6DL1132-6BL00-0PH1 Et200sp - Ha - DQ - 32x24vdc - 0 - 5a - en-US - en-US

6DL1132-6BL00-0PH1 et200sp_ha_dq_32x24vdc_0_5a_en-US_en-US

Uploaded by

Tanase Georgeta
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 36

Security information 1

Preface 2
2D Matrix code (QR code /
EAN code) 3
SIMATIC
Product overview 4
ET 200SP HA
DQ 32x24VDC/0.5A HA
Connection 5

Parameters 6
Equipment Manual

Displays and interrupts 7

Technical specifications 8
Drivers, parameters,
diagnostics messages and A
address space

6DL1132-6BL00-0PH1

08/2019
A5E48262762-AB
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage
to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices
referring only to property damage have no safety alert symbol. These notices shown below are graded according to
the degree of danger.

DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION
indicates that minor personal injury can result if proper precautions are not taken.

NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be
used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property
damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:

WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or
approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance
are required to ensure that the products operate safely and without any problems. The permissible ambient
conditions must be complied with. The information in the relevant documentation must be observed.

Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may
be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described.
Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this
publication is reviewed regularly and any necessary corrections are included in subsequent editions.

Siemens AG A5E48262762-AB Copyright © Siemens AG 2018 - 2019.


Digital Industries Ⓟ 11/2021 Subject to change All rights reserved
Postfach 48 48
90026 NÜRNBERG
GERMANY
Table of contents

1 Security information.............................................................................................................................. 5
2 Preface ................................................................................................................................................... 7
3 2D Matrix code (QR code / EAN code) .................................................................................................... 9
4 Product overview ................................................................................................................................. 11
4.1 I/O module......................................................................................................................... 11
4.2 Accessories ........................................................................................................................ 12
4.3 Output disable switch ........................................................................................................ 13
4.4 Pulling the I/O module in runtime....................................................................................... 13
4.5 Terminal blocks.................................................................................................................. 14
5 Connection........................................................................................................................................... 15
5.1 Pin assignment .................................................................................................................. 15
5.2 Sample connection scheme for 1-wire connection .............................................................. 16
5.3 Wiring diagram for actuators .............................................................................................. 16
5.4 Schematic circuit diagram .................................................................................................. 17
6 Parameters........................................................................................................................................... 19
6.1 Parameter types................................................................................................................. 19
6.2 Module/channel parameters............................................................................................... 19
6.3 Explanation of the module/channel parameters .................................................................. 20
6.3.1 Diagnostics, Missing supply voltage L+ ............................................................................... 20
6.3.2 Diagnostics, Short-circuit to ground.................................................................................... 20
6.3.3 Channel activated .............................................................................................................. 21
6.3.4 Reaction to CPU STOP......................................................................................................... 21
6.3.5 Substitute value ................................................................................................................. 21
6.3.6 Potential group .................................................................................................................. 21
6.3.7 Double-width terminal block .............................................................................................. 22
7 Displays and interrupts ........................................................................................................................ 23
7.1 Status and error displays .................................................................................................... 23
7.2 LEDs .................................................................................................................................. 24
7.2.1 DIAG LED ........................................................................................................................... 24
7.2.2 MT LED .............................................................................................................................. 24
7.2.3 Channel status LED ............................................................................................................ 25
7.2.4 PWR LED ............................................................................................................................ 25
7.3 Interrupts .......................................................................................................................... 25

DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB 3
Table of contents

8 Technical specifications ....................................................................................................................... 27


A Drivers, parameters, diagnostics messages and address space .......................................................... 31
A.1 Parameter assignment ....................................................................................................... 31
A.2 Parameter assignment and structure of the module/channel parameters............................. 32
A.3 Diagnostic messages.......................................................................................................... 34
A.4 Maintenance events........................................................................................................... 35
A.5 Address space .................................................................................................................... 35

Tables

Table A-1 Address space of the DQ 32x24VDC/0.5A HA ........................................................................... 36

Figures

Figure A-3 Configuration byte x and x+1 for the channels 0 to 31 ............................................................. 34
Figure A-2 Header information and module parameters of data record 128 .............................................. 33
Figure A-1 Structure of data record 128 ................................................................................................... 32

DQ 32x24VDC/0.5A HA
4 Equipment Manual, 08/2019, A5E48262762-AB
Security information 1
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary
to implement – and continuously maintain – a holistic, state-of-the-art industrial security
concept. Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems,
machines and networks. Such systems, machines and components should only be connected to
an enterprise network or the internet if and to the extent such a connection is necessary and only
when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be implemented, please
visit
https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are no longer
supported, and failure to apply the latest updates may increase customer’s exposure to cyber
threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed
under
https://www.siemens.com/industrialsecurity.

DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB 5
Security information

DQ 32x24VDC/0.5A HA
6 Equipment Manual, 08/2019, A5E48262762-AB
Preface 2
Validity of the documentation
This manual describes the following I/O module:

System family I/O module Article No.


SIMATIC; DQ 32x24VDC/0.5A HA 6DL1132-6BL00-0PH1
Distributed I/O System;
ET 200SP HA

It supplements the ET 200SP HA Distributed I/O system system manual.


Functions that generally relate to the system are described in this manual.
The information in this device manual and the system/function manuals enables you to put the
ET 200SP HA into operation.

Configuring the ET 200SP HA


You can configure the following components of the ET 200SP HA when the following updates
are installed:

Component of the ET 200SP HA Required updates


DQ 32x24VDC/0.5A HA HSP0276 V02.00.00

Conventions
Please also observe notes marked as follows:

Note
A note contains important information on the product described in the documentation, on the
handling of the product or on the section of the documentation to which particular attention
should be paid.

DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB 7
Preface

DQ 32x24VDC/0.5A HA
8 Equipment Manual, 08/2019, A5E48262762-AB
2D Matrix code (QR code / EAN code) 3
The 2D matrix code on the product is a coded representation of the product-specific article
number.

Access to product-related information


For reading the 2D matrix code, SIEMENS offers an app for mobile use.
Information about the app and the download can be found on the Internet: "Mobile use via app
(https://support.industry.siemens.com/cs/ww/en/sc/2067)".
The app provides direct access to the technical forum and product-related posts, such as:
• FAQs
• Application examples
• Manuals
• Certificates
• Product notices

DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB 9
2D Matrix code (QR code / EAN code)

DQ 32x24VDC/0.5A HA
10 Equipment Manual, 08/2019, A5E48262762-AB
Product overview 4
4.1 I/O module

Definition
The DQ 32x24VDC/0.5A I/O module is a digital output module with 32 power outputs for process
control.
In addition to the technical specifications, this module has the following properties:
• Source output (PNP, switching to P potential)
• Suitable for solenoid valves, DC contactors, and indicator lights
• Re-parameterization in RUN

DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB 11
Product overview
4.2 Accessories

Description
The I/O module consists of the following components:

 DQ
32x 24V DC/ 0,5A HA

 DIA G MT


 1 DQ. 0+
3 DQ. 2+ DQ.1+ 2
DQ a

5 DQ. 4+ DQ. 3+ 4
7 DQ. 6+ DQ. 5+ 6
DQ. 7+
 9 DQ. 0+ 8
11 DQ. 2+ DQ.1+ 10
DQ b

13 DQ. 4+ DQ. 3+ 12
15 DQ. 6+ DQ. 5+ 14
DQ. 7+ 16
17 DQ. 0+
19 DQ. 2+ DQ.1+ 18
DQ c

21 DQ. 4+ DQ. 3+ 20
23 DQ. 6+ DQ. 5+ 22
DQ. 7+ 24
25 DQ. 0+


27 DQ. 2+ DQ.1+ 26
DQ d

29 DQ. 4+ DQ. 3+ 28
31 DQ. 6+ DQ. 5+ 30
DQ. 7+ 32
1P1 L+ 24V
2P1 L+ 24V DC M 1P2
DC
MA X. 10 A M 2P2


.0 .1
.2 .3
DQ a


.4 .5
.6 .7
.0 .1


.2 .3
DQ b

.4 .5
.6 .7
.0 .1
.2 .3
DQ c


.4 .5
.6 .7
.0 .1
.2 .3 X 2
DQ d

.4 .5 3 4


.6


.7 V 1.0.0
PW R
CC0 0


6DL113 2-6BL
00- 0PH1

① Module type and designation ⑧ Output disable switch


② LED for diagnostics ⑨ Module type color coding
③ LED for maintenance ⑩ Product version
④ 2D matrix code ⑪ Function status and firmware version
⑤ Wiring diagram ⑫ Color code for selection of the color-coded labels
⑥ LEDs for channel status ⑬ Serial number
⑦ LED for supply voltage ⑭ Article number

4.2 Accessories

Definition
Accessories for the I/O module must be ordered separately.

Description
The following accessories must be ordered separately:
• Labeling strips
• Color-coded labels

DQ 32x24VDC/0.5A HA
12 Equipment Manual, 08/2019, A5E48262762-AB
Product overview
4.4 Pulling the I/O module in runtime

• Reference identification label


• Shield connector

4.3 Output disable switch

Definition
The output disable switch switches the I/O module load-free.

NOTICE
Dangerous plant conditions possible (disconnect the load)
If you want to pull the I/O module in runtime, you have to press the output disable switch for
3 seconds for the I/O module to be load free (deenergized).
Pulling the I/O module in runtime (Page 13)

4.4 Pulling the I/O module in runtime

Requirement
The normally closed contacts are closed.

Procedure
Press the output disable switch for 3 seconds.

Note
Pressing the output disable switch interrupts any ongoing firmware update. A firmware update
cannot be performed when the device is deenergized.

Result
The I/O module is load-free.
The LED DIAG flashes red, the LED MT lights up yellow and the I/O module generates a
diagnostics message.
Status and error displays (Page 23)

DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB 13
Product overview
4.5 Terminal blocks

4.5 Terminal blocks

Definition
The terminal blocks provide the process terminals (push-in terminals) for the connection of
components, such as devices.

Description
The following terminal blocks are available for the I/O module:

Article No. Color Description


6DL1193-6TP00-0DH1 Lit
6DL1193-6TP00-0BH1 Dark
6DL1193-6TP00-0DN0 Lit With additional potential distributor for ground connection of the actuators
6DL1193-6TP00-0BN0 Dark With additional potential distributor for ground connection of the actuators

Note
The terminal blocks are not included in the scope of delivery of the I/O module and must be
ordered separately.
You can find additional information on the configuration in the system manual.

DQ 32x24VDC/0.5A HA
14 Equipment Manual, 08/2019, A5E48262762-AB
Connection 5
5.1 Pin assignment

Definition
The pin assignment provides information about the arrangement and identification of the
terminals when wiring a connector.

Description
The general pin assignment is structured as follows:

Terminal Allocation Terminal Allocation Explanations


1 DQ a/DQ.0+ 2 DQ a/DQ.1+ DQ a /DQ.n+: Output signal, channel n (0…7)
3 DQ a/DQ.2+ 4 DQ a/DQ.3+ DQ b /DQ.n+: Output signal, channel n (8…15)
5 DQ a/DQ.4+ 6 DQ a/DQ.5+ DQ c /DQ.n+: Output signal, channel n (16...23)
7 DQ a/DQ.6+ 8 DQ a/DQ.7+ DQ d /DQ.n+: Output signal, channel n (24…31)
9 DQ b/DQ.0+ 10 DQ b/DQ.1+ M: Ground
11 DQ b/DQ.2+ 12 DQ b/DQ.3+ 1P1: Supply voltage L+ of the voltage bus 1P
13 DQ b/DQ.4+ 14 DQ b/DQ.5+ 2P1: Supply voltage L+ of the voltage bus 2P
15 DQ b/DQ.6+ 16 DQ b/DQ.7+ 1P2: Ground reference of the voltage bus 1P
17 DQ c/DQ.0+ 18 DQ c/DQ.1+ 2P2: Ground reference of the voltage bus 2P
19 DQ c/DQ.2+ 20 DQ c/DQ.3+
21 DQ c/DQ.4+ 22 DQ c/DQ.5+ 1 DQ.0+ DQ.1+ 2
3 DQ.2+ 4
DQ a

23 DQ c/DQ.6+ 24 DQ c/DQ.7+ DQ.3+


5 DQ.4+ DQ.5+ 6
25 DQ d/DQ.0+ 26 DQ d/DQ.1+ 7 DQ.6+ DQ.7+ 8
27 DQ d/DQ.2+ 28 DQ d/DQ.3+ 9 DQ.0+ DQ.1+ 10
11 DQ.2+ DQ.3+
DQ b

12
29 DQ d/DQ.4+ 30 DQ d/DQ.5+ 13 DQ.4+ DQ.5+ 14
31 DQ d/DQ.6+ 32 DQ d/DQ.7+ 15 DQ.6+ DQ.7+ 16
1P1 L+ 1P2 M 17 DQ.0+ DQ.1+ 18
19 DQ.2+ DQ.3+
DQ c

20
2P1 L+ 2P2 M 21 DQ.4+ DQ.5+ 22
23 DQ.6+ DQ.7+ 24
25 DQ.0+ DQ.1+ 26
27 DQ.2+ DQ.3+ 28
DQ d

29 DQ.4+ DQ.5+ 30
31 DQ.6+ DQ.7+ 32

1P1 L+ 24VDC M 1P2


2P1 L+ 24VDC M 2P2
MAX. 10 A

DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB 15
Connection
5.3 Wiring diagram for actuators

General pin assignment with potential distributor


The potential distributor with 36 M terminals is located on the right side of the terminal block.
The left side corresponds to the general pin assignment.

Note
Connection information
• The M terminals on the potential distributor are intended exclusively for the loads connected
to the I/O module using a two-wire connection system. You may not use these terminals as
the ground terminals for other devices in the system.
• Ensure that the total current does not exceed 10 A.

5.2 Sample connection scheme for 1-wire connection

Example

'4Q

'4 Q 

'4 Q 

• Ensure that the total current does not exceed 10 A.


• Ensure that the total current does not exceed 2 A for each terminal.

5.3 Wiring diagram for actuators

Example
The figure below shows the connection of actuators with potential distributor.

'4Q

This connection variant is approved only for terminal blocks with potential distributor.

DQ 32x24VDC/0.5A HA
16 Equipment Manual, 08/2019, A5E48262762-AB
Connection
5.4 Schematic circuit diagram

5.4 Schematic circuit diagram

Definition
A block diagram contains the schematic representation of individual function blocks.

Description
The block diagram for the I/O module is structured as follows:


%DFNSODQHEXVLQWKHFDUULHUPRGXOH

(763+$

%DFNSODQHEXV
LQWHUIDFH
7HUPLQDOEORFN
3RZHUEXV

0 5HYHUVHSRODULW\
SURWHFWLRQ 0
33
/ /
33
,QIHHGPRGXOHVXSSO\
DWOLJKWWHUPLQDOEORFN

DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB 17
Connection
5.4 Schematic circuit diagram

DQ 32x24VDC/0.5A HA
18 Equipment Manual, 08/2019, A5E48262762-AB
Parameters 6
6.1 Parameter types

Definition
You define and thereby influence the functions supported by the module operation of the I/O
module via the parameter types.

6.2 Module/channel parameters

Definition
Module/channel parameters are specific parameters whose configuration can affect the entire
module or channels.

Note
Each re-parameterization resets the corresponding reaction.

Description
The following module/channel parameters are available:

Parameters Value range Default Parameter re‐ Efficiency range


assignment in
RUN
Diagnostics, Missing supply • Enabled Enabled Yes Module
voltage L+ (Page 20) • Disabled
Diagnostics, Short-circuit to • Enabled Enabled Yes Channel
ground (Page 20) • Disabled
Channel activated • Enabled Enabled Yes Channel
(Page 21) • Disabled
Reaction to CPU STOP • Shutdown Shutdown Yes Channel
(Page 21) • Keep last value
• Output substitute value
Substitute value (Page 21) 1
• 0 0 Yes Channel
• 1

DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB 19
Parameters
6.3 Explanation of the module/channel parameters

Parameters Value range Default Parameter re‐ Efficiency range


assignment in
RUN
Potential group (Page 21) • Potential group of the left mod‐ Use potential No Module
ule (dark gray terminal block) group of the left
module
• New potential group (light gray
terminal block)
• No potential group (black termi‐
nal block)
Double-width terminal • Enabled Disabled No Configuration (HW
block (Page 22)2 Config)
• Disabled
1
Only applicable when the value "Output substitute value" has been enabled for the "Reaction to CPU STOP" parameter.
2
I/O module on terminal block with potential distributor: Select the "Double-width terminal block" parameter in the hardware
properties for the I/O module.

6.3 Explanation of the module/channel parameters

6.3.1 Diagnostics, Missing supply voltage L+

Definition
Enabling of the diagnostics for missing or insufficient supply voltage L+.

6.3.2 Diagnostics, Short-circuit to ground

Definition
When the digital output is enabled, you can enable diagnostics that report a digital output short
circuit to M.
A short circuit to M is only recognized when the output is switched on (output value = 1).

Note
Short-circuit signal
If the output is disabled with pending short circuit (output value = 0), the diagnostics Short-
circuit to M is reset.

DQ 32x24VDC/0.5A HA
20 Equipment Manual, 08/2019, A5E48262762-AB
Parameters
6.3 Explanation of the module/channel parameters

6.3.3 Channel activated

Definition
Specifies whether a channel is activated or deactivated.

6.3.4 Reaction to CPU STOP

Definition
Specifies the behavior of the digital output as a reaction to CPU stop or to failure of
communication between the interface module and CPU.

6.3.5 Substitute value

Definition
The substitute value is output by the module at CPU STOP if you set the "Reaction to CPU STOP"
parameter to "Substitute value".

Description
The entered substitute value is output by the I/O module in the following cases:
• When there is no connection to the CPU (for example, PROFInet cable unplugged)
• With CPU STOP

6.3.6 Potential group

Definition
A potential group consists of a group of directly adjacent I/O modules within an ET 200SP HA
station that are supplied via a common supply voltage.

Description
A potential group is built up from left to right by using terminal blocks.
A new potential group starts on the left side with a light gray terminal block, via which the supply
voltage for the potential group is fed in.
The potential group is continued to the right with dark gray terminal blocks and ends when a
new potential group is built up next to it.

DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB 21
Parameters
6.3 Explanation of the module/channel parameters

The potential group also ends if there is a black terminal block next to it. Black terminal blocks
are fed individually and cannot be included in potential groups.
You can find additional information on the configuration of the potential group in the system
manual SIMATIC; Distributed I/O System; ET 200SP HA.

6.3.7 Double-width terminal block

Definition
The parameter applies to the I/O module on the terminal block with a potential distributor.
This parameter only affects the configuration in HW Config.

Description
The "Double-width terminal block" parameter can be activated in the hardware properties for the
I/O module.

DQ 32x24VDC/0.5A HA
22 Equipment Manual, 08/2019, A5E48262762-AB
Displays and interrupts 7
7.1 Status and error displays

Definition
The LED displays are status and fault indicators.
Diagnostic messages and maintenance events, as well as their possible causes and solutions, are
described in the diagnostic messages and maintenance events.
Diagnostic messages (Page 34)

Description
The following figure explains the LED displays of the I/O module.


DQ HA
32x24VDC/0,5A
DIAG MT


1 DQ.0 + DQ.1+ 2
DQ.3 + 4
DQ a

3 DQ.2 +
5 DQ.4 + DQ.5 + 6
7 DQ.6 + DQ.7 + 8
9 DQ.0 + DQ.1+ 10
DQ b

11 DQ.2 + DQ.3 + 12
13 DQ.4 + DQ.5 + 14
15 DQ.6 + DQ.7 + 16
17 DQ.0 + DQ.1+ 18
DQ c

19 DQ.2 + DQ.3 + 20
21 DQ.4 + DQ.5 +22
23 DQ.6 + DQ.7 + 24
25 DQ.0 + DQ.1+ 26
DQ.3 + 28
DQ d

27 DQ.2 +
29 DQ.4 + DQ.5 + 30
31 DQ.6 + DQ.7 + 32

1P1 L+ 24VDC M 1P2


2P1 L+ 24VDC M 2P2
MAX. 10 A

.0 .1
.2 .3
DQ a

.4 .5
.6 .7
.0 .1
.2 .3
DQ b

.4 .5
.6 .7
.0 .1
.2 .3
DQ c

.4 .5
.6 .7
.0 .1 X 2
.2 .3
DQ d

3 4
.4 .5 V 1.0.0
.6 .7

 PWR CC00

6DL1132-6BL00-0PH1

① DIAG LED (Page 24) (green/red)


② MT LED (Page 24) (yellow)
③ Channel status LED (Page 25) (green)
④ PWR LED (Page 25) (green)

DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB 23
Displays and interrupts
7.2 LEDs

7.2 LEDs

7.2.1 DIAG LED

Definition
The DIAG LED provides you diagnostic information.

Description
The diagnostic display of the DIAG LED is as follows:

DIAG LED Meaning


The power supply of the ET 200SP HA is disrupted or switched off.
Off
Module is not configured.
flashes
Module parameters are assigned. No diagnostic message is pending.
On
Module parameters are assigned. At least one diagnostic message is pending.
flashes

7.2.2 MT LED

Definition
The MT LED provides you with information about maintenance.

Description
The MT LED indicates the following statuses:

MT LED Meaning
No maintenance is required.
Off
Maintenance is required. At least one maintenance event has occurred.
On Note: After activating the output disable switch, only the associated diagnostic alarm
is pending.

DQ 32x24VDC/0.5A HA
24 Equipment Manual, 08/2019, A5E48262762-AB
Displays and interrupts
7.3 Interrupts

7.2.3 Channel status LED

Definition
The green LED channel status shows the signal level at the input terminal.

Description
The channel status LED indicates the following statuses:

LED channel status Meaning


• Process signal = 0 or channel disabled
Off • Module has been switched off
• Module or channel diagnostics pending
Channel enabled and process signal = 1 (no channel diagnostics / module diag‐
On nostics pending)

7.2.4 PWR LED

Definition
The PWR LED provides you status information about supply voltage L+.

Description
The PWR LED indicates the following status:

PWR LED Meaning


Supply voltage L+ missing.
Off
Supply voltage L+ present.
On

7.3 Interrupts

Definition
A diagnostic interrupt is an alarm that reports activated events of a device status to the system
operator with the appropriate operator authorization (maintenance and service).

DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB 25
Displays and interrupts
7.3 Interrupts

Description
The I/O module generates a diagnostics interrupt at the following events:
• Supply voltage L+ missing
• Parameter assignment error
• Channel/component temporarily unavailable
• Short-circuit to ground
• Retentive memory in carrier module defective
• Retentive memory in the terminal block defective
• Module is faulty
• Shutdown on button activation
The I/O module generates a maintenance message for the following events:
• Retentive memory in carrier module defective
• Retentive memory in the terminal block defective

DQ 32x24VDC/0.5A HA
26 Equipment Manual, 08/2019, A5E48262762-AB
Technical specifications 8
Technical specifications of the DQ 32×24VDC/0.5A HA

Article number 6DL1132-6BL00-0PH1


General information
Product type designation DQ 32x24VDC/0.5A HA
Firmware version V1.0
• FW update possible Yes
Usable terminal block TB type H1 and N0
Color code for module-specific color identifica‐ CC00
tion plate
Product function
• I&M data Yes; I&M0 to I&M3
Engineering with
• STEP 7 TIA Portal configurable/integrated V16
from version
• STEP 7 configurable/integrated from version V5.6
• PCS 7 configurable/integrated from version V9.0
• PCS neo can be configured/integrated from V3.0
version
• PROFINET from GSD version/GSD revision GSDML V2.3
Operating mode
• DQ Yes
• DQ with energy-saving function No
• PWM No
• Oversampling No
Redundancy
• Redundancy capability No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption (rated value) 60 mA; without load
Current consumption, max. 70 mA; without load
output voltage / header
Rated value (DC) 24 V
Power loss

DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB 27
Technical specifications

Article number 6DL1132-6BL00-0PH1


Power loss, typ. 1.6 W; minimum - typ. specification not possible
because load-dependent
Address area
Address space per module
• Inputs 4 byte; QI of the outputs
• Outputs 4 byte
Digital outputs
Number of digital outputs 32
Current-sinking No
Current-sourcing Yes
Digital outputs, parameterizable Yes
Short-circuit protection Yes; Clocked electronically
• Response threshold, typ. 2 A; Overload / short circuit
Open-circuit detection No
Overload protection Yes
Limitation of inductive shutdown voltage to Typ. L+ (-53 V)
Controlling a digital input Yes
Switching capacity of the outputs
• with resistive load, max. 0.5 A
• on lamp load, max. 5W
Load resistance range
• lower limit 48 Ω
• upper limit 4 kΩ
Output current
• for signal "1" rated value 0.5 A
• for signal "0" residual current, max. 0.1 mA
Output delay with resistive load
• "0" to "1", typ. 54 µs
• "1" to "0", typ. 48 µs
Parallel switching of two outputs
• for uprating No
• for redundant control of a load Yes; only outputs of the same group
Switching frequency
• with resistive load, max. 100 Hz
• with inductive load, max. 2 Hz
• on lamp load, max. 10 Hz
Total current of the outputs
• Current per channel, max. 0.5 A
• Current per module, max. 10 A
Total current of the outputs (per module)
horizontal installation
– up to 70 °C, max. 10 A
vertical installation

DQ 32x24VDC/0.5A HA
28 Equipment Manual, 08/2019, A5E48262762-AB
Technical specifications

Article number 6DL1132-6BL00-0PH1


– up to 60 °C, max. 10 A
Cable length
• shielded, max. 1 000 m
• unshielded, max. 600 m
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
• Diagnostic alarm Yes
Diagnoses
• Monitoring the supply voltage Yes
– parameterizable Yes
• Wire-break No
• Short-circuit Yes
• Short-circuit to M Yes; channel by channel
• Short-circuit to L+ No
• Group error Yes
Diagnostics indication LED
• MAINT LED Yes; Yellow LED
• Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
• Channel status display Yes; green LED
• for channel diagnostics No
• for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
• between the channels No
• between the channels and backplane bus Yes
Isolation
Isolation tested with 1 500 V DC/1 min, type test
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -40 °C
• horizontal installation, max. 70 °C
• vertical installation, min. -40 °C
• vertical installation, max. 60 °C
Dimensions
Width 22.5 mm
Height 115 mm
Depth 138 mm
Weights
Weight, approx. 150 g

DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB 29
Technical specifications

Power supply (SELV/PELV)


Ensure that the power supply is safely disconnected in accordance with the following standard:
IEC/UL61010-2-201 This separation is referred to in the standard as SELV (Safety Extra Low
Voltage) / PELV (Protective Extra Low Voltage).
Make sure that the supply and input voltages of the ET 200SP HA IO device are generated safely
separately:
Nominal value: 24 VDC +-20% ( )

Cycle time
The cycle time describes the time slice in which new process values are output. The cycle time
of the I/O module is 150 μs.

Response to short-circuit detection


The I/O module is equipped with an overload protection that triggers as of about 2 A. When this
limit is exceeded, the I/O module automatically limits the current (typically: to 1.3 A). If the
overload continues, it results in a temperature increase in the I/O module. The respective output
switches on and off again cyclically (clocked).

Note
Cable length
Ensure sufficient low-resistance cable routing to the sensor/actuators to reach the response
threshold. Depending on the cable cross-section used, there may be restrictions in the cable
lengths that can be used.

DQ 32x24VDC/0.5A HA
30 Equipment Manual, 08/2019, A5E48262762-AB
Drivers, parameters, diagnostics messages and
address space A
A.1 Parameter assignment

Parameter assignment in the user program


You can reconfigure individual channels of the module in RUN without this having an effect on
the other channels.

Changing parameters in RUN


The parameters are transferred to the module with the "WRREC" instruction via data record 128.

Output parameter STATUS of the WRREC


If errors occur when transferring parameters with the "WRREC" instruction, the module
continues operation with the previous parameter assignment. The STATUS output parameter
contains the corresponding error code.
The STATUS output parameter is 4 bytes long and is configured as followed:
• Byte1: Function_Num, general error code
• Byte2: Error_Decode, location of the error code
• Byte3: Error_Code_1, error code
• Byte4: Error_Code_2, manufacturer-specific extension of the error code
Module-specific errors are displayed via Error_Decode = 0x80 and Error_Code_1 / Error_Code_2.

Error_ Error_ Cause Remedy


Code_1 Code_2
0xB0 0x00 Number of the data record unknown Enter valid number for data record.
0xB1 0x01 Length of the data record is incorrect Enter valid value for data record length.
0xB2 0x00 to 0xFF Module cannot be reached • Check station - is the module plugged in
correctly?
• Check the parameters of the WRREC in‐
struction.
0xE0 0x01 Wrong version in the header Correct the version number of the parameter
block.
0xE0 0x02 Header error (number or length of parameter Correct the length and number of the param‐
block) eter blocks.
0xE1 0x01 Reserved bit set Check and correct the parameters
0xE1 0x06 Invalid encoding for substitute value reaction
0xE1 0x0E Invalid redundancy parameter assignment

DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB 31
Drivers, parameters, diagnostics messages and address space
A.2 Parameter assignment and structure of the module/channel parameters

A.2 Parameter assignment and structure of the module/channel


parameters

Structure of data record 128


Data record 128 has a length of 76 bytes.
It contains the channel parameters of the 32 channels.

%\WH +HDGHULQIRUPDWLRQ PRGXOH

%\WH 0RGXOHSDUDPHWHUV

%\WH +HDGHULQIRUPDWLRQ FKDQQHO

%\WH &KDQQHO
'LJLWDORXWSXW

%\WH &KDQQHO
'LJLWDORXWSXW

%\WH &KDQQHO
'LJLWDORXWSXW

%\WH &KDQQHO
'LJLWDORXWSXW

%\WH &KDQQHO
'LJLWDORXWSXW

Figure A-1 Structure of data record 128

DQ 32x24VDC/0.5A HA
32 Equipment Manual, 08/2019, A5E48262762-AB
Drivers, parameters, diagnostics messages and address space
A.2 Parameter assignment and structure of the module/channel parameters

Header information and module parameters


The following figure shows the configuration of the header information and module parameters.

       
%\WH        

0LQRUYHUVLRQ
0DMRUYHUVLRQ
5HVHUYHG

       
%\WH         1XPEHURIVXEVHTXHQWSDUDPHWHUVWUXFWXUHV

       
%\WH         1XPEHURIVXEVHTXHQWPRGXOHSDUDPHWHUEORFNV

       
%\WH         /HQJWKRIWKHPRGXOHSDUDPHWHUEORFN

       
%\WH       
'LDJQRVWLFVPLVVLQJVXSSO\YROWDJH/

       
%\WH         5HVHUYHG

       
%\WH 5HVHUYHG

       
%\WH 5HVHUYHG

       
%\WH 5HVHUYHG

       
%\WH 5HVHUYHG

       
%\WH         1XPEHURIVXEVHTXHQWFKDQQHOSDUDPHWHUEORFNV 

       
%\WH         /HQJWKRIWKHFKDQQHOSDUDPHWHUEORFN E\WHV

Figure A-2 Header information and module parameters of data record 128

Channel parameters
Each channel parameter block contains the channel parameters for a digital output (2 bytes).

DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB 33
Drivers, parameters, diagnostics messages and address space
A.3 Diagnostic messages

The following figure shows the configuration of the channel parameters for channels 0 to 31.
x = 12 + (channel number * 2); with channel number = 0…31
All unused bits and the bits or bytes marked as "reserved" must be set to zero.
You activate a channel parameter by setting the corresponding bit to "1" or the corresponding
value.

       
%\WH[        (QDEOHGLDJQRVWLFV

6KRUWFLUFXLWWRJURXQG

       
%\WH[    

&KDQQHODFWLYDWHG
 'LVDEOHG
 (QDEOHG
6XEVWLWXWHYDOXHEHKDYLRU
 6ZLWFKRII
 .HHSODVWYDOXH
 2XWSXWVXEVWLWXWHYDOXH

6XEVWLWXWHYDOXHV
 6XEVWLWXWHYDOXH
 6XEVWLWXWHYDOXH
Figure A-3 Configuration byte x and x+1 for the channels 0 to 31

A.3 Diagnostic messages

Diagnostic messages
A diagnostics message is generated for each diagnostics event and the DIAG LED on the I/O
module flashes red or the MT LED lights up yellow.
The diagnostics messages can be read in the diagnostics buffer of the CPU.
Diagnostic messages are assigned either channel-specific to an output or assigned as module
messages to all outputs. All channels are switched off for diagnostics messages that affect the
entire module. Only the corresponding digital output is affected by diagnostics messages, which
refer to individual channels.

Diagnostics Error code Assign‐ Meaning Remedy


message ment
Parameter as‐ 10H Module • Parameter assignment does not match the • Correct the parameter as‐
signment error terminal block used signment
• Incorrect parameter assignment • Check terminal block
Supply voltage 11H Module Supply voltage L+ missing or too low • Check wiring of the supply
missing voltage at the terminal block
• Check terminal block type

DQ 32x24VDC/0.5A HA
34 Equipment Manual, 08/2019, A5E48262762-AB
Drivers, parameters, diagnostics messages and address space
A.5 Address space

Diagnostics Error code Assign‐ Meaning Remedy


message ment
Channel/compo‐ 1FH Module Firmware update is in progress or has been • Restart the firmware update
nent temporarily canceled during the update. The module gen‐ • Wait for firmware update
unavailable erates no process and substitute values in this
state.
Module is faulty 100H Module Module is faulty Replace I/O module
Short-circuit to M 106H Channel Short-circuit of the actuator supply to ground Correction of the process wiring
Only effective in the connected state: Output
value=1
Shutdown on 122H Module The output disable switch was activated. Pull module
button activation
Retentive memo‐ 154H Module Fault detected in the memory block on the Replace carrier module
ry in carrier mod‐ carrier module during startup.
ule defective
Retentive memo‐ 155H Module Fault detected in the memory block on the Replace terminal block
ry in the terminal terminal block during startup.
block defective

A.4 Maintenance events

Maintenance events
A maintenance event is generated for each maintenance required identified. The MT LED lights
up on the module.
Maintenance messages have no direct effect on the function of the module or digital outputs.

Maintenance Error code Assign‐ Meaning / Cause Remedy


message ment
Retentive memo‐ 154H Module Fault detected in the memory block on the Replace carrier module
ry in carrier mod‐ carrier module during operation.
ule defective
Retentive memo‐ 155H Module Fault detected in the memory block on the ter‐ Replace terminal block
ry in the terminal minal block during operation.
block defective

A.5 Address space

Abbreviations
• "IB" stands for input byte, that is, the module start address in the input area
• "QB" stands for output byte, that is the module start address in the output area
• "DQn" stands for digital output n
• "QDQn" stands for the value status (QI) of digital output n

DQ 32x24VDC/0.5A HA
Equipment Manual, 08/2019, A5E48262762-AB 35
Drivers, parameters, diagnostics messages and address space
A.5 Address space

Address space
The following figure shows the mapping of the address space of the DQ 32x24VDC/0.5A HA:

Table A-1 Address space of the DQ 32x24VDC/0.5A HA

IB x + AB x + 7 6 5 4 3 2 1 0
0 - QDQ7 QDQ6 QDQ5 QDQ4 QDQ3 QDQ2 QDQ1 QDQ0
1 - QDQ15 QDQ14 QDQ13 QDQ12 QDQ11 QDQ10 QDQ9 QDQ8
2 - QDQ23 QDQ22 QDQ21 QDQ20 QDQ19 QDQ18 QDQ17 QDQ16
3 - QDQ31 QDQ30 QDQ29 QDQ28 QDQ27 QDQ26 QDQ25 QDQ24
- 0 DQ7 DQ6 DQ5 DQ4 DQ3 DQ2 DQ1 DQ0
- 1 DQ15 DQ14 DQ13 DQ12 DQ11 DQ10 DQ9 DQ8
- 2 DQ23 DQ22 DQ21 DQ20 DQ19 DQ18 DQ17 DQ16
- 3 DQ31 DQ30 DQ29 DQ28 DQ27 DQ26 DQ25 DQ24

Evaluate value status


There is a bit value status for each digital output in the input address space.
Irrespective of the diagnostics enables, each value status provides information on the validity of
the corresponding process value.
• Value status = 1: Process value okay, "good"
• Value status = 0: Process value not okay, "bad"
Basically, the value status is set to "good" if the digital value can be output without error. The
value status is set to "bad" in the following cases:
• The digital value cannot be output due to an error.
• The digital channel is deactivated.

DQ 32x24VDC/0.5A HA
36 Equipment Manual, 08/2019, A5E48262762-AB