0% found this document useful (0 votes)
59 views

ECL310 Manual

Uploaded by

Niko Lazić
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
59 views

ECL310 Manual

Uploaded by

Niko Lazić
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 162

Installation Guide

ECL Comfort 310, application A376

1.0 Table of Contents

1.0 Table of Contents ............................................... 1 6.0 Common controller settings............................ 116


1.1 Important safety and product information. . . . . . . . . . . . . . . . . . . . . 2 6.1 Introduction to ‘Common controller settings’ . . . . . . . . . . . . . . 116
6.2 Time & Date. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
2.0 Installation ........................................................ 6 6.3 Schedule output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
2.1 Before you start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 6.4 Holiday . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
2.2 Identifying the system type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 6.5 Input overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
2.3 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 6.6 Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
2.4 Placing the temperature sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 6.7 Output override. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
2.5 Electrical connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 6.8 Key functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
2.6 Inserting the ECL Application Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 6.9 System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
2.7 Check list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
2.8 Navigation, ECL Application Key A376 . . . . . . . . . . . . . . . . . . . . . . . . . 33 7.0 Miscellaneous ................................................ 133
7.1 ECA 30 / 31 setup procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
3.0 Daily use ......................................................... 48 7.2 Override function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
3.1 How to navigate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 7.3 Several controllers in the same system . . . . . . . . . . . . . . . . . . . . . . 144
3.2 Understanding the controller display . . . . . . . . . . . . . . . . . . . . . . . . . . 49 7.4 Frequently asked questions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
3.3 A general overview: What do the symbols mean? . . . . . . . . . . . 53 7.5 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
3.4 Monitoring temperatures and system 7.6 Type (ID 6001), overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 7.7 Parameter ID overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
3.5 Influence overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
3.6 Manual control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
3.7 Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

4.0 Settings overview ............................................ 58

5.0 Settings........................................................... 61
5.1 Introduction to Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
5.2 Flow temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
5.3 Room limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
5.4 Return limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
5.5 Flow / power limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
5.6 Optimization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
5.7 Control parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
5.8 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
5.9 Heat cut-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
5.10 Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
5.11 Alarm overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
5.12 Anti-bacteria. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
5.13 Water meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 1


Installation Guide ECL Comfort 310, application A376

1.1 Important safety and product information

1.1.1 Important safety and product information

This Installation Guide is associated with ECL Application Key A376


(order code no. 087H3810).

The ECL Application Key A376 contains 6 subtypes, all applicable in


ECL Comfort 310:
• A376.1: 2 x Heating and 1 x DHW
• A376.2: 2 x Heating and 1 x advanced DHW
• A376.3: 2 x Heating and 1 x DHW; motorized control valves
are 0 - 10 Volt controlled
• A376.4: 1 x Heating, 1 x DHW and 1 x advanced DHW
• A376.9: 2 x Heating inclusive pressure and return temperature
monitoring on heating sides.
1 x DHW inclusive return temperature limitation / monitoring.
Monitoring of installation's supply and return temperatures.
• A376.10: 2 x Heating inclusive pressure and return temperature
monitoring on heating sides.
1 x DHW inclusive return temperature limitation / monitoring.
Monitoring of installation's supply and return pressures.
See the Mounting Guide (delivered with the application key) for
application examples and electrical connections.

The described functions are realized in ECL Comfort 310 which


includes M-bus, Modbus and Ethernet (Internet) communication.

The application Key A376 complies with ECL Comfort 310


controllers as of software version 1.11 (visible at start-up of the
controller and in 'Common controller settings' in 'System').

Up to two Remote Control Units, ECA 30 or ECA 31, can be


connected and the built-in room temperature sensor can be
utilized.

Together with the ECL Comfort 310, the additional Internal I/O
module ECA 32 (order code no. 087H3202) can be used for extra
data communication to SCADA:
• Temperature, Pt 1000 (default)
• 0 - 10 volt signals
The set-up of input type can be done by means of the Danfoss
Software "ECL Tool".

Navigation: Danfoss.com > Products & Solutions > District Heating


and Cooling > Tools & Software > ECL Tool.
The URL is: http://district-heating.danfoss.com/download/tools/
The Internal I/O module ECA 32 is placed in the base part for ECL
Comfort 310.

ECL Comfort 310 is available as:


• ECL Comfort 310, 230 volt a.c. (087H3040)
• ECL Comfort 310B, 230 volt a.c. (087H3050)
• ECL Comfort 310, 24 volt a.c. (087H3044)

2 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

The B-types have no display and dial. The B-types are operated by
means of the Remote Control unit ECA 30 / 31:
• ECA 30 (087H3200)
• ECA 31 (087H3201)

Base parts for ECL Comfort:


• for ECL Comfort 310, 230 volt and 24 volt (087H3230)

Additional documentation for ECL Comfort 310, modules and


accessories is available on http://den.danfoss.com/.

Documentation for ECL Portal: See ecl.portal.danfoss.com.

Safety Note
To avoid injury of persons and damages to the device, it is absolutely
necessary to read and observe these instructions carefully.

Necessary assembly, start-up, and maintenance work must be


performed by qualified and authorized personnel only.

Local legislations must be respected. This comprises also cable


dimensions and type of isolation (double isolated at 230 V).

A fuse for the ECL Comfort installation is max. 10 A typically.

The ambient temperature range for the ECL Comfort in operation is


0 - 55 °C. Exceeding this temperature range can result in malfunctions.

Installation must be avoided if there is a risk for condensation (dew).

The warning sign is used to emphasize special conditions that should


be taken into consideration.

This symbol indicates that this particular piece of information should


be read with special attention.

Application keys might be released before all display texts are


translated. In this case the text is in English.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 3


Installation Guide ECL Comfort 310, application A376

Automatic update of controller software:


The software of the controller is updated automatically when the key
is inserted (as of controller version 1.11). The following animation will
be shown when the software is being updated:

Progress bar

During update:
• Do not remove the KEY
If the key is removed before the hour-glass is shown, you have
to start afresh.
• Do not disconnect the power
If the power is interrupted when the hour-glass is shown, the
controller will not work.

As this Installation Guide covers several system types, special system


settings will be marked with a system type. All system types are shown
in the chapter: 'Identifying your system type'.

°C (degrees Celsius) is a measured temperature value whereas K


(Kelvin) often is used for temperature differences.

The ID no. is unique for the selected parameter.

Example First digit Second digit Last three digits


11174 1 1 174
- Circuit 1 Parameter no.

12174 1 2 174
- Circuit 2 Parameter no.

If an ID description is mentioned more than once, it means that there


are special settings for one or more system types. It will be marked
with the system type in question (e.g. 12174 - A266.9).

Parameters indicated with an ID no. like "1x607" mean a universal


parameter.
x stands for circuit / parameter group.

4 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Disposal Note
This product should be dismantled and its components
sorted, if possible, in various groups before recycling
or disposal.
Always follow the local disposal regulations.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 5


Installation Guide ECL Comfort 310, application A376

2.0 Installation

2.1 Before you start


The applications (subtypes) in the A376 application key are almost
Typical A376 application:
identical. However, some applications have extra functions which
are described separately. ECL 310

87H2097.11
S1

Da nfos s
The applications are very flexible. These are the basic principles: A1

S3

Heating (circuit 1): S2

Typically, the flow temperature is adjusted according to your P2 1


M2
requirements. The flow temperature sensor (S3) is the most S5

important sensor. The desired flow temperature at S3 is calculated


in the ECL controller, based on the outdoor temperature (S1) and S9
the desired room temperature. The lower the outdoor temperature, S7

the higher the desired flow temperature. By means of a week P3 2


M3
schedule, the heating circuit can be in ‘Comfort’ or ‘Saving’ mode S10
(two values for the desired room temperature). In Saving mode the
heating can be reduced or switched off totally.
S4

The motorized control valve M2 is opened gradually when the


flow temperature is lower than the desired flow temperature and M1 3
S6
vice versa.
P1
The return temperature (S5) can be limited, for example not to be
too high. If so, the desired flow temperature at S3 can be adjusted
(typically to a lower value), thus resulting in a gradual closing of
the motorized control valve. Furthermore, the return temperature
limitation can be dependent on the outdoor temperature.
Typically, the lower the outdoor temperature, the higher the The shown diagram is a fundamental and simplified example and
accepted return temperature. does not contain all components that are necessary in a system. The
numbers in circles refer to the circuit numbers.
In boiler-based heating supply the return temperature should not All named components are connected to the ECL Comfort controller.
be too low (same adjustment procedure as above).
List of components: A376 in general, sensors
A connected flow or energy meter based on M-bus signal can limit
the flow or energy to a set maximum value. Furthermore, the ECL 310 Electronic controller ECL Comfort 310
limitation can be in relation to the outdoor temperature. Typically, S1 Outdoor temperature sensor
the lower the outdoor temperature, the higher the accepted flow / S2 A376.1, A376.2, A376.3, A376.4:
power. Room temperature sensor, circuit 1
A376.2: Room temperature sensor, circuits 1 and 2
The circulation pump (P2) is ON at heat demand or at frost A376.9: Return temperature sensor, monitoring, circuit 1
protection. A376.10: Return temperature sensor, monitoring, circuit 2
S3 Flow temperature sensor, circuit 1
The heating can be switched OFF when the outdoor temperature is
higher than a selectable value. S4 DHW temperature sensor, circuit 3
S5 Return temperature sensor, circuit 1
The frost protection mode maintains a selectable flow temperature, S6 Return temperature sensor, circuit 3
for example 10 °C. S7 A376.1, A376.3: Room temperature sensor, circuit 2
A376.2, A376.4: Supply flow temperature sensor
A376.1, A376.2, A376.3, A376.4: A376.9, A376.10: Pressure signal
If the measured room temperature does not equal the desired S8 A376.2, A376.4: Flow switch, DHW draw-off
room temperature, the desired flow temperature can be adjusted. A376.9, A376.10: Alarm input
S9 Flow temperature sensor, circuit 2
S10 A376.1, A376.2, A376.3, A376.4:
Return temperature sensor, circuit 2
A376.9, A376.10:
Return temperature sensor, monitoring, circuit 2
(S11) (A376.9: Supply flow temperature sensor)
A376.10: Supply flow pressure signal
(S12) A376.9: Supply return temperature sensor
A376.10: Supply return pressure signal
(S13) A376.9, A376.10: Return temperature sensor, circuit 2
(S14) A376.9, A376.10: Pressure signal
(S15) A376.9, A376.10: Alarm input
(S16) A376.9, A376.10: Alarm input

6 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Heating (circuit 2 in A376.1, A376.2, A376.3, A376.9, A376.10) List of components: A376 in general, pumps and actuators
This circuit works after same principles as circuit 1.
P1 DHW circulation pump, circuit 3
The flow temperature sensor S9 is the most important sensor. P2 Heating circulation pump, circuit 1
By means of a week schedule (up to 3 ‘Comfort’ periods / day), P3 A376.1, A376.2, A376.3, A376.9, A376.10:
heating circuit 2 can be in ‘Comfort’ or ‘Saving’ mode (two different Heating circulation pump, circuit 2
temperature values for desired room temperature). The motorized A376.4: DHW circulation pump, circuit 2
control valve M3 controls the circuit.
M1 Motorized control valve, circuit 3
The return temperature (S10) enables limitation as described M2 Motorized control valve, circuit 1
previously.
M3 Motorized control valve, circuit 2
A connected flow or energy meter based on M-bus signal can limit A1 Alarm
the flow or energy to a set maximum value. Furthermore, the
limitation can be in relation to the outdoor temperature. Typically,
the lower the outdoor temperature, the higher the accepted flow / A376.1 example a:
power. ECL 310

87H2097.11
S1

Da nfos s
The circulation pump (P3) is ON at heat demand or at frost A1

protection. S3
S2

P2 1
The heating can be switched OFF when the outdoor temperature is M2
S5
higher than a selectable value.
S9

Heating circuit 2 can be connected after heating circuit 1. If so, the S7


2
desired flow temperature at S3 can be influenced by the desired M3
P3

flow temperature at S9. S10

The frost protection mode maintains a selectable flow temperature, S4

for example 10 °C.


M1 3
S6

A376.1, A376.2, A376.3, A376.4:


P1
If the measured room temperature does not equal the desired
room temperature, the desired flow temperature can be adjusted.

Heating related circuits, in general: A376.1 example b:


Exercise of circulation pumps and control valves in periods without ECL 310

87H2098.11
S1
heating demand can be arranged.

Da nfos s
A1

S3
S2

P2 1
M2
S5

M3
S9
S7

P3 2

S10

S4

M1 3
S6

P1

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 7


Installation Guide ECL Comfort 310, application A376

Domestic Hot Water (DHW)


A376.2 example a:
A376.1, A376.2, A376.3, A376.9, A376.10: Circuit 3
A376.4: Circuit 2 ECL 310

87H2099.11
S1

Da nfos s
A1
If the measured DHW temperature (S4 / S9) is lower than the S3
desired DHW temperature, the motorized control valve (M1 / M3) is (S2)

opened gradually and vice versa. M2


P2 1
S5

By means of a week schedule, the DHW circuit can be in ‘Comfort’


or ‘Saving’ mode (two values for the desired DHW temperature). S9
(S2)

P3 2
The return temperature (S6 / S10) can be limited to a fixed value. M3
S10

A376.9, A376.10: S7 S4
The return temperature S6 can measure, for monitoring purpose,
the return temperature on the secondary side. An alternative M1 3
position for S6 can be in the return on the primary side in order to S6

limit the return temperature to a fixed value. S8


P1

Domestic Hot Water (DHW), advanced temperature control


A376.2, A376.4: Circuit 3
A376.2 example b:
By means of a week schedule, the DHW circuit can be in ‘Comfort’
ECL 310

87H2100.11
S1
or ‘Saving’ mode (two values for the desired DHW temperature).

Da nfos s
A1

The DHW temperature at S4 is maintained at ‘Comfort’ level at a S3


(S2)
DHW draw-off (DHW tapping) (the flow switch S8 is activated). If P2 1
the measured DHW temperature S4 is lower than the desired DHW M2
S5
temperature, the motorized control valve (M1) is opened gradually
and vice versa. The DHW temperature control is in relation to M3
S9
actual supply temperature S7. In order to compensate for the (S2)
2
reaction time, the motorized control valve can be pre-activated at P3

the start of a DHW draw-off (DHW tapping). An idle temperature S10

(the desired saving temperature) can be maintained at either S7 or


S4 when there is no draw-off (DHW tapping). S7 S4

The return temperature (S6) can be limited to a fixed value.


M1 3
S6

DHW circuits, in general S8


P1
A connected flow or energy meter based on M-bus signal can limit
the flow or energy to a set maximum value.

If the desired DHW temperature cannot be reached, the heating A376.3 example a:
circuit can be closed gradually to allow more energy to the DHW
circuit. ECL 310
87H2101.11

S1
Da nfos s

A1
An anti-bacteria function is available for activation on selected + ECA 32

days of the week. S3


S2

P2 1
The outdoor temperature (S1) is used to protect the circulation A
M2
S5
circuit(s) against frost.
S9
S7

P3 2
M3
A S10

S4

M1 3
A S6

P1

8 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Application A376.3 in general:


A376.3 example b:
The application is similar to the A376.1 application, but the
motorized control valves are controlled by means of 0-10 volt
signals (analog signals). The triac outputs are not active for A1
activating 3-point controlled actuators. The application A 376.3
requires the internal I/O module ECA 32 in order to activate 0-10
volt controlled actuators. 1

Application A376.4, in general


The heating circuit (1) and DHW circuit (3) are similar to the A376.2
application. The DHW circuit 2 is similar to the DHW circuit in the
2
A376.1 application.

Application A376.9 in general:


The application A376.9 is similar to the A376.1, but with special
functions.
3
The application A376.9 requires the internal I/O module ECA 32.
S11 and S12 measure supply flow and return temperatures for
monitoring.
S13 measures return temperature.
S14 measures pressure.
A376.4 example a:
S15 and S16 are alarm inputs.
ECL 310

87H1430.11
S1

Da nfos s
Schedule in "Common controller" is connected to the output O1 A1
and can be used for various issues.
S3
S2

P2 1
M2
Heating circuits 1 and 2: S5

• There are no room temperature influence possibilities. S9

• The secondary return temperatures (S2 and S10) are used for
M3 2
monitoring only. S10

• The pressure measurings, 0-10 volt (S7 and S14,) are used to S7 S4
P3

activate an alarm if the actual pressure is higher or lower than


the chosen settings. M1 3
S6

S8
P1

DHW circuit 3:
• The return temperature S6 can measure, for monitoring
purpose, the return temperature on the secondary side. An A376.9 example a:
alternative position for S6 can be in the return on the primary
side in order to limit the return temperature to a fixed value.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 9


Installation Guide ECL Comfort 310, application A376

All circuits:
A376.9 example b:
• The temperatures (S11 and S12) are used for monitoring only. ECL 310

87H2104.11
S1 S8 S15 S16

Da nfos s
• The switch inputs (S8, S15 and S16) are related to the circuits + ECA 32
A1

1, 2 and 3 respectively. Typically used as alarm signal for S3


malfunction of the circulation pump in question.
P2 1
M2 S7
S5 S2

Application A376.10
The application A376.10 is similar to the A376.9. S 11
M3
S9

The application A376.10 requires the internal I/O module ECA 32.
S11 and S12 measure supply flow and return pressures for S14
P3
2
S12 S10
monitoring.
S13 measures return temperature.
S14 measures pressure. S4

S15 and S16 are alarm inputs.


M1 3
(S6) S6

Schedule in "Common controller" is connected to the output O1 P1


and can be used for various issues.

A376.10 example a:

10 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Application A376 in general:


The alarm output A1 is present on these outputs:

Application: Relay:
A376.1, A376.2, A376.3, A376.4 Relay 6
A376.9, A376.10 Relay 4

See the Mounting Guide (delivered with the application key) for
application examples and electrical connections.

Alarm A1 (= relay 6) can be activated if:


• The actual flow temperature differs from the desired flow
temperature.
• If a temperature sensor or its connection disconnects / short
circuits. (See: Common controller settings > System > Raw
input overview).

Modbus communication to a SCADA system can be established.

Up to two Remote Control Units, ECA 30 / 31 can be connected to


one ECL controller in order to control the ECL controller remotely.

Additional ECL Comfort controllers can be connected via the ECL


485 bus in order to utilize common outdoor temperature signal,
time and date signals.
The ECL controllers in the ECL 485 system can work in master -
slave system.

Unused inputs can, by means of an override switch or relay contact,


be used for overriding the schedule to a fixed 'Comfort', 'Saving',
'Frost protection' or 'Constant temperature' mode.

Circuit 1 can act as master and the remaining circuits can act as
slaves.

Holiday programs are present for Heating and DHW circuits.


Besides, a holiday program is present for the entire controller.

When the A376 has been uploaded with the subtypes A376.1,
A376.2, A376.3 and A376.4, the ECL Comfort controller starts
in Manual mode. This can be used for checking the controlled
components for correct functionality.
The subtypes A376.9 and A376.10 start, after upload, in Scheduled
mode.

The controller is pre-programmed with factory settings that are shown


in the ‘Parameter ID overview’ appendix.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 11


Installation Guide ECL Comfort 310, application A376

2.2 Identifying the system type


Sketch your application
The ECL Comfort controller series is designed for a wide range
of heating, domestic hot-water (DHW) and cooling systems with
different configurations and capacities. If your system differs
from the diagrams shown here, you may want to make a sketch
of the system about to be installed. This makes it easier to use
the Installation Guide, which will guide you step-by-step from
installation to final adjustments before the end-user takes over.

The ECL Comfort controller is a universal controller that can be


used for various systems. Based on the shown standard systems,
it is possible to configure additional systems. In this chapter you
find the most frequently used systems. If your system is not quite
as shown below, find the diagram which has the best resemblance
with your system and make your own combinations.

See the Mounting Guide (delivered with the application key) for
application types / sub-types.

The circulation pump(s) in heating circuit(s) can be placed in the flow


as well as the return. Place the pump according to the manufacturer’s
specification.

Advices for settings:


When circuit 1 must be able to receive a heat demand from circuit
2, circuit 3 or a slave:
MENU \ Settings \ Application: 'Demand offset' (ID 11017): 3 K*

When a heating or DHW circuit must be able to send its heat


demand to circuit 1 or the master:
MENU \ Settings \ Application: 'Send desired T' (ID 1x500): ON

When a heating or DHW circuit should not send its heat demand
to circuit 1 or the master:
MENU \ Settings \ Application: 'Send desired T' (ID 1x500): OFF

* This recommended value is added to the heat demand value from


circuit 2, circuit 3 or the slave; always the highest demand.

12 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

2.3 Mounting

2.3.1 Mounting the ECL Comfort controller

For easy access, you should mount the ECL Comfort controller near
the system. Select one of the following methods using the same
base part (code no. 087H3220):
• Mounting on a wall
• Mounting on a DIN rail (35 mm)
ECL Comfort 210 can be mounted in an ECL Comfort 310 base part
(for future upgrade).

Screws, PG cable glands and rawlplugs are not supplied.

Locking the ECL Comfort controller


In order to fasten the ECL Comfort controller to its base part, secure
the controller with the locking pin.

To prevent injuries to persons or the controller, the controller has to


be securely locked into the base. For this purpose, press the locking
pin into the base until a click is heard and the controller no longer
can be removed from the base.

If the controller is not securely locked into the base part, there is a risk
that the controller during operation can unlock from the base and the
base with terminals (and also the 230 V a.c. connections) are exposed.
To prevent injuries to persons, always make sure that the controller
is securely locked into its base. If this is not the case, the controller
should not be operated!

The easy way to lock the controller to its base or unlock it is to use a
screw driver as lever.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 13


Installation Guide ECL Comfort 310, application A376

Mounting on a wall
Mount the base part on a wall with a smooth surface. Establish the
electrical connections and position the controller in the base part.
Secure the controller with the locking pin.

Mounting on a DIN rail (35 mm)


Mount the base part on a DIN rail. Establish the electrical
connections and position the controller in the base part. Secure
the controller with the locking pin.

Dismounting the ECL Comfort controller


In order to remove the controller from the base part, pull out the
locking pin by means of a screwdriver. The controller can now be
removed from the base part.

The easy way to lock the controller to its base or unlock it is to use a
screw driver as lever.

Before removing the ECL Comfort controller from the base part, ensure
that the supply voltage is disconnected.

14 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

2.3.2 Mounting the Remote Control Units ECA 30 / 31

Select one of the following methods:


• Mounting on a wall, ECA 30 / 31
• Mounting in a panel, ECA 30
Screws and rawlplugs are not supplied.

Mounting on a wall
Mount the base part of the ECA 30 / 31 on a wall with a smooth
surface. Establish the electrical connections. Place the ECA 30 /
31 in the base part.

Mounting in a panel
Mount the ECA 30 in a panel using the ECA 30 frame kit (order code
no. 087H3236). Establish the electrical connections. Secure the
frame with the clamp. Place the ECA 30 in the base part. The ECA
30 can be connected to an external room temperature sensor.

The ECA 31 must not be mounted in a panel if the humidity


function is to be used.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 15


Installation Guide ECL Comfort 310, application A376

2.3.3 Mounting the internal I/O module ECA 32

Mounting of the internal I/O module ECA 32


The ECA 32 module (order code no. 087H3202) can be inserted
into the ECL Comfort 310 / 310B base part for additional input and
output signals in relevant applications.

16 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

2.4 Placing the temperature sensors

2.4.1 Placing the temperature sensors

It is important that the sensors are mounted in the correct position


in your system.

The temperature sensor mentioned below are sensors used for


the ECL Comfort 210 and 310 series which not all will be needed
for your application!

Outdoor temperature sensor (ESMT)


The outdoor sensor should be mounted on that side of the building
where it is less likely to be exposed to direct sunshine. It should not
be placed close to doors, windows or air outlets.
Flow temperature sensor (ESMU, ESM-11 or ESMC)
Place the sensor max. 15 cm from the mixing point. In systems
with heat exchanger, Danfoss recommends that the ESMU-type to
be inserted into the exchanger flow outlet.

Make sure that the surface of the pipe is clean and even where
the sensor is mounted.
Return temperature sensor (ESMU, ESM-11 or ESMC)
The return temperature sensor should always be placed so that it
measures a representative return temperature.

Room temperature sensor


(ESM-10, ECA 30 / 31 Remote Control Unit)

Place the room sensor in the room where the temperature is to be


controlled. Do not place it on outside walls or close to radiators,
windows or doors.

Boiler temperature sensor (ESMU, ESM-11 or ESMC)


Place the sensor according to the boiler manufacturer’s
specification.
ESM-11: Do not move the sensor after it has been fastened in order to
Air duct temperature sensor (ESMB-12 or ESMU types) avoid damage to the sensor element.
Place the sensor so that it measures a representative temperature.

DHW temperature sensor (ESMU or ESMB-12)


Place the DHW temperature sensor according to the manufacturer’s
specification.
ESM-11, ESMC and ESMB-12: Use heat conducting paste for quick
measurement of the temperature.
Slab temperature sensor (ESMB-12)
Place the sensor in a protection tube in the slab.

ESMU and ESMB-12: Using a sensor pocket to protect the sensor will,
however, result in a slower temperature measurement.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 17


Installation Guide ECL Comfort 310, application A376

Pt 1000 temperature sensor (IEC 751B, 1000 Ω / 0 °C) Relationship between temperature and ohmic value:


°C Ω 1600

-50 803
1500
-40 843
-30 882
-20 922 1400
-10 961
0 1000
1300
10 1039
20 1078
30 1117 1200
40 1155
50 1194 1100
60 1232
70 1271
80 1309 1000

90 1347
100 1385 900
110 1423
120 1461
800
130 1498
140 1535
150 1573 °C
-50 -25 0 25 50 75 100 125 150

18 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

2.5 Electrical connections

2.5.1 Electrical connections 230 V a.c.

Safety Note
Necessary assembly, start-up, and maintenance work must be
performed by qualified and authorized personnel only.

Local legislations must be respected. This comprises also cable size


and isolation (reinforced type).

A fuse for the ECL Comfort installation is max. 10 A typically.

The ambient temperature range for the ECL Comfort in operation is


0 - 55 °C. Exceeding this temperature range can result in malfunctions.

Installation must be avoided if there is a risk for condensation (dew).

The common ground terminal is used for connection of relevant


components (pumps, motorized control valves).

See also the Mounting Guide (delivered with the application key)
for application specific connections.

Wire cross section: 0.5 - 1.5 mm²


Incorrect connection can damage the electronic outputs.
Max. 2 x 1.5 mm² wires can be inserted into each screw terminal.

Maximum load ratings:

Relay terminals 4 (2) A / 230 V a.c.


(4 A for ohmic load, 2 A for
inductive load)
Triac (= electronic 0,2 A / 230 V a.c.
relay) terminals

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 19


Installation Guide ECL Comfort 310, application A376

2.5.2 Electrical connections 24 V a.c.

See also the Mounting Guide (delivered with the application key)
for application specific connections.

Maximum load ratings:

Relay terminals 4 (2) A / 24 V a.c.


(4 A for ohmic load, 2 A for
inductive load)
Triac (= electronic 1 A / 24 V a.c.
relay) terminals

Do not connect 230 V a.c. powered components to a 24 V a.c. power


supplied controller directly. Use auxilliary relays (K) to separate 230
V a.c. from 24 V a.c.

20 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

2.5.3 Electrical connections, safety thermostats, in general

See also the Mounting Guide (delivered with the application key)
for application specific connections.

When ST is activated by a high temperature, the safety circuit in the


motorized control valve closes the valve immediately.

When ST1 is activated by a high temperature (the TR temperature), the


motorized control valve is closed gradually. At a higher temperature
(the ST temperature), the safety circuit in the motorized control valve
closes the valve immediately.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 21


Installation Guide ECL Comfort 310, application A376

2.5.4 Electrical connections, Pt 1000 temperature sensors and signals

See the Mounting Guide (delivered with the application key) for
sensor and input connections.

Sen- Description Recomm. type * If the outdoor temperature sensor is not connected or the
sor cable is short-circuited, the controller assumes that the
outdoor temperature is 0 (zero) °C.
S1 Outdoor temperature sensor * ESMT
** Only for room temperature sensor connection. The room
temperature signal can also be available from a Remote
S2 A376.1, A376.2, A376.3, A376.4: ESM-10 Control Unit (ECA 30 / 31). See the Mounting Guide (delivered
Room temperature sensor ** with the application key) for specific connections.
Alternative: ECA 30 / 31
*** The flow temperature sensor must always be connected
A376.9, A376.10: ESM-11 / ESMB / in order to have the desired functionality. If the sensor is
Return temperature sensor ESMC / ESMU not connected or the cable is short-circuited, the motorized
(heating, secondary side) control valve closes (safety function).
(S2) A376.2: ESM-10
Room temperature sensor **
Alternative: ECA 30 / 31
S3 Flow temperature sensor *** ESM-11 / ESMB /
(heating) ESMC / ESMU
S4 Flow temperature sensor *** ESM-11 / ESMB /
(DHW) ESMC / ESMU
S5 Return temperature sensor ESM-11 / ESMB /
(heating) ESMC / ESMU
S6 A376.1, A376.2, A376.3, A376.4: ESM-11 / ESMB /
Return temperature sensor ESMC / ESMU
(DHW)
A376.9, A376.10: ESM-11 / ESMB /
Return temperature sensor ESMC / ESMU
(DHW), for monitoring
(S6) A376.9, A376.10: ESM-11 / ESMB /
Return temperature sensor, ESMC / ESMU
(DHW), alternative position.
S7 A376.1, A376.3: ESM-10
Room temperature sensor **
Alternative: ECA 30 / 31
A376.2, A376.4: ESM-11 / ESMB /
Supply flow temperature sensor ESMC / ESMU
A376.9, A376.10:
Pressure transmitter, 0 - 10 V or
4 - 20 mA
S8 A376.2, A376.4:
Flow switch
A376.9, A376.10:
Alarm contact / switch
S9 Flow temperature sensor *** ESM-11 / ESMB /
(heating) ESMC / ESMU
S10 A376.1, A376.2, A376.3, A376.4: ESM-11 / ESMB /
Return temperature sensor ESMC / ESMU
(heating)
A376.9, A376.10: ESM-11 / ESMB /
Return temperature sensor, for ESMC / ESMU
monitoring

22 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

See the Mounting Guide (delivered with the application key) for
sensor and input connections.

ECA 32:

Sen- Description Recommended type


sor
S11 A376.9: ESM-11 / ESMB /
Supply flow temperature ESMC / ESMU
sensor
A376.10:
Supply flow pressure
transmitter, 0 - 10 V or 4 -
20 mA
S12 A376.9: ESM-11 / ESMB /
Supply return temperature ESMC / ESMU
sensor
A376.10:
Supply return pressure
transmitter, 0 - 10 V or 4 -
20 mA
S13 Return temperature sensor ESM-11 / ESMB /
(heating) ESMC / ESMU
S14 Pressure transmitter, 0 - 10
V or 4 - 20 mA
S15 Alarm contact / switch
S16 Alarm contact / switch

Wire cross section for sensor connections: Min. 0.4 mm².


Total cable length: Max. 200 m (all sensors incl. internal ECL 485
communication bus)
Cable lengths of more than 200 m may cause noise sensibility (EMC).

Connection of flow switch


(A376.2, A376.4)
The contacts in the flow switch must be rated for low voltage (12
Volt).

Connection of alarm contact / switch


(A376.9, A376.10)
The contacts in the alarm contact / switch must be rated for low
voltage (12 Volt).

The alarm contact acts as a Normally Closed (NC) contact. The


set-up can be changed to react on a Normally Open (NO) contact.
See Circuit 1 > MENU > Alarm > Digital > Alarm value:

0 = Alarm for NO contact


1 = Alarm for NC contact

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 23


Installation Guide ECL Comfort 310, application A376

Connection of pressure transmitter


Scale for conversion of voltage to pressure is set in the ECL Comfort.
The pressure transmitter is powered with 12 - 24 V d.c.
Output types: 0 - 10 V or 4 - 20 mA.
4 - 20 mA signal is converted to a 2 - 10 V signal by means of a 500
ohm (0,5 W) resistor.

Connection of Cold Water (CW) meter


(A376.9, A376.10)
Pulse value is set in Circuit 3 > MENU > Settings > Water meter.

Cold Water consumption can be read in:


• Circuit 3 > MENU > Settings > Water meter
• Common controller > Input overview 3

2.5.5 Electrical connections, ECA 30 / 31

Terminal Terminal Description Type


ECL ECA 30 / 31 (recomm.)
30 4
Twisted pair
31 1 Cable 2 x
32 2 twisted pair
Twisted pair
33 3
4 Ext. room temperature
ESM-10
5 sensor*

* After an external room temperature sensor has been connected,


ECA 30 / 31 must be repowered.

The communication to the ECA 30 / 31 must be set up in the ECL


Comfort controller in 'ECA addr.'

The ECA 30 / 31 must be set up accordingly.

After application setup the ECA 30 / 31 is ready after 2–5 min. A


progress bar in the ECA 30 / 31 is displayed.

If the actual application contains two heating circuits, it is possible


to connect an ECA 30 / 31 to each circuit. The electrical connections
are done in parallel.

Max. 2 ECA 30 / 31 can be connected to an ECL Comfort 310 controller


or to ECL Comfort 310 controllers in a master-slave system.

Setup procedures for ECA 30 / 31: See section ‘Miscellaneous’.

24 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

ECA information message:


‘Application req. newer ECA’:
The software of your ECA does not comply with the software of your
ECL Comfort controller. Please contact your Danfoss sales office.

Some applications do not contain functions related to actual room


temperature. The connected ECA 30 / 31 will only function as remote
control.

Total cable length: Max. 200 m (all sensors incl. internal ECL 485
communication bus).
Cable lengths of more than 200 m may cause noise sensibility (EMC).

2.5.6 Electrical connections, master / slave systems

The controller can be used as master or slave in master / slave


systems via the internal ECL 485 communication bus (2 x twisted
pair cable).

The ECL 485 communication bus is not compatible with the ECL
bus in ECL Comfort 110, 200, 300 and 301!

Terminal Description Type


(recomm.)
30 Common terminal
31* +12 V*, ECL 485 communication bus Cable 2 x
32 B, ECL 485 communication bus twisted pair
33 A, ECL 485 communication bus
* Only for ECA 30 / 31 and master / slave communication

Total cable length: Max. 200 m (all sensors incl. internal ECL 485
communication bus).
Cable lengths of more than 200 m may cause noise sensibility (EMC).

2.5.7 Electrical connections, communication

Electrical connections, Modbus

ECL Comfort 210: Non-galvanic isolated Modbus connections


ECL Comfort 310: Galvanic isolated Modbus connections

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 25


Installation Guide ECL Comfort 310, application A376

2.6 Inserting the ECL Application Key

2.6.1 Inserting the ECL Application Key

The ECL Application Key contains


• the application and its subtypes,
• currently available languages,
• factory settings: e.g. schedules, desired temperatures,
limitation values etc. It is always possible to recover the factory
settings,
• memory for user settings: special user / system settings.

After having powered-up the controller, different situations might


be existing:
1. The controller is new from the factory, the ECL Application Key
is not inserted.
2. The controller already runs an application. The ECL Application
Key is inserted, but the application needs to be changed.
3. A copy of the controllers settings is needed for configuring
another controller.

User settings are, among others, desired room temperature, desired


DHW temperature, schedules, heat curve, limitation values etc.

System settings are, among others, communication set-up, display


brightness etc.

26 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Automatic update of controller software:


The software of the controller is updated automatically when the key
is inserted (as of controller version 1.11). The following animation will
be shown when the software is being updated:

Progress bar

During update:
• Do not remove the KEY
If the key is removed before the hour-glass is shown, you have
to start afresh.
• Do not disconnect the power
If the power is interrupted when the hour-glass is shown, the
controller will not work.

The “Key overview” does not inform — through ECA 30 / 31 — about


the subtypes of the application key.

Key inserted / not inserted, description:

ECL Comfort 210 / 310, controller versions lower than 1.36:


- Take out the application key; for 20 minutes
settings can be changed.
- Power up the controller without the
application key inserted; for 20 minutes
settings can be changed.

ECL Comfort 210 / 310, controller versions 1.36 and up:


- Take out the application key; for 20 minutes
settings can be changed.
- Power up the controller without the
application key inserted; settings cannot be
changed.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 27


Installation Guide ECL Comfort 310, application A376

Application Key: Situation 1


The controller is new from the factory, the ECL Application Key
is not inserted.

An animation for the ECL Application Key insertion is displayed.


Insert the Application Key .

Application Key name and Version is indicated (example: A266


Ver. 1.03).

If the ECL Application Key is not suitable for the controller, a "cross"
is displayed over the ECL Application Key-symbol.

Action: Purpose: Examples:


Select language
Confirm
Select application

Confirm with ‘Yes’


Set 'Time & Date'
Turn and push the dial to select and
change 'Hours', 'Minutes', 'Date',
'Month' and 'Year'.
Choose ''Next'

Confirm with ‘Yes’

Go to ‘Aut. daylight’
Choose whether ‘Aut. daylight´ *
YES or NO
should be active or not

* ‘Aut. daylight’ is the automatic changeover between summer


and winter time.

Depending on the contents of the ECL Application Key, procedure


A or B is taking place:
A
The ECL Application key contains factory settings:
The controller reads / transfers data from the ECL Application Key
to ECL controller.

The application is installed, and the controller resets and starts up.

B
The ECL Application key contains changed system settings:
Push the dial repeatedly.
’NO’: Only factory settings from the ECL Application Key will
be copied to the controller.
’YES*: Special system settings (differing from the factory
settings) will be copied to the controller.

If the key contains user settings:


Push the dial repeatedly.

‘NO: Only factory settings from the ECL Application Key will
be copied to the controller.
‘YES*: Special user settings (differing from the factory settings)
will be copied to the controller.

* If ‘YES’ cannot be chosen, the ECL Application Key does not


contain any special settings.

Choose ‘Start copying’ and confirm with 'Yes'.

28 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

(Example):

The "i" in the upper right corner indicates that - besides the factory
settings - the subtype also contains special user / systems settings.

Application Key: Situation 2


The controller already runs an application. The ECL Application
Key is inserted, but the application needs to be changed.

To change to another application on the ECL Application Key, the


current application in the controller must be erased (deleted).

Be aware that the Application Key must be inserted.

Action: Purpose: Examples:


Choose ‘MENU’ in any circuit

Confirm
Choose the circuit selector at the top
right corner in the display
Confirm

Choose ‘Common controller settings’

Confirm

Choose ‘Key functions’

Confirm

Choose ‘Erase application’

Confirm with ‘Yes’

The controller resets and is ready to be configured.

Follow the procedure described in situation 1.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 29


Installation Guide ECL Comfort 310, application A376

Application Key: Situation 3


A copy of the controllers settings is needed for configuring
another controller.

This function is used


• for saving (backup) of special user and system settings
• when another ECL Comfort controller of the same type (210 or
310) must be configured with the same application but user /
system settings differ from the factory settings.
How to copy to another ECL Comfort controller:

Action: Purpose: Examples:


Choose ‘MENU’

Confirm
Choose the circuit selector at the top
right corner in the display
Confirm

Choose 'Common controller settings'

Confirm

Go to ‘Key functions’

Confirm

Choose ‘Copy’

Confirm
Choose ‘To’.
*
‘ECL’ or ‘KEY’ will be indicated. Choose
’ECL’ or ‘KEY’.
’ECL’ or KEY’
Push the dial repeatedly to choose
copy direction
Choose ‘System settings’ or ‘User **
settings’ ‘NO’ or ‘YES’
Push the dial repeatedly to choose
‘Yes’ or ‘No’ in ‘Copy’. Push to confirm.
Choose ‘Start copying’
The Application Key or the controller
is updated with special system or user
settings.

*
‘ECL’: Data will be copied from the Application Key to the
ECL Controller.
‘KEY’: Data will be copied from the ECL Controller to the
Application Key.

**
‘NO’: The settings from the ECL controller will not be copied
to the Application Key or to the ECL Comfort controller.
‘YES’: Special settings (differing from the factory settings) will
be copied to the Application Key or to the ECL Comfort
controller. If YES can not be chosen, there are no special
settings to be copied.

30 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

2.6.2 ECL Application Key, copying data

General principles
When the controller is connected and operating, you can check
and adjust all or some of the basic settings. The new settings can
be stored on the Key. Factory settings can always be restored.

How to update the ECL Application Key after settings have


been changed?
All new settings can be stored on the ECL Application Key.

How to store factory setting in the controller from the Make a note of new settings in the 'Settings overview' table.
Application Key?
Please read the paragraph concerning Application Key, Situation
1: The controller is new from the factory, the ECL Application Key
is not inserted.
Do not remove the ECL Application Key while copying. The data on
How to store personal settings from the controller to the Key? the ECL Application Key can be damaged!
Please read the paragraph concerning Application Key, Situation 3:
A copy of the controllers settings is needed for configuring another
controller

As a main rule, the ECL Application Key should always remain in


the controller. If the Key is removed, it is not possible to change It is possible to copy settings from one ECL Comfort controller to
settings. another controller provided that the two controllers are from the same
series (210 or 310).

The “Key overview” does not inform — through ECA 30 / 31 — about


the subtypes of the application key.

Key inserted / not inserted, description:

ECL Comfort 210 / 310, controller versions lower than 1.36:


- Take out the application key; for 20 minutes
settings can be changed.
- Power up the controller without the
application key inserted; for 20 minutes
settings can be changed.

ECL Comfort 210 / 310, controller versions 1.36 and up:


- Take out the application key; for 20 minutes
settings can be changed.
- Power up the controller without the
application key inserted; settings cannot be
changed.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 31


Installation Guide ECL Comfort 310, application A376

2.7 Check list

Is the ECL Comfort controller ready for use?

Make sure that the correct power supply is connected to terminals 9 and 10 (230 V or 24 V).

Make sure the correct phase conditions are connected:


230 V: Live = terminal 9 and Neutral = terminal 10
24 V: SP = terminal 9 and SN = terminal 10

Check that the required controlled components (actuator, pump etc.) are connected to the correct terminals.

Check that all sensors / signals are connected to the correct terminals (see 'Electrical connections').

Mount the controller and switch on the power.

Is the ECL Application Key inserted (see 'Inserting the Application Key').

Does the ECL Comfort controller contain an existing application (see 'Inserting the Application Key').

Is the correct language chosen (see 'Language' in 'Common controller settings').

Is the time & date set correctly (see 'Time & Date' in 'Common controller settings').

Is the right application chosen (see 'Identifying the system type').

Check that all settings in the controller (see 'Settings overview') are set or that the factory settings comply with your
requirements.
Choose manual operation (see 'Manual control'). Check that valves open and close, and that required controlled
components (pump etc.) start and stop when operated manually.

Check that the temperatures / signals shown in the display match the actual connected components.

Having completed the manual operation check, choose controller mode (scheduled, comfort, saving or frost protection).

32 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

2.8 Navigation, ECL Application Key A376

Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, circuit 1, Heating

Home Applications A376


MENU ID no. Function A376.1 A376.2 A376.3 A376.4 A376.9 A376.10
Schedule Selectable ( ( ( ( ( (
Settings Flow temperature Heat curve ( ( ( ( ( (
11178 Temp. max. ( ( ( ( ( (
11177 Temp. min. ( ( ( ( ( (
11004 Desired T ( ( ( ( ( (
Room limit 11182 Infl. - max. ( ( ( (
11183 Infl. - min. ( ( ( (
11015 Adapt. time ( ( ( (
Return limit 11031 High T out X1 ( ( ( ( ( (
11032 Low limit Y1 ( ( ( ( ( (
11033 Low T out X2 ( ( ( ( ( (
11034 High limit Y2 ( ( ( ( ( (
11035 Infl. - max. ( ( ( ( ( (
11036 Infl. - min. ( ( ( ( ( (
11037 Adapt. time ( ( ( ( ( (
11085 Priority ( ( ( ( ( (
11029 DHW, ret. T limit ( ( ( ( ( (
11028 Con. T, ret. T lim. ( ( ( ( ( (

Flow/power limit Actual ( ( ( ( ( (


Actual limit ( ( ( ( ( (
11119 High T out X1 ( ( ( ( ( (
11117 Low limit Y1 ( ( ( ( ( (
11118 Low T out X2 ( ( ( ( ( (
11116 High limit Y2 ( ( ( ( ( (
11112 Adapt. time ( ( ( ( ( (
11113 Filter constant ( ( ( ( ( (
11109 Input type ( ( ( ( ( (
11115 Units ( ( ( ( ( (
Optimization 11011 Auto saving ( ( ( ( ( (
11012 Boost ( ( ( ( ( (
11013 Ramp ( ( ( ( ( (
11014 Optimizer ( ( ( ( ( (
11026 Pre-stop ( ( ( ( ( (
11020 Based on ( ( ( (
11021 Total stop ( ( ( ( ( (
11179 Summer, cut-out ( ( ( ( ( (
11043 Parallel operation ( ( ( (

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 33


Installation Guide ECL Comfort 310, application A376

Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, circuit 1, Heating continued

Home Applications A376


MENU ID no. Function A376.1 A376.2 A376.3 A376.4 A376.9 A376.10
Settings Control par. 11174 Motor pr. ( ( ( ( ( (
11184 Xp ( ( ( ( ( (
11185 Tn ( ( ( ( ( (
11186 M run ( ( ( ( (
11187 Nz ( ( ( ( ( (
11189 Min. act. time ( ( ( ( (
11024 Actuator ( ( ( ( (
Application 11010 ECA addr. ( ( ( (
11017 Demand offset ( ( ( ( ( (
11050 P demand ( ( ( ( ( (
11500 Send desired T ( ( ( ( ( (
11022 P exercise ( ( ( ( ( (
11023 M exercise ( ( ( ( ( (
11052 DHW priority ( ( ( ( ( (
11077 P frost T ( ( ( ( ( (
11078 P heat T ( ( ( ( ( (
11040 P post-run ( ( ( ( ( (
11093 Frost pr. T ( ( ( ( ( (
11141 Ext. input ( ( ( ( ( (
11142 Ext. mode ( ( ( ( ( (
Heat cut-out 11393 Sum. start, day ( ( ( ( ( (
11392 Sum. start, month ( ( ( ( ( (
11179 Summer, cut-out ( ( ( ( ( (
11395 Summer, filter ( ( ( ( ( (
11397 Winter start, day ( ( ( ( ( (
11396 Win. start, month ( ( ( ( ( (
11398 Winter, cut-out ( ( ( ( ( (
11399 Winter, filter ( ( ( ( ( (

34 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, circuit 1, Heating continued

Home Applications A376


MENU ID no. Function A376.1 A376.2 A376.3 A376.4 A376.9 A376.10
Holiday Selectable ( ( ( ( ( (

Alarm S7 pressure Pressure ( (


11607 Low X ( (
11608 High X ( (
11614 Alarm high ( (
11615 Alarm low ( (
11617 Alarm time-out ( (

Digital S8 11636 Alarm value ( (


11637 Alarm time-out ( (
Temp. monitor. 11147 Upper difference ( ( ( ( ( (
11148 Lower difference ( ( ( ( ( (
11149 Delay ( ( ( ( ( (
11150 Lowest temp. ( ( ( ( ( (
Max. temp 11079 Max. flow T ( (
11080 Delay ( (

Alarm overview Selectable ( ( ( ( ( (

Influence Des. flow T Return lim. ( ( ( ( ( (

overview Room lim. ( ( ( (

Parallel priority ( ( ( (

Flow / power lim. ( ( ( ( ( (

Holiday ( ( ( ( ( (

Ext. override ( ( ( ( ( (

ECA override ( ( (
Boost ( ( ( ( ( (
Ramp ( ( ( ( ( (
Slave, demand ( ( ( ( ( (
Heating cut-out ( ( ( ( ( (
DHW priority ( ( ( ( ( (
SCADA offset ( ( ( ( ( (

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 35


Installation Guide ECL Comfort 310, application A376

Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, circuit 2, Heating

Home Applications A376


MENU ID no. Function A376.1 A376.2 A376.3 A376.4 A376.9 A376.10
Schedule Selectable ( ( ( ( ( (
Settings Flow
temperature Heat curve ( ( ( ( ( (
12178 Temp. max. ( ( ( ( ( (
12177 Temp. min. ( ( ( ( ( (
12004 Desired T ( ( ( ( (
Room limit 12182 Infl. - max. ( ( (
12183 Infl. - min. ( ( (
12015 Adapt. time ( ( (
Return limit 12031 High T out X1 ( ( ( ( (
12032 Low limit Y1 ( ( ( ( (
12033 Low T out X2 ( ( ( ( (
12034 High limit Y2 ( ( ( ( (
12035 Infl. - max. ( ( ( ( ( (
12036 Infl. - min. ( ( ( ( ( (
12037 Adapt. time ( ( ( ( ( (
12085 Priority ( ( ( ( ( (
12028 Con. T, ret. T lim. ( ( ( ( (

Flow/power limit Actual ( ( ( ( ( (


Actual limit ( ( ( ( ( (
12119 High T out X1 ( ( ( ( (
12117 Low limit Y1 ( ( ( ( (
12118 Low T out X2 ( ( ( ( (
12116 High limit Y2 ( ( ( ( (
12112 Adapt. time ( ( ( ( ( (
12113 Filter constant ( ( ( ( ( (
12109 Input type ( ( ( ( ( (
12115 Units ( ( ( ( ( (
Optimization 12011 Auto saving ( ( ( ( (
12012 Boost ( ( ( ( (
12013 Ramp ( ( ( ( (
12014 Optimizer ( ( ( ( (
12026 Pre-stop ( ( ( ( (
12020 Based on ( ( (
12021 Total stop ( ( ( ( (
12179 Summer, cut-out ( ( ( ( (
12043 Parallel operation ( ( (

36 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, circuit 2, Heating continued

Home Applications A376


MENU ID no. Function A376.1 A376.2 A376.3 A376.4 A376.9 A376.10
Settings Control par. 12174 Motor pr. ( ( ( ( ( (
12184 Xp ( ( ( ( ( (
12185 Tn ( ( ( ( ( (
12186 M run ( ( ( ( (
12187 Nz ( ( ( ( ( (
12189 Min. act. time ( ( ( ( (
12024 Actuator ( ( ( ( (
Application 12010 ECA addr. ( ( (
12500 Send desired T ( ( ( ( ( (
12022 P exercise ( ( ( ( ( (
12023 M exercise ( ( ( ( ( (
12052 DHW priority ( ( ( ( (
12077 P frost T ( ( ( ( ( (
12078 P heat T ( ( ( ( ( (
12040 P post-run ( ( ( ( ( (
12093 Frost pr. T ( ( ( ( ( (
12141 Ext. input ( ( ( ( ( (
12142 Ext. mode ( ( ( ( ( (
Heat cut-out 12179 Summer, cut-out ( ( ( ( (
12395 Summer, filter ( ( ( ( (
13398 Winter, cut-out ( ( ( ( (
13399 Winter, filter ( ( ( ( (

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 37


Installation Guide ECL Comfort 310, application A376

Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, circuit 2, Heating continued

Home Applications A376


MENU ID no. Function A376.1 A376.2 A376.3 A376.4 A376.9 A376.10
Holiday Selectable ( ( ( ( ( (

Alarm S14 pressure Pressure ( (


12607 Low X ( (
12608 High X ( (
12614 Alarm high ( (
12615 Alarm low ( (
12617 Alarm time-out ( (

Digital S15 12636 Alarm value ( (


12637 Alarm time-out ( (
Temp. monitor. 12147 Upper difference ( ( ( ( ( (
12148 Lower difference ( ( ( ( ( (
12149 Delay ( ( ( ( ( (
12150 Lowest temp. ( ( ( ( ( (
Max. temp 12079 Max. flow T ( (
12080 Delay ( (

Alarm overview Selectable ( ( ( ( ( (

Influence Des. flow T Return lim. ( ( ( ( (

overview Room lim. ( ( (

Parallel priority ( ( (

Flow / power lim. ( ( ( ( (

Holiday ( ( ( ( (

Ext. override ( ( ( ( (

ECA override ( (
Boost ( ( ( ( (
Ramp ( ( ( ( (
Heating cut-out ( ( ( ( (
DHW priority ( ( ( ( (
SCADA offset ( ( ( ( (

38 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, DHW

Home Applications A376


MENU ID no. Function A376.1 A376.2 A376.3 A376.4 A376.9 A376.10
Schedule Selectable ( ( ( ( ( (
Settings Flow temperature 13178 Temp. max. ( ( ( ( ( (
13177 Temp. min. ( ( ( ( ( (
Return limit 12030 Limit (
13030 Limit ( ( ( ( ( (
13035 Infl. - max. ( ( ( ( ( (
13036 Infl. - min. ( ( ( ( ( (
13037 Adapt. time ( ( ( ( ( (
13085 Priority ( ( ( ( ( (
Flow/power limit Actual ( ( ( ( ( (
12111 Limit (
13111 Limit ( ( ( ( ( (
13112 Adapt. time ( ( ( ( ( (
13113 Filter constant ( ( ( ( ( (
13109 Input type ( ( ( ( ( (
13115 Units ( ( ( ( ( (
Control par. 12173 Auto tuning (
13173 Auto tuning ( ( ( ( (
13174 Motor pr. ( ( ( ( ( (
13184 Xp ( ( ( ( ( (
13185 Tn ( ( ( ( ( (
13186 M run ( ( ( ( (
13187 Nz ( ( ( ( ( (
13189 Min. act. time ( ( ( ( (
13097 Supply T (idle) ( (
13096 Tn (idle) ( (
13094 Open time ( (
13095 Close time ( (
13024 Actuator ( ( ( ( (

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 39


Installation Guide ECL Comfort 310, application A376

Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, DHW continued

Home Applications A376


MENU ID no. Function A376.1 A376.2 A376.3 A376.4 A376.9 A376.10
Settings Application 13500 Send desired T ( ( ( ( ( (
13022 P exercise ( ( ( ( ( (
13023 M exercise ( ( ( ( ( (
13077 P frost T ( ( ( ( ( (
13078 P heat T ( ( ( ( ( (
13040 P post-run ( ( ( ( ( (
13093 Frost pr. T ( ( ( ( ( (
13141 Ext. input ( ( ( ( ( (
13142 Ext. mode ( ( ( ( ( (
Anti- ( ( ( ( ( (
Selectable
bacteria
Water CW consump. ( (
meter 13513 Pulse value ( (
13514 Preset ( (

40 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Navigation, A376, applications A376.1, A376.2, A376.3, A376.4, A376.9, A376.10, DHW continued

Home Applications A376


MENU ID no. Function A376.1 A376.2 A376.3 A376.4 A376.9 A376.10
Holiday Selectable ( ( ( ( ( (

Alarm Digital S16 13636 Alarm value ( (


13637 Alarm time-out ( (
Temp. monitor. 12147 Upper difference (
12148 Lower difference (
12149 Delay (
12150 Lowest temp. (
13147 Upper difference ( ( ( ( ( (
13148 Lower difference ( ( ( ( ( (
13149 Delay ( ( ( ( ( (
13150 Lowest temp. ( ( ( ( ( (
Alarm overview Selectable ( ( ( ( ( (

Influence Des. flow T Return lim. ( ( ( ( ( (

overview Flow / power lim. ( ( ( ( ( (

Holiday ( ( ( ( ( (

Ext. override ( ( ( ( ( (

Anti-bacteria ( ( ( ( ( (

SCADA offset ( ( ( ( ( (

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 41


Installation Guide ECL Comfort 310, application A376

Navigation, application A376.1, Common controller settings

Home Common controller settings


MENU ID no. Function
Time & Date Selectable
Holiday Selectable
Input overview 1, 2 & 3 Circuit 1 Circuit 2 Circuit 3
Outdoor T Outdoor T DHW flow T
Outdoor acc. T Outdoor acc. T DHW return T
Room T Room T
Heat flow T Heat flow T
Heat return T Heat return T
Log 1, 2 & 3 (sensors) Log today Outdoor T Outdoor T DHW flow & des.
Log yesterday Heating flow & des. Heating flow & des. DHW return T
Log 2 days Heat return T & limit Heat return T & limit
Log 4 days Room T Room T

Output override M1, P1, M2, P2, M3, P3, A1


Key functions New application Erase application
Application
Factory setting System settings
User settings
Go to factory
Copy To
System settings
User settings
Start copying
Key overview
System ECL version Code no.
Hardware
Software
Build no.
Serial no.
MAC
Production week
Extension
Ethernet
Portal config
M-bus config
Energy Meters
Raw input overview S1...S10
Alarm T sensor defect
Display 60058 Backlight
60059 Contrast
Communication 38 Modbus addr.
39 Baud
2048 ECL 485 addr.
2150 Service pin
2151 Ext. reset
Language 2050 Language

42 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Navigation, application A376.2, Common controller settings

Home Common controller settings


MENU ID no. Function
Time & Date Selectable
Holiday Selectable
Input overview 1, 2 & 3 Circuit 1 Circuit 2 Circuit 3
Outdoor T Outdoor T DHW flow T
Outdoor acc. T Outdoor acc. T DHW return T
Room T Room T Supply T
Heat flow T Heat flow T Flow switch
Heat return T Heat return T

Log 1, 2 & 3 (sensors) Log today Outdoor T Outdoor T DHW flow & des.
Log yesterday Heating flow & des. Heating flow & des. DHW return T
Log 2 days Heat return T & limit Heat return T & limit Supply T
Log 4 days Room T Room T

Output override M1, P1, M2, P2, M3, P3, A1


Key functions New application Erase application
Application
Factory setting System settings
User settings
Go to factory
Copy To
System settings
User settings
Start copying
Key overview
System ECL version Code no.
Hardware
Software
Build no.
Serial no.
MAC
Production week
Extension
Ethernet
Portal config
M-bus config
Energy meters
Raw input overview S1...S10
Alarm T sensor defect
Display 60058 Backlight
60059 Contrast
Communication 38 Modbus addr.
39 Baud
2048 ECL 485 addr.
2150 Service pin
2151 Ext. reset
Language 2050 Language

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 43


Installation Guide ECL Comfort 310, application A376

Navigation, application A376.3, Common controller settings

Home Common controller settings


MENU ID no. Function
Time & Date Selectable
Holiday Selectable
Input overview 1, 2 & 3 Circuit 1 Circuit 2 Circuit 3
Outdoor T Outdoor T DHW flow T
Outdoor acc. T Outdoor acc. T DHW return T
Room T Room T
Heat flow T Heat flow T
Heat return T Heat return T

Log 1, 2 & 3 (sensors) Log today Outdoor T Outdoor T DHW flow & des.
Log yesterday Heating flow & des. Heating flow & des. DHW return T
Log 2 days Heat return T & limit Heat return T & limit
Log 4 days Room T Room T

Output override M1, P1, M2, P2, M3, P3, A1


Key functions New application Erase application
Application
Factory setting System settings
User settings
Go to factory
Copy To
System settings
User settings
Start copying
Key overview
System ECL version Code no.
Hardware
Software
Build no.
Serial no.
MAC
Production week
Extension
Ethernet
Portal config
M-bus config
Energy Meters
Raw input overview S1...S10
Alarm T sensor defect
Display 60058 Backlight
60059 Contrast
Communication 38 Modbus addr.
39 Baud
2048 ECL 485 addr.
2150 Service pin
2151 Ext. reset
Language 2050 Language

44 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Navigation, application A376.4, Common controller settings

Home Common controller settings


MENU ID no. Function
Time & Date Selectable
Holiday Selectable
Input overview 1, 2 & 3 Circuit 1 Circuit 2 Circuit 3
Outdoor T DHW flow T DHW flow T
Outdoor acc. T DHW return T DHW return T
Room T Supply T
Heat flow T Flow switch
Heat return T

Log 1, 2 & 3 (sensors) Log today Outdoor T DHW flow & des. DHW flow & des.
Log yesterday Heating flow & des. DHW return T DHW return T
Log 2 days Heat return T & limit Supply T
Log 4 days Room T

Output override M1, P1, M2, P2, M3, P3, A1


Key functions New application Erase application
Application
Factory setting System settings
User settings
Go to factory
Copy To
System settings
User settings
Start copying
Key overview
System ECL version Code no.
Hardware
Software
Build no.
Serial no.
MAC
Production week
Extension
Ethernet
Portal config
M-bus config
Energy Meters
Raw input overview S1...S10
Alarm T sensor defect
Display 60058 Backlight
60059 Contrast
Communication 38 Modbus addr.
39 Baud
2048 ECL 485 addr.
2150 Service pin
2151 Ext. reset
Language 2050 Language

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 45


Installation Guide ECL Comfort 310, application A376

Navigation, application A376.9, Common controller settings

Home Common controller settings


MENU ID no. Function
Time & Date Selectable
Schedule output Selectable
Holiday Selectable
Input overview 1, 2 & 3 Circuit 1 Circuit 2 Circuit 3
Outdoor T Outdoor T DHW flow T
Outdoor acc. T Outdoor acc. T DHW return T
Heat return T Heat return T CW consump.
Heat flow T Heat flow T
Prim. return T Prim. return T
S7 pressure S14 pressure
S8 status S15 status S16 status
Log 1, 2 & 3 (sensors) Log today Outdoor T Outdoor T DHW flow & des.
Log yesterday Heating flow & des. Heating flow & des. DHW return T
Log 2 days Heat return T Heat return T
Log 4 days Return T sec. Return T sec.
Heating pressure Heating pressure

Output override M1, P1, M2, P2, M3, P3, A1, O1


Key functions New application Erase application
Application
Factory setting System settings
User settings
Go to factory
Copy To
System settings
User settings
Start copying
Key overview
System ECL version Code no.
Hardware
Software
Build no.
Serial no.
MAC
Production week
Extension
Ethernet
Portal config
M-bus config
Energy Meters
Raw input overview S1...S10
Alarm T sensor defect
Display 60058 Backlight
60059 Contrast
Communication 38 Modbus addr.
39 Baud
2048 ECL 485 addr.
2150 Service pin
2151 Ext. reset
Language 2050 Language

46 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Navigation, application A376.10, Common controller settings

Home Common controller settings


MENU ID no. Function
Time & Date Selectable
Schedule output Selectable
S11 pressure Pressure
13607 Low X
13608 High X
S12 pressure Pressure
14607 Low X
14608 High X
Holiday Selectable
Input overview 1, 2 & 3 Circuit 1 Circuit 2 Circuit 3
Outdoor T Outdoor T DHW flow T
Outdoor acc. T Outdoor acc. T DHW return T
Heat return T Heat return T CW consump.
Heat flow T Heat flow T
Prim. return T Prim. return T
S7 pressure S14 pressure
S8 status S15 status S16 status
Log 1, 2 & 3 (sensors) Log today Outdoor T Outdoor T DHW flow & des.
Log yesterday Heating flow & des. Heating flow & des. DHW return T
Log 2 days Heat return T Heat return T
Log 4 days Return T sec. Return T sec.
Heating pressure Heating pressure
Output override M1, P1, M2, P2, M3, P3, A1, O1
Key functions New application Erase application
Application
Factory setting System settings
User settings
Go to factory
Copy To
System settings
User settings
Start copying
Key overview
System ECL version Code no.
Hardware
Software
Build no.
Serial no.
MAC
Production week
Extension
Ethernet
Portal config
M-bus config
Energy Meters
Raw input overview S1...S10
Alarm T sensor defect
Display 60058 Backlight
60059 Contrast
Communication 38 Modbus addr.
39 Baud
2048 ECL 485 addr.
2150 Service pin
2151 Ext. reset
Language 2050 Language

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 47


Installation Guide ECL Comfort 310, application A376

3.0 Daily use

3.1 How to navigate


You navigate in the controller by turning the dial left or right to
the desired position ( ).

The dial has a built-in accellerator. The faster you turn the dial, the
faster it reaches the limits of any wide setting range.

The position indicator in the display ( ) will always show you where
you are.

Push the dial to confirm your choices ( ).

The display examples are from a two-circuit application: One


heating circuit ( ) and one domestic hot-water (DHW) circuit ( ).
The examples might differ from your application.

Heating circuit ( ): DHW circuit ( );

Some general settings which apply to the entire controller are


Circuit selector
located in a specific part of the controller.

To enter ‘Common controller settings’:

Action: Purpose: Examples:


Choose ‘MENU’ in any circuit

Confirm
Choose the circuit selector at the top
right corner in the display
Confirm

Choose ‘Common controller settings’

Confirm

48 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

3.2 Understanding the controller display


This section describes the function in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application
related. They might differ from the displays in your application.

Choosing a favorite display


Your favorite display is the display you have chosen as the default
display. The favorite display will give you a quick overview of the
temperatures or units that you want to monitor in general. To shift between displays: Turn the dial until you reach the display
selector ( ) at the bottom right side of the display. Push the dial and
If the dial has not been activated for 20 min., the controller will turn to choose your favorite overview display. Push the dial again.
revert to the overview display you have chosen as favorite.

Heating circuit Overview display 1: Overview display 2:


Overview display 1 informs about:
actual outdoor temperature, controller mode,
actual room temperature, desired room temperature.

Overview display 2 informs about:


actual outdoor temperature, trend in outdoor temperature,
controller mode, max. and min. outdoor temperatures since
midnight as well as desired room temperature.

Overview display 3 informs about: Overview display 3: Overview display 4:


date, actual outdoor temperature, controller mode, time, desired
room temperature as well as shows the comfort schedule of the
current day.

Overview display 4 informs about:


state of the controlled components, actual flow temperature,
(desired flow temperature), controller mode, return temperature
(limitation value), influence on desired flow temperature.

Dependent on the chosen display, the overview displays for the


heating circuit inform you about:
• actual outdoor temperature (-0.5) Example of overview display with
Influence indication:
• controller mode ( )
• actual room temperature (24.5)
• desired room temperature (20.7 °C)
• trend in outdoor temperature ( )
• min. and max. outdoor temperatures since midnight ( )
• date (23.02.2010)
• time (7:43)
• comfort schedule of the current day (0 - 12 - 24)
• state of the controlled components (M2, P2)
• actual flow temperature (49 °C), (desired flow temperature (31))
• return temperature (24 °C) (limitation temperature (50))

The setting of the desired room temperature is important even if a


room temperature sensor / Remote Control Unit is not connected.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 49


Installation Guide ECL Comfort 310, application A376

If the temperature value is displayed as

"- -" the sensor in question is not connected.


"- - -" the sensor connection is short-circuited.

DHW circuit Overview display 1: Overview display 2:


Overview display 1 informs about:
actual DHW temperature, controller mode, desired DHW
temperature as well as the comfort schedule of the current day.

Overview display 2 informs about:


state of the controlled components, actual DHW temperature,
(desired DHW temperature), controller mode, return temperature
(limitation value), influence on desired DHW temperature.

Dependent on chosen display, the overview displays for the DHW Example of overview display with
circuit inform you about: Influence indication:
• actual DHW temperature (50.3)
• controller mode ( )
• desired DHW temperature (50 °C)
• comfort schedule of the current day(0 - 12 - 24)
• state of the controlled components (M1, P1)
• actual DHW temperature (50 °C), (desired DHW temperature (50))
• return temperature (- - °C) (limitation temperature (30))

Setting the desired temperature

Depending on the chosen circuit and mode, it is possible to enter


all daily settings directly from the overview displays (see also the
next page concerning symbols).

Setting the desired room temperature

The desired room temperature can easily be adjusted in the


overview displays for the heating circuit.

Action: Purpose: Examples:

Desired room temperature 20.5

Confirm

Adjust the desired room temperature 21.0

Confirm

This overview display informs about outdoor temperature, actual


room temperature as well as desired room temperature.

The display example is for comfort mode. If you want to change


the desired room temperature for saving mode, choose the mode
selector and select saving.

50 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Overview of setting range and settings for desired room temperature:

Mode Setting range Factory setting


Comfort 5... 40 °C 20 °C
Saving 5... 40 °C 16°C
Frost protection* 5 ... 40 °C 10 °C

* related to desired flow temperature

The setting of the desired room temperature is important even if a


room temperature sensor / Remote Control Unit is not connected.

Setting the desired room temperature, ECA 30 / ECA 31

The desired room temperature can be set exactly as in the


controller. However, other symbols can be present in the display With the ECA 30 / ECA 31 you can override the desired room
(please see 'What do the symbols mean?'). temperature set in the controller temporarily by means of the override
functions:

Setting the desired DHW temperature

The desired DHW temperature can easily be adjusted in the


overview displays for the DHW circuit.

Action: Purpose: Examples:

Desired DHW temperature 50

Confirm

Adjust the desired DHW temperature 55

Confirm

In addition to the information about desired and actual DHW


temperature, the today's schedule is visible.

The display example indicates that the controller is in scheduled


operation and in comfort mode.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 51


Installation Guide ECL Comfort 310, application A376

Overview of setting range and settings for DHW modes:

Mode Setting range Factory setting


Comfort 10 ... 150 °C 50 °C
Saving 10 ... 150 °C 10 °C
Frost protection* 5 ... 40 °C 10 °C

* related to desired flow temperature

52 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

3.3 A general overview: What do the symbols mean?

Symbol Description Symbol Description

Outdoor temp. Alarm

Monitoring temperature sensor


Relative humidity indoor connection
Temperature Display selector
Room temp.
Max. and min. value
DHW temp.
Trend in outdoor temperature
Position indicator
Wind speed sensor

Scheduled mode Sensor not connected or not used


Sensor connection short-circuited
Comfort mode
7-23 Fixed comfort day (holiday)
Saving mode
Active influence
Frost protection mode

Manual mode Heating active


Mode

Standby Cooling active

Cooling mode

Additional symbols, ECA 30 / 31:


! Active output override
Symbol Description
Optimized start or stop time
ECA Remote Control Unit
Heating
15 Connection address (master: 15, slaves: 1 - 9)
Cooling
Circuit Day off
DHW

Common controller settings Holiday

Pump ON Relaxing (extended comfort period)

Pump OFF Going out (extended saving period)

Actuator opens Controlled


component
Actuator closes

42 Actuator, analogue control


signal
In ECA 30 / 31 only the symbols that are relevant to the application in
the controller are displayed.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 53


Installation Guide ECL Comfort 310, application A376

3.4 Monitoring temperatures and system components


This section describes the function in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application
related. They might differ from the displays in your application.

Heating circuit

The overview display in the heating circuit ensures a quick


overview of the actual and (desired) temperatures as well as the
actual state of the system components.

Display example:

49 °C Flow temperature
(31) Desired flow temperature
24 °C Return temperature
(50) Return temperature limitation

DHW circuit Display example with heat exchanger:

The overview display in the DHW circuit ensures a quick overview


of the actual and (desired) temperatures as well as the actual state
of the system components.

Display example (heat exchanger):

50 °C Flow temperature
(50) Desired flow temperature
-- Return temperature: sensor not connected
(30) Return temperature limitation

Input overview

Another option to get a quick overview of measured temperatures


is the 'Input overview' which is visible in the common controller
settings (how to enter the common controller settings, see
‘Introduction to common controller settings’.)

As this overview (see display example) only states the measured


actual temperatures, it is read-only.

54 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

3.5 Influence overview


This section describes the function in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application
related. They might differ from the displays in your application.

The menu gives an overview of the influences on the desired


flow temperature. It differs from application to application which Example of overview display with Influence indication:
parameters are listed. It can be helpful in a service situation to
explain unexpected conditions or temperatures among others.

If the desired flow temperature is influenced (corrected) by one or


more parameters, it is indicated by a small line with arrow-down,
arrow-up or double-arrow:

Arrow-down:
The parameter in question reduces the desired flow temperature.

Arrow-up:
The parameter in question increases the desired flow temperature.

Double-arrow:
The parameter in question creates an override (e.g. Holiday).

Straight line:
No active influence.

In the example, the arrow in the symbol points downwards for


'Room lim.'. This means that the actual room temperature is
higher than the desired room temperature which again results in a
decrease of the desired flow temperature.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 55


Installation Guide ECL Comfort 310, application A376

3.6 Manual control


This section describes the function in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application
related. They might differ from the displays in your application.

It is possible to manually control the installed components.


Manual control can only be selected in favorite displays in which
the symbols for the controlled components (valve, pump etc.) are
visible.
Action: Purpose: Examples:
Choose mode selector

Confirm
Controlled components Circuit selector
Choose manual mode

Confirm

Choose pump

Confirm

Switch ON the pump

Switch OFF the pump.

Confirm pump mode

Choose motorized control valve

Confirm During manual operation:


• All control functions are deactivated
Open the valve
• Output override is not possible
Stop opening the valve • Frost protection is not active

Close the valve

Stop closing the valve

Confirm valve mode When manual control is selected for one circuit, it is automatically
selected for all circuits!
To leave manual control, use the mode selector to select the
desired mode. Push the dial.

Manual control is typically used when commisioning the


installation. The controlled components, valve, pump etc., can be
controlled for correct function.

Manual control of 0 – 10 volt controlled actuator:


The actuator symbol has a value (in %) which can be changed. The %
value is corresponding to a voltage in the range 0 – 10 volt.

56 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

3.7 Schedule

3.7.1 Set your schedule

This section describes the schedule in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application
related. They might differ from the displays in your application.
In some applications, however, there might be more than one
schedule. Additional schedules can be found in ‘Common
controller settings’.

The schedule consists of a 7-day week:


M = Monday
T = Tuesday
W = Wednesday
T = Thursday
F = Friday
S = Saturday
S = Sunday

The schedule will day-by-day show you the start and stop times of
your comfort periods (heating / DHW circuits).

Changing your schedule:

Action: Purpose: Examples:


Choose 'MENU' in any of the overview
displays
Confirm

Confirm the choice 'Schedule'


Choose the day to change
Confirm* T
Go to Start1
Confirm
Adjust the time
Confirm
Go to Stop1, Start2 etc. etc.
Return to 'MENU'
Confirm
Choose 'Yes' or 'No' in 'Save'

Confirm

* Several days can be marked


Each circuit has its own schedule. To change to another circuit, go to
The chosen start and stop times will be valid for all the chosen days 'Home', turn the dial and choose the desired circuit.
(in this example Thursday and Saturday).

You can set max. 3 comfort periods a day. You can delete a comfort
period by setting start and stop times to the same value.
The start and stop times can be set in half-hourly (30 min. ) intervals.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 57


Installation Guide ECL Comfort 310, application A376

4.0 Settings overview

It is recommendable to make a note of any changed settings in the empty columns.

Setting ID Page Factory settings in circuit(s)


1 2 3
Heat curve 62 1.0
Desired T 1x004 64 *
Temp. min. (duct / flow / inlet temp. limit, min.) 1x177 64 *
Temp. max. (duct / flow / inlet temp. limit, max.) 1x178 64 *
Adapt. time (adaption time) 1x015 66 *
Infl. - max. (room / duct temp. limitation, max.) 1x182 66 *
Infl. - min. (room / duct temp. limitation, min.) 1x183 67 *
Con.T, re. T lim. (Constant temperature mode, return
1x028 70 *
temperature limitation)
DHW, ret. T limit 1x029 70 *
Limit (return temp. limitation) 1x030 71 *
High T out X1 (return temp. limitation, high limit, X-axis) 1x031 71 *
Low limit Y1 (return temp. limitation, low limit, Y-axis) 1x032 71 *
Low T out X2 (return temp. limitation, low limit, X-axis) 1x033 71 *
High limit Y2 (return temp. limitation, high limit, Y-axis) 1x034 72 *
Infl. - max. (return temp. limitation - max. influence) 1x035 72 *
Infl. - min. (return temp. limitation - min. influence) 1x036 72 *
Adapt. time (adaptation time) 1x037 73 *
Priority (priority for return temp. limitation) 1x085 73 *
Input type 1x109 75 OFF
Actual (actual flow or power) 75 OFF
Limit (limitation value) 1x111 75 *
Adapt. time (adaptation time) 1x112 76 *
Filter constant 1x113 76 *
Units 1x115 76 l/h
High limit Y2 (flow / power limitation, high limit, Y-axis) 1x116 77 *
Low limit Y1 (flow / power limitation, low limit, Y-axis) 1x117 77 *
Low T out X2 (flow / power limitation, low limit, X-axis) 1x118 77 *
High T out X1 (flow / power limitation, high limit, X-axis) 1x119 77 *
Auto saving (saving temp. dependent on outdoor temp.) 1x011 79 *
Boost 1x012 80 *
Ramp (reference ramping) 1x013 80 *
Optimizer (optimizing time constant) 1x014 81 *
Based on (optimization based on room / outdoor temp.) 1x020 81 *
Total stop 1x021 82 *
Pre-stop (optimized stop time) 1x026 82 *
Parallel operation 1x043 83 *
Summer, cut-out (limit for heating cut-out) 1x179 84 *
Actuator 1x024 87 GEAR
Open time 1x094 87 *
Close time 1x095 87 *
Tn (idle) 1x096 87 *

58 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Setting ID Page Factory settings in circuit(s)


1 2 3
Supply T (idle) 1x097 88 *
Auto tuning 1x173 88 *
Motor pr. (motor protection) 1x174 89 *
Xp (proportional band) 1x184 89 *
Xp actual 89
Tn (integration time constant) 1x185 90 *
M run (running time of the motorized control valve) 1x186 90 *
Nz (neutral zone) 1x187 91 *
Min. act. time (min. activation time gear motor) 1x189 91 *
ECA addr. (ECA address, choice of Remote Control Unit) 1x010 93 *
Demand offset 1x017 93 *
P exercise (pump exercise) 1x022 94 *
M exercise (valve exercise) 1x023 94 *
P post-run 1x040 94 *
P demand 1x050 95 *
DHW priority (closed valve / normal operation) 1x052 95 *
P frost T (circulation pump, frost protection temp.) 1x077 96 *
P heat T (heat demand) 1x078 96 *
Frost pr. T (frost protection temp.) 1x093 96 *
Ext. input (external override) 1x141 97 *
COM-
Ext. mode (external override mode) 1x142 98
FORT
Send desired T 1x500 100 *
Extended heat cut-out setting 1x395 102 *
Extended winter cut-out setting 1x399 102 *
S7 pressure 107
Low X 1x607 107 *
High X 1x608 107 *
Alarm high 1x614 108 *
Alarm low 1x615 108 *
Alarm time-out 1x617 108 *
Digital S8 109
Digital S15 109
Digital S16 109
Alarm value 1x636 109 *
Alarm time-out 1x637 109 *
Upper difference 1x147 110 *
Lower difference 1x148 110 *
Delay 1x149 110 *
Lowest temp. 1x150 111 *
Max. flow T (Maximum flow temperature) 1x079 111 *
Delay 1x080 111 *
Alarm overview, in general 111
Day 113
Start time 114 00:00

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 59


Installation Guide ECL Comfort 310, application A376

Setting ID Page Factory settings in circuit(s)


1 2 3
Duration 114 120 m
Desired T 114 *
CW consump. 115
Pulse value 1x513 115 *
Preset 1x514 115 *
Read- -
State 127
out
Baud (bits per second) 5997 127 300
Command 5998 128 NONE
M-bus address 6000 128 255
Type 6001 128 0
Scan time 6002 129 60 sec
Read- -
ID 129
out
Energy meter 1 (2, 3, 4, 5) Read-
129 0
out
Backlight (display brightness) 60058 130 5
Contrast (display contrast) 60059 130 3
Modbus addr. 38 130 1
ECL 485 addr. (master / slave address) 2048 131 15
Service Pin 2150 131 0
Ext. reset 2151 131 0
Language 2050 132 English
Room T Offset 135 0.0 K
RH offset (ECA 31 only) 135 0.0 %
Backlight (display brightness) 135 5
Contrast (display contrast) 136 3
Use as remote 136 *)
Slave addr. (Slave address) 136 A
Connection addr. (Connection address) 137 15
Override addr. (Override address) 137 OFF
Override circuit 138 OFF

60 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

5.0 Settings

5.1 Introduction to Settings


Descriptions of settings (parameter's functions) are divided into
groups as used in the ECL Comfort 210 / 310 controller's menu
structure. Examples: "Flow temperature", "Room limit" and so on.
Each group starts with a general explanation.

The descriptions of each parameter are in numeric order, related to


the parameter's ID numbers. You might come across differences
between the order in this Installation Guide and the ECL Comfort
210 / 310 controllers.
You might also come across navigation hints which are not present
in your application.

The note "See Appendix …" refers to the Appendix at the end
of this Installation Guide, where parameter's setting ranges and
factory settings are listed.

The navigation hints (for example MENU > Settings > Return limit
… ) cover multiple subtypes.

Some parameter descriptions refer to Duct or Flow or Inlet


temperature because the parameters in question are used in other
applications too.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 61


Installation Guide ECL Comfort 310, application A376

5.2 Flow temperature


Desired flow temperature
The ECL Comfort controller determines and controls the flow
temperature related to the outdoor temperature. This relationship °C
is called the heat curve.
110
The heat curve is set by means of 6 coordinate points. The desired 100 C
flow temperature is set at 6 pre-defined outdoor temperature 80
B

values. 60
A
40
The shown value for the heat curve is an average value (slope),
based on the actual settings. 20

-50 -40 -30 -20 -10 0 10 20


Outdoor Your
Desired flow temp.
temp. settings
A B C
-30 °C 45 °C 75 °C 95 °C
-15 °C 40 °C 60 °C 90 °C
-5 °C 35 °C 50 °C 80 °C
0 °C 32 °C 45 °C 70 °C
5 °C 30 °C 40 °C 60 °C
15 °C 25 °C 28 °C 35 °C

A: Example for floor heating


B: Factory settings Slope changes
C: Example for radiator heating (high demand)

Heat curve
Circuit Setting range Factory setting
1 0.1 ... 4.0 1.0

The heat curve can be changed in two ways:


1. The value of the slope is changed (see heat curve examples Coordinate changes
on next page)
2. The coordinates of the heat curve are changed

Change the value of the slope:


Push the dial to enter / change the slope value of the heat curve
(example: 1.0).

When the slope of the heat curve is changed by means of the slope
value, the common point for all heat curves will be a desired flow
temperature = 24.6 °C at an outdoor temperature = 20 °C

Change the coordinates:


Push the dial to enter / change the coordinates of the heat curve The calculated flow temperature can be influenced by the ‘Boost’ and
(example: -30,75). ‘Ramp’ functions etc.

The heat curve represents the desired flow temperatures at


different outdoor temperatures and at a desired room temperature Example:
of 20 °C.
Heat curve: 1.0
Desired flow temp.: 50 °C
If the desired room temperature is changed, the desired flow
Desired room temp.: 22 °C
temperature also changes:
Calculation (22–20) × 1.0 × 2.5 = 5
(Desired room T - 20) × HC × 2.5
Result:
where "HC" is the Heat Curve slope and "2.5" is a constant.
The desired flow temperature will be corrected from 50 °C to 55 °C.

62 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Choosing a heat curve slope

The heat curves represent the desired flow temperature at different outdoor temperatures and at a desired room temperature of 20 °C.

1.8 2.2 2.6 3.0 3.4


120

110
1.4
100

90
1.0
80

70
0.6
60

50

40 0.2

30

20

10

-30 -20 -10 0 10 20

The small arrows ( ) indicate 6 different outdoor temperature values at which you can change the heat curve.

The ECL Comfort 310 controls the DHW temperature according to


Actual DHW temp.
the desired flow temperature for example under the influence of
the return temperature.

The desired DHW temperature is set in the overview display.

50.3: Actual DHW temperature


50: Desired DHW temperature
Desired DHW
temp.

Parameters indicated with an ID no. like "1x607" mean a universal


parameter.
x stands for circuit / parameter group.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 63


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Flow temperature


MENU > Settings > Tank temperature

Desired T 1x004 Override mode


Circuit Setting range Factory setting When ECL Comfort is in Scheduled mode, a contact (switch) signal can
be applied to an input in order to override to Comfort, Saving, Frost
All * * Protection or Constant temperature. As long as the contact (switch)
signal is applied, the override is active.
When the ECL Comfort is in override mode, type "Const. T", the desired flow
temperature can be set.
A "Const. T" related return temperature limitation can also be set. See MENU
> Settings > Return limit > 'Con. T, ret. T lim.'

The "Desired T" value can be influenced by:


* See Appendix “Parameter ID overview”
• temp. max.
• temp. min.
• room temp. limit
• return temp. limit
• flow / power limit

MENU > Settings > Flow temperature


MENU > Settings > Inlet temperature

Temp. min. (duct / flow / inlet temp. limit, min.) 1x177 ‘Temp. min.’ is overruled if 'Total stop' is active in Saving mode or
'Cut-out' is active.
Circuit Setting range Factory setting
‘Temp. min.’ can be overruled by the influence from the return
All * * temperature limitation (see 'Priority').

* See Appendix “Parameter ID overview”

Set the min. duct / flow / inlet temperature for the system. The
desired duct / flow / inlet temperature will not be lower than this The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.
setting. Adjust the factory setting, if required.

MENU > Settings > Flow temperature


MENU > Settings > Inlet temperature

Temp. max. (duct / flow / inlet temp. limit, max.) 1x178 The setting of ‘heat curve’ is possible for heating circuits only.
Circuit Setting range Factory setting
All * *

* See Appendix “Parameter ID overview” The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.

Set the max. flow / duct / inlet temperature for the system. The
desired temperature will not be higher than this setting. Adjust
the factory setting, if required.

64 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

5.3 Room limit


The following section is a general description for Duct temperature
limitation and Room temperature limitation.
The actual application might not have both limitation types.

This section is only relevant if you have installed a duct / room


temperature sensor or a Remote Control Unit for utilizing the room
temperature signal.

In the following description is referred to "flow temperature" in


general. This can be air duct or inlet temperature too.

The controller adjusts the desired flow temperature to compensate


for the difference between the desired and the actual duct / room
temperature.

If the duct / room temperature is higher than the desired value, the
desired flow temperature can be reduced.

The 'Infl. -max.' (Influence, max. duct / room temp.) determines


how much the desired flow temperature should be reduced.

Use this influence type to avoid a too high duct / room temperature.
The controller will allow for free heat gains, i.e. solar radiation or
heat from a fire place etc.

If the duct / room temperature is lower than the desired value, the
desired flow temperature can be increased.

The 'Infl. -min.' (Influence, min. duct / room temperature)


determines how much the desired flow temperature should be
increased.

Use this influence type to avoid a too low duct / room temperature.
This could e.g. be caused by windy surroundings.

A typical setting will be -4.0 for 'Infl. -max.' and 4.0 for 'Infl. -min.'

Some parameter descriptions refer to "duct temperature" because


the parameter in question is used in other applications too.

Parameters indicated with an ID no. like "1x607" mean a universal


parameter.
x stands for circuit / parameter group.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 65


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Duct T limit


MENU > Settings > Room limit

Adapt. time (adaption time) 1x015 If your application key has a heat curve setting:
Circuit Setting range Factory setting The adaptation function can correct the desired room temperature
with max. 8 K x heat curve slope value.
All * *
Controls how fast the actual room / duct temperature adapts to the desired
room / duct temperature (I control).

If your application key does not have a heat curve setting:


* See Appendix “Parameter ID overview” The adaptation function can correct the desired flow temperature
with max. 8 K.
OFF: The control function is not influenced by the 'Adapt.
time'.
Minor The desired room / duct temperature is adapted quickly.
value:
Major The desired room / duct temperature is adapted slowly.
value:

MENU > Settings > Duct T limit Influence


MENU > Settings > Room limit

Infl. - max. (room / duct temp. limitation, max.) 1x182


‘Infl. - min.’ (min. limitation)
Circuit Setting range Factory setting
Desired room / duct
All * * temperature
Actual room / duct
Determines how much the desired flow / duct temperature will be influenced temperature
(decreased) if the actual room / duct temperature is higher than the desired ‘Infl. - max.’ (max. limitation)
room / duct temperature (P control).

* See Appendix “Parameter ID overview” The ‘Infl. - max.’ and 'Infl. - min.' determine how much the room / duct
temperature should influence the desired flow / duct temperature.
0.0: No influence
-2.0: Minor influence
-5.0: Medium influence
-9.9: Maximum influence
If the ‘Infl.’ factor is too high and / or the ‘Adapt. time’ too low, there is
a risk of unstable control.

Example 1 (application with heat curve value):


The actual room temperature is 2 degrees too high.
The ‘Infl. - max.’ is set to -4.0.
The heat curve slope is 1.8 (see 'Heat curve' in 'Flow temperature').
Result:
The desired flow temperature is changed by (2 x -4.0 x 1.8)
–14.4 degrees.

Example 2 (application, no heat curve value):


The actual room temperature is 3 degrees too high.
The ‘Infl. - max.’ is set to -4.0.
Result:
The desired flow temperature is changed by (3 x -4.0)
-12 degrees.

66 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Duct T limit


Example 1 (application with heat curve value):
MENU > Settings > Room limit
The actual room temperature is 2 degrees too low.
The ‘Infl. - min.’ is set to 4.0.
Infl. - min. (room / duct temp. limitation, min.) 1x183
The heat curve slope is 1.8 (see 'Heat curve' in 'Flow temperature').
Circuit Setting range Factory setting Result:
The desired flow temperature is changed by (2 x 4.0 x 1.8)
All * * 14.4 degrees.
Determines how much the desired flow / duct temperature will be influenced
(increased) if the actual room / duct temperature is lower than the desired
room / duct temperature (P control). Example 2 (application, no heat curve value):
The actual room temperature is 3 degrees too low.
The ‘Infl. - min.’ is set to 4.0.
* See Appendix “Parameter ID overview” Result:
The desired flow temperature is changed by (3 x 4.0)
9.9: Maximum influence 12 degrees.
5.0: Medium influence
2.0: Minor influence
0.0: No influence

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 67


Installation Guide ECL Comfort 310, application A376

5.4 Return limit


The return temperature limitation is based on the outdoor Return temperature limitation
temperature. Typically in district heating systems a higher return
temperature is accepted at a decrease in outdoor temperature. The °C

relationship between the return temperature limits and outdoor


temperature is set in two coordinates.
High limit Y2 60

The outdoor temperature coordinates are set in 'High T out X1'


and 'Low T out X2'. The return temperature coordinates are set in
'High limit Y2' and 'Low limit Y1'.
Low limit Y1 40
The controller automatically changes the desired flow temperature
to obtain an acceptable return temperature when the return Outdoor temp.
-15 15 °C
temperature falls below or gets higher than the calculated limit.
Low T out X2 High T out X1
This limitation is based on a PI regulation where P ('Infl.' factor)
responds quickly to deviations and I ('Adapt. time') responds
slower and over time removes the small offsets between the
desired and actual values. This is done by changing the desired
flow temperature. The calculated limit is shown in brackets ( ) in the monitoring display.
See the section "Monitoring temperatures and system components".

DHW circuit Influence

The return temperature limitation is based on a constant ‘Infl. - min.’ > 0


temperature value. ‘Limit’

The controller automatically changes the desired flow temperature ‘Infl. - max.’ > 0
to obtain an acceptable return temperature when the return Return temperature
temperature falls below or gets higher than the set limit.
‘Infl. - max.’ < 0
This limitation is based on a PI regulation where P ('Infl.' factor)
responds quickly to deviations and I ('Adapt. time') responds ‘Infl. - min.’ < 0
slower and over time removes the small offsets between the
desired and actual values. This is done by changing the desired
flow temperature.

If the ‘Infl.’ factor is too high and / or the ‘Adapt. time’ too low, there is
a risk of unstable control.

68 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Example, maximum return temperature limitation;


return temperature gets higher than limit

T = Temperature

Y = Temperature

X = Time

# 1 # = Return temperature
# 2 # = Return temperature limit
# 3 # = Desired flow temperature
# 4 # = Action point

Example, minimum return temperature limitation;


return temperature gets lower than limit

T = Temperature

Y = Temperature

X = Time

# 1 # = Return temperature
# 2 # = Return temperature limit
# 3 # = Desired flow temperature
# 4 # = Action point

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 69


Installation Guide ECL Comfort 310, application A376

Parameters indicated with an ID no. like "1x607" mean a universal


parameter.
x stands for circuit / parameter group.

MENU > Settings > Return limit

Con.T, re. T lim. (Constant temperature mode, return 1x028


temperature limitation)
Circuit Setting range Factory setting
All * *
The "Con. T, ret. T limit" is the return temperature limitation value when the
circuit is set to override mode type "Const. T" (= Constant temperature).

* See Appendix “Parameter ID overview”

Value: Set the return temperature limitation

Override mode
When ECL Comfort is in Scheduled mode, a contact (switch) signal can
be applied to an input in order to override to Comfort, Saving, Frost
Protection or Constant temperature. As long as the contact (switch)
signal is applied, the override is active.

MENU > Settings > Return limit

DHW, ret. T limit 1x029


Circuit Setting range Factory setting
All * *
When an addressed slave is active in DHW-tank heating / charging, the
return temperature limitation in the master can be set.

Notes:
• The master circuit must be set to react on the desired flow temperature
in the slave(s). See "Demand offset" (ID 11017). # 1 # = Master, example A266, address 15
# 2 # = Slave, example A237, address 9
• The slave(s) must be set to send its / their desired flow temperature to the
# 3 # = Slave, example A367, address 6
master. See "Send desired T" (ID 1x500).

* See Appendix “Parameter ID overview”

OFF: No influence from slaves. The return temperature Some examples of applications with DHW-tank heating / charging are:
limitation is related to settings in "Return limit".
• A217, A237, A247, A367, A377
Value: Return temperature limitation value when slave is in
DHW tank heating / charging operation.

70 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Return limit

Limit (return temp. limitation) 1x030


Circuit Setting range Factory setting
All * *
Set the return temperature value you accept for the system.

* See Appendix “Parameter ID overview”

When the return temperature falls below or gets higher than the
set value, the controller automatically changes the desired flow /
duct temperature to obtain an acceptable return temperature. The
influence is set in 'Infl. - max.' and 'Infl. - min.'.

MENU > Settings > Return limit


High T out X1 (return temp. limitation, high limit, X-axis) 1x031
Circuit Setting range Factory setting
All * *
Set the outdoor temperature value for the low return temperature limitation.

* See Appendix “Parameter ID overview”

The corresponding Y coordinate is set in 'Low limit Y1'.

MENU > Settings > Return limit


Low limit Y1 (return temp. limitation, low limit, Y-axis) 1x032
Circuit Setting range Factory setting
All * *
Set the return temperature limitation referring to the outdoor temperature
value set in 'High T out X1'.

* See Appendix “Parameter ID overview”

The corresponding X coordinate is set in 'High T out X1'.

MENU > Settings > Return limit


Low T out X2 (return temp. limitation, low limit, X-axis) 1x033
Circuit Setting range Factory setting
All * *
Set the outdoor temperature value for the high return temperature
limitation.

* See Appendix “Parameter ID overview”

The corresponding Y coordinate is set in 'High limit Y2'.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 71


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Return limit


High limit Y2 (return temp. limitation, high limit, Y-axis) 1x034
Circuit Setting range Factory setting
All * *
Set the return temperature limitation referring to the outdoor temperature
value set in 'Low T out X2'.

* See Appendix “Parameter ID overview”

The corresponding X coordinate is set in 'Low T out X2'.

MENU > Settings > Return limit


Example
The return limit is active above 20 °C.
Infl. - max. (return temp. limitation - max. influence) 1x035
The influence is set to 0.5.
Circuit Setting range Factory setting The actual return temperature is 2 degrees too high.
Result:
All * * The desired flow / duct temperature is changed by 0.5 x 2 = 1.0 degree.
Determines how much the desired flow / duct temperature will be influenced
if the return temperature is higher than the set limit.

* See Appendix “Parameter ID overview”

Influence higher than 0:


The desired flow / duct temperature is increased, when the return
temperature gets higher than the set limit.

Influence lower than 0:


The desired flow / duct temperature is decreased, when the return
temperature gets higher than the set limit.

MENU > Settings > Return limit


Example
Infl. - min. (return temp. limitation - min. influence) 1x036 The return limit is active below 50 °C.
The influence is set to -3.0.
Circuit Setting range Factory setting The actual return temperature is 2 degrees too low.
All * * Result:
The desired flow / duct temperature is changed by -3.0 x 2 = -6.0
Determines how much the desired flow / duct temperature will be influenced degrees.
if the return temperature is lower than the calculated limit.

* See Appendix “Parameter ID overview”

Influence higher than 0: Normally, this setting is 0 in district heating systems because a lower
The desired flow / duct temperature is increased, when the return return temperature is acceptable.
temperature gets below the calculated limit. Typically, this setting is higher than 0 in boiler systems to avoid a too
low return temperature (see also 'Infl. - max.').
Influence lower than 0:
The desired flow / duct temperature is decreased, when the return
temperature gets below the calculated limit.

72 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Return limit

Adapt. time (adaptation time) 1x037


Circuit Setting range Factory setting The adaptation function can correct the desired flow / duct
temperature with max. 8 K.
All * *
Controls how fast the return temperature adapts to the desired return
temperature limit (Integration control).

* See Appendix “Parameter ID overview”

OFF: The control function is not influenced by the ‘Adapt.


time’.
Minor The desired temperature is adapted quickly.
value:
Major The desired temperature is adapted slowly.
value:

MENU > Settings > Return limit


Priority (priority for return temp. limitation) 1x085
Circuit Setting range Factory setting If you have a DHW application:
Please also see ‘Parallel operation’ (ID 11043).
All * *
Choose whether the return temperature limitation should overrule the set
min. flow temperature ‘Temp. min.’ .

* See Appendix “Parameter ID overview” If you have a DHW application:


When dependent parallel operation is in function:
OFF: The min. flow temperature limit is not overruled. • Desired flow temperature for the heating circuit will be minimum
ON: The min. flow temperature limit is overruled. limited, when "Priority for return temperature" (ID 1x085) is set
to OFF.
• Desired flow temperature for the heating circuit will not be
minimum limited, when "Priority for return temperature"
(ID 1x085) is set to ON.

The return temperature limitation for the DHW circuit is based on the
setting in 'Limit (return temp. limitation)'.
The influence factors are set in heating circuit 1.

If the return temperature limitation value in heating circuit 1 is higher


than the return temperature limitation value in the DHW circuit, the
highest value is used.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 73


Installation Guide ECL Comfort 310, application A376

5.5 Flow / power limit


Heating circuit

A flow or energy meter can be connected (M-bus signal) to the ECL Flow / power limitation
controller in order to limit the flow or consumed power.

The flow / power limitation can be based on the outdoor


temperature. Typically, in district heating systems a higher flow or
High limit Y2
power is accepted at lower outdoor temperatures.

The relationship between the flow or power limits and the outdoor
temperature is set in two coordinates.
Low limit Y1
The outdoor temperature coordinates are set in 'High T out X1'
and 'Low T out X2'. Outdoor temp.
-15 15 °C

The flow or power coordinates are set in 'Low limit Y1' and 'High Low T out X2 High T out X1
limit Y2'. Based on these settings, the controller calculates the
limitation value.
Flow / power
When the flow / power gets higher than the calculated limit, the limitation Limit
controller gradually reduces the desired flow temperature to obtain
an acceptable max. flow or power consumption.

°C

Desired flow
temp.

Time

If the ‘Adapt. time’ is too high, there is a risk of unstable control.

DHW circuit
Flow / power
A flow or energy meter can be connected (M-bus signal) to the ECL limitation Limit
controller in order to limit the flow or consumed power.

When the flow / power gets higher than the calculated limit, the
controller gradually reduces the desired flow temperature to obtain
an acceptable max. flow or power consumption.
°C

Desired DHW
temp.

Time

The parameter 'Units' (ID 1x115) has a reduced setting range when
the flow / energy signal comes via M-bus.

74 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Pulse based signal for flow / energy, applied to input S7


For monitoring:
Frequency range is 0.01 - 200 Hz

For limitation:
Minimum frequency is recommended to be 1 Hz in order to have a
stable control. Furthermore, the pulses must appear regularly.

Parameters indicated with an ID no. like "1x607" mean a universal


parameter.
x stands for circuit / parameter group.

MENU > Settings > Flow / power limit

Input type 1x109


Circuit Setting range Factory setting Flow or power limitation is based on M-bus signal (ECL Comfort 310
controllers only).
EM1 ... EM5 / OFF OFF
Choice of M-bus signal from energy meter number 1 ... 5. Only possible
in ECL Comfort 310.

OFF: No M-bus signal acquired.


EM1 ... EM5: Energy meter number.

MENU > Settings > Flow / power limit

Actual (actual flow or power)


Circuit Setting range Factory setting
All
The value is the actual flow or power based on the signal from flow / energy
meter.

MENU > Settings > Control par., fan


MENU > Settings > Flow / power limit
Limit (limitation value) 1x111
Circuit Setting range Factory setting
All * *
This value is in some applications a calculated limitation value, based on the
actual outdoor temperature.
In other applications the value is a selectable limitation value.

* See Appendix “Parameter ID overview”

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 75


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Flow / power limit


Adapt. time (adaptation time) 1x112
Circuit Setting range Factory setting If the ‘Adapt. time’ is too low, there is a risk of unstable control.

All * *
Controls how fast the flow / power limitation adapts to the desired
limitation.

* See Appendix “Parameter ID overview”

OFF: The control function is not influenced by the ‘Adapt.


time’.
1: The desired temperature is adapted quickly.
50: The desired temperature is adapted slowly.

MENU > Settings > Control par., fan


MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Flow / power limit
MENU > Settings > Refill tank
MENU > Settings > S7 (S8, S9, S10) pressure
Filter constant 1x113
Circuit Setting range Factory setting
All * *
The value of the filter constant determines the dampening of the measured
value.
The higher the value, the more dampening.
By this, a too quick change of the measured value can be avoided.

* See Appendix “Parameter ID overview”

Minor Lower dampening


value:
Major Higher dampening
value:

MENU > Settings > Flow / power limit

Units 1x115
Circuit Setting range Factory setting List for setting range of 'Units':
l/h
See the list l/h m³/h
kW
Choice of units for measured values.
MW
GW
Flow values are expressed as l/h or m³/h
Power values are expressed as kW, MW or GW.

76 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Flow / power limit


High limit Y2 (flow / power limitation, high limit, Y-axis) 1x116
Circuit Setting range Factory setting
All * *
Set the flow / power limitation referring to the outdoor temperature set
in 'Low T out X2'.

* See Appendix “Parameter ID overview”

The corresponding X coordinate is set in 'Low T out X2'.

MENU > Settings > Flow / power limit


Low limit Y1 (flow / power limitation, low limit, Y-axis) 1x117

Circuit Setting range Factory setting The limitation function can overrule the set 'Temp. min' of the desired
flow temperature.
All * *
Set the flow / power limitation referring to the outdoor temperature set in
'High T out X1'.

* See Appendix “Parameter ID overview”

The corresponding X coordinate is set in 'High T out X1'.

MENU > Settings > Flow / power limit


Low T out X2 (flow / power limitation, low limit, X-axis) 1x118
Circuit Setting range Factory setting
All * *
Set the outdoor temperature value for the high flow / power limitation.

* See Appendix “Parameter ID overview”

The corresponding Y coordinate is set in 'High limit Y2'.

MENU > Settings > Flow / power limit


High T out X1 (flow / power limitation, high limit, X-axis) 1x119
Circuit Setting range Factory setting
All * *
Set the outdoor temperature value for the low flow / power limitation.

* See Appendix “Parameter ID overview”

The corresponding Y coordinate is set in 'Low limit Y1'.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 77


Installation Guide ECL Comfort 310, application A376

5.6 Optimization
The section "Optimization" describes specific application related
issues.

The parameters 'Auto saving', 'Boost', 'Optimizer', 'Total stop' are all
related to heating mode only.

'Summer, cut-out' determine, at rising outdoor temperature, the


stop of heating.

Parameters indicated with an ID no. like "1x607" mean a universal


parameter.
x stands for circuit / parameter group.

78 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Optimization


Auto saving (saving temp. dependent on outdoor temp.) 1x011
Circuit Setting range Factory setting
All * *
Below the set value for the outdoor temperature, the saving temperature
setting has no influence. Above the set value for the outdoor temperature,
the saving temperature relates to the actual outdoor temperature. The
function is relevant in district heating installations in order to avoid a big
change in the desired flow temperature after a saving period.

* See Appendix “Parameter ID overview”

OFF: The saving temperature does not depend on the


outdoor temperature; the reduction is 100%.
X = Outdoor temperature (°C)
Value: The saving temperature depends on the outdoor
temperature. When the outdoor temperature is above Y = Desired room temperature (°C)
10 °C, the reduction is 100%. The lower the outdoor #1# = Desired room temperature (°C), Comfort mode
temperature, the less the temperature reduction.
Below the set value, the saving temperature setting #2# = Desired room temperature (°C), Saving mode
has no influence. #3# = Auto saving temperature (°C), ID 11011

Comfort temperature: The desired room temperature in


Comfort mode
Saving temperature: The desired room temperature in Saving Example:
mode Actual outdoor temperature (T.out): –5 °C

The desired room temperatures for Comfort and Saving modes Desired room temperature setting in Comfort mode: 22 °C
are set in the display overviews. Desired room temperature setting in Saving mode: 16 °C
Setting in ‘Auto saving’: –15 °C
The condition for the outdoor temperature influence:
T.out.influence = (10 - T.out) / (10 - setting) =
(10 - (-5)) / (10 - (-15)) =
15 / 25 = 0,6
The corrected desired room temperature in Saving mode:
T.room.ref.Saving + (T.out.influence x (T.room.ref.Comfort -
T.room.ref.Saving))
16 + (0,6 x (22 - 16)) = 19,6 °C

X = Outdoor temperature (°C)


Y = Desired room temperature (°C)

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 79


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Optimization


Boost 1x012
Circuit Setting range Factory setting
All * *
Shortens the heating-up period by increasing the desired flow temperature
by the percentage you set.

* See Appendix “Parameter ID overview”

OFF: The boost function is not active.


Value: The desired flow temperature is increased temporarily
with the set percentage.

In order to shorten the heating-up period after a saving


temperature period, the desired flow temperature can be increased
temporarily (max. 1 hour). At optimizing the boost is active in the
optimization period ('Optimizer').

If a room temperature sensor or an ECA 30 / 31 is connected, the


boost stops when the room temperature is reached.

MENU > Settings > Optimization Temp. °C


Ramp (reference ramping) 1x013

Circuit Setting range Factory setting


All * *
The time (minutes) in which the desired flow temperature increases
gradually to avoid load peaks in the heat supply.
Time (min.)
* See Appendix “Parameter ID overview”
Ramping time
OFF: The ramping function is not active.
Value: The desired flow temperature is increased gradually with
the set minutes.

In order to avoid load peaks in the supply network, the flow


temperature can be set to increase gradually after a period with
saving temperature. This causes the valve to open gradually.

80 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Optimization Table I:


Optimizer (optimizing time constant) 1x014 Left digit Heat accumulation of the System type
Circuit Setting range Factory setting building
1- light Radiator
All * * systems
2- medium
Optimizes the start and stop times for the comfort temperature period to
obtain the best comfort at the lowest energy consumption. 3- heavy
The lower the outdoor temperature, the earlier the heating cut-in. The lower
the outdoor temperature, the later the heating cut-out.
4- medium Floor heating
The optimized heating cut-out time can be automatic or disabled. The systems
5- heavy
calculated start and stop times are based on the setting of the optimizing
time constant.
Table II:
Adjust the optimizing time constant. Right digit Dimensioning temperature Capacity
The value consists of a two digit number. The two digits have the -0 -50 °C large
following meaning (digit 1 = Table I, digit 2 = Table II). -1 -45 °C ·

OFF: No optimization. The heating starts and stops at the · · ·


times set in the schedule. -5 -25 °C normal
10 ... 59: See tables I and II.
· · ·

* See Appendix “Parameter ID overview” -9 -5 °C small

Dimensioning temperature:
The lowest outdoor temperature (usually determined by your system
designer in connection with the design of the heating system) at which
the heating system can maintain the designed room temperature.

Example
The system type is radiator, and the heat accumulation of the building
is medium.
The left digit is 2.
The dimensioning temperature is -25 °C, and the capacity is normal.
The right digit is 5.

Result:
The setting is to be changed to 25.

MENU > Settings > Optimization


Based on (optimization based on room / outdoor temp.) 1x020
Circuit Setting range Factory setting
All * *
The optimized start and stop time can be based on either room or outdoor
temperature.

* See Appendix “Parameter ID overview”

OUT: Optimization based on outdoor temperature. Use this


setting if the room temperature is not measured.
ROOM: Optimization based on room temperature, if measured.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 81


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Application Desired flow temp. °C


MENU > Settings > Optimization
Total stop = ON
Total stop 1x021
Circuit Setting range Factory setting
All * *
Decide whether you want a total stop during the saving temperature period.
‘Frost pr.’
Time
* See Appendix “Parameter ID overview”

OFF: No total stop. The desired flow temperature is reduced Desired flow temp. °C
according to: Total stop = OFF
• desired room temperature in saving mode
• auto saving
ON: The desired flow temperature is lowered to the set value
in ‘Frost pr.’ The circulation pump is stopped but frost
protection is still active, see 'P frost T'.
‘Frost pr.’
Time

The min. flow temperature limitation ('Temp. min.') is overruled when


'Total stop' is ON.

MENU > Settings > Optimization Example: Optimization of Comfort from 07:00 - 22:00
Pre-stop (optimized stop time) 1x026
Circuit Setting range Factory setting 07:00 22:00

All * * Schedule

Disable the optimized stop time. Pre-stop OFF

Pre-stop ON
* See Appendix “Parameter ID overview”

OFF: The optimized stop time is disabled.


ON: The optimized stop time is enabled.
Optimization start Optimization stop

82 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Optimization


Temp.
Parallel operation 1x043
°C
Circuit Setting range Factory setting Acceptable deviation
All * * Desired DHW temp.
Choose whether the heating circuit is to operate in dependence of the DHW
circuit. This function might be useful if an installation has limited power
or flow.
Actual DHW temp.
* See Appendix “Parameter ID overview”
Time

OFF: Independent parallel operation, i.e. the DHW and


the heating circuits operate independently of each
other. It makes no difference whether the desired DHW 100% Parallel operation with
temperature can be reached or not. parallel decreased heating temp.
Value: Dependent parallel operation, i.e. the desired heating operation
temperature depends on the DHW demand. Choose
how much the DHW temperature can drop before the
desired heating temperature has to be decreased.

If the actual DHW temperature deviates more than the set value, the
gear motor M2 in the heating circuit will gradually close to such an
extent that the DHW temperature stabilizes at the lowest acceptable
value.

In case the Parallel operation is active (a too low DHW temperature


and therefore a reduced heating circuit temperature), a slave's
temperature demand will not change the desired flow temperature in
the heating circuit.

When dependent parallel operation is in function:


• Desired flow temperature for the heating circuit will be minimum
limited, when "Priority for return temperature" (ID 1x085) is set
to OFF.
• Desired flow temperature for the heating circuit will not be
minimum limited, when "Priority for return temperature"
(ID 1x085) is set to ON.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 83


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Application


MENU > Settings > Heat cut-out
Temp. Actual outdoor temp. Accumulated outdoor temp.
MENU > Settings > Optimization

Summer, cut-out (limit for heating cut-out) 1x179


18 °C
Circuit Setting range Factory setting
All * *

* See Appendix “Parameter ID overview”

The heating can be switched OFF when the outdoor temperature is


higher than the set value. The valve closes and after the post-run Time
time, the heating circulation pump stops. ‘Temp. min.’ will be Heating ON Heating OFF Heating ON
overruled.

The heating system switches ON again when the outdoor


temperature and the accumulated (filtered) outdoor temperature
become lower than the set limit. The heating cut-out is only active when the controller mode is in
scheduled operation. When the cut-out value is set to OFF, there is
This function can save energy. no heating cut-out.

Set the value for outdoor temperature at which you want the
heating system to switch OFF.

84 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

5.7 Control parameters


Control of valves

A376.1, A376.2, A376.4, A376.9, A376.10:


The motorized control valves are controlled by means of 3-point or
"PWM-like" control signals.

A376.3:
The motorized control valves are controlled by means of 0 - 10
volt control signals.

Valve control:
The motorized control valve is opened gradually when the flow
temperature is lower than the desired flow temperature and vice
versa.
The water flow through the control valve is managed by means
of an electric actuator. The combination "actuator" and "control
valve" is also called motorized control valve. The actuator can in
this way gradually increase or decrease the flow in order to change
the supplied energy. Different types of actuators are available.

3-point controlled actuator:


The electric actuator contains a reversible gear-motor. Electric
"open" and "close" signals come from the electronic outputs of the
ECL Comfort controller in order to manage the control valve. The
signals are in the ECL Comfort controller expressed as "Arrow-up"
(open) and "Arrow-down" (close) and displayed at the valve symbol.
When the flow temperature (for example at S3) is lower than the
desired flow temperature, short open-signals come from the ECL
Comfort controller in order to gradually increase the flow. By this,
the flow temperature will align with the desired temperature.
Oppositely, when the flow temperature is higher than the desired
flow temperature, short close-signals come from the ECL Comfort
controller in order to gradually reduce the flow. Again, the flow
temperature aligns with the desired temperature.
Neither open-signals nor close-signals will come as long as the flow
temperature corresponds to the desired temperature.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 85


Installation Guide ECL Comfort 310, application A376

Thermo-hydraulic actuator, ABV

Danfoss thermo-actuator type ABV is a slow acting valve actuator.


Inside the ABV an electric heat coil will heat a thermostatic element
when an electric signal is applied. When heating the thermostatic
element it expands in order to manage the control valve.

Two basic types are available: ABV NC (Normal Closed) and ABV NO
(normal open). For example, ABV NC keeps a 2-port control valve
closed when no open-signals are applied.

Electric open-signals come from the electronic output of the ECL


Comfort controller in order to manage the control valve. When
open-signals are applied to the ABV NC, the valve gradually opens.

Open-signals are in the ECL Comfort controller expressed as


"Arrow-up" (open) and displayed at the valve symbol.

When the flow temperature (for example at S3) is lower than the
desired flow temperature, relatively long open-signals come from
the ECL Comfort controller in order to increase the flow. By this,
the flow temperature will over time be aligned with the desired
temperature.

Oppositely, when the flow temperature is higher than the desired


flow temperature, relatively short open-signals come from the ECL
Comfort controller in order to reduce the flow. Again, the flow
temperature aligns, over time, with the desired temperature.

The control of the Danfoss thermo-actuator type ABV uses a unique


designed algorithm and is based on the PWM principle (Pulse
Width Modulation), where the duration of the pulse determines
the management of the control valve. The pulses are repeated
each 10 sec.

As long as the flow temperature corresponds to the desired


temperature, the duration of the open-signals will remain constant.

0 - 10 volt controlled actuator:

This actuator type is indicated in the application diagrams with


an "A". This electric actuator contains a reversible gear-motor. A
control voltage between 0 and 10 volt comes from the extension
module ECA 32 in order to manage the control valve. The voltage in
the ECL Comfort controller is expressed as a % value and displayed
at the valve symbol. Example: 45 % corresponds to 4.5 volt. When
the flow temperature (for example at S3) is lower than the desired
flow temperature, the control voltage is gradually increased in
order to gradually increase the flow. By this, the flow temperature
will align with the desired temperature. The control voltage
remains on a constant value as long as the flow temperature
corresponds to the desired temperature. Oppositely, when the
flow temperature is higher than the desired flow temperature, the
control voltage is gradually reduced in order to reduce the flow.
Again, the flow temperature aligns with the desired temperature.

Parameters indicated with an ID no. like "1x607" mean a universal


parameter.
x stands for circuit / parameter group.

86 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Control par.


Actuator 1x024
Circuit Setting range Factory setting When selecting "ABV", the control parameters:

ABV / GEAR GEAR • Motor protection (ID 1x174)


• Xp (ID 1x184)
Selection of valve actuator type. • Tn (ID 1x185)
• M run (ID 1x186)
ABV: Danfoss type ABV (thermo actuator). • Nz (ID 1x187)
GEAR: Gear motor based actuator. • Min. act. time (ID 1x189)
are not considered.

MENU > Settings > Control par.


Open time 1x094
Circuit Setting range Factory setting
All * *
The ‘Open time’ is the forced time (in seconds) that it takes to open the
motorized control valve when a DHW draw-off (tapping) is detected (the
flow switch is activated). This function compensates for the delay before the
flow temperature sensor measures a change in temperature.

* See Appendix “Parameter ID overview”

MENU > Settings > Control par.


Close time 1x095
Circuit Setting range Factory setting
All * *
The ‘Close time’ is the forced time (in seconds) that it takes to close the
motorized control valve when a DHW draw-off (tapping) is stopped (the
flow switch is deactivated). This function compensates for the delay before
the flow temperature sensor measures a change in temperature.

* See Appendix “Parameter ID overview”

MENU > Settings > Control par.


Tn (idle) 1x096
Circuit Setting range Factory setting
All * *
When no DHW draw-off (tapping) is detected (the flow switch is deactivated),
the temperature is maintained at a low level (saving temperature). The
integration time ‘Tn (idle)’ can be set to obtain a slow but stable control.

* See Appendix “Parameter ID overview”

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 87


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Control par.


Supply T (idle) 1x097
Circuit Setting range Factory setting If the supply temperature sensor is not connected, the idle supply
temperature will be maintained at the DHW flow temperature sensor.
All * *
The ‘supply T (idle)’ is the supply temperature when there is no DHW
draw-off (tapping). When DHW draw-off is not detected (the flow switch
is deactivated), the temperature is maintained at a lower level (saving
temperature). Choose which temperature sensor is to maintain the saving
temperature.

* See Appendix “Parameter ID overview”

OFF: The saving temperature is maintained at the DHW flow


temperature sensor.
ON: The saving temperature is maintained at the supply
temperature sensor.

MENU > Settings > Control par. No. of Heat Constant DHW draw-off (l / min)
apartments transfer
Auto tuning 1x173
(kW)
Circuit Setting range Factory setting 1-2 30-49 3 (or 1 tap 25% open)
All * * 3-9 50-79 6 (or 1 tap 50% open)
Automatically determines the control parameters for the DHW control. 'Xp' 10-49 80-149 12 (or 1 tap 100% open)
'Tn' and 'M run' do not need to be set, when using auto tuning. 'Nz' must
be set. (or 1 tap 100% + 1 tap 50%
50-129 150-249 18
open)
130-210 250-350 24 (or 2 taps 100% open)
* See Appendix “Parameter ID overview”

OFF: Auto tuning is not activated.


ON: Auto tuning is activated.
In order to meet the summer- / winter variations, the ECL clock must
be set to the correct date for an successful auto tuning.
The auto tuning function automatically determines the control
parameters for DHW control. Thus you do not need to set the 'Xp', The motor protection function ('Motor pr.') has to be deactivated
'Tn' and 'M run', as they are automatically set when the auto tuning during auto tuning. During auto tuning the circulation pump for tap
function is set to ON. water must be switched off. This is done automatically if the pump is
controlled by the ECL controller.
Auto tuning is typically used in connection with the installation of
the controller, but it can be activated when needed, e.g. for an Auto tuning is only applicable in connection with valves that are
approved for auto tuning, i.e. the Danfoss types VB 2 and VM 2 with
extra check of the control parameters. split characteristic as well as logarithmic valves such as VF and VFS.

Before starting the auto tuning, the tapping flow should be


adjusted to the relevant value (see table).

If possible, any additional DHW consumption should be avoided


during the auto tuning process. Should the tapping load vary too
much, the auto tuning and controller will return to the default
settings.

Auto tuning is activated by setting the function to ON. When the


auto tuning is ended, the function is automatically converted to
OFF (default setting). This will be indicated in the display.

The auto tuning process takes up to 25 minutes.

88 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Control par.


MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
Recommended for duct systems with variable load.
Motor pr. (motor protection) 1x174
Circuit Setting range Factory setting
All * *
Prevents the controller from unstable temperature control (and resulting
actuator oscillations). This can occur at very low load. The motor protection
increases the lifetime of all involved components.

* See Appendix “Parameter ID overview”

OFF: Motor protection is not activated.


Value: Motor protection is activated after the set activation
delay in minutes.

MENU > Settings > Boiler


MENU > Settings > Control par.
MENU > Settings > Control par., cool.
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
MENU > Settings > Control par. 3
MENU > Settings > Control par., P circ.
MENU > Settings > Control par., P refill

Xp (proportional band) 1x184


Circuit Setting range Factory setting
All * *

* See Appendix “Parameter ID overview”

Set the proportional band. A higher value will result in a stable but
slow control of the flow / duct temperature.

MENU > Settings > Control par.


Xp actual
Circuit Setting range Factory setting
All Read-out only
‘Xp actual’ is the read-out of the actual Xp (proportional band) based on
the supply temperature. Xp is determined by settings related to the supply
temperature. Typically, the higher the supply temperature, the higher the Xp
must be in order to achieve a stable temperature control.

Xp setting range: 5 ... 250 K


Fixed supply temperature settings: 65 °C and 90 °C
Factory settings: (65,40) and (90,120)

This means that the ‘Xp’ is 40 K at 65 °C supply temperature, and


‘Xp’ is 120 K at 90 °C.

Set the desired Xp values at the two fixed supply temperatures.

If the supply temperature is not measured (the supply temperature


sensor is not connected), the Xp value at the setting 65 °C is used.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 89


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Boiler


MENU > Settings > Control par.
MENU > Settings > Control par., cool.
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
MENU > Settings > Control par. 3
MENU > Settings > Control par., P circ.
MENU > Settings > Control par., P refill
Tn (integration time constant) 1x185
Circuit Setting range Factory setting
All * *

* See Appendix “Parameter ID overview”

Set a high integration time constant (in seconds) to obtain a slow


but stable reaction to deviations.

A low integration time constant will make the controller react fast
but with less stability.

MENU > Settings > Boiler


MENU > Settings > Control par. How to calculate the running time of a motorized control valve
MENU > Settings > Control par., cool. The running time of the motorized control valve is calculated using
MENU > Settings > Control par. 1 the following methods:
MENU > Settings > Control par. 2 Seated valves

M run (running time of the motorized control valve) 1x186 Running time = Valve stroke (mm) x actuator speed (sec. / mm)

Circuit Setting range Factory setting Example: 5.0 mm x 15 sec. / mm = 75 sec.

All * * Rotating valves


Running time = Turning degrees x actuator speed (sec. / degr.)
‘M run’ is the time in seconds it takes the controlled component to move
from fully closed to fully open position. Example: 90 degr. x 2 sec. / degr. = 180 sec.

* See Appendix “Parameter ID overview”

Set the ‘M run’ according to the examples or measure the running


time by means of a stop watch.

90 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Boiler


MENU > Settings > Control par.
MENU > Settings > Control par., cool.
MENU > Settings > Control par., fan The neutral zone is symmetrical around the desired flow / duct
MENU > Settings > Control par., inlet temperature value, i.e. half the value is above and half the value is
MENU > Settings > Control par., outlet below this temperature.
MENU > Settings > Control par., P circ.
MENU > Settings > Control par., P refill
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
MENU > Settings > Control par. 3

Nz (neutral zone) 1x187


Circuit Setting range Factory setting
All * *
When the actual flow / duct temperature is within the neutral zone, the
controller does not activate the motorized control valve.

* See Appendix “Parameter ID overview”

Set the acceptable flow /duct temperature deviation.

Set the neutral zone to a high value if you can accept a high
variation in flow temperature.

MENU > Settings > Boiler Setting example Value x 20 ms


MENU > Settings > Control par.
MENU > Settings > Control par., cool. 2 40 ms
MENU > Settings > Control par. 1 10 200 ms
MENU > Settings > Control par. 2
50 1000 ms
Min. act. time (min. activation time gear motor) 1x189
Circuit Setting range Factory setting
All * *
The setting should be kept as high as acceptable to increase the
The min. pulse period of 20 ms (milliseconds ) for activation of the gear lifetime of the actuator (gear motor).
motor.

* See Appendix “Parameter ID overview”

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 91


Installation Guide ECL Comfort 310, application A376

If you want to tune the PI regulation precisely, you can use the following method:
• Set the ‘Tn’ (integration time constant) to its max. value (999 sec.).
• Decrease the value for the ‘Xp’ (proportional band) until the system starts hunting (i.e. gets unstable) with a constant amplitude (it
might be necessary to force the system by setting an extreme low value).
• Find the critical time period on the temperature recorder or use a stop watch.

Temp. Critical time period

Time
This critical time period will be characteristic for the system, and you can evaluate the settings from this critical period.
‘Tn’ = 0.85 x critical time period
‘Xp’ = 2.2 x proportional band value in the critical time period
If the regulation seems to be too slow, you can decrease the proportional band value by 10%. Make sure there is a consumption
when you set the parameters.

92 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

5.8 Application
The section "Application" describes specific application related
issues.

Parameters indicated with an ID no. like "1x607" mean a universal


parameter.
x stands for circuit / parameter group.

MENU > Settings > Application

ECA addr. (ECA address, choice of Remote Control Unit) 1x010

Circuit Setting range Factory setting The Remote Control Unit must be set accordingly (A or B).

All * *
Decides the room temperature signal transfer and communication with the
Remote Control Unit.

* See Appendix “Parameter ID overview”

OFF: No Remote Control Unit. Only room temperature sensor,


if any.
A: Remote Control Unit ECA 30 / 31 with address A.
B: Remote Control Unit ECA 30 / 31 with address B.

MENU > Settings > Application Temp. Setting in


‘Demand offset’
Demand offset 1x017

Circuit Setting range Factory setting


All * * Des. flow temp.,
circuit 1
The desired flow temperature in heating circuit 1 can be influenced by the
demand for a desired flow temperature from another controller (slave) or Des. flow temp.,
another circuit. circuit 2
Time
* See Appendix “Parameter ID overview”

OFF: The desired flow temperature in circuit 1 is not


influenced by the demand of any other controller (slave
or circuit 2).
Value: The desired flow temperature is increased by the set
value in ‘Demand offset’, if the demand of the slave / The function of ‘Demand offset’ can compensate for heat losses
circuit 2 is higher. between master and slave controlled systems.

When setting "Demand offset" to a value, the return temperature


limitation will react according to the highest limitation value (Heating
/ DHW).

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 93


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Application


P exercise (pump exercise) 1x022
Circuit Setting range Factory setting
All * *
Exercises the pump to avoid blocking in periods without heat demand.

* See Appendix “Parameter ID overview”

OFF: The pump exercise is not active.


ON: The pump is switched ON for 1 minute every third day at
noon (12:14 hours).

MENU > Settings > Application


M exercise (valve exercise) 1x023
Circuit Setting range Factory setting
All * *
Exercises the valve to avoid blocking in periods without heat demand.

* See Appendix “Parameter ID overview”

OFF: The valve exercise is not active.


ON: The valve opens for 7 minutes and closes for 7 minutes
every third day at noon (12:00 hours).

MENU > Settings > Application

P post-run 1x040
Circuit Setting range Factory setting
All * *
Heating applications:
The circulation pump in the heating circuit can be ON for a number of
minutes (m) after heating stop. Heating stop is when the desired flow
temperature gets lower than the setting in 'P heat T' (ID no. 1x078).

Cooling applications:
The circulation pump in the cooling circuit can be ON for a number of
minutes (m) after cooling stop. Cooling stop is when the desired flow
temperature gets higher than the setting in 'P cool T' (ID no. 1x070).

This P post-run function can utilize the remaining energy in for example a
heat exchanger.

* See Appendix “Parameter ID overview”

0: The circulation pump stops immediately after heating


or cooling stop.
Value: The circulation pump is ON for the set time after heating
or cooling stop.

94 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Application

P demand 1x050
Circuit Setting range Factory setting The circulation pump is always controlled according to frost protection
conditions.
All * *
The circulation pump in the master circuit can be controlled in relation to
the master circuit's demand or slave circuit's demand.

* See Appendix “Parameter ID overview”

Heating applications:
OFF: The circulation pump is ON when the desired flow
temperature in the heating circuit is higher than the
value set in 'P heat T'.
ON: The circulation pump is ON when the desired flow
temperature from slaves is higher than the value set in
'P heat T'.

Cooling applications:
OFF: The circulation pump is ON when the desired flow
temperature in the cooling circuit is lower than the value
set in 'P cool T'.
ON: The circulation pump is ON when the desired flow
temperature from slaves is lower than the value set in
'P cool T'.

MENU > Settings > Application


DHW priority (closed valve / normal operation) 1x052
Circuit Setting range Factory setting This setting must be considered if this controller is a slave.

All * *
The heating circuit can be closed when the controller acts as slave and when
DHW heating / charging is active in the master.

* See Appendix “Parameter ID overview”

OFF: The flow temperature control remains unchanged


during active DHW heating / charging in the master
controller.
ON: The valve in the heating circuit is closed* during active
DHW heating / charging in the master controller.
* The desired flow temperature is set to the value set in
‘Frost pr. T’

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 95


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Application


MENU > Settings > Fan / acc. control

P frost T (circulation pump, frost protection temp.) 1x077 Under normal conditions, your system is not frost protected if your
setting is below 0 °C or OFF.
Circuit Setting range Factory setting For water-based systems, a setting of 2 °C is recommended.
All * *
Frost protection, based on the outdoor temperature.
When the outdoor temperature gets below the set temperature value in ‘P
frost T’, the controller automatically switches ON the circulation pump (for
example P1 or X3) to protect the system. If the outdoor temperature sensor is not connected and the factory
setting has not been changed to 'OFF', the circulation pump is always
ON.
* See Appendix “Parameter ID overview”

OFF: No frost protection.


Value: Circulation pump is ON when the outdoor temperature
is below the set value.

MENU > Settings > Application


P heat T (heat demand) 1x078
Circuit Setting range Factory setting The valve is fully closed as long as the pump is not switched on.

All * *
When the desired flow temperature is above the set temperature in ‘P heat T’,
the controller automatically switches ON the circulation pump.

* See Appendix “Parameter ID overview”

Value: The circulation pump is switched ON when the desired


flow temperature is above the set value.

MENU > Settings > Application


MENU > Settings > Tank temperature

Frost pr. T (frost protection temp.) 1x093 The frost protection temperature can also be set in your favorite
display when the mode selector is in frost protection mode.
Circuit Setting range Factory setting
All * *
Set the desired flow temperature at temperature sensor S3 to protect the
system against frost (at heating cut-out, total stop etc.).
When the temperature at S3 gets lower than the setting, the motorized
control valve opens gradually.

* See Appendix “Parameter ID overview”

96 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Override mode functions: Example: Connection of an override switch

The following settings describe the function in general for the ECL
Comfort 210 / 310 series. The explained modes are typical and not
application related. They might differ from the override modes
in your application.

MENU > Settings > Application

Ext. input (external override) 1x141

Circuit Setting range Factory setting


All * *
Choose the input for 'Ext. input' (external override). By means of a switch
the controller can be overridden to ‘Comfort’, 'Saving', 'Frost protection' or
'Constant temperature' mode.

* See Appendix “Parameter ID overview” Example: Connection of an override relay

OFF: No inputs have been selected for external override.


S1 ... S16: Input selected for external override.

If S1... S6 is chosen as override input, the override switch must have


gold-plated contacts.
If S7 ... S16 is chosen as override input, the override switch can be a
standard contact.

See the drawings for connection examples of override switch and


override relay to input S8.

Choose only an unused input for override. If an already used input is


applied for override, the functionality of this input is also neglected.

See also ‘Ext. mode’.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 97


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Application

Ext. mode (external override mode) 1x142


Circuit Setting range Factory setting See also ‘Ext. input’.

COMFORT / SAVING / COMFORT


FROST PR. / CONST. T Example: Override to Comfort mode
The mode override can be activated for Saving, Comfort, Frost pr. or
Constant T mode.
For override, the controller mode must be in scheduled mode.

Choose an override mode:


SAVING: The circuit in question is in saving mode when the
override switch is closed.
COMFORT: The circuit in question is in comfort mode when the
override switch is closed.
FROST PR.: The heating or DHW circuit closes, but is still frost
protected.
CONSTANT T: The circuit in question controls a constant
temperature *) # 1 # = Override switch (not activated / activated)
# 2 # = Function mode (Schedule / Comfort)
*) See also 'Desired T' (1x004), setting of desired flow # 3 # = Time
temperature (MENU > Settings > Flow temperature)

See also ' Con. T, ret. T lim.' (1x028), setting of return Example: Override to Saving mode
temperature limitation (MENU > Settings > Return
limit)

The process diagrams show the functionality.

# 1 # = Override switch (not activated / activated)


# 2 # = Function mode (Schedule / Saving)
# 3 # = Time

The result of override to 'Saving' mode depends on the setting in


'Total stop'.
Total stop = OFF: Heating reduced
Total stop = ON: Heating stopped

98 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Example: Override to Frost protection mode

# 1 # = Override switch (not activated / activated)


# 2 # = Function mode (Schedule / Frost pr.)
# 3 # = Time

Example: Override to Constant temperature mode

# 1 # = Override switch (not activated / activated)


# 2 # = Function mode (Schedule / Const. T)
# 3 # = Time

The "Const. T" value can be influenced by:


• temp. max.
• temp. min.
• room temp. limit
• return temp. limit
• flow / power limit

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 99


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Application

Send desired T 1x500


Circuit Setting range Factory setting In the master controller, 'Demand offset' must be set to a value in order
to react on a desired flow temperature from a slave controller.
All * *
When the controller acts as a slave controller in a master / slave system,
information about the desired flow temperature can be sent to the master
controller via the ECL 485 bus.
When the controller acts as a slave, its address must be 1, 2, 3 ... 9 in
order to send the desired temperature to the master (see the section
* See Appendix “Parameter ID overview” ‘Miscellaneous’, ‘Several controllers in the same system’).

OFF: Information about the desired flow temperature is not


sent to the master controller.
ON: Information about the desired flow temperature is sent
to the master controller.

100 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

5.9 Heat cut-out

MENU > Settings > Heat cut-out

The setting “Summer cut-out” under “Optimization” for the heating


circuit in question determines a heating cut-out when the outdoor
temperature exceeds the set value.

A filtering constant for calculating the accumulated outdoor


temperature is internally set to a value of "250". This filtering
constant represents an average building with solid outer and inner
walls (bricks).

An option for differentiated cut-out temperatures, based on a


set summer period, can be utilized in order to avoid discomfort
at falling outdoor temperature. Furthermore, separate filtering
constants can be set.

The factory set values for Summer period start and Winter period
start are set to same date: May, 20 (Date = 20, Month = 5).
This means:

• "Differentiated cut-out temperatures" are disabled (not active)


• Separate "Filtering constant" values are disabled (not active)

In order to enable differentiated

• cut-out temperature based on summer / winter period


• filtering constants

the start dates for the periods must be different.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 101


Installation Guide ECL Comfort 310, application A376

5.9.1 Differentiated heat cut-out

To set differentiated cut-out parameters for a heating circuit for


“Summer” and “Winter” go to “Heat cut-out”:
(MENU > Settings > Heat cut-out)

This function is active when the dates for “Summer” and “Winter”
are different in the “Heat cut-out” menu.

Parameters indicated with an ID no. like "1x607" mean a universal


parameter.
x stands for circuit / parameter group.

Extended heat cut-out setting


Parameter ID Setting range Factory
setting
Summer day 1x393 * *
Summer month 1x392 * *
Summer cut-out 1x179 * *
Summer filter 1x395 * *

* See Appendix “Parameter ID overview”

Extended winter cut-out setting


Parameter ID Setting range Factory
setting
Winter day 1x397 * *
Winter month 1x396 * *
Winter cut-out 1x398 * *
Winter filter 1x399 * *
The heating cut-out is only active when the controller mode is in
scheduled operation. When the cut-out value is set to OFF, there is
no heating cut-out.
* See Appendix “Parameter ID overview”

The above settings of the dates for the cut-out function are only
to be done in the heating circuit 1 and are valid for other heating
circuits in the controller as well, if applicable.

The cut-out temperatures as well as the filter constant are to be set


individually per heating circuit.

102 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

5.9.2 Summer/winter filter constant

The filter constant of 250 is applicable for average buildings. A


filter constant of 1 is close switching according to actual outdoor
temperature meaning low filtering (very “light” building).

A filter constant of 300 is then to be chosen if a big filtering is


needed (very heavy building).

For heating circuits where the heat cut-out is demanded according


to the same outdoor temperature for the whole year, but different
filtering is wanted, different dates have to be set in the “Heat
cut-out” menu enabling a selection of a filter constant different
from the factory setting.
These different values have to be set in both the “Summer” and
“Winter” menu.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 103


Installation Guide ECL Comfort 310, application A376

5.10 Alarm
The section "Alarm" describes specific application related issues.
Application A376 offers different types of alarms:

Type: Description:
1 Actual flow temperature differs from the desired
flow temperature
2 Disconnection or short-circuiting of a temperature
sensor or its connection
3 Max. flow temperature in heating circuit(s)
(A376.9, A376.10)
4 Activation of alarm input(s) (A376.9, A376.10)
5 Pressure alarm (A376.9, A376.10)

The alarm functions activate the alarm bell symbol.


The alarm functions activate A1:

A1: Application:
Relay 6 A376.1, A376.2, A376.3, A376.4
Relay 4 A376.9, A376.10

The alarm relay can activate a lamp, a horn, an input to an alarm


transmitting device etc.

The alarm symbol / relay is activated:


• (type 1, 3, 4 and 5) as long as the alarm reason is present
(automatic reset)
• (type 2) even if the alarm reason disappears again (manual
reset)

Alarm type 1:
If the flow temperature deviates more than the set differences from
the desired flow temperature, the alarm symbol / relay will be
activated after a set delay.
If the flow temperature becomes acceptable, the alarm symbol /
relay will be de-activated.

Alarm type 2:
Selected temperature sensors can be monitored.
Should the connection to the temperature sensor be disconnected,
short-circuited or the sensor gets defective, the alarm symbol
/ relay will be activated. In the "Raw input overview" (MENU >
Common controller settings > System > Raw input overview) the
sensor in question is marked and the alarm can be reset.

Alarm type 3:
If the flow temperature exceeds the alarm temperature value, the
circulation pump is switched OFF, the control valve closes and the
alarm symbol / relay will be activated. This safety function can, for
example, prevent a too high flow temperature in the floor circuit.
When the flow temperature gets 5 K below the alarm value, the
circulation pump will be switched ON, the control valve will operate
normally and the alarm symbol / relay will be de-activated.

Alarm type 4:
When the alarm input S8 (for circuit 1) or S15 (for circuit 2) or S16
(for circuit 3) is activated, the alarm symbol / relay will be activated
after a set delay.
When the alarm input S8 is de-activated, the alarm symbol / relay
will be de-activated.

104 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Alarm type 5:
When the pressure gets higher or lower than set limits, the alarm
symbol / relay will be activated after a set delay.
When the pressure gets acceptable, the alarm symbol / relay will
be de-activated.

When an alarm is activated, the appears in the right favorite


displays.

To find the reason for an alarm:


• select MENU
• select ‘Alarm’
• select ‘Alarm overview’. A "bell" will be shown at the alarm in
question.

Alarm overview (example):


2: Max. temp.
3: Temp. monitor
32: T sensor defect

The numbers in the 'Alarm overview' refer to the alarm number


in the Modbus communication.

To reset an alarm:
When the "bell" is present to the right of the alarm line, place the
cursor at the alarm line in question and press the dial.

To reset alarm 32:


MENU > Common controller settings > System > Raw input
overview: The sensor in question is marked and the alarm can be
reset.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 105


Installation Guide ECL Comfort 310, application A376

Alarm overview, lists:

Alarm Description: Alarm Sensor A376.1 A376.2 A376.3


no.: type: ref.:
2 Temp. monitor, circuit 1 1 S3 x x x
3 Temp. monitor, circuit 2 1 S9 x x x
4 Temp. monitor, circuit 3 1 S4 x x x
17 S7 pressure, circuit 1 5 S7
18 Digital S8, circuit 1 4 S8
19 Max. temp., circuit 1 3 S3
20 S14 pressure, circuit 2 5 S14
21 Digital S15, circuit 2 4 S15
22 Digital S16, circuit 3 4 S16
23 Max. temp., circuit 2 3 S9
32 T sensor defect 2 all x x x

Alarm Description: Alarm Sensor A376.4 A376.9 A376.10


no.: type: ref.:
2 Temp. monitor, circuit 1 1 S3 x x x
3 Temp. monitor, circuit 2 1 S9 x x x
4 Temp. monitor, circuit 3 1 S4 x x x
17 S7 pressure, circuit 1 5 S7 x x
18 Digital S8, circuit 1 4 S8 x x
19 Max. temp., circuit 1 3 S3 x x
20 S14 pressure, circuit 2 5 S14 x x
21 Digital S15, circuit 2 4 S15 x x
22 Digital S16, circuit 3 4 S16 x x
23 Max. temp., circuit 2 3 S9 x x
32 T sensor defect 2 all x x x

106 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

The scale and conversion settings for pressure sensors S7 and S14
are the same. The description is present for S7.

S7 pressure
Circuit Setting range Factory setting
1 0.0 ... 20.0 bar
Access to settings related to pressure measuring via input S7. Actual
measured pressure is shown. Conversion of input voltage to displayed
pressure.

The pressure is measured by means of a pressure transmitter. The


transmitter sends the measured pressure as a 0-10 V or a 4-20 mA
signal. The voltage signal can be applied directly to the input in
question. A current signal is converted by means of a resistor to a
voltage and then applied to the input. The measured voltage must
be converted to a pressure value by the controller.

The following procedure sets up the conversion:


Push the dial to see the graph. Enter the value sets for the 2 input
voltages (set in "Low X" and "High X") and displayed pressure (in
bar).

Pressure range: 0.0 ... 25.0 bar


Factory settings: 2, 0.0 (= 2 V / 0.0 bar) and 10, 2.3 (= 10 V / 2.3 bar)
This means that the ‘Pressure' is 0.0 bar at 2 V and 2.3 bar at 10 V.)

Typically, the higher the voltage, the higher the displayed pressure.

MENU > Alarm > Pressure Example: Relationship between input voltage and indicated pressure
Low X 1x607 Pressure (bar)
Circuit Setting range Factory setting
All * *
High Y 6.0
The pressure is measured by means of a pressure transmitter. The transmitter
sends the measured pressure as a 0-10 V or a 4-20 mA signal.

A voltage signal can be applied directly to input S7. A current signal is


converted by means of a resistor to a voltage and then applied to input S7.
The measured voltage on input S7 must be converted to a pressure value by 0.0
the controller. This and the following setting set up the conversion. Low Y
Volt
'Low X' defines the voltage value for the lowest pressure value ('Low Y'). 1 5

Low X High X
* See Appendix “Parameter ID overview”
This example shows that 1 volt corresponds to 0.0 bar and 5 volt correspond
to 6.0 bar.

MENU > Alarm > Pressure


High X 1x608
Circuit Setting range Factory setting
All * *
The measured voltage on input S7 must be converted to a pressure value.
High X defines the voltage value for the highest pressure value ('High Y').

* See Appendix “Parameter ID overview”

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 107


Installation Guide ECL Comfort 310, application A376

MENU > Alarm > Air quality


MENU > Alarm > Inlet pressure
MENU > Alarm > Outlet pressure
MENU > Alarm > Refill tank
MENU > Alarm > S7 (S8, S9, S10) pressure

Alarm high 1x614


Circuit Setting range Factory setting
All * *
When the measured value gets higher than the set value, the alarm will
be activated.

* See Appendix “Parameter ID overview”

Value: Set the alarm value

MENU > Alarm > Air quality


MENU > Alarm > Heat recovery
MENU > Alarm > Inlet pressure
MENU > Alarm > Outlet pressure
MENU > Alarm > Refill tank
MENU > Alarm > S7 (S8, S9, S10) pressure

Alarm low 1x615


Circuit Setting range Factory setting
All * *
When the measured value gets lower than the set value, the alarm will be
activated.

* See Appendix “Parameter ID overview”

Value: Set the alarm value

MENU > Alarm > Air quality


MENU > Alarm > Frost thermostat
MENU > Alarm > Heat recovery
MENU > Alarm > Inlet pressure
MENU > Alarm > Low pressure
MENU > Alarm > Outlet pressure
MENU > Alarm > Refill tank
MENU > Alarm > S7 (S8, S9, S10) pressure

Alarm time-out 1x617


Circuit Setting range Factory setting
All * *
The alarm is activated when the alarm reason has been present for a longer
time (in seconds) than the set value.

* See Appendix “Parameter ID overview”

Value: Set the alarm time-out

108 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Digital S8
Circuit Setting range Factory setting
1
Access to settings related to alarm input S8.

Digital S15
Circuit Setting range Factory setting
2
Access to settings related to alarm input S15.

Digital S16
Circuit Setting range Factory setting
3
Access to settings related to alarm input S16.

MENU > Alarm > Fire safety

Alarm value 1x636


Circuit Setting range Factory setting An active alarm is indicated by a in the display.

All * * S8 input status:


Activation of the alarm input can be done by means of closing or opening a MENU > Common controller > System > Raw input overview > S8:
contact. 0 = Input activated. 1 = input not activated

See also 'Alarm time-out', parameter 1x637.


* See Appendix “Parameter ID overview”

0: The alarm is activated when the contacts close.


1: The alarm is activated when the contacts open.

MENU > Alarm > Fire safety

Alarm time-out 1x637


Circuit Setting range Factory setting
All * *
The alarm is activated when the alarm reason has been present for a longer
time (in seconds) than the set value.

* See Appendix “Parameter ID overview”

Value: Set the alarm time-out

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 109


Installation Guide ECL Comfort 310, application A376

5.10.1 Temp. monitor.

MENU > Alarm > Charge T


Flow / duct temp. °C
MENU > Alarm > Temp. monitor

Upper difference 1x147


Upper difference (set
Circuit Setting range Factory setting value)
All * * Desired flow / duct
temp.
The alarm is activated if the actual flow / duct temperature increases more
than the set difference (acceptable temperature difference above the desired
flow / duct temperature). See also 'Delay'.

* See Appendix “Parameter ID overview”


Time
OFF: The related alarm function is not active.
Value: The alarm function is active if the actual temperature
gets above the acceptable difference.

MENU > Alarm > Charge T


Flow / duct temp. °C
MENU > Alarm > Temp. monitor

Lower difference 1x148


Lower difference (set
Circuit Setting range Factory setting value)
Desired flow / duct
All * * temp.
The alarm is activated if the actual flow / duct temperature decreases more
than the set difference (acceptable temperature difference below the desired
flow / duct temperature). See also 'Delay'.

Time
* See Appendix “Parameter ID overview”

OFF: The related alarm function is not active.


Value: The alarm function is active if the actual temperature
gets below the acceptable difference.

MENU > Alarm > Charge T


Temp.
MENU > Alarm > Temp. monitor
Delay 1x149 Flow temp.
Circuit Setting range Factory setting
All * *
Alarm limit
If an alarm condition from either 'Upper difference' or 'Lower difference' is
present for a longer time than the set delay (in minutes), the alarm function
is activated.
Time
* See Appendix “Parameter ID overview” Delay

Value: The alarm function will be activated if the alarm


condition remains after the set delay.

110 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

MENU > Alarm > Charge T


MENU > Alarm > Temp. monitor
Lowest temp. 1x150
If the cause of the alarm disappears, the alarm indication and output
Circuit Setting range Factory setting also disappear.

All * *
The alarm function will not be activated if the desired flow / duct
temperature is lower than the set value.

* See Appendix “Parameter ID overview”

MENU > Alarm > Max. temp.


Max. flow T (Maximum flow temperature) 1x079
Also observe the settings:
Circuit Setting range Factory setting * Delay' (ID 1x080)
All * *
The maximum acceptable flow temperature is set here.
When the flow temperature gets higher than the set value, the alarm symbol
/ relay go ON.
When the flow temperature gets 5 K below the set value, the alarm symbol /
relay go OFF.

* See Appendix “Parameter ID overview”

Value: Set the acceptable maximum flow temperature

MENU > Alarm > Max. temp.


Delay 1x080
Circuit Setting range Factory setting Also observe the settings:
* 'Max. flow T' (ID 1x079)
All * *
If an alarm condition from 'Max. flow T' is present for a longer time than the
set delay (in seconds), the alarm function is activated.

* See Appendix “Parameter ID overview”

Value: The alarm function will be activated if the alarm condition


remains after the set delay.

Alarm overview, in general


Circuit Setting range Factory setting
1
Access to overview showing the alarm number / alarm type. The alarm
number is entered into the alarm register and can be obtained from a
SCADA system.
Example: "3: Temp. monitor": If an alarm is activated because of conditions
in 'Temp. monitor' the alarm number 3 is placed in the alarm register.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 111


Installation Guide ECL Comfort 310, application A376

5.11 Alarm overview


MENU > Alarm > Alarm overview

This menu shows the alarm types, for example "2: Temp. monitor".
Resetting an alarm, in general:
The alarm has been activated if the alarm symbol is present to the
right of the alarm type. MENU > Alarm > Alarm overview:
Look for alarm symbol in specific line.

(Example: "2: Temp. monitor")


Move cursor to the line in question.
Push dial.

Alarm overview:

Alarm sources are listed in this overview menu.

Some examples:
"2: Temp. monitor"
"5: Pump 1"
"10: Digital S12"

Related to the examples, the numbers 2, 5 and 10 are used in the alarm
communication to the BMS / SCADA system.
Related to the examples, "Temp. monitor", "Pump 1" and "Digital S12"
are the alarm points.
Alarm numbers and alarm points might differ depending on actual
application.

112 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

5.12 Anti-bacteria
On selected days during the week the DHW temperature can
Desired temp.
be increased in order to neutralize bacteria in the DHW system.
The desired DHW temperature 'Desired T' (typically 80 °C) will be °C
present for the selected day(s) and duration.

The anti-bacteria function is not active in frost protection mode. 80

55

Time

Day / start time Duration

During the anti-bacteria process, the return temperature limitation is


not active.

MENU > Settings > Anti-bacteria


Day
Circuit Setting range Factory setting
Weekdays
Select (mark) the day(s) of the week where the anti-bacteria function must
be active.

M = Monday
T = Tuesday
W = Wednesday
T = Thursday
F = Friday
S = Saturday
S = Sunday

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 113


Installation Guide ECL Comfort 310, application A376

MENU > Settings > Anti-bacteria


Start time
Circuit Setting range Factory setting
00:00 ... 23:30 00:00
Set the start time for the anti-bacteria function.

MENU > Settings > Anti-bacteria


Duration
Circuit Setting range Factory setting
10 ... 600 m 120 m
Set the duration (minutes) for the anti-bacteria function.

MENU > Settings > Anti-bacteria


Desired T
Circuit Setting range Factory setting
* *
Set the desired DHW temperature for the anti-bacteria function.

* See Appendix “Parameter ID overview”

OFF: The anti-bacteria function is not active.


Value: Desired DHW temperature during the anti-bacteria
function period.

114 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

5.13 Water meter

Parameters indicated with an ID no. like "1x607" mean a universal


parameter.
x stands for circuit / parameter group.

CW consump.
Circuit Setting range Factory setting
3 Read-out only
The displayed value (actual value) is based on pulses from the cold water
meter and 'Pulse value' (13513).

MENU > Settings > Water meter


Pulse value 1x513
Circuit Setting range Factory setting
All * *
Setting of the value of each pulse from the water (flow) meter.
This parameter is used when the water meter is connected to the "Pulse 1"
on the ECA 32 module.

* See Appendix “Parameter ID overview”

MENU > Settings > Water meter


Preset 1x514
Circuit Setting range Factory setting
All * *
Is used for resetting the measured water consumption (registered by the
water meter).
Via the Modbus communication a value can be preset to a defined value, for
example if the water meter is replaced.

* See Appendix “Parameter ID overview”

OFF: Normal status.


ON: The registered amount of water is reset to 0 (zero). The
setting returns to OFF.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 115


Installation Guide ECL Comfort 310, application A376

6.0 Common controller settings

6.1 Introduction to ‘Common controller settings’


Some general settings which apply to the entire controller are
Circuit selector
located in a specific part of the controller.

To enter ‘Common controller settings’:

Action: Purpose: Examples:


Choose ‘MENU’ in any circuit

Confirm
Choose the circuit selector at the top
right corner in the display
Confirm

Choose ‘Common controller settings’

Confirm

116 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

6.2 Time & Date


It is only necessary to set the correct date and time in connection
with the first use of the ECL Comfort controller or after a power
break of more than 72 hours.

The controller has a 24 hour clock.

Aut. daylight (Daylight saving time changeover)


YES: The controller’s built-in clock automatically changes + /
- one hour on the standardized days for daylight saving
time changeover for Central Europe.

NO: You change manually between summer and winter time


by setting the clock backward or forward.

When controllers are connected as slaves in a master / slave system


(via ECL 485 communication bus), they will receive ‘Time & Date’ from
the master.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 117


Installation Guide ECL Comfort 310, application A376

6.3 Schedule output


Application A376.9 and A376.10 only:

Besides the week schedules for the circuits 1, 2 and 3, this week
schedule controls relay output R5.

The week schedule is set in the same way as the week schedules for
circuits 1, 2 and 3.

Comfort periods will activate the relay 5 in order to close the


contacts.

118 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

6.4 Holiday
There is a holiday program for each circuit and a holiday program
for the common controller.

Each holiday program contains one or more schedules. Each The holiday program in the ‘Common controller settings’ is valid for
schedule can be set to a start date and an end date. The set period all circuits. The holiday program can also be set individually in the
starts on the start date at 00.00 and stops on the end date at 00.00. heating or DHW circuits.

Selectable modes are Comfort, Saving, Frost protection or Comfort


7-23 (before 7 and after 23, the mode is scheduled).
How to set your holiday schedule:
The end date must be at least be one day later than the start date.
Action: Purpose: Examples:
Choose ‘MENU’

Confirm
Choose the circuit selector at the top
right corner in the display
Confirm
Choose a circuit or 'Common controller
settings'
Heating
DHW
Common controller settings
Confirm
Go to ‘Holiday’

Confirm

Choose a schedule

Confirm

Confirm choice of mode selector

Choose mode
. Comfort

∙ Comfort 7–23 7-23

. Saving

∙ Frost protection

Confirm
Enter the start time first and then the
end time
Confirm

Go to ‘Menu’

Confirm
Choose ‘Yes’ or ‘No’ in ‘Save’. Choose
the next schedule, if required

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 119


Installation Guide ECL Comfort 310, application A376

Holiday, specific circuit / Common Controller


Example 1:
When setting one holiday program in specific circuit and another
Circuit 1:
holiday program in Common Controller, a priority will be taken
Holiday set to "Saving"
into account:
Common Controller:
1. Comfort Holiday set to "Comfort"

2. Comfort 7 - 23 Result:
3. Saving As long as "Comfort" is active in Common Controller, circuit 1 will be in
"Comfort".
4. Frost protection
Example 2:

Circuit 1:
Holiday set to "Comfort"

Common Controller:
Holiday set to "Saving"

Result:
As long as "Comfort" is active in circuit 1, it will be in "Comfort".

Example 3:

Circuit 1:
Holiday set to "Frost protection"

Common Controller:
Holiday set to "Saving"

Result:
As long as "Saving" is active in Common Controller, circuit 1 will be
in "Saving".

The ECA 30 / 31 cannot override the holiday schedule of the


controller temporarily.

However, it is possible to make use of the following options from Energy-saving trick:
the ECA 30 / 31 when the controller is in scheduled mode: Use 'Going out' (the extended saving period) for airing purposes (e.g.
for ventilating the rooms by means of fresh air from open windows).

Day off

Holiday
Connections and setup procedures for ECA 30 / 31:
See section 'Miscellaneous'.
Relaxing (extended comfort period)

Going out (extended saving period)

Quick guide "ECA 30 / 31 to override mode":


1. Go to ECA MENU
2. Move cursor to "Clock" symbol
3. Select the "Clock" symbol
4. Choose and select one of 4 override functions
5. Below the override symbol: Set hours or date
6. Below hours / date: Set desired room temperature for the override
period

120 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

6.5 Input overview


This section describes the function in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application
related. They might differ from the displays in your application.

The input overview is located in the common controller settings.

This overview will always show you the actual temperatures in the
system (read-only).

"Outdoor acc. T" means "Accummulated outdoor temperature" and is


a calculated value in the ECL Comfort controller.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 121


Installation Guide ECL Comfort 310, application A376

6.6 Log
This section describes the function in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application
related. They might differ from the displays in your application.

The log function (temperature history) allows you to monitor the


logs of today, yesterday, the past 2 days as well as the past 4 days
for the connected sensors.

There is a log display for the relevant sensor, showing the measured
temperature.

The log function is only available in the 'Common controller


settings'.

Example 1:
1 day log for yesterday showing the development in outdoor
temperature during the past 24 hours.

Example 2:
Today’s log for the actual heating flow temperature as well as the
desired temperature.

Example 3:
Yesterday’s log for the DHW flow temperature as well as the desired
temperature.

122 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

6.7 Output override


This section describes the function in general for the ECL Comfort
210 / 310 series. The shown displays are typical and not application
related. They might differ from the displays in your application.

The output override is used to disable one or more of the controlled


components. This could among others be useful in a service
situation.

Action: Purpose: Examples: Controlled components Circuit selector


Choose 'MENU' in any of the overview
displays
Confirm
Choose the circuit selector at the top
right corner in the display
Confirm

Choose common controller settings

Confirm

Choose 'Output override'

Confirm "Manual control" has higher priority than "Output override".

Choose a controlled component M1, P1 etc.

Confirm
Adjust the status of the controlled
component: When the selected controlled component (output) is not ‘AUTO’, the
Motorized control valve: AUTO, STOP, ECL Comfort controller does not control the component in question
CLOSE, OPEN (pump or motorized control valve e.g.). Frost protection is not active.
Pump: AUTO, OFF, ON
Confirm status change

Remember to change the status back again as soon as an override


is not required any longer.
When output override of a controlled component is active the symbol
‘ ! ’ is shown to the right of the mode indicator in the enduser displays.

A376.3 only:
The motorized control valves M1, M2 and M3 are controlled by 0–10
volt (0–100%) signals. Each of them can be set to AUTO or ON.

AUTO: Normal control (0–100%)


ON: The 0–10 volt signal is set to the %-value, set below the
indication 'ON'.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 123


Installation Guide ECL Comfort 310, application A376

A376.9 and A376.10 only:


The 'Schedule' in *Common controller settings' controls the output
O1, which again controls the relay output R5.

124 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

6.8 Key functions

New application Erase application:


Removes the existing application. As
soon as the ECL key is inserted, another
application can be chosen.
Application Gives an overview over the application
and its subtypes of the ECL key in
question.
Factory setting System settings:
System settings are, among others,
communication set-up, display
brightness etc.
User settings:
User settings are, among others, desired
room temperature, desired DHW
temperature, schedules, heat curve,
limitation values etc.
Go to factory:
Restores the factory settings.
Copy To:
Copy direction
System settings
User settings
Start copying

A more detailed description of how to use the individual ‘Key


functions’ can also be seen in ‘Inserting the ECL application key’.

The “Key overview” does not inform — through ECA 30 / 31 — about


the subtypes of the application key.

Key inserted / not inserted, description:

ECL Comfort 210 / 310, controller versions lower than 1.36:


- Take out the application key; for 20 minutes
settings can be changed.
- Power up the controller without the
application key inserted; for 20 minutes
settings can be changed.

ECL Comfort 210 / 310, controller versions 1.36 and up:


- Take out the application key; for 20 minutes
settings can be changed.
- Power up the controller without the
application key inserted; settings cannot be
changed.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 125


Installation Guide ECL Comfort 310, application A376

6.9 System

6.9.1 ECL version

In ‘ECL version’ you will always be able to find an overview of the


Example, ECL version
data related to your electronic controller.

Please have this information available if you need to contact your


Danfoss sales organization concerning the controller.

Information about your ECL Application Key can be found in ‘Key


functions’ and ‘ Key overview’.
Code no.: The Danfoss sales and order no.
for the controller
Hardware: Hardware version of the
controller
Software: Software version of the
controller
Serial no.: Unique number for the
individual controller
Production week: Week no. and year (WW.YYYY)

6.9.2 Extension

ECL Comfort 310 only:


‘Extension’ will offer you information about additional modules, if
any. An example could be the ECA 32 module.

6.9.3 Ethernet

The ECL Comfort 310 (only) has a Modbus/TCP communication


interface that allows the ECL controller to be connected to an
Ethernet network. This allows remote access to the ECL 310
controller based on standard communication infrastructures.

In ‘Ethernet’ it is possible to set up the required IP addresses.

6.9.4 Portal config

The ECL Comfort 310 (only) has a Modbus/TCP communication


interface that allows the ECL controller to be monitored and
controlled via the ECL Portal.

ECL Portal related parameters are set here.

Documentation for ECL Portal: See ecl.portal.danfoss.com

126 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

6.9.5 Energy meter (heat-meter) and M-bus, general information

ECL 310 only

When using the Application Key in the ECL Comfort 310 / 310B, up
to 5 energy meters (heat-meters) can be connected to the M-bus Energy meter data acquisition from ECL Portal is possible without
connections. setting up the M-bus configuration.

Connection of energy meter can:


• limit the flow
• limit the power
• transfer energy meter data to the ECL Portal, via Ethernet, and /
or a SCADA system, via Modbus.

Many applications with control of heating, DHW or cooling circuit


have the possibility to react on energy meter data.
To verify if actual application key can be set to react on energy
meter data:
See Circuit > MENU > Settings > Flow / power.

The ECL Comfort 310 can always be used for monitoring purpose
of up to 5 energy meters.

The ECL Comfort 310 acts as an M-bus master and must be set to
communicate with connected energy meter(s).
See MENU > Common controller > System > M-bus config.

Technical info:
• The M-bus data are based on standard EN-1434.
• Danfoss recommends AC supplied energy meters in order to
avoid battery draining.

MENU > Common controller > System > M-bus config.

State Read-out
Circuit Setting range Factory setting The ECL Comfort 310 will return to IDLE when commands have been
completed.
- - - Gateway is used for read-out of energy meter via ECL Portal.

Information about the current M-bus activity.

IDLE: Normal state


INIT: The command for initialization has been activated
SCAN: The command for scanning has been activated
GATEW: The command Gateway has been activated

MENU > Common controller > System > M-bus config.

Baud (bits per second) 5997


Circuit Setting range Factory setting Typically, 300 or 2400 baud is used.
If ECL Comfort 310 is connected to the ECL Portal, a baud rate of 2400
- 300 / 600 / 1200 / 2400 300 is recommendable, provided the energy meter allows this.

The communication speed between ECL Comfort 310 and the connected
energy meter(s).

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 127


Installation Guide ECL Comfort 310, application A376

MENU > Common controller > System > M-bus config.

Command 5998
Circuit Setting range Factory setting Scan time can take up to 12 minutes.
When all energy meters are found, the command can be changed
- NONE / INIT / SCAN / GATEW NONE to INIT or NONE.

The ECL Comfort 310 is M-bus master. In order to verify connected energy
meters, different commands can be activated.

NONE: No command activated


INIT: Initialization is activated
SCAN: Scanning is activated in order to search for connected
energy meters. The ECL Comfort 310 detects the
M-bus addresses of up to 5 connected energy meters
and place these automatically in the "Energy meters"
section. The verified address is placed after "Energy
meter 1 (2, 3, 4, 5)"

GATEW: The ECL Comfort 310 acts as a gateway between


energy meters and ECL Portal. Used only for service.

MENU > Common controller > System > M-bus config.

M-bus address
Energy meter 1 (2, 3, 4, 5) 6000

Circuit Setting range Factory setting


- 0 - 255 255
The set or verified address of energy meter 1 (2, 3, 4, 5).

0: Normally not used


1 - 250: Valid M-bus addresses
251 - 254: Special functions. Use only M-bus address 254 when
one energy meter is connected.
255: Not used

MENU > Common controller > System > M-bus config.

Type
Energy meter 1 (2, 3, 4, 5) 6001
Data examples:
Circuit Setting range Factory setting
0:
- 0-4 0 Flow temp., return temp., flow, power, acc. volume, acc. energy.
Selecting data range from the M-bus telegram.
3:
Flow temp., return temp., flow, power, acc. volume, acc. energy,
0: Small data set, small units tariff 1, tariff 2.
1: Small data set, large units
See also the "Instructions, ECL Comfort 210 / 310, communication
2: Large data set, small units description" for further details.
3: Large data set, large units See also Appendix for detailed description of "Type".
4: Volume and energy data only
(example: HydroPort Pulse)

128 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

MENU > Common controller > System > M-bus config.

Scan time
Energy meter 1 (2, 3, 4, 5) 6002
If the energy meter is battery powered, the scan time should be set to
a high value to prevent a too fast battery draining.
Circuit Setting range Factory setting
Oppositely, if the flow / power limitation function is used in the ECL
- 1 - 3600 sec 60 sec Comfort 310, the scan time should be set to a low value in order to
have quick limitation.
Setting the scanning time for acquiring data of connected energy meter(s).

MENU > Common controller > System > M-bus config.

ID
Energy meter 1 (2, 3, 4, 5) Read-out

Circuit Setting range Factory setting


- - -

Information about the energy meter's serial no.

MENU > Common controller > System > Energy meters

Energy meter 1 (2, 3, 4, 5) Read-out


Circuit Setting range Factory setting
- 0-4 0
Information from actual energy meter about, for example, ID, temperatures,
flow / volume, power / energy.
The shown information depends on the settings made in the “M-bus config.”
menu.

6.9.6 Raw input overview

Measured temperatures, input status and voltages are displayed.

In addition, a detection of malfunctions can be chosen for activated


temperature inputs. The temperature sensor inputs have a measuring range from -60 ...
150 ° C.
Monitoring the sensors:
Choose the sensor which measures a temperature, for example the If a temperature sensor or its connection breaks, the value indication
S5. When the dial is pressed, a magnifying glass appears in the is " - - ".
selected line. The S5 temperature is now being monitored.
If a temperature sensor or its connection is short-circuited, the value
Alarm indication: indication is " - - - ".
Should the connection to the temperature sensor be disconnected,
short-circuited or the sensor itself be defective, the alarm function
is activated.

In the "Raw input overview" an alarm symbol is shown at the


defective temperature sensor in question.

Resetting the alarm:


Choose the sensor (S number) for which you want to clear the
alarm. Press the dial. The magnifying glass and alarm symbols
disappear.

When the dial is pressed again, the monitoring function is


reactivated.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 129


Installation Guide ECL Comfort 310, application A376

6.9.7 Display

Backlight (display brightness) 60058


Circuit Setting range Factory setting
0 ... 10 5

Adjust the brightness of the display.

0: Weak backlight.
10: Strong backlight.

Contrast (display contrast) 60059


Circuit Setting range Factory setting
0 ... 10 3

Adjust the contrast of the display.

0: Low contrast.
10: High contrast.

6.9.8 Communication

Modbus addr. 38
Circuit Setting range Factory setting
1 ... 247 1

Set the Modbus address if the controller is part of a Modbus network.

1 ... 247: Assign the Modbus address within the stated setting
range.

130 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

ECL 485 addr. (master / slave address) 2048


Circuit Setting range Factory setting
0 ... 15 15 The total cable length of max. 200 m (all devices incl. the internal ECL
485 communication bus) should not be exceeded.
This settting is relevant if more controllers are working in the same ECL Cable lengths of more than 200 m may cause noise sensibility (EMC).
Comfort system (connected via the ECL 485 communication bus) and / or
Remote Control Units (ECA 30 / 31) are connected.

0: The controller works as slave.


The slave receives information about the outdoor In a system with MASTER / SLAVE controllers, only one MASTER
temperature (S1), system time, and signal for DHW controller with address 15 is allowed.
demand in the master.
If by mistake more MASTER controllers are present in an ECL 485
1 ... 9: The controller works as slave. communication bus system, decide which controller is to be MASTER.
The slave receives information about the outdoor Change the address in the remaining controllers. However, the system
temperature (S1), system time, and signal for DHW will operate but not be stable with more than one MASTER controller.
demand in the master. The slave sends information
about the desired flow temperature to the master.
10 ... 14: Reserved.
15: The ECL 485 communication bus is active.
The controller is master. The master sends information In the MASTER controller, the address in ‘ECL 485 addr. (master / slave
about the outdoor temperature (S1) and system time. address)’, ID no. 2048, must always be 15.
Connected Remote Control Units (ECA 30 / 31) are
powered.

The ECL Comfort controllers can be connected via the ECL 485
communication bus to perform a larger system (the ECL 485
communication bus can connect to max. 16 devices).

Each slave must be configured with its own address (1 ... 9).

However, more slaves can have the address 0 if they only have to
receive information about outdoor temperature and system time
(listeners).

Service Pin 2150


Circuit Setting range Factory setting
0/1 0

This setting is only used in connection with set-up of Modbus


communication.

Not applicable for the time being and reserved for future use!

Ext. reset 2151


Circuit Setting range Factory setting
0/1 0

This setting is only used in connection with set-up of Modbus


communication.

0: Reset not activated.


1: Reset.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 131


Installation Guide ECL Comfort 310, application A376

6.9.9 Language

Language 2050
Circuit Setting range Factory setting
English / ‘Local’ English Local language is selected during installation. If you want to change to
another local language, the application must be reinstalled. However,
Choose your language. it is always possible to change between the local language and English.

132 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

7.0 Miscellaneous

7.1 ECA 30 / 31 setup procedures


ECA 30 (code no. 087H3200) is a remote control unit with built-in
room temperature sensor.

ECA 31 (code no. 087H3201) is a remote control unit with built-in


room temperature sensor and humidity sensor (relative humidity).

An external room temperature sensor can be connected to both


types to substitute the built-in sensor.
An external room temperature sensor will be recognized at ECA
30 / 31 power-up.

Connections: See the section 'Electrical connections'.

Max. two ECA 30 / 31 can be connected to one ECL controller


or a system (master-slave) consisting of several ECL controllers
connected on the same ECL 485 bus. In the master-slave system
only one of the ECL controllers is master. The ECA 30 / 31 can,
among others, be set to:

• monitor and set the ECL controller remotely


• measure the room temperature and (ECA 31) humidity
• extend comfort / saving period temporarily

After application upload in the ECL Comfort controller, the remote


control unit ECA 30 / 31 will after approx. one minute ask to 'Copy
application'.
Confirm this in order to upload the application to the ECA 30 / 31.

Menu structure
Part of the ECA 30 / 31 display in ECL mode:
The menu structure of ECA 30 / 31 is an "ECA MENU" and the ECL
menu, copied from the ECL Comfort controller.

The ECA MENU contains:

Part of the ECA 30 / 31 display in ECA mode:


• ECA settings
• ECA system
• ECA factory

ECA settings: Offset adjustment of the measured room


temperature.
If only the "ECA MENU" is shown, it can indicate that the ECA 30 / 31 is
Offset adjustment of relative humidity (ECA 31 only). not having correct communication address.
See ECA MENU > ECA system > ECA communication: ECL address.
ECA system: Display, communication, override settings and version In most cases the ECL address setting must be "15".
info.

ECA factory: Erase of all applications in the ECA 30 / 31, restore to


factory settings, reset of ECL address and firmware update.

Regarding ECA settings:


When ECA 30 / 31 is not used as remote unit, the offset adjustments
menu(s) are not present.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 133


Installation Guide ECL Comfort 310, application A376

The ECL menus are as described for the ECL controller.

Most of the settings done directly in the ECL controller can be done
via the ECA 30 / 31 too. All settings can be seen even if the application key is not inserted in
the ECL controller.
For changing settings, the application key must be inserted.

The Key overview (MENU > 'Common controller settings' > 'Key
functions') does not show the applications of the key.

The ECA 30 / 31 will display this information (an X on the ECA 30 / 31


symbol) if the application in the ECL controller does not comply with
the ECA 30 / 31:

In the example 1.10 is current version and 1.42 is desired version.

Display part of ECA 30 / 31:

This display indicates that an application has not been uploaded or the
communication to the ECL controller (master) is not working properly.
An X on the ECL controller symbol indicates wrong setup of
communication addresses.

Display part of ECA 30 / 31:


87H1495.10
Da nfos s

Newer versions of ECA 30 / 31 indicate the address number of the


connected ECL Comfort controller.
Address number can be changed in the ECA MENU.
A stand-alone ECL Controller has the address 15.

134 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

When ECA 30 / 31 is in ECA MENU mode, the date and measured


room temperature is displayed.

ECA MENU > ECA settings > ECA sensor

Room T Offset Example:


Setting range Factory setting 0.0 K
Room T offset:
–10.0 ... 10.0 K 0.0 K Displayed room temperature: 21.9 °C
The measured room temperature can be corrected with Room T offset: 1.5 K
a number of Kelvin. The corrected value is used by the
heating circuit in the ECL controller. Displayed room temperature: 23.4 °C

Minus
value: The indicated room temperature is lower.

0.0 K: No correction of the measured room temperature.

Plus The indicated room temperature is higher.


value:

ECA MENU > ECA settings > ECA sensor

RH offset (ECA 31 only) Example:


Setting range Factory setting
RH offset: 0.0 %
–10.0 ... 10.0 % 0.0 %
Displayed relative humidity: 43.4 %
The measured relative humidity can be corrected with a
RH offset: 3.5 %
number of %-values. The corrected value is used by the
application in the ECL controller. Displayed relative humidity: 46.9 %

Minus
value: The indicated relative humidity is lower.

0.0 %: No correction of the measured relative humidity.

Plus The indicated relative humidity is higher.


value:

ECA MENU > ECA system > ECA display

Backlight (display brightness)


Setting range Factory setting
0 ... 10 5
Adjust the brightness of the display.

0: Weak backlight.
10: Strong backlight.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 135


Installation Guide ECL Comfort 310, application A376

ECA MENU > ECA system > ECA display

Contrast (display contrast)


Setting range Factory setting
0 ... 10 3
Adjust the contrast of the display.

0: Low contrast.
10: High contrast.

ECA MENU > ECA system > ECA display

Use as remote
Setting range Factory setting
OFF / ON *) When set to OFF: The ECA menu shows date and time.
ECA 30 / 31 can act as a simple or normal remote control When set to ON: The ECA menu shows date and room temperature
for the ECL controller. (and for ECA 31 relative humidity).

OFF: Simple remote control, no room temperature signal.


ON: Remote control, room temperature signal is available.
*): Differently, depending on chosen application.

ECA MENU > ECA system > ECA communication

Slave addr. (Slave address)


Setting range Factory setting
A/B A For installation of an application in an ECL Comfort 210 / 310 controller
the 'Slave addr.' must be A.
The setting of 'Slave addr.' is related to the setting 'ECA
address' in the ECL controller.
In the ECL controller it is selected from which ECA 30 / 31
unit the room temperature signal is received.

A: If two ECA 30 / 31 are connected in the same ECL 485 bus system, the
The ECA 30 / 31 has the address A. 'Slave addr.' must be "A" in the one ECA 30 / 31 unit and "B" in the other.
B: The ECA 30 / 31 has the address B.

136 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

ECA MENU > ECA system > ECA communication

Connection addr. (Connection address)


Setting range Factory setting
1 … 9 / 15 15 An ECA 30 / 31 can in an ECL 485 bus system (master – slave) be set to
communicate, one by one, with all addressed ECL controllers.
Setting of the address to which ECL controller the
communication must run.

1 .. 9: Slave controllers.
Example:
15: Master controller.
Connection addr. = 15: The ECA 30 / 31 communicates with the
ECL master controller.
Connection addr. = 2: The ECA 30 / 31 communicates with the
ECL controller with address 2.

There must be a master controller present in order to broadcast time


and date information.

An ECL Comfort controller 210 / 310, type B (without display and dial)
cannot be assigned to the address 0 (zero).

ECA MENU > ECA system > ECA override

Override addr. (Override address)


Setting range Factory setting
OFF / 1 … 9 / 15 OFF
Extended saving mode:
The feature 'Override' (to extended comfort or saving
period or holiday) must be addressed to the ECL controller Extended comfort mode:
in question.
Override functions:
Holiday away from home:
OFF: Override not possible.
Holiday at home:
1 .. 9: Address of slave controller for override.

15: Address of master controller for override.

Override by means of settings in ECA 30 / 31 are cancelled if the ECL


Comfort controller goes into holiday mode or is changed to another
mode than scheduled mode.

The circuit in question for override in the ECL controller must be in


scheduled mode.
See also the parameter 'Override circuit'.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 137


Installation Guide ECL Comfort 310, application A376

ECA MENU > ECA system > ECA override

Override circuit
Setting range Factory setting
OFF / 1 … 4 OFF The circuit in question for override in the ECL controller must be in
scheduled mode.
The feature 'Override' (to extended comfort or saving See also the parameter 'Override addr.'.
period or holiday) must be addressed to the heating circuit
in question.

OFF: No heating circuit is selected for override.


Example 1:
1 … 4: The heating circuit number in question.
(One ECL controller and one ECA 30 / 31)
Override of heating Set 'Connection addr.' to Set 'Override
circuit 2: 15 circuit' to 2

Example 2:

(Several ECL controllers and one ECA 30 / 31)


Override of heating Set 'Connection addr.' to 6 Set 'Override
circuit 1 in ECL circuit' to 1
controller with the
address 6:

Quick guide "ECA 30 / 31 to override mode":


1. Go to ECA MENU
2. Move cursor to "Clock" symbol
3. Select the "Clock" symbol
4. Choose and select one of 4 override functions
5. Below the override symbol: Set hours or date
6. Below hours / date: Set desired room temperature for the override
period

ECA MENU > ECA system > ECA version

ECA version (read-out only), examples


Code no. 087H3200
Hardware A
Software 1.42
Build no. 5927
Serial no. 13579
Production week 23.2012

The ECA version information is useful in service situations.

138 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

ECA MENU > ECA factory > ECA clear apps.

Erase all apps. (Erase all applications)


Erase all applications which are in the ECA 30 / 31.
After erasing, the application can be uploaded again.
After the erase procedure, a pop-up in the display indicates "Copy
application". Choose "Yes".
NO: The erase procedure is not done. Hereafter the application is uploaded from the ECL controller. An
upload bar is shown.
YES: The erase procedure is done (await 5 sec.).

ECA MENU > ECA factory > ECA default

Restore factory
The ECA 30 / 31 is set back to factory settings.
Affected settings by the restore procedure:
• Room T offset
• RH offset (ECA 31)
• Backlight
• Contrast
• Use as remote
• Slave addr.
• Connection addr.
• Override addr.
• Override circuit
• Override mode
• Override mode end time

NO: The restore procedure is not done.

YES: The restore procedure is done.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 139


Installation Guide ECL Comfort 310, application A376

ECA MENU > ECA factory > Reset ECL addr.

Reset ECL addr. (Reset ECL address)


If none of the connected ECL Comfort controllers has the address
15, the ECA 30 / 31 can set all connected ECL controllers on the
ECL 485 bus back to address 15. The ECL 485 bus related address of the ECL controller is found:
MENU > 'Common controller settings' > 'System' > 'Communication' >
'ECL 485 addr.'
NO: The reset procedure is not done.

YES: The reset procedure is done (await 10 sec.).

The "Reset ECL addr." cannot be activated if one or more of the


connected ECL Comfort controllers has the address 15.

In a system with MASTER / SLAVE controllers, only one MASTER


controller with address 15 is allowed.

If by mistake more MASTER controllers are present in an ECL 485


communication bus system, decide which controller is to be MASTER.
Change the address in the remaining controllers. However, the system
will operate but not be stable with more than one MASTER controller.

ECA MENU > ECA factory > Update firmware

Update firmware
The ECA 30 / 31 can be updated with new firmware (software).
The firmware comes with the ECL application key, when the key
version is at least 2.xx. The ECA 30 / 31 automatically verifies if a new firmware is present on
the application key in the ECL Comfort controller.
If no new firmware is available, a symbol of the application key The ECA 30 / 31 is automatically updated at new application upload in
is displayed with an X. the ECL Comfort controller.
The ECA 30 / 31 is not automatically updated when connected to an
NO: The updating procedure is not done. ECL Comfort controller with uploaded application. A manual update
is always possible.
YES: The updating procedure is done.

Quick guide "ECA 30 / 31 to override mode":


1. Go to ECA MENU
2. Move cursor to "Clock" symbol
3. Select the "Clock" symbol
4. Choose and select one of 4 override functions
5. Below the override symbol: Set hours or date
6. Below hours / date: Set desired room temperature for the override
period

140 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

7.2 Override function

The ECL 210 / 310 controllers can receive a signal in order to Example, override switch connected to S8:
override the existing schedule. The override signal can be a switch
or a relay contact.

Different override modes can be selected, depending on


application key type.

Override modes: Comfort, Saving, Constant temperature and Frost


protection.

"Comfort" is also called normal heating temperature.


"Saving" can be reduced heating or heating stopped.
"Constant temperature" is a desired flow temperature, set in the
menu "Flow temperature".
"Frost protection" stops the heating totally.

Override by means of override switch or relay contact is possible


when the ECL 210 / 310 is in scheduled mode (clock).
Example, override relay connected to S8:

Example 1

ECL in Saving mode, but in Comfort mode at override.

Choose an unused input, for example S8. Connect the override


switch or override relay contact.

Settings in ECL:

1. Select circuit > MENU > Settings > Application > Ext. input:
Select the input S8 (the wiring example)
2. Select circuit > MENU > Settings > Application > Ext. mode:
Select COMFORT # 1 # = Override switch or relay contact (not activated / activated)
# 2 # = Function mode (Schedule / Comfort)
3. Select circuit > MENU > Schedule: # 3 # = Time
Select all weekdays
Set "Start1" to 24.00 (this disables Comfort mode)
Exit menu and confirm by "Save"
4. Remember to set the circuit in question in scheduled mode
("clock").

Result: When the override switch (or the relay contact) is ON, the
ECL 210 / 310 will operate in Comfort mode.

When the override switch (or the relay contact) is OFF, the ECL 210 /
310 will operate in Saving mode.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 141


Installation Guide ECL Comfort 310, application A376

Example 2

ECL in Comfort mode, but in Saving mode at override.

Choose an unused input, for example S8. Connect the override


switch or override relay contact.

Settings in ECL:

1. Select circuit > MENU > Settings > Application > Ext. input:
Select the input S8 (the wiring example)
2. Select circuit > MENU > Settings > Application > Ext. mode:
Select SAVING # 1 # = Override switch or relay contact (not activated / activated)
# 2 # = Function mode (Schedule / Saving)
3. Select circuit > MENU > Schedule: # 3 # = Time
Select all weekdays
Set "Start1" to 00.00
Set "Stop1" to 24.00
Exit menu and confirm by "Save"
4. Remember to set the circuit in question in scheduled mode
("clock").

Result: When the override switch (or the relay contact) is ON, the
ECL 210 / 310 will operate in Saving mode.

When the override switch (or the relay contact) is OFF, the ECL 210 /
310 will operate in Comfort mode.

Example 3

The week schedule for the building is set with comfort periods
Monday - Friday: 07.00 - 17.30. Sometimes, a team meeting takes
place in the evening or in the week-end.

An override switch is installed and heating must be ON (Comfort


mode) as long as the switch is ON.

Choose an unused input, for example S8. Connect the override


switch.

Settings in ECL:

# 1 # = Override switch (not activated / activated)


1. Select circuit > MENU > Settings > Application > Ext. input: # 2 # = Function mode (Schedule / Comfort)
Select the input S8 (the wiring example) # 3 # = Time
2. Select circuit > MENU > Settings > Application > Ext. mode:
Select COMFORT
3. Remember to set the circuit in question in scheduled mode
("clock").

Result: When the override switch (or a relay contact) is ON, the ECL
210 / 310 will operate in Comfort mode.

When the override switch is OFF, the ECL 210 / 310 will operate
according to the schedule.

142 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Example 4

The week schedule for the building is set with comfort periods all
weekdays: 06.00 - 20.00. Sometimes, the desired flow temperature
must be constant on 65 °C.

An override relay is installed and the flow temperature must be


65 °C as long as the override relay is activated.

Choose an unused input, for example S8. Connect the contacts of


the override relay.

Settings in ECL:

# 1 # = Override switch (not activated / activated)


1. Select circuit > MENU > Settings > Application > Ext. input: # 2 # = Function mode (Schedule / Const. temp.)
Select the input S8 (the wiring example) # 3 # = Time
2. Select circuit > MENU > Settings > Application > Ext. mode:
Select CONST. T
3. Select circuit > MENU > Settings > Flow temperature >
Desired T (ID 1x004):
Set to 65 °C
4. Remember to set the circuit in question in scheduled mode
("clock").

Result: When the override relay is activated, the ECL 210 / 310 will
operate in Const. temp. mode and control a flow temperature of
65 °C.

When the override relay is not activated, the ECL 210 / 310 will
operate according to the schedule.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 143


Installation Guide ECL Comfort 310, application A376

7.3 Several controllers in the same system


When ECL Comfort controllers are interconnected by means of
the ECL 485 communication bus (cable type: 2 x twisted pair), the
master controller will broadcast the following signals to the slave
controllers:
• Outdoor temperature (measured by S1)
• Time and date
• DHW tank heating / charging activity
Furthermore, the master controller can receive information about:
• the desired flow temperature (demand) from slave controllers
• and (as from ECL controller version 1.48) DHW tank heating /
charging activity in slave controllers

In a system with MASTER / SLAVE controllers, only one MASTER


controller with address 15 is allowed.
Situation 1:
SLAVE controllers: How to make use of the outdoor If by mistake more MASTER controllers are present in an ECL 485
temperature signal sent from the MASTER controller communication bus system, decide which controller is to be MASTER.
Change the address in the remaining controllers. However, the system
will operate but not be stable with more than one MASTER controller.
The slave controllers only receive information about outdoor
temperature and date / time.

SLAVE controllers:
Change the factory set address from 15 to address 0.
In the MASTER controller, the address in ‘ECL 485 addr. (master / slave
• In , go to System > Communication > ECL 485 addr: address)’, ID no. 2048, must always be 15.

ECL 485 addr. (master / slave address) 2048


Circuit Setting range Choose
0 ... 15 0

144 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Situation 2:
SLAVE controller: How to react on a DHW tank heating /
charging activity sent from the MASTER controller

The slave receives information about a DHW tank heating /


charging activity in the master controller and can be set to close
the selected heating circuit.

ECL controller versions 1.48 (as from August 2013):


The master receives information about DHW tank heating /
charging activity in the master controller itself and also slaves in
the system.
This status is broadcasted to all ECL controllers in the system and
each heating circuit can be set to close the heating.

SLAVE controller:
Set the desired function:
• In circuit 1 / circuit 2, go to ‘Settings’ > ‘Application’ >’DHW
priority’:

DHW priority (closed valve / normal 11052


operation) / 12052
Circuit Setting range Choose
1/2 OFF / ON OFF / ON

OFF: The flow temperature control remains unchanged during


active DHW heating / charging in the master / slave
system.
ON: The valve in the heating circuit is closed during active
DHW heating / charging in the master / slave system.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 145


Installation Guide ECL Comfort 310, application A376

Situation 3:
SLAVE controller: How to make use of the outdoor temperature
signal and send information about the desired flow In the MASTER controller, the address in ‘ECL 485 addr. (master / slave
temperature back to the MASTER controller address)’, ID no. 2048, must always be 15.

The slave controller receives information about outdoor


temperature and date / time. The master controller receives
information about the desired flow temperature from slave
controllers with an address from 1 ... 9:

SLAVE controller:
• In , go to System > Communication > ECL 485 addr.
• Change the factory set address from 15 to an address (1 ... 9).
Each slave must be configured with its own address.

ECL 485 addr. (master / slave address) 2048


Circuit Setting range Choose
0 ... 15 1 ... 9

Furthermore, each slave can send information about the desired


flow temperature (demand) in each circuit back to the master
controller.

SLAVE controller:
• In the circuit in question, go to Settings > Application > Send
desired T
• Choose ON or OFF.

Send desired T 11500


/ 12500
Circuit Setting range Choose
1/2 OFF / ON ON or OFF

OFF: Information about the desired flow temperature is not


sent to the master controller.
ON: Information about the desired flow temperature is sent
to the master controller.

146 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

7.4 Frequently asked questions

The definitions apply to the Comfort 210 as well as ECL Comfort


310 series. Consequently, you might come across expressions
that are not mentioned in your guide.

The time shown in the display is one hour off?


See ‘Time and Date’.
The time shown in the display is not correct?
The internal clock may have been reset, if there has been a power
break for more than 72 hours.
Go to the 'Common controller settings' and 'Time & Date' to set
the correct time.
The ECL Application Key is lost?
Switch the power off and on again to see the system type and the
software generation of the controller or go to 'Common controller
settings' >'Key functions' > 'Application'. The system type (e.g.
TYPE A266.1) and the system diagram is displayed.
Order a replacement from your Danfoss representative (e.g. ECL
Application Key A266).
Insert the new ECL Application Key and copy your personal
settings from the controller to the new ECL Application Key, if
required.
The room temperature is too low?
Make sure that the radiator thermostat does not limit the room
temperature.
If you still cannot obtain the desired room temperature by
adjusting the radiator thermostats, the flow temperature is too
low. Increase the desired room temperature (display with desired
room temperature). If this does not help, adjust the ‘Heat curve’
(‘Flow temp.’).
The room temperature is too high during saving periods?
Make sure that the min. flow temperature limitation ('Temp. min.')
is not too high.
The temperature is unstable?
Check that the flow temperature sensor is correctly connected
and in the right place. Adjust the control parameters ('Control
par.').
If the controller has a room temperature signal, see 'Room limit'.
The controller does not operate and the control valve is
closed?
Check that the flow temperature sensor is measuring the correct
value, see 'Daily use' or 'Input overview'.
Check the influence from other measured temperatures.
How to make an extra comfort period in the schedule?
You can set an additional comfort period by adding new ‘Start’
and ‘Stop’ times in ‘Schedule’.
How to remove a comfort period in the schedule?
You can remove a comfort period by setting start and stop times
to the same value.
How to restore your personal settings?
Please read the chapter concerning ‘Inserting the ECL Application
Key’.
How to restore the factory settings?
Please read the chapter concerning ‘Inserting the ECL Application
Key’.
Why can’t the settings be changed?
The ECL Application Key has been removed.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 147


Installation Guide ECL Comfort 310, application A376

Why can’t an application be selected when inserting the ECL


application key into the controller?
The actual application in the ECL Comfort controller must be
deleted before a new application (subtype) can be selected.
How to react on alarms?
An alarm indicates that the system is not operating satisfactorily.
Please contact your installer.
What does P and PI control mean?
P control: Proportional control.
By using a P control, the controller will change the flow
temperature proportional to the difference between a desired
and an actual temperature, e.g. a room temperature.
A P control will always have an offset which not will disappear
over time.

PI control: Proportional and Integrating control.


A PI control does the same as a P control, but the offset will
disappear over time.
A long ‘Tn’ will give a slow but stable control, and a short ‘Tn’ will
result in a fast control but with a higher risk of unstability.
What does the "i" in the upper right corner of the display
mean ?
When uploading an application (subtype) from the application
key into the ECL Comfort controller, the "i" in the upper right
corner indicates that - besides the factory settings - the subtype
also contains special user / systems settings.

148 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

87H1420.10
How to set a correct heat curve?

Da nfos s
Short answer: 120
1.8 2.2 2.6 3.0 3.4

Set the heat curve to the lowest possible value, but still having
comfortable room temperature. 110
1.4
100
The table shows some recommendations:
90

House with Needed flow temp. Recom- 80 1.0

radiators: when the outdoor mended heat


70
temp. is -10 °C: curve value:
0.6
65 °C 1.4 60
Older than 20 years:
50
Between 10 and 20 60 °C 1.2
years old: 40 0.2
Rather new: 50 °C 0.8 30
Floor heating systems need, in general, a lower heat curve value 20

10
Technical answer:
In order to save energy, the flow temperature should be as low as -30 -20 -10 0 10 20
possible, but still considering a comfortable room temperature.
This means the heat curve slope should have a low value.

See the heat curve slope diagram.


Choose the desired flow temperature (vertical axis) for your heating
system at the expected lowest outdoor temperature (horizontal axis)
for your area. Pick the heat curve closest to the common point of
these two values.

Example: Desired flow temperature: 60 (°C) at outdoor temperature:


-10 (°C)
Result: Heat curve slope value = 1.2 (mid-way between 1.4 and 1.0).

In general:
• Smaller radiators in your heating system might require a higher
heat curve slope. (Example: Desired flow temperature 70 °C
resulting in heat curve = 1.5).
• Floor heating systems require a lower heat curve slope. (Example:
Desired flow temperature 35 °C resulting in heat curve = 0.4).
• Corrections of the heat curve slope should be done in small steps
when having outdoor temperatures below 0 °C; one step pr. day.
• If required, adjust the heat curve in the six coordinate points.
• Setting of the desired room temperature has an influence on the
desired flow temperature even if a room temperature sensor /
Remote Control Unit is not connected. An example: Increasing the
desired room temperature results in a higher flow temperature.
• Typically, the desired room temperature should be adjusted when
having outdoor temperatures above 0 °C.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 149


Installation Guide ECL Comfort 310, application A376

7.5 Definitions

The definitions apply to the Comfort 210 as well as ECL Comfort


310 series. Consequently, you might come across expressions
that are not mentioned in your guide.

Accumulated temperature value


A filtered (dampened) value, typically for room and outdoor
temperatures. Is calculated in the ECL controller and is used
to express the heat stored in the walls of the house. The
accumulated value does not change so rapidly as the actual
temperature.
Air duct temperature
Temperature measured in the air duct where the temperature
is to be controlled.
Alarm function
Based on the alarm settings, the controller can activate an output.
Anti-bacteria function
For a defined period, the DHW temperature is increased in order
to neutralize dangerous bacteria, e.g. Legionella.
Balance temperature
This setpoint is the basis for the flow / air duct temperature. The
balance temperature can be adjusted by the room temperature,
the compensation temperature and the return temperature. The
balance temperature is only active if a room temperature sensor
is connected.
BMS
Building Management System. A supervisory system for remote
control and monitoring.
Comfort operation
Normal temperature in the system controlled by the schedule.
During heating the flow temperature in the system is higher to
maintain the desired room temperature. During cooling the flow
temperature in the system is lower to maintain the desired room
temperature.
Comfort temperature
Temperature maintained in the circuits during comfort periods.
Normally during daytime.
Compensation temperature
A measured temperature influencing the flow temperature
reference / balance temperature.
Desired flow temperature
Temperature calculated by the controller on basis of the outdoor
temperature and influences from the room and / or return
temperatures. This temperature is used as a reference for the
control.
Desired room temperature
Temperature which is set as the desired room temperature. The
temperature can only be controlled by the ECL Comfort controller
if a room temperature sensor is installed.
If a sensor is not installed, the set desired room temperature
however still influences the flow temperature.
In both cases the room temperature in each room is typically
controlled by radiator thermostats / valves.
Desired temperature
Temperature based on a setting or a controller calculation.
Dew point temperature
Temperature at which the humidity in the air condensates.

150 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

DHW circuit
The circuit for heating the domestic hot water (DHW).
Duct temperature
Temperature measured in the air duct where the temperature
is to be controlled.
ECL Portal
A supervisory system for remote control and monitoring, locally
and via Internet.
EMS
Energy Management System. A supervisory system for remote
control and monitoring.
Factory settings
Settings stored on the ECL Application Key to simplify the set up
of your controller the first time.
Flow temperature
Temperature measured in the water flow where the temperature
is to be controlled.
Flow temperature reference
Temperature calculated by the controller on basis of the outdoor
temperature and influences from the room and / or return
temperatures. This temperature is used as a reference for the
control.
Heat curve
A curve showing the relationship between actual outdoor
temperature and desired flow temperature.
Heating circuit
The circuit for heating the room / building.
Holiday schedule
Selected days can be programmed to be in comfort, saving or
frost protection mode. Besides this, a day schedule with comfort
period from 07.00 to 23.00 can be selected.
Humidistat
A device, which reacts on the air's humidity. A switch can go ON if
the measured humidity gets above a set point.
Humidity, relative
This value (stated in %) refers to the indoor moisture content
compared to the max. moisture content. The relative humidity
is measured by the ECA 31 and is used for the calculation of the
dew point temperature.
Inlet temperature
Temperature measured in the inlet air flow where the temperature
is to be controlled.
Limitation temperature
Temperature that influences the desired flow / balance
temperature.
Log function
The temperature history is displayed.
Master / slave
Two or more controllers are interconnected on the same bus,
the master sends out e.g. time, date and outdoor temperature.
The slave receives data from master and sends e.g. desired flow
temperature value.
Modulating control (0 - 10 V control)
Positioning (by means of a 0 - 10 V control signal) of the actuator
for the motorized control valve in order to control the flow.
Optimization
The controller optimizes the start time of the scheduled
temperature periods. Based on the outdoor temperature, the
controller automatically calculates when to start in order to reach
the comfort temperature at the set time. The lower the outdoor
temperature, the earlier the start time.

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 151


Installation Guide ECL Comfort 310, application A376

Outdoor temperature trend


The arrow indicates the tendency, i.e. whether the temperature
rises or falls.
Override mode
When ECL Comfort is in Scheduled mode, a switch or contact
signal can be applied to an input in order to override to Comfort,
Saving, Frost protection or Constant temperature. As long as the
switch or contact signal is applied, the override is active.
Pt 1000 sensor
All sensors used with the ECL Comfort controller are based on the
Pt 1000 type (IEC 751B). The resistance is 1000 ohm at 0 °C and it
changes with 3.9 ohm / degree.
Pump control
One circulation pump is working and the other is the spare
circulation pump. After a set time, the roles are exchanged.
Refill water function
If the measured pressure in the heating system is too low (e.g.
due to a leakage), water can be supplemented.
Return temperature
The temperature measured in the return influences the desired
flow temperature.
Room temperature
Temperature measured by the room temperature sensor or
the Remote Control Unit. The room temperature can only be
controlled directly if a sensor is installed. The room temperature
influences the desired flow temperature.
Room temperature sensor
Temperature sensor placed in the room (reference room, typically
the living room) where the temperature is to be controlled.
Saving temperature
Temperature maintained in the heating / DHW circuit during
saving temperature periods. Typically, the Saving temperature is
lower than the Comfort temperature in order to save energy.
SCADA
Supervisory Control And Data Acquisition. A supervisory system
for remote control and monitoring.
Schedule
Schedule for periods with comfort and saving temperatures. The
schedule can be made individually for each week day and may
consist of up to 3 comfort periods per day.
Weather compensation
Flow temperature control based on the outdoor temperature.
The control is related to a user-defined heat curve.
2-point control
ON / OFF control, e.g. circulation pump, ON / OFF valve,
change-over valve or damper control.
3-point control
Opening, closing or no action of the actuator for the motorized
control valve. No action means that the actuator remains in its
current position.

152 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

7.6 Type (ID 6001), overview

Type 0 Type 1 Type 2 Type 3 Type 4


Address ✔ ✔ ✔ ✔ ✔
Type ✔ ✔ ✔ ✔ ✔
Scan time ✔ ✔ ✔ ✔ ✔
ID / Serial ✔ ✔ ✔ ✔ ✔
Reserved ✔ ✔ ✔ ✔ ✔
Flow temp. [0.01 °C] ✔ ✔ ✔ ✔ -
Return temp. [0.01 °C] ✔ ✔ ✔ ✔ -
Flow [0.1 l/h] ✔ ✔ ✔ ✔ -
Power [0.1 kW] ✔ ✔ ✔ ✔ -
Acc. Volume [0.1 m3] [0.1 m3] [0.1 m3] [0.1 m3] -
Acc. Energy [0.1 kWh] [0.1 MWh] [0.1 kWh] [0.1 MWh] -

Tariff1 Acc. Energy - - [0.1 kWh] [0.1 MWh] -


Tariff2 Acc. Energy - - [0.1 kWh] [0.1 MWh] -
Up time [days] - - ✔ ✔ -
Current time [M-bus - - ✔ ✔ ✔
defined structure]
Error status [heat meter - - ✔ ✔ -
defined bitmask]
Acc. Volume - - - - [0.1 m3]
Acc. Energy - - - - [0.1 kWh]
Acc. Volume2 - - - - [0.1 m3]
Acc. Energy2 - - - - [0.1 kWh]
Acc. Volume3 - - - - [0.1 m3]
Acc. Energy3 - - - - [0.1 kWh]
Acc. Volume4 - - - - [0.1 m3]
Acc. Energy4 - - - - [0.1 kWh]

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 153


Installation Guide ECL Comfort 310, application A376

7.7 Parameter ID overview

A376.x — x refers to the subtypes listed in the column.

ID Parameter Name A376.x Setting range Factory Unit Own settings


11004 Desired T 1, 2, 3, 4, 9, 10 5 ... 150 50 °C
11010 ECA addr. 1, 2, 3, 4 OFF ; A ; B OFF
11011 Auto saving 1, 2, 3, 4, 9, 10 OFF, -29 ... 10 -15 °C
11012 Boost 1, 2, 3, 4, 9, 10 OFF, 1 ... 99 OFF %
11013 Ramp 1, 2, 3, 4, 9, 10 OFF, 1 ... 99 OFF Min
11014 Optimizer 1, 2, 3, 4, 9, 10 OFF, 10 ... 59 OFF
11015 Adapt. time 1, 2, 3, 4 OFF, 1 ... 50 OFF Sec
11017 Demand offset 1, 2, 3, 4, 9, 10 OFF, 1 ... 20 OFF K
11020 Based on 1, 2, 3, 4 OUT ; ROOM OUT
11021 Total stop 1, 2, 3, 4, 9, 10 OFF ; ON OFF
11022 P exercise 1, 2, 3, 4, 9, 10 OFF ; ON ON
11023 M exercise 1, 2, 3, 4, 9, 10 OFF ; ON OFF
11024 Actuator 1, 2, 4, 9, 10 ABV ; GEAR GEAR
11026 Pre-stop 1, 2, 3, 4, 9, 10 OFF ; ON ON
11028 Con. T, ret. T lim. 1, 2, 3, 4, 9, 10 10 ... 110 70 °C
11029 DHW, ret. T limit 1, 2, 3, 4, 9, 10 OFF, 10 ... 110 OFF °C
11031 High T out X1 1, 2, 3, 4, 9, 10 -60 ... 20 15 °C
11032 Low limit Y1 1, 2, 3, 4, 9, 10 10 ... 150 50 °C
11033 Low T out X2 1, 2, 3, 4, 9, 10 -60 ... 20 -15 °C
11034 High limit Y2 1, 2, 3, 4, 9, 10 10 ... 150 60 °C
11035 Infl. - max. 1, 2, 3, 4 -9.9 ... 9.9 -2.0
-||- 9, 10 -9.9 ... 9.9 0.0
11036 Infl. - min. 1, 2, 3, 4, 9, 10 -9.9 ... 9.9 0.0
11037 Adapt. time 1, 2, 3, 4, 9, 10 OFF, 1 ... 50 25 Sec
11040 P post-run 1, 2, 3, 4, 9, 10 0 ... 99 3 Min
11043 Parallel operation 1, 2, 3, 4 OFF, 1 ... 99 OFF K
11050 P demand 1, 2, 3, 4, 9, 10 OFF ; ON OFF
11052 DHW priority 1, 2, 3, 4, 9, 10 OFF ; ON OFF
11077 P frost T 1, 2, 3, 4, 9, 10 OFF, -10 ... 20 2 °C
11078 P heat T 1, 2, 3, 4, 9, 10 5 ... 40 20 °C
11079 Max. flow T 9, 10 10 ... 110 90 °C
11080 Delay 9, 10 5 ... 250 60 Sec
11085 Priority 1, 2, 3, 4, 9, 10 OFF ; ON OFF
11093 Frost pr. T 1, 2, 3, 4, 9, 10 5 ... 40 10 °C
11109 Input type 1, 2, 3, 4, 9, 10 EM1 ; EM2 ; EM3 ; OFF
EM4 ; EM5 ; OFF
11112 Adapt. time 1, 2, 3, 4, 9, 10 OFF, 1 ... 50 OFF Sec
11113 Filter constant 1, 2, 3, 4, 9, 10 1 ... 50 10

154 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

ID Parameter Name A376.x Setting range Factory Unit Own settings


11115 Units 1, 2, 3, 4, 9, 10 ml, l/h ; l, l/h ; ml, ml, l/h
m3/h ; l, m3/h ; Wh,
kW ; kWh, kW ; kWh,
MW ; MWh, MW ;
MWh, GW ; GWh, GW
11116 High limit Y2 1, 2, 3, 4, 9, 10 0.0 ... 999.9 999.9
11117 Low limit Y1 1, 2, 3, 4, 9, 10 0.0 ... 999.9 999.9
11118 Low T out X2 1, 2, 3, 4, 9, 10 -60 ... 20 -15 °C
11119 High T out X1 1, 2, 3, 4, 9, 10 -60 ... 20 15 °C
11141 Ext. input 1, 2, 3, 9, 10 OFF ; S1 ; S2 ; S3 ; S4 OFF
; S5 ; S6 ; S7 ; S8 ; S9
; S10
-||- 4 OFF ; S1 ; S2 ; S3 ; S4 OFF
; S5 ; S6 ; S7 ; S8 ; S9 ;
S10 ; S11 ; S12 ; S13 ;
S14 ; S15 ; S16
11142 Ext. mode 1, 2, 3, 4, 9, 10 COMFORT ; SAVING ; COMFORT
FROST PR. ; CONST. T
11147 Upper difference 1, 2, 3, 4, 9, 10 OFF, 1 ... 30 OFF K
11148 Lower difference 1, 2, 3, 4, 9, 10 OFF, 1 ... 30 OFF K
11149 Delay 1, 2, 3, 4, 9, 10 1 ... 99 10 Min
11150 Lowest temp. 1, 2, 3, 4, 9, 10 10 ... 50 30 °C
11174 Motor pr. 1, 2, 3, 4, 9, 10 OFF, 10 ... 59 OFF Min
11177 Temp. min. 1, 2, 3, 4, 9, 10 10 ... 150 10 °C
11178 Temp. max. 1, 2, 3, 4, 9, 10 10 ... 150 90 °C
11179 Summer, cut-out 1, 2, 3, 4, 9, 10 OFF, 1 ... 50 20 °C
11182 Infl. - max. 1, 2, 3, 4 -9.9 ... 0.0 -4.0
11183 Infl. - min. 1, 2, 3, 4 0.0 ... 9.9 0.0
11184 Xp 1, 2, 4, 9, 10 5 ... 250 120 K
-||- 3 5 ... 250 80 K
11185 Tn 1, 2, 4, 9, 10 1 ... 999 50 Sec
-||- 3 1 ... 999 30 Sec
11186 M run 1, 2, 4, 9, 10 5 ... 250 60 Sec
11187 Nz 1, 2, 3, 4, 9, 10 1 ... 9 3 K
11189 Min. act. time 1, 2, 4, 9, 10 2 ... 50 10
11392 Sum. start, month 1, 2, 3, 4, 9, 10 1 ... 12 5
11393 Sum. start, day 1, 2, 3, 4, 9, 10 1 ... 31 20
11395 Summer, filter 1, 2, 3, 4, 9, 10 OFF, 1 ... 300 250
11396 Win. start, month 1, 2, 3, 4, 9, 10 1 ... 12 5
11397 Winter start, day 1, 2, 3, 4, 9, 10 1 ... 31 20
11398 Winter, cut-out 1, 2, 3, 4, 9, 10 OFF, 1 ... 50 20 °C
11399 Winter, filter 1, 2, 3, 4, 9, 10 OFF, 1 ... 300 250
11500 Send desired T 1, 2, 3, 4, 9, 10 OFF ; ON ON
11607 Low X 9, 10 0.0 ... 10.0 2.0 V

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 155


Installation Guide ECL Comfort 310, application A376

ID Parameter Name A376.x Setting range Factory Unit Own settings


11608 High X 9, 10 0.0 ... 10.0 10.0 V
11609 Low Y 9, 10 0.0 ... 25.0 0.0 Bar
11610 High Y 9, 10 0.0 ... 25.0 20.0 Bar
11614 Alarm high 9, 10 0.0 ... 25.0 2.3 Bar
11615 Alarm low 9, 10 0.0 ... 25.0 0.0 Bar
11617 Alarm time-out 9, 10 0 ... 240 30 Sec
11623 Digital 9, 10 0 ... 1 0
11636 Alarm value 9, 10 0 ... 1 0
11637 Alarm time-out 9, 10 0 ... 240 30 Sec
12004 Desired T 1, 2, 3, 9, 10 5 ... 150 50 °C
12010 ECA addr. 1, 2, 3 OFF ; A ; B OFF
12011 Auto saving 1, 2, 3, 9, 10 OFF, -29 ... 10 -15 °C
12012 Boost 1, 2, 3, 9, 10 OFF, 1 ... 99 OFF %
12013 Ramp 1, 2, 3, 9, 10 OFF, 1 ... 99 OFF Min
12014 Optimizer 1, 2, 3, 9, 10 OFF, 10 ... 59 OFF
12015 Adapt. time 1, 2, 3 OFF, 1 ... 50 OFF Sec
12020 Based on 1, 2, 3 OUT ; ROOM OUT
12021 Total stop 1, 2, 3, 9, 10 OFF ; ON OFF
12022 P exercise 1, 2, 3, 9, 10 OFF ; ON ON
-||- 4 OFF ; ON OFF
12023 M exercise 1, 2, 3, 4, 9, 10 OFF ; ON OFF
12024 Actuator 1, 2, 4, 9, 10 ABV ; GEAR GEAR
12026 Pre-stop 1, 2, 3, 9, 10 OFF ; ON ON
12028 Con. T, ret. T lim. 1, 2, 3, 9, 10 10 ... 110 70 °C
12030 Limit 4 10 ... 120 60 °C
12031 High T out X1 1, 2, 3, 9, 10 -60 ... 20 15 °C
12032 Low limit Y1 1, 2, 3, 9, 10 10 ... 150 50 °C
12033 Low T out X2 1, 2, 3, 9, 10 -60 ... 20 -15 °C
12034 High limit Y2 1, 2, 3, 9, 10 10 ... 150 60 °C
12035 Infl. - max. 1, 2, 3 -9.9 ... 9.9 -2.0
-||- 4, 9, 10 -9.9 ... 9.9 0.0
12036 Infl. - min. 1, 2, 3, 4, 9, 10 -9.9 ... 9.9 0.0
12037 Adapt. time 1, 2, 3, 4, 9, 10 OFF, 1 ... 50 25 Sec
12040 P post-run 1, 2, 3, 4, 9, 10 0 ... 99 3 Min
12043 Parallel operation 1, 2, 3 OFF, 1 ... 99 OFF K
12052 DHW priority 1, 2, 3, 9, 10 OFF ; ON OFF
12077 P frost T 1, 2, 3, 4, 9, 10 OFF, -10 ... 20 2 °C
12078 P heat T 1, 2, 3, 4, 9, 10 5 ... 40 20 °C
12079 Max. flow T 9, 10 10 ... 110 90 °C
12080 Delay 9, 10 5 ... 250 60 Sec
12085 Priority 1, 2, 3, 4, 9, 10 OFF ; ON OFF

156 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

ID Parameter Name A376.x Setting range Factory Unit Own settings


12093 Frost pr. T 1, 2, 3, 4, 9, 10 5 ... 40 10 °C
12109 Input type 1, 2, 3, 4, 9, 10 EM1 ; EM2 ; EM3 ; OFF
EM4 ; EM5 ; OFF
12111 Limit 4 0.0 ... 999.9 999.9
12112 Adapt. time 1, 2, 3, 4, 9, 10 OFF, 1 ... 50 OFF Sec
12113 Filter constant 1, 2, 3, 4, 9, 10 1 ... 50 10
12115 Units 1, 2, 3, 4, 9, 10 ml, l/h ; l, l/h ; ml, ml, l/h
m3/h ; l, m3/h ; Wh,
kW ; kWh, kW ; kWh,
MW ; MWh, MW ;
MWh, GW ; GWh, GW
12116 High limit Y2 1, 2, 3, 9, 10 0.0 ... 999.9 999.9
12117 Low limit Y1 1, 2, 3, 9, 10 0.0 ... 999.9 999.9
12118 Low T out X2 1, 2, 3, 9, 10 -60 ... 20 -15 °C
12119 High T out X1 1, 2, 3, 9, 10 -60 ... 20 15 °C
12122 Day: 4 0 ... 127 0
12123 Start time 4 0 ... 47 0
12124 Duration 4 10 ... 600 120 Min
12125 Desired T 4 OFF, 10 ... 110 OFF °C
12141 Ext. input 1, 2, 3, 9, 10 OFF ; S1 ; S2 ; S3 ; S4 OFF
; S5 ; S6 ; S7 ; S8 ; S9
; S10
-||- 4 OFF ; S1 ; S2 ; S3 ; S4 OFF
; S5 ; S6 ; S7 ; S8 ; S9 ;
S10 ; S11 ; S12 ; S13 ;
S14 ; S15 ; S16
12142 Ext. mode 1, 2, 3, 9, 10 COMFORT ; SAVING ; COMFORT
FROST PR. ; CONST. T
-||- 4 COMFORT ; SAVING ; COMFORT
FROST PR.
12147 Upper difference 1, 2, 3, 4, 9, 10 OFF, 1 ... 30 OFF K
12148 Lower difference 1, 2, 3, 4, 9, 10 OFF, 1 ... 30 OFF K
12149 Delay 1, 2, 3, 4, 9, 10 1 ... 99 10 Min
12150 Lowest temp. 1, 2, 3, 4, 9, 10 10 ... 50 30 °C
12173 Auto tuning 4 OFF ; ON OFF
12174 Motor pr. 1, 2, 3, 4, 9, 10 OFF, 10 ... 59 OFF Min
12177 Temp. min. 1, 2, 3, 4, 9, 10 10 ... 150 10 °C
12178 Temp. max. 1, 2, 3, 4, 9, 10 10 ... 150 90 °C
12179 Summer, cut-out 1, 2, 3, 9, 10 OFF, 1 ... 50 20 °C
12182 Infl. - max. 1, 2, 3 -9.9 ... 0.0 -4.0
12183 Infl. - min. 1, 2, 3 0.0 ... 9.9 0.0
12184 Xp 1, 2, 9, 10 5 ... 250 120 K
-||- 3 5 ... 250 80 K
-||- 4 5 ... 250 40 K

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 157


Installation Guide ECL Comfort 310, application A376

ID Parameter Name A376.x Setting range Factory Unit Own settings


12185 Tn 1, 2, 9, 10 1 ... 999 50 Sec
-||- 3 1 ... 999 30 Sec
-||- 4 1 ... 999 20 Sec
12186 M run 1, 2, 9, 10 5 ... 250 60 Sec
-||- 4 5 ... 250 20 Sec
12187 Nz 1, 2, 3, 4, 9, 10 1 ... 9 3 K
12189 Min. act. time 1, 2, 9, 10 2 ... 50 10
-||- 4 2 ... 50 3
12395 Summer, filter 1, 2, 3, 9, 10 OFF, 1 ... 300 250
12398 Winter, cut-out 1, 2, 3, 9, 10 OFF, 1 ... 50 20 °C
12399 Winter, filter 1, 2, 3, 9, 10 OFF, 1 ... 300 250
12500 Send desired T 1, 2, 3, 4, 9, 10 OFF ; ON ON
12607 Low X 9, 10 0.0 ... 10.0 2.0 V
12608 High X 9, 10 0.0 ... 10.0 10.0 V
12609 Low Y 9, 10 0.0 ... 25.0 0.0 Bar
12610 High Y 9, 10 0.0 ... 25.0 20.0 Bar
12614 Alarm high 9, 10 0.0 ... 25.0 2.3 Bar
12615 Alarm low 9, 10 0.0 ... 25.0 0.0 Bar
12617 Alarm time-out 9, 10 0 ... 240 30 Sec
12623 Digital 9, 10 0 ... 1 0
12636 Alarm value 9, 10 0 ... 1 0
12637 Alarm time-out 9, 10 0 ... 240 30 Sec
13022 P exercise 1, 2, 3, 4, 9, 10 OFF ; ON ON
13023 M exercise 1, 2, 3, 4, 9, 10 OFF ; ON OFF
13024 Actuator 1, 2, 4, 9, 10 ABV ; GEAR GEAR
13030 Limit 1, 2, 3, 4, 9, 10 10 ... 120 60 °C
13035 Infl. - max. 1, 2, 3, 4 -9.9 ... 9.9 -2.0
-||- 9, 10 -9.9 ... 9.9 0.0
13036 Infl. - min. 1, 2, 3, 4, 9, 10 -9.9 ... 9.9 0.0
13037 Adapt. time 1, 2, 3, 4, 9, 10 OFF, 1 ... 50 25 Sec
13040 P post-run 1, 2, 3, 4, 9, 10 0 ... 99 3 Min
13077 P frost T 1, 2, 3, 4, 9, 10 OFF, -10 ... 20 2 °C
13078 P heat T 1, 2, 3, 4, 9, 10 5 ... 40 20 °C
13085 Priority 1, 2, 3, 4, 9, 10 OFF ; ON OFF
13093 Frost pr. T 1, 2, 3, 4, 9, 10 5 ... 40 10 °C
13094 Open time 2, 4 OFF, 0.1 ... 25.0 4.0 Sec
13095 Close time 2, 4 OFF, 0.1 ... 25.0 2.0 Sec
13096 Tn (idle) 2, 4 1 ... 999 120 Sec
13097 Supply T (idle) 2, 4 OFF ; ON OFF
13109 Input type 1, 2, 3, 4, 9, 10 EM1 ; EM2 ; EM3 ; OFF
EM4 ; EM5 ; OFF
13111 Limit 1, 2, 3, 4, 9, 10 0.0 ... 999.9 999.9

158 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

ID Parameter Name A376.x Setting range Factory Unit Own settings


13112 Adapt. time 1, 2, 3, 4, 9, 10 OFF, 1 ... 50 OFF Sec
13113 Filter constant 1, 2, 3, 4, 9, 10 1 ... 50 10
13115 Units 1, 2, 3, 4, 9, 10 ml, l/h ; l, l/h ; ml, ml, l/h
m3/h ; l, m3/h ; Wh,
kW ; kWh, kW ; kWh,
MW ; MWh, MW ;
MWh, GW ; GWh, GW
13122 Day: 1, 2, 3, 4, 9, 10 0 ... 127 0
13123 Start time 1, 2, 3, 4, 9, 10 0 ... 47 0
13124 Duration 1, 2, 3, 4, 9, 10 10 ... 600 120 Min
13125 Desired T 1, 2, 3, 4, 9, 10 OFF, 10 ... 110 OFF °C
13141 Ext. input 1, 2, 3, 9, 10 OFF ; S1 ; S2 ; S3 ; S4 OFF
; S5 ; S6 ; S7 ; S8 ; S9
; S10
-||- 4 OFF ; S1 ; S2 ; S3 ; S4 OFF
; S5 ; S6 ; S7 ; S8 ; S9 ;
S10 ; S11 ; S12 ; S13 ;
S14 ; S15 ; S16
13142 Ext. mode 1, 2, 3, 4, 9, 10 COMFORT ; SAVING ; COMFORT
FROST PR.
13147 Upper difference 1, 2, 3, 4, 9, 10 OFF, 1 ... 30 OFF K
13148 Lower difference 1, 2, 3, 4, 9, 10 OFF, 1 ... 30 OFF K
13149 Delay 1, 2, 3, 4, 9, 10 1 ... 99 10 Min
13150 Lowest temp. 1, 2, 3, 4, 9, 10 10 ... 50 30 °C
13173 Auto tuning 1, 2, 4, 9, 10 OFF ; ON OFF
13174 Motor pr. 1, 2, 3, 4, 9, 10 OFF, 10 ... 59 OFF Min
13177 Temp. min. 1, 2, 3, 4, 9, 10 10 ... 150 10 °C
13178 Temp. max. 1, 2, 3, 4, 9, 10 10 ... 150 65 °C
13184 Xp 1, 2, 3, 4 5 ... 250 40 K
-||- 9, 10 5 ... 250 90 K
13185 Tn 1, 2, 3, 4 1 ... 999 20 Sec
-||- 9, 10 1 ... 999 13 Sec
13186 M run 1, 2, 4 5 ... 250 20 Sec
-||- 9, 10 5 ... 250 15 Sec
13187 Nz 1, 2, 3, 4, 9, 10 1 ... 9 3 K
13189 Min. act. time 1, 2, 4 2 ... 50 3
-||- 9, 10 2 ... 50 2
13500 Send desired T 1, 2, 3, 4, 9, 10 OFF ; ON ON
13513 Pulse value 9, 10 0.1 ... 1000.0 10.0 l
13514 Preset 9, 10 OFF ; ON OFF
13607 Low X 10 0.0 ... 10.0 2.0 V
13608 High X 10 0.0 ... 10.0 10.0 V
13609 Low Y 10 0.0 ... 25.0 0.0 Bar
13610 High Y 10 0.0 ... 25.0 20.0 Bar
13623 Digital 9, 10 0 ... 1 0

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 159


Installation Guide ECL Comfort 310, application A376

ID Parameter Name A376.x Setting range Factory Unit Own settings


13636 Alarm value 9, 10 0 ... 1 0
13637 Alarm time-out 9, 10 0 ... 240 30 Sec
14607 Low X 10 0.0 ... 10.0 2.0 V
14608 High X 10 0.0 ... 10.0 10.0 V
14609 Low Y 10 0.0 ... 25.0 0.0 Bar
14610 High Y 10 0.0 ... 25.0 20.0 Bar

160 DEN-SMT/DK VI.GU.B2.02 Danfoss District Energy


Installation Guide ECL Comfort 310, application A376

Installer:

By:
Date:

Danfoss District Energy VI.GU.B2.02 DEN-SMT/DK 161


Installation Guide ECL Comfort 310, application A376

*087H9059*

*VIGUB202*

Produced by Danfoss A/S © 05/2015

You might also like