0% found this document useful (0 votes)
493 views

Rxq6Ary1 Rxq8Ary1 RXQ10ARY1 RXQ12ARY1 RXQ14ARY1 RXQ16ARY1 RXQ18ARY1 RXQ20ARY1

This document provides installation instructions for Daikin VRV-X heat pump systems. It outlines procedures for removing a sealed rubber plug from the refrigerant piping, connecting the piping to outdoor units, and setting the power supply specifications. Key details include using accessory pipes for field piping connections, adding brazing material to joints, and selecting fuses based on circuit amperage ratings ranging from 32.2 to 84 amps depending on the outdoor unit model. Wiring must be insulation type 60245 IEC 57 and capable of handling the specified voltage and phase.

Uploaded by

Tangtang Satang
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
493 views

Rxq6Ary1 Rxq8Ary1 RXQ10ARY1 RXQ12ARY1 RXQ14ARY1 RXQ16ARY1 RXQ18ARY1 RXQ20ARY1

This document provides installation instructions for Daikin VRV-X heat pump systems. It outlines procedures for removing a sealed rubber plug from the refrigerant piping, connecting the piping to outdoor units, and setting the power supply specifications. Key details include using accessory pipes for field piping connections, adding brazing material to joints, and selecting fuses based on circuit amperage ratings ranging from 32.2 to 84 amps depending on the outdoor unit model. Wiring must be insulation type 60245 IEC 57 and capable of handling the specified voltage and phase.

Uploaded by

Tangtang Satang
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 44

RXQ6ARY1

RXQ8ARY1
RXQ10ARY1
RXQ12ARY1
RXQ14ARY1
RXQ16ARY1
RXQ18ARY1
RXQ20ARY1
DR17-1044A Daikin Installation Manual VRV-X 44Page 3P508501-1E, 26Sept18
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Procedure 1

Use the following procedure to remove the sealed rubber plug:


Remove the valve cover and make sure that the stop valves are
fully closed.
1 Service port and service
1
port cover
2 Stop valve
3 Field piping connection pipe
2
4 Stop valve cover
3
4

Close direction

Procedure 2
1 Connect the vacuuming/recovery unit to service ports of all stop
valves.
6 10
9 8
7


1 A 12
13

B
14
4 C 11
15
2 3 5
1 Pressure reducing valve 10 Outdoor unit
2 Nitrogen 11 To indoor unit
3 Measuring instrument 12 Needle valve
4 Refrigerant R-410A tank (siphon system) 13 Stop valve
5 Vacuum pump 14 Field piping
6 Charge hose 15 Gas flow
7 Refrigerant auto charge valve A Valve A
8 Gas pipe stop valve B Valve B
9 Liquid pipe stop valve C Valve C

2 Recover gas and oil from the sealed rubber plug pipe by using
a recovery unit.

3 When all gas and oil is recovered from the sealed rubber plug
pipe, disconnect the charge hose and close the service ports.

4 Now remove the sealed rubber plug with the help of nose plier/
suitable instrument

CAUTION
Do not vent gases into the atmosphere.
(Refer to figure shown in
below)

17
10.2.3 Connecting refrigerant piping to the outdoor unit

INFORMATION
All local inter unit piping are field supplied except the
accessory pipes.

NOTICE
Precautions when connecting field piping. Add brazing
material as shown in the figure.

1
1

2 2

1
1

NOTICE
• Be sure to use the supplied accessory pipes when
carrying out piping work in the field.
• Be sure that the field installed piping does not touch
other pipes, the bottom panel or side panel. Especially
for the bottom and side connection, be sure to protect
the piping with suitable insulation, to prevent it from
coming into contact with the casing.

Connection from the stop valves to the field piping can be done by
using accessory pipes supplied as accessory.

The connections to the branch kits are the responsibility of the


installer (field piping).

18
19
20
21
22
High COP Model
Minimum circuit Recommended Wire
Model
ampere fuses Size
RXQ12AH 32.2 A 35 A
RXQ14AH 32.2 A 35 A
RXQ16AH 32.2 A 35 A
RXQ18AH 37.3 A 45 A
RXQ20AH 42.4 A 50 A
RXQ22AH 48.3 A 60 A Select and
install the
RXQ24AH 48.3 A 60 A
power
RXQ26AH 53.4 A 60 A supply
wiring in
RXQ28AH 54.7 A 60 A
accordance
RXQ30AH 59.8 A 70 A with IEC
60335-1
RXQ32AH 61.1 A 70 A
RXQ34AH 66.2 A 70 A
RXQ36AH 70.6 A 80 A
RXQ38AH 71.9 A 80 A
RXQ40AH 76.3 A 80 A
RXQ42AH 80.7 A 90 A
RXQ44AH 84 A 90 A

For all models:

Phase and frequency: 3N~50/60 Hz

Voltage: 380-415 V

Transmission line section: 0.75~1.25mm2, maximum length is 1000 m.

Remark: For other model please see detail in Engineering Data.

Note: Insulation of supply wiring must not lighter than 60245 IEC 57.

Phase and frequency: 3N~50/60 Hz

23