DR17-1044A Daikin Installation Manual VRV-X 44Page 3P508501-1E, 26Sept18
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Procedure 1
Close direction
Procedure 2
1 Connect the vacuuming/recovery unit to service ports of all stop
valves.
6 10
9 8
7
1 A 12
13
B
14
4 C 11
15
2 3 5
1 Pressure reducing valve 10 Outdoor unit
2 Nitrogen 11 To indoor unit
3 Measuring instrument 12 Needle valve
4 Refrigerant R-410A tank (siphon system) 13 Stop valve
5 Vacuum pump 14 Field piping
6 Charge hose 15 Gas flow
7 Refrigerant auto charge valve A Valve A
8 Gas pipe stop valve B Valve B
9 Liquid pipe stop valve C Valve C
2 Recover gas and oil from the sealed rubber plug pipe by using
a recovery unit.
3 When all gas and oil is recovered from the sealed rubber plug
pipe, disconnect the charge hose and close the service ports.
4 Now remove the sealed rubber plug with the help of nose plier/
suitable instrument
CAUTION
Do not vent gases into the atmosphere.
(Refer to figure shown in
below)
17
10.2.3 Connecting refrigerant piping to the outdoor unit
INFORMATION
All local inter unit piping are field supplied except the
accessory pipes.
NOTICE
Precautions when connecting field piping. Add brazing
material as shown in the figure.
1
1
2 2
1
1
NOTICE
• Be sure to use the supplied accessory pipes when
carrying out piping work in the field.
• Be sure that the field installed piping does not touch
other pipes, the bottom panel or side panel. Especially
for the bottom and side connection, be sure to protect
the piping with suitable insulation, to prevent it from
coming into contact with the casing.
Connection from the stop valves to the field piping can be done by
using accessory pipes supplied as accessory.
18
19
20
21
22
High COP Model
Minimum circuit Recommended Wire
Model
ampere fuses Size
RXQ12AH 32.2 A 35 A
RXQ14AH 32.2 A 35 A
RXQ16AH 32.2 A 35 A
RXQ18AH 37.3 A 45 A
RXQ20AH 42.4 A 50 A
RXQ22AH 48.3 A 60 A Select and
install the
RXQ24AH 48.3 A 60 A
power
RXQ26AH 53.4 A 60 A supply
wiring in
RXQ28AH 54.7 A 60 A
accordance
RXQ30AH 59.8 A 70 A with IEC
60335-1
RXQ32AH 61.1 A 70 A
RXQ34AH 66.2 A 70 A
RXQ36AH 70.6 A 80 A
RXQ38AH 71.9 A 80 A
RXQ40AH 76.3 A 80 A
RXQ42AH 80.7 A 90 A
RXQ44AH 84 A 90 A
Voltage: 380-415 V
Note: Insulation of supply wiring must not lighter than 60245 IEC 57.