HVAC Piping System
HVAC Piping System
Air Outlets
• whenever there is an enlargement in the cross-sectional area of the duct, the velocity of
air decreases, and the velocity pressure is converted into static pressure. The increase in
static pressure due to a decrease in velocity pressure is known as static regain
Static Regain
X
Aspect Ratio
• Increasing the aspect ratio,
• increases both the installed cost
• Increase the operating cost of the system.
• Usually small rectangular duct with an aspect ratio closer to 1to be
use:-Reasons
1. Other benefits include low friction drop,
2. Low weight of metal, and lower insulation
3. Lower installation costs.
Example: Duct cross sectional area 4ft2 with
100ft length
• Duct can fabricate 2’ x 2’ (Aspect ration 1:1) or 1’x 4’(Aspect ratio 1:4)
• 2’x 2’ perimeter 8 ft, material required= 8 x100ft= 800ft
• 1’x4’perimeter 10ft, material required= 10 x 100ft= 1000ft.
• As Aspect ratio 1:1 increase to 1:4, the surface area and insulation
requirement increase by 40%
Friction Chart
In any duct section thru which air is flowing, there is a
continuous loss of pressure. This loss is called duct
friction loss and depends on the following:
1. Air velocity
2. Duct size
3. Interior surface roughness
4. Duct length Varying any one of these four factors
influences the friction loss in the ductwork.
The relationship of these factors is illustrated in the
following equation:
Simplification done by Duct
calculator
Most Popular Method
• Equal Friction method:-This method is far superior than Velocity
reduction because requires less balancing for symmetrical duct
layouts
A B C D E
Say Blower Fan 7200CFM
A B 40’ C 30’ D 30’ E
V=Q/A
Say Blower Fan 7200CFM,
Usually by choosing maximum recommended velocity
A B 40’ C 30’ D 30’ E
The equal friction method is recommended for return and exhaust air
systems.
Note :
Pressure drop characteristics for the ducts and fittings are derived from ASHRAE 1997 Fundamentals Chapter 32 pp 32.01-32.49.
Density of std. Air (r) 1.2 kg/m3
Kinematic viscosity (n) 1.6E-05 m²/s
Rectangular ducts De = 1.30(ab)0.625/(a+b)0.25
Reynolds Number Re = DhV/1000n
Friction factor f' = 0.11[(e/Dh)+(68/Re)]0.25 If f'<0.018: l = 0.85f'+0.0028 , Else l = f'
Friction Loss (pa) DPf = (1000lL/Dh)*(rV²/2)
Total Tot
Duct Air Flow Rate Duct Dimension Straight Equivalent Length For Elbow Eqv. al
Equip. Ref. Area Served System Sect. Insul Width Height Length Eqv. Len Qty Total Eqv. Length A V Dh De Re e f' l DPf Friction
No. (L/S) (m3/s) (mm) (mm) (m) (m) (nos) Len. (m) (m) (m2) (m/s) (mm) (m) (mm) (Pa/m) Loss (Pa)
AHU 16-2 Ruang Legar A/C Supply Air 1 5663 5.66 int. 730 730 2 5.1 1 5.1 7.1 0.53 10.62 730.00 0.80 4.8E+05 0.9 2.1E-02 2.1E-02 1.96 13.94
2 5663 5.66 int. 1000 600 6.6 7 1 7 13.6 0.60 9.43 750.00 0.84 4.4E+05 0.9 2.1E-02 2.1E-02 1.50 20.43
ARAS 1 3 3775.4 3.78 ext. 800 600 11.6 5.6 2 11.2 22.8 0.48 7.88 685.71 0.76 3.4E+05 0.09 1.5E-02 1.5E-02 0.84 19.09
4 3067.5 3.07 ext. 750 600 2.4 5.3 0 0 2.4 0.45 6.82 666.67 0.73 2.8E+05 0.09 1.5E-02 1.6E-02 0.66 1.59
5 2831.5 2.83 ext. 700 600 7 4.9 0 0 7 0.42 6.74 646.15 0.71 2.7E+05 0.09 1.5E-02 1.6E-02 0.67 4.70
6 2595.6 2.6 ext. 600 600 2.4 4.2 0 0 2.4 0.36 7.22 600.00 0.66 2.7E+05 0.09 1.6E-02 1.6E-02 0.84 2.01
7 2359.6 2.36 ext. 600 550 2.5 4.2 0 0 2.5 0.33 7.15 573.91 0.63 2.6E+05 0.09 1.6E-02 1.6E-02 0.87 2.17
8 1887.7 1.89 ext. 600 500 6.3 4.2 0 0 6.3 0.30 6.30 545.45 0.60 2.1E+05 0.09 1.6E-02 1.7E-02 0.73 4.58
9 1651.7 1.65 ext. 600 400 5 4.2 0 0 5 0.24 6.88 480.00 0.53 2.1E+05 0.09 1.7E-02 1.7E-02 1.00 4.99
10 1179.8 1.18 ext. 600 300 5.5 4.2 0 5.5 0.18 6.56 400.00 0.46 1.6E+05 0.09 1.7E-02 1.8E-02 1.14 6.27
11 943.84 0.94 ext. 600 250 3.1 4.2 0 3.1 0.15 6.27 352.94 0.41 1.4E+05 0.09 1.8E-02 1.8E-02 1.21 3.76
12 471.92 0.47 ext. 400 250 2.7 2.8 0 2.7 0.10 4.70 307.69 0.34 9.0E+04 0.09 2.0E-02 2.0E-02 0.85 2.30
13 235.96 0.24 ext. 250 250 2.1 1.8 0 2.1 0.06 3.84 250.00 0.27 6.0E+04 0.09 2.2E-02 2.2E-02 0.77 1.61
14 117.98 0.12 ext. 200 150 2.3 1.4 1 1.4 3.7 0.03 4.00 171.43 0.19 4.3E+04 0.09 2.4E-02 2.4E-02 1.32 4.89
A/C Return Air 1 5663 5.66 ext. 1200 600 5.5 8.4 1 8.4 13.9 0.72 7.86 800.00 0.91 3.9E+05 0.09 1.4E-02 1.5E-02 0.69 9.63
1.366m
coil M1=Q1
V3,A3
P1,V1,A1
1.35m
0.72m
• Q=AV, M=þAV
•QαVαA
• If given Area has been reduced by half net free area ie
(louvre application)
• Ie 2 x A2=A1
• Q also reduce by half; so
• At point 2, M2=Q2 = Q1/2 =2.25 m3/s
• When flow rate Q reduces by half, velocity also
reduces by half V2= V1/2 = 2.31m/s
• At the point of louvre,the minor losses
• ^P= (£ x V22 x §AIR ) /2 Pa
• ^P= (5 x 2.312 x 1.2)/2 =6.93 Pa -----(2)
• Pressure losses across the 90º bend at static of 50 Pa
~0.25 inWg (refer to duct design equivalent length
55/100 x 0.17 ~0.093 inWg = 18.7 Pa-------(3)
• Total Pressure losses => P2
• P2= 50Pa-18.7Pa-6.93Pa
• =24.37Pa
For perfact gas per unit gas (Isothermal process)
• P1V´=M1 R ^T1----------(4)
• P 2V´=M2 R ^T2---------(5)
• Work done per unit volume
• W= M R T Loge (P1/P2)
• (P1V1) / P2 V2 =(50 x 4.5)/ (24.37x 2.31)
=225/56.29
• % losses in efficiency
(225-56.29)/225 x 100%
75% losses in efficiency
Component or Fitting Minor Loss Coefficient
-ξ-
1.366m
coil M1=Q1
V3,A3
P1,V1,A1
1.35m
0.72m
2.Mollier diagram
Evaporating pressure
2.40Mpa
Condensing temp
35℃
Super heat 3 degrees
Condensation pressure
0.75Mpa