CO2 Technical Data Sheets - 2020 UL FM VDS
CO2 Technical Data Sheets - 2020 UL FM VDS
Unit 36-38
APD Industrial park
Elsecar street, Kya Sand
Table of contents
I Table of contents 2
II CO2 agent specification 3
III High pressure CO2 cylinders 4
IV Cylinder mounting straps and pipe clamps 5
V Electrical actuator for CO2 Valves with reset tool 6
VI CO2 cylinder valve 7
VII Pneumatic and manual actuators 8
VIII High pressure discharge hose 9
IX Pneumatic pilot hose and pneumatic slave hose 10
X End plug and Odouriser 11
XI Non return valve 12
XII Total flood and local application nozzles 13
XIII Discharge manifold 14
XIV Warning signage 15
XV General arrangement 16
XVI General installation notes 17
XVII Material safety data sheet 18-19
Red G Page 2
High pressure Carbon Dioxide fire suppression systems
The original "clean" agent, carbon dioxide suppresses fire without leaving behind an agent to damage sensitive
equipment. And because there is no agent to clean up, you’re back in business faster. To provide the most economical
system arrangement without sacrificing performance, we offer both Total Flooding and Local Application, high pressure
systems (excluding distribution pipework and fittings)
DESCRIPTION
Carbon dioxide is a plentiful, non-corrosive, non-conductive, dry, clean agent gas that does not support combustion nor
react with most substances. It has a low toxicity classification by Underwriters Laboratories (Group 5a). It is commonly
compressed under its own pressure to the liquid state for storage and transportation in ISO 9809-1 cylinders. Upon
release, it discharges under its own pressure giving the appearance of steam as its low temperature crystalizes water in
the air. For fire suppression purposes the discharge is designed to raise the carbon dioxide concentration in the hazard.
This removes the free oxygen which supports combustion*, and results in fire extinguishment. The resultant lack of free
oxygen dictates that total flooding hazards are evacuated immediately, and carbon dioxide from local application be
avoided by personnel.
For local application systems, the liquid phase and vapour phases of the CO 2 are used to accomplish fire suppression.
PERFORMANCE
Carbon dioxide is an effective fire extinguishing agent that can be used on many types of fires. It is effective for surface
fires, such as flammable liquids and most solid combustible materials. It expands at a ratio of 450 to 1 by volume. Other
desirable attributes are its high degree of effectiveness, its excellent thermal stability, and freedom from deterioration.
In addition, carbon dioxide has so many additional commercial uses that refills are available in practically every large
city or seaport throughout the world. Criteria for quantity and concentration of carbon dioxide are developed in SANS
306:4 for both local and total flooding applications.
ORDERING INFORMATION
Carbon dioxide cylinders for use in engineered systems may be ordered in 45kg cylinder sizes.
APPROVALS
The 45kg CO2 cylinders are manufactured in accordance with ISO 9809-1 and all have TUV approval certificates.
The manifolds are pressure tested to 190Bar in accordance with SANS 306:4 by a SANAS approved HP test station.
PHYSICAL DATA
Chemical Symbol CO2
Molecular Weight 44.01
Specific volume @ 20°C & 101,325 kPa 547 ml/g
Density gas @ 101,325 kPa & 20°C 1.839 kg/m3
Relative density (Air=1) @ 101,325 kPa 1,522
Colour None
Taste Acidic
Red G Page 3
High pressure Carbon Dioxide fire suppression systems
TECHNICAL REQUIREMENTS
1: Manufacture Standard: ISO 9809-1:2010; FINISH
2: Manufacture Process: Seamless Steel Tube; Primed and painted
signal RED in
3: Working Pressure: 166.7bar;
accordance with SANS
4: Hydraulic Testing Pressure: 250bar; 306:4
5: Minimum Burst Pressure: 400bar;
6: Material: 37Mn, Chemical Composition
Material C Si Mn P S Cr Ni Cu V+Ti+B+Nb+Zr
Minimum Average
≥780a ≥660 ≥14 225-275
28 35
“A” Standard
PZ27.8 GB8335
1”.14 BS 341
25E ISO11363-1
Capacity+5%/0(L) 67.5
Weight (kg) ~ 76
Red G Page 4
High pressure Carbon Dioxide fire suppression systems
P/N RED011
DESCRIPTION
Cylinder Straps are made of galvanised steel. All
mounting hardware is supplied by the system installer.
MATERIALS:
Galvanised Steel
Red G Page 5
High pressure Carbon Dioxide fire suppression systems
P/N COF1120004 – (Electrical Actuator for P/N COA023076 valves) – VDS / UL / FM APPROVED
Technical Data:
current 0,5A
Red G Page 6
High pressure Carbon Dioxide fire suppression systems
Technical Data:
Red G Page 7
High pressure Carbon Dioxide fire suppression systems
Pneumatic actuator
Technical Data:
Technical Data:
Manual actuator
Technical Data:
Red G Page 8
High pressure Carbon Dioxide fire suppression systems
P/N CO2023
Technical Data:
12.7 x 480
Red G Page 9
High pressure Carbon Dioxide fire suppression systems
P/N CO2036
Technical Data:
P/N CO2037
Technical Data:
Red G Page 10
High pressure Carbon Dioxide fire suppression systems
End plug
P/N CO2034
Technical Data:
1/8” NPT
Brass fitting
Fit the end plug into the port of the double entry pneumatic or manual/pneumatic actuator which is on the last cylinder
in the bank.
Tighten with a spanner.
Odouriser
P/N CO2025
Technical Data:
1/2” NPT
Brass fitting
To be installed on the manifold (or distribution piping for a one cylinder system)
Red G Page 11
High pressure Carbon Dioxide fire suppression systems
P/N CO2021
Non-return valve
Technical Data:
15mm x 20mm
Material: Brass
Red G Page 12
High pressure Carbon Dioxide fire suppression systems
P/N CO2041
P/N CO2041B
Technical Data:
Material: Brass
P/N CO2042
½” directional nozzle
Technical data:
Brass inner
Red G Page 13
High pressure Carbon Dioxide fire suppression systems
Discharge manifold
For multiple cylinder system banks. The discharge manifolds are all manufactured with ASTM A Grade B, schedule 80
piping and pressure tested to 190 Bar in accordance with SANS 306:4 at our SANAS accredited HP testing station.
COMAN2 CO2 Manifold 2-Port Straight COMAN2 T CO2 Manifold 2-Port T shaped
COMAN3 CO2 Manifold 3-Port Straight COMAN3 T CO2 Manifold 3-Port T shaped
COMAN4 CO2 Manifold 4-Port Straight COMAN4 T CO2 Manifold 4-Port T shaped
COMAN5 CO2 Manifold 5-Port Straight COMAN5 T CO2 Manifold 5-Port T shaped
COMAN6 CO2 Manifold 6-Port Straight COMAN6 T CO2 Manifold 6-Port T shaped
COMAN7 CO2 Manifold 7-Port Straight COMAN7 T CO2 Manifold 7-Port T shaped
COMAN8 CO2 Manifold 8-Port Straight COMAN8 T CO2 Manifold 8-Port T shaped
COMAN9 CO2 Manifold 9-Port Straight COMAN9 T CO2 Manifold 9-Port T shaped
COMAN10 CO2 Manifold 10-Port Straight COMAN10 T CO2 Manifold 10-Port T shaped
COMAN11 CO2 Manifold 11-Port Straight COMAN11 T CO2 Manifold 11-Port T shaped
COMAN12 CO2 Manifold12 -Port Straight COMAN12 T CO2 Manifold 12-Port T shaped
COMAN13 CO2 Manifold 13-Port Straight COMAN13 T CO2 Manifold 13-Port T shaped
COMAN14 CO2 Manifold 14-Port Straight COMAN14 T CO2 Manifold 14-Port T shaped
Red G Page 14
High pressure Carbon Dioxide fire suppression systems
Warning signage
Safety signs shall be installed at all entrances to CO2 protected areas and manual operation points.
P/N CO2039
CO2 RELEASE
Manual release CO2 caution signage
Manual
Control Point
To be installed at any CO2 manual release point
CO2
210
CAUTION!
Ensure all
personnel ara
evacuated
before
releasing CO2
75
P/N CO2038
CAUTION !
Door caution signage
Do NOT enter unless
automatic release To be installed at the entrance to every CO2
is isolated
protected area.
CO2
210
75 135
Red G Page 15
High pressure Carbon Dioxide fire suppression systems
General arrangement
Red G Page 16
High pressure Carbon Dioxide fire suppression systems
Pipe Sealant:
Only PTFE tape or SWAK may be used as pipe sealants for the piping and fittings
Piping:
Pipe Fittings:
3000lb steel
Lock off / isolating switches to be installed at the entrance to every CO 2 gas protected area.
All open ended piping shall be pneumatically tested in a closed circuit for a period of 10 min at 3 bar.
At the end of 10 min, the pressure drop shall not exceed 20 % of the test pressure
Red G Page 17