(s). See "Demand offset" (ID 11017). # 1 # = Master, example A266, address 15
# 2 # = Slave, example A237, address 9
• The slave(s) must be set to send its / their desired flow temperature to the
# 3 # = Slave, example A367, address 6
master. See "Send desired T" (ID 1x500).
OFF: No influence from slaves. The return temperature Some examples of applications with DHW-tank heating / charging are:
limitation is related to settings in "Return limit".
• A217, A237, A247, A367, A377
Value: Return temperature limitation value when slave is in
DHW tank heating / charging operation.
When the return temperature falls below or gets higher than the
set value, the controller automatically changes the desired flow /
duct temperature to obtain an acceptable return temperature. The
influence is set in 'Infl. - max.' and 'Infl. - min.'.
Influence higher than 0: Normally, this setting is 0 in district heating systems because a lower
The desired flow / duct temperature is increased, when the return return temperature is acceptable.
temperature gets below the calculated limit. Typically, this setting is higher than 0 in boiler systems to avoid a too
low return temperature (see also 'Infl. - max.').
Influence lower than 0:
The desired flow / duct temperature is decreased, when the return
temperature gets below the calculated limit.
The return temperature limitation for the DHW circuit is based on the
setting in 'Limit (return temp. limitation)'.
The influence factors are set in heating circuit 1.
A flow or energy meter can be connected (M-bus signal) to the ECL Flow / power limitation
controller in order to limit the flow or consumed power.
The relationship between the flow or power limits and the outdoor
temperature is set in two coordinates.
Low limit Y1
The outdoor temperature coordinates are set in 'High T out X1'
and 'Low T out X2'. Outdoor temp.
-15 15 °C
The flow or power coordinates are set in 'Low limit Y1' and 'High Low T out X2 High T out X1
limit Y2'. Based on these settings, the controller calculates the
limitation value.
Flow / power
When the flow / power gets higher than the calculated limit, the limitation Limit
controller gradually reduces the desired flow temperature to obtain
an acceptable max. flow or power consumption.
°C
Desired flow
temp.
Time
DHW circuit
Flow / power
A flow or energy meter can be connected (M-bus signal) to the ECL limitation Limit
controller in order to limit the flow or consumed power.
When the flow / power gets higher than the calculated limit, the
controller gradually reduces the desired flow temperature to obtain
an acceptable max. flow or power consumption.
°C
Desired DHW
temp.
Time
The parameter 'Units' (ID 1x115) has a reduced setting range when
the flow / energy signal comes via M-bus.
For limitation:
Minimum frequency is recommended to be 1 Hz in order to have a
stable control. Furthermore, the pulses must appear regularly.
All * *
Controls how fast the flow / power limitation adapts to the desired
limitation.
Units 1x115
Circuit Setting range Factory setting List for setting range of 'Units':
l/h
See the list l/h m³/h
kW
Choice of units for measured values.
MW
GW
Flow values are expressed as l/h or m³/h
Power values are expressed as kW, MW or GW.
Circuit Setting range Factory setting The limitation function can overrule the set 'Temp. min' of the desired
flow temperature.
All * *
Set the flow / power limitation referring to the outdoor temperature set in
'High T out X1'.
5.6 Optimization
The section "Optimization" describes specific application related
issues.
The parameters 'Auto saving', 'Boost', 'Optimizer', 'Total stop' are all
related to heating mode only.
The desired room temperatures for Comfort and Saving modes Desired room temperature setting in Comfort mode: 22 °C
are set in the display overviews. Desired room temperature setting in Saving mode: 16 °C
Setting in ‘Auto saving’: –15 °C
The condition for the outdoor temperature influence:
T.out.influence = (10 - T.out) / (10 - setting) =
(10 - (-5)) / (10 - (-15)) =
15 / 25 = 0,6
The corrected desired room temperature in Saving mode:
T.room.ref.Saving + (T.out.influence x (T.room.ref.Comfort -
T.room.ref.Saving))
16 + (0,6 x (22 - 16)) = 19,6 °C
Dimensioning temperature:
The lowest outdoor temperature (usually determined by your system
designer in connection with the design of the heating system) at which
the heating system can maintain the designed room temperature.
Example
The system type is radiator, and the heat accumulation of the building
is medium.
The left digit is 2.
The dimensioning temperature is -25 °C, and the capacity is normal.
The right digit is 5.
Result:
The setting is to be changed to 25.
OFF: No total stop. The desired flow temperature is reduced Desired flow temp. °C
according to: Total stop = OFF
• desired room temperature in saving mode
• auto saving
ON: The desired flow temperature is lowered to the set value
in ‘Frost pr.’ The circulation pump is stopped but frost
protection is still active, see 'P frost T'.
‘Frost pr.’
Time
MENU > Settings > Optimization Example: Optimization of Comfort from 07:00 - 22:00
Pre-stop (optimized stop time) 1x026
Circuit Setting range Factory setting 07:00 22:00
All * * Schedule
Pre-stop ON
* See Appendix “Parameter ID overview”
If the actual DHW temperature deviates more than the set value, the
gear motor M2 in the heating circuit will gradually close to such an
extent that the DHW temperature stabilizes at the lowest acceptable
value.
Set the value for outdoor temperature at which you want the
heating system to switch OFF.
A376.3:
The motorized control valves are controlled by means of 0 - 10
volt control signals.
Valve control:
The motorized control valve is opened gradually when the flow
temperature is lower than the desired flow temperature and vice
versa.
The water flow through the control valve is managed by means
of an electric actuator. The combination "actuator" and "control
valve" is also called motorized control valve. The actuator can in
this way gradually increase or decrease the flow in order to change
the supplied energy. Different types of actuators are available.
Two basic types are available: ABV NC (Normal Closed) and ABV NO
(normal open). For example, ABV NC keeps a 2-port control valve
closed when no open-signals are applied.
When the flow temperature (for example at S3) is lower than the
desired flow temperature, relatively long open-signals come from
the ECL Comfort controller in order to increase the flow. By this,
the flow temperature will over time be aligned with the desired
temperature.
MENU > Settings > Control par. No. of Heat Constant DHW draw-off (l / min)
apartments transfer
Auto tuning 1x173
(kW)
Circuit Setting range Factory setting 1-2 30-49 3 (or 1 tap 25% open)
All * * 3-9 50-79 6 (or 1 tap 50% open)
Automatically determines the control parameters for the DHW control. 'Xp' 10-49 80-149 12 (or 1 tap 100% open)
'Tn' and 'M run' do not need to be set, when using auto tuning. 'Nz' must
be set. (or 1 tap 100% + 1 tap 50%
50-129 150-249 18
open)
130-210 250-350 24 (or 2 taps 100% open)
* See Appendix “Parameter ID overview”
Set the proportional band. A higher value will result in a stable but
slow control of the flow / duct temperature.
A low integration time constant will make the controller react fast
but with less stability.
M run (running time of the motorized control valve) 1x186 Running time = Valve stroke (mm) x actuator speed (sec. / mm)
Set the neutral zone to a high value if you can accept a high
variation in flow temperature.
If you want to tune the PI regulation precisely, you can use the following method:
• Set the ‘Tn’ (integration time constant) to its max. value (999 sec.).
• Decrease the value for the ‘Xp’ (proportional band) until the system starts hunting (i.e. gets unstable) with a constant amplitude (it
might be necessary to force the system by setting an extreme low value).
• Find the critical time period on the temperature recorder or use a stop watch.
Time
This critical time period will be characteristic for the system, and you can evaluate the settings from this critical period.
‘Tn’ = 0.85 x critical time period
‘Xp’ = 2.2 x proportional band value in the critical time period
If the regulation seems to be too slow, you can decrease the proportional band value by 10%. Make sure there is a consumption
when you set the parameters.
5.8 Application
The section "Application" describes specific application related
issues.
Circuit Setting range Factory setting The Remote Control Unit must be set accordingly (A or B).
All * *
Decides the room temperature signal transfer and communication with the
Remote Control Unit.
P post-run 1x040
Circuit Setting range Factory setting
All * *
Heating applications:
The circulation pump in the heating circuit can be ON for a number of
minutes (m) after heating stop. Heating stop is when the desired flow
temperature gets lower than the setting in 'P heat T' (ID no. 1x078).
Cooling applications:
The circulation pump in the cooling circuit can be ON for a number of
minutes (m) after cooling stop. Cooling stop is when the desired flow
temperature gets higher than the setting in 'P cool T' (ID no. 1x070).
This P post-run function can utilize the remaining energy in for example a
heat exchanger.
P demand 1x050
Circuit Setting range Factory setting The circulation pump is always controlled according to frost protection
conditions.
All * *
The circulation pump in the master circuit can be controlled in relation to
the master circuit's demand or slave circuit's demand.
Heating applications:
OFF: The circulation pump is ON when the desired flow
temperature in the heating circuit is higher than the
value set in 'P heat T'.
ON: The circulation pump is ON when the desired flow
temperature from slaves is higher than the value set in
'P heat T'.
Cooling applications:
OFF: The circulation pump is ON when the desired flow
temperature in the cooling circuit is lower than the value
set in 'P cool T'.
ON: The circulation pump is ON when the desired flow
temperature from slaves is lower than the value set in
'P cool T'.
All * *
The heating circuit can be closed when the controller acts as slave and when
DHW heating / charging is active in the master.
P frost T (circulation pump, frost protection temp.) 1x077 Under normal conditions, your system is not frost protected if your
setting is below 0 °C or OFF.
Circuit Setting range Factory setting For water-based systems, a setting of 2 °C is recommended.
All * *
Frost protection, based on the outdoor temperature.
When the outdoor temperature gets below the set temperature value in ‘P
frost T’, the controller automatically switches ON the circulation pump (for
example P1 or X3) to protect the system. If the outdoor temperature sensor is not connected and the factory
setting has not been changed to 'OFF', the circulation pump is always
ON.
* See Appendix “Parameter ID overview”
All * *
When the desired flow temperature is above the set temperature in ‘P heat T’,
the controller automatically switches ON the circulation pump.
Frost pr. T (frost protection temp.) 1x093 The frost protection temperature can also be set in your favorite
display when the mode selector is in frost protection mode.
Circuit Setting range Factory setting
All * *
Set the desired flow temperature at temperature sensor S3 to protect the
system against frost (at heating cut-out, total stop etc.).
When the temperature at S3 gets lower than the setting, the motorized
control valve opens gradually.
The following settings describe the function in general for the ECL
Comfort 210 / 310 series. The explained modes are typical and not
application related. They might differ from the override modes
in your application.
See also ' Con. T, ret. T lim.' (1x028), setting of return Example: Override to Saving mode
temperature limitation (MENU > Settings > Return
limit)
The factory set values for Summer period start and Winter period
start are set to same date: May, 20 (Date = 20, Month = 5).
This means:
This function is active when the dates for “Summer” and “Winter”
are different in the “Heat cut-out” menu.
The above settings of the dates for the cut-out function are only
to be done in the heating circuit 1 and are valid for other heating
circuits in the controller as well, if applicable.
5.10 Alarm
The section "Alarm" describes specific application related issues.
Application A376 offers different types of alarms:
Type: Description:
1 Actual flow temperature differs from the desired
flow temperature
2 Disconnection or short-circuiting of a temperature
sensor or its connection
3 Max. flow temperature in heating circuit(s)
(A376.9, A376.10)
4 Activation of alarm input(s) (A376.9, A376.10)
5 Pressure alarm (A376.9, A376.10)
A1: Application:
Relay 6 A376.1, A376.2, A376.3, A376.4
Relay 4 A376.9, A376.10
Alarm type 1:
If the flow temperature deviates more than the set differences from
the desired flow temperature, the alarm symbol / relay will be
activated after a set delay.
If the flow temperature becomes acceptable, the alarm symbol /
relay will be de-activated.
Alarm type 2:
Selected temperature sensors can be monitored.
Should the connection to the temperature sensor be disconnected,
short-circuited or the sensor gets defective, the alarm symbol
/ relay will be activated. In the "Raw input overview" (MENU >
Common controller settings > System > Raw input overview) the
sensor in question is marked and the alarm can be reset.
Alarm type 3:
If the flow temperature exceeds the alarm temperature value, the
circulation pump is switched OFF, the control valve closes and the
alarm symbol / relay will be activated. This safety function can, for
example, prevent a too high flow temperature in the floor circuit.
When the flow temperature gets 5 K below the alarm value, the
circulation pump will be switched ON, the control valve will operate
normally and the alarm symbol / relay will be de-activated.
Alarm type 4:
When the alarm input S8 (for circuit 1) or S15 (for circuit 2) or S16
(for circuit 3) is activated, the alarm symbol / relay will be activated
after a set delay.
When the alarm input S8 is de-activated, the alarm symbol / relay
will be de-activated.
Alarm type 5:
When the pressure gets higher or lower than set limits, the alarm
symbol / relay will be activated after a set delay.
When the pressure gets acceptable, the alarm symbol / relay will
be de-activated.
To reset an alarm:
When the "bell" is present to the right of the alarm line, place the
cursor at the alarm line in question and press the dial.
The scale and conversion settings for pressure sensors S7 and S14
are the same. The description is present for S7.
S7 pressure
Circuit Setting range Factory setting
1 0.0 ... 20.0 bar
Access to settings related to pressure measuring via input S7. Actual
measured pressure is shown. Conversion of input voltage to displayed
pressure.
Typically, the higher the voltage, the higher the displayed pressure.
MENU > Alarm > Pressure Example: Relationship between input voltage and indicated pressure
Low X 1x607 Pressure (bar)
Circuit Setting range Factory setting
All * *
High Y 6.0
The pressure is measured by means of a pressure transmitter. The transmitter
sends the measured pressure as a 0-10 V or a 4-20 mA signal.
Low X High X
* See Appendix “Parameter ID overview”
This example shows that 1 volt corresponds to 0.0 bar and 5 volt correspond
to 6.0 bar.
Digital S8
Circuit Setting range Factory setting
1
Access to settings related to alarm input S8.
Digital S15
Circuit Setting range Factory setting
2
Access to settings related to alarm input S15.
Digital S16
Circuit Setting range Factory setting
3
Access to settings related to alarm input S16.
Time
* See Appendix “Parameter ID overview”
All * *
The alarm function will not be activated if the desired flow / duct
temperature is lower than the set value.
This menu shows the alarm types, for example "2: Temp. monitor".
Resetting an alarm, in general:
The alarm has been activated if the alarm symbol is present to the
right of the alarm type. MENU > Alarm > Alarm overview:
Look for alarm symbol in specific line.
Alarm overview:
Some examples:
"2: Temp. monitor"
"5: Pump 1"
"10: Digital S12"
Related to the examples, the numbers 2, 5 and 10 are used in the alarm
communication to the BMS / SCADA system.
Related to the examples, "Temp. monitor", "Pump 1" and "Digital S12"
are the alarm points.
Alarm numbers and alarm points might differ depending on actual
application.
5.12 Anti-bacteria
On selected days during the week the DHW temperature can
Desired temp.
be increased in order to neutralize bacteria in the DHW system.
The desired DHW temperature 'Desired T' (typically 80 °C) will be °C
present for the selected day(s) and duration.
55
Time
M = Monday
T = Tuesday
W = Wednesday
T = Thursday
F = Friday
S = Saturday
S = Sunday
CW consump.
Circuit Setting range Factory setting
3 Read-out only
The displayed value (actual value) is based on pulses from the cold water
meter and 'Pulse value' (13513).
Confirm
Choose the circuit selector at the top
right corner in the display
Confirm
Confirm
Besides the week schedules for the circuits 1, 2 and 3, this week
schedule controls relay output R5.
The week schedule is set in the same way as the week schedules for
circuits 1, 2 and 3.
6.4 Holiday
There is a holiday program for each circuit and a holiday program
for the common controller.
Each holiday program contains one or more schedules. Each The holiday program in the ‘Common controller settings’ is valid for
schedule can be set to a start date and an end date. The set period all circuits. The holiday program can also be set individually in the
starts on the start date at 00.00 and stops on the end date at 00.00. heating or DHW circuits.
Confirm
Choose the circuit selector at the top
right corner in the display
Confirm
Choose a circuit or 'Common controller
settings'
Heating
DHW
Common controller settings
Confirm
Go to ‘Holiday’
Confirm
Choose a schedule
Confirm
Choose mode
. Comfort
. Saving
∙ Frost protection
Confirm
Enter the start time first and then the
end time
Confirm
Go to ‘Menu’
Confirm
Choose ‘Yes’ or ‘No’ in ‘Save’. Choose
the next schedule, if required
2. Comfort 7 - 23 Result:
3. Saving As long as "Comfort" is active in Common Controller, circuit 1 will be in
"Comfort".
4. Frost protection
Example 2:
Circuit 1:
Holiday set to "Comfort"
Common Controller:
Holiday set to "Saving"
Result:
As long as "Comfort" is active in circuit 1, it will be in "Comfort".
Example 3:
Circuit 1:
Holiday set to "Frost protection"
Common Controller:
Holiday set to "Saving"
Result:
As long as "Saving" is active in Common Controller, circuit 1 will be
in "Saving".
However, it is possible to make use of the following options from Energy-saving trick:
the ECA 30 / 31 when the controller is in scheduled mode: Use 'Going out' (the extended saving period) for airing purposes (e.g.
for ventilating the rooms by means of fresh air from open windows).
Day off
Holiday
Connections and setup procedures for ECA 30 / 31:
See section 'Miscellaneous'.
Relaxing (extended comfort period)
This overview will always show you the actual temperatures in the
system (read-only).
6.6 Log
This section describes the function in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application
related. They might differ from the displays in your application.
There is a log display for the relevant sensor, showing the measured
temperature.
Example 1:
1 day log for yesterday showing the development in outdoor
temperature during the past 24 hours.
Example 2:
Today’s log for the actual heating flow temperature as well as the
desired temperature.
Example 3:
Yesterday’s log for the DHW flow temperature as well as the desired
temperature.
Confirm
Confirm
Adjust the status of the controlled
component: When the selected controlled component (output) is not ‘AUTO’, the
Motorized control valve: AUTO, STOP, ECL Comfort controller does not control the component in question
CLOSE, OPEN (pump or motorized control valve e.g.). Frost protection is not active.
Pump: AUTO, OFF, ON
Confirm status change
A376.3 only:
The motorized control valves M1, M2 and M3 are controlled by 0–10
volt (0–100%) signals. Each of them can be set to AUTO or ON.
6.9 System
6.9.2 Extension
6.9.3 Ethernet
When using the Application Key in the ECL Comfort 310 / 310B, up
to 5 energy meters (heat-meters) can be connected to the M-bus Energy meter data acquisition from ECL Portal is possible without
connections. setting up the M-bus configuration.
The ECL Comfort 310 can always be used for monitoring purpose
of up to 5 energy meters.
The ECL Comfort 310 acts as an M-bus master and must be set to
communicate with connected energy meter(s).
See MENU > Common controller > System > M-bus config.
Technical info:
• The M-bus data are based on standard EN-1434.
• Danfoss recommends AC supplied energy meters in order to
avoid battery draining.
State Read-out
Circuit Setting range Factory setting The ECL Comfort 310 will return to IDLE when commands have been
completed.
- - - Gateway is used for read-out of energy meter via ECL Portal.
The communication speed between ECL Comfort 310 and the connected
energy meter(s).
Command 5998
Circuit Setting range Factory setting Scan time can take up to 12 minutes.
When all energy meters are found, the command can be changed
- NONE / INIT / SCAN / GATEW NONE to INIT or NONE.
The ECL Comfort 310 is M-bus master. In order to verify connected energy
meters, different commands can be activated.
M-bus address
Energy meter 1 (2, 3, 4, 5) 6000
Type
Energy meter 1 (2, 3, 4, 5) 6001
Data examples:
Circuit Setting range Factory setting
0:
- 0-4 0 Flow temp., return temp., flow, power, acc. volume, acc. energy.
Selecting data range from the M-bus telegram.
3:
Flow temp., return temp., flow, power, acc. volume, acc. energy,
0: Small data set, small units tariff 1, tariff 2.
1: Small data set, large units
See also the "Instructions, ECL Comfort 210 / 310, communication
2: Large data set, small units description" for further details.
3: Large data set, large units See also Appendix for detailed description of "Type".
4: Volume and energy data only
(example: HydroPort Pulse)
Scan time
Energy meter 1 (2, 3, 4, 5) 6002
If the energy meter is battery powered, the scan time should be set to
a high value to prevent a too fast battery draining.
Circuit Setting range Factory setting
Oppositely, if the flow / power limitation function is used in the ECL
- 1 - 3600 sec 60 sec Comfort 310, the scan time should be set to a low value in order to
have quick limitation.
Setting the scanning time for acquiring data of connected energy meter(s).
ID
Energy meter 1 (2, 3, 4, 5) Read-out
6.9.7 Display
0: Weak backlight.
10: Strong backlight.
0: Low contrast.
10: High contrast.
6.9.8 Communication
Modbus addr. 38
Circuit Setting range Factory setting
1 ... 247 1
1 ... 247: Assign the Modbus address within the stated setting
range.
The ECL Comfort controllers can be connected via the ECL 485
communication bus to perform a larger system (the ECL 485
communication bus can connect to max. 16 devices).
Each slave must be configured with its own address (1 ... 9).
However, more slaves can have the address 0 if they only have to
receive information about outdoor temperature and system time
(listeners).
Not applicable for the time being and reserved for future use!
6.9.9 Language
Language 2050
Circuit Setting range Factory setting
English / ‘Local’ English Local language is selected during installation. If you want to change to
another local language, the application must be reinstalled. However,
Choose your language. it is always possible to change between the local language and English.
7.0 Miscellaneous
Menu structure
Part of the ECA 30 / 31 display in ECL mode:
The menu structure of ECA 30 / 31 is an "ECA MENU" and the ECL
menu, copied from the ECL Comfort controller.
Most of the settings done directly in the ECL controller can be done
via the ECA 30 / 31 too. All settings can be seen even if the application key is not inserted in
the ECL controller.
For changing settings, the application key must be inserted.
The Key overview (MENU > 'Common controller settings' > 'Key
functions') does not show the applications of the key.
This display indicates that an application has not been uploaded or the
communication to the ECL controller (master) is not working properly.
An X on the ECL controller symbol indicates wrong setup of
communication addresses.
Minus
value: The indicated room temperature is lower.
Minus
value: The indicated relative humidity is lower.
0: Weak backlight.
10: Strong backlight.
0: Low contrast.
10: High contrast.
Use as remote
Setting range Factory setting
OFF / ON *) When set to OFF: The ECA menu shows date and time.
ECA 30 / 31 can act as a simple or normal remote control When set to ON: The ECA menu shows date and room temperature
for the ECL controller. (and for ECA 31 relative humidity).
A: If two ECA 30 / 31 are connected in the same ECL 485 bus system, the
The ECA 30 / 31 has the address A. 'Slave addr.' must be "A" in the one ECA 30 / 31 unit and "B" in the other.
B: The ECA 30 / 31 has the address B.
1 .. 9: Slave controllers.
Example:
15: Master controller.
Connection addr. = 15: The ECA 30 / 31 communicates with the
ECL master controller.
Connection addr. = 2: The ECA 30 / 31 communicates with the
ECL controller with address 2.
An ECL Comfort controller 210 / 310, type B (without display and dial)
cannot be assigned to the address 0 (zero).
Override circuit
Setting range Factory setting
OFF / 1 … 4 OFF The circuit in question for override in the ECL controller must be in
scheduled mode.
The feature 'Override' (to extended comfort or saving See also the parameter 'Override addr.'.
period or holiday) must be addressed to the heating circuit
in question.
Example 2:
Restore factory
The ECA 30 / 31 is set back to factory settings.
Affected settings by the restore procedure:
• Room T offset
• RH offset (ECA 31)
• Backlight
• Contrast
• Use as remote
• Slave addr.
• Connection addr.
• Override addr.
• Override circuit
• Override mode
• Override mode end time
Update firmware
The ECA 30 / 31 can be updated with new firmware (software).
The firmware comes with the ECL application key, when the key
version is at least 2.xx. The ECA 30 / 31 automatically verifies if a new firmware is present on
the application key in the ECL Comfort controller.
If no new firmware is available, a symbol of the application key The ECA 30 / 31 is automatically updated at new application upload in
is displayed with an X. the ECL Comfort controller.
The ECA 30 / 31 is not automatically updated when connected to an
NO: The updating procedure is not done. ECL Comfort controller with uploaded application. A manual update
is always possible.
YES: The updating procedure is done.
The ECL 210 / 310 controllers can receive a signal in order to Example, override switch connected to S8:
override the existing schedule. The override signal can be a switch
or a relay contact.
Example 1
Settings in ECL:
1. Select circuit > MENU > Settings > Application > Ext. input:
Select the input S8 (the wiring example)
2. Select circuit > MENU > Settings > Application > Ext. mode:
Select COMFORT # 1 # = Override switch or relay contact (not activated / activated)
# 2 # = Function mode (Schedule / Comfort)
3. Select circuit > MENU > Schedule: # 3 # = Time
Select all weekdays
Set "Start1" to 24.00 (this disables Comfort mode)
Exit menu and confirm by "Save"
4. Remember to set the circuit in question in scheduled mode
("clock").
Result: When the override switch (or the relay contact) is ON, the
ECL 210 / 310 will operate in Comfort mode.
When the override switch (or the relay contact) is OFF, the ECL 210 /
310 will operate in Saving mode.
Example 2
Settings in ECL:
1. Select circuit > MENU > Settings > Application > Ext. input:
Select the input S8 (the wiring example)
2. Select circuit > MENU > Settings > Application > Ext. mode:
Select SAVING # 1 # = Override switch or relay contact (not activated / activated)
# 2 # = Function mode (Schedule / Saving)
3. Select circuit > MENU > Schedule: # 3 # = Time
Select all weekdays
Set "Start1" to 00.00
Set "Stop1" to 24.00
Exit menu and confirm by "Save"
4. Remember to set the circuit in question in scheduled mode
("clock").
Result: When the override switch (or the relay contact) is ON, the
ECL 210 / 310 will operate in Saving mode.
When the override switch (or the relay contact) is OFF, the ECL 210 /
310 will operate in Comfort mode.
Example 3
The week schedule for the building is set with comfort periods
Monday - Friday: 07.00 - 17.30. Sometimes, a team meeting takes
place in the evening or in the week-end.
Settings in ECL:
Result: When the override switch (or a relay contact) is ON, the ECL
210 / 310 will operate in Comfort mode.
When the override switch is OFF, the ECL 210 / 310 will operate
according to the schedule.
Example 4
The week schedule for the building is set with comfort periods all
weekdays: 06.00 - 20.00. Sometimes, the desired flow temperature
must be constant on 65 °C.
Settings in ECL:
Result: When the override relay is activated, the ECL 210 / 310 will
operate in Const. temp. mode and control a flow temperature of
65 °C.
When the override relay is not activated, the ECL 210 / 310 will
operate according to the schedule.
SLAVE controllers:
Change the factory set address from 15 to address 0.
In the MASTER controller, the address in ‘ECL 485 addr. (master / slave
• In , go to System > Communication > ECL 485 addr: address)’, ID no. 2048, must always be 15.
Situation 2:
SLAVE controller: How to react on a DHW tank heating /
charging activity sent from the MASTER controller
SLAVE controller:
Set the desired function:
• In circuit 1 / circuit 2, go to ‘Settings’ > ‘Application’ >’DHW
priority’:
Situation 3:
SLAVE controller: How to make use of the outdoor temperature
signal and send information about the desired flow In the MASTER controller, the address in ‘ECL 485 addr. (master / slave
temperature back to the MASTER controller address)’, ID no. 2048, must always be 15.
SLAVE controller:
• In , go to System > Communication > ECL 485 addr.
• Change the factory set address from 15 to an address (1 ... 9).
Each slave must be configured with its own address.
SLAVE controller:
• In the circuit in question, go to Settings > Application > Send
desired T
• Choose ON or OFF.
87H1420.10
How to set a correct heat curve?
Da nfos s
Short answer: 120
1.8 2.2 2.6 3.0 3.4
Set the heat curve to the lowest possible value, but still having
comfortable room temperature. 110
1.4
100
The table shows some recommendations:
90
10
Technical answer:
In order to save energy, the flow temperature should be as low as -30 -20 -10 0 10 20
possible, but still considering a comfortable room temperature.
This means the heat curve slope should have a low value.
In general:
• Smaller radiators in your heating system might require a higher
heat curve slope. (Example: Desired flow temperature 70 °C
resulting in heat curve = 1.5).
• Floor heating systems require a lower heat curve slope. (Example:
Desired flow temperature 35 °C resulting in heat curve = 0.4).
• Corrections of the heat curve slope should be done in small steps
when having outdoor temperatures below 0 °C; one step pr. day.
• If required, adjust the heat curve in the six coordinate points.
• Setting of the desired room temperature has an influence on the
desired flow temperature even if a room temperature sensor /
Remote Control Unit is not connected. An example: Increasing the
desired room temperature results in a higher flow temperature.
• Typically, the desired room temperature should be adjusted when
having outdoor temperatures above 0 °C.
7.5 Definitions
DHW circuit
The circuit for heating the domestic hot water (DHW).
Duct temperature
Temperature measured in the air duct where the temperature
is to be controlled.
ECL Portal
A supervisory system for remote control and monitoring, locally
and via Internet.
EMS
Energy Management System. A supervisory system for remote
control and monitoring.
Factory settings
Settings stored on the ECL Application Key to simplify the set up
of your controller the first time.
Flow temperature
Temperature measured in the water flow where the temperature
is to be controlled.
Flow temperature reference
Temperature calculated by the controller on basis of the outdoor
temperature and influences from the room and / or return
temperatures. This temperature is used as a reference for the
control.
Heat curve
A curve showing the relationship between actual outdoor
temperature and desired flow temperature.
Heating circuit
The circuit for heating the room / building.
Holiday schedule
Selected days can be programmed to be in comfort, saving or
frost protection mode. Besides this, a day schedule with comfort
period from 07.00 to 23.00 can be selected.
Humidistat
A device, which reacts on the air's humidity. A switch can go ON if
the measured humidity gets above a set point.
Humidity, relative
This value (stated in %) refers to the indoor moisture content
compared to the max. moisture content. The relative humidity
is measured by the ECA 31 and is used for the calculation of the
dew point temperature.
Inlet temperature
Temperature measured in the inlet air flow where the temperature
is to be controlled.
Limitation temperature
Temperature that influences the desired flow / balance
temperature.
Log function
The temperature history is displayed.
Master / slave
Two or more controllers are interconnected on the same bus,
the master sends out e.g. time, date and outdoor temperature.
The slave receives data from master and sends e.g. desired flow
temperature value.
Modulating control (0 - 10 V control)
Positioning (by means of a 0 - 10 V control signal) of the actuator
for the motorized control valve in order to control the flow.
Optimization
The controller optimizes the start time of the scheduled
temperature periods. Based on the outdoor temperature, the
controller automatically calculates when to start in order to reach
the comfort temperature at the set time. The lower the outdoor
temperature, the earlier the start time.
Installer:
By:
Date:
*087H9059*
*VIGUB202*