6FL4343-1CX10-0XE0: Building Technologies
6FL4343-1CX10-0XE0: Building Technologies
9291P01
DESIGO™ S7
CM1N9291en_02
17 Sep 2009 Building Technologies
• Engineering with NCM S7 for Ethernet (integrateable as of STEP 7 Version
V5.4 SP4 HF6 ).
• Cross-network PD/OP communications using S7 routing.
• Diagnostic functions in STEP 7 and via web browser.
• Direct integration of S7-300 in complex plants over Ethernet at 100 Mbps.
• Ideal for deployment on line-structure networks using integrated 2-port
real-time switch.
• Investment protection for existing plants by integrating SIMATIC S7-300
via S5-compatible communications.
• Flexible use thanks to free port selection.
• Saving space required for integration thanks to single-width design.
• Remote programming possible also via telephone network (e.g. ISDN)
thanks to TCP/IP's WAN properties.
• Multicast function to reach many members.
• Access of max. 4 operating and monitoring systems to SIMATIC S7-300.
• Use of socket interface in partner system possible without RFC 1006.
• Initial commissioning direct via Industrial Ethernet.
• Use of uncrossed connecting lines possible thanks to integrated auto
crossover function.
• Secure data communications via industrial-type device connection with IE
FC RJ45 plug 145/180 plug connector and additional strain relief thanks to
latching the connector to the housing.
Functions
2/8
Programming device / All S7 stations connected to the network can be remote programmed using PD/OP
OP communications communications.
S7 communications Operating and monitoring devices and PCs (SOFTNET-S7 or CP 1613 A2 with S7-
1613) help connect S7-300 (server only) to S7-400.
Open IE- and S5- S5-compatible communications with SEND/RECEIVE offers a simple and
compatible optimized interface for communications based on Layer 4.
communications Max 8 KB data can be transmitted per incident.
This interface allows for using:
− TCP transport connections
− UDP
− Multicasts for UDP
3/8
SNMP allows for reading all MIB-2 objects. This in turn allows for querying the
current Ethernet interface status.
4/8
Engineering software Engineering software NCM S7 Version V5.4 for Part of STEP 7 V5.4
NCM S7 for Industrial Industrial Ethernet CPs, from STEP 7 V5.4; additional scope of delivery
Ethernet hardware support package (HSP); 1)
documentation on CD-ROM, with electronic manuals in
German, English, French, Spanish, Italian.
Documentation for S7 - For Industrial Ethernet and PROFIBUS; package of
CPs/NCM S7 manuals to engineer S7-CPs, IE/PB link and PC
stations (STEP 7 from V5.3).
• German 6GK7 080-0AA01-8AA0
1) The HSP for CP 343-1 BACnet (6FL4343-1CX10-0XE0) can be downloaded and installed directly via STEP
7 from the Internet, and can be integrated from STEP 7 Version V5.4 SP4 HF6.
CFC 7.0 SP11, S7 SCL from 5.3 SP2 are required for Building Solution
Mechanical design
5/8
STEP 7 V5.4 SP4 or higher and NCM S7 for Industrial Ethernet plus hardware
support package (HSP) is required to engineer CP 343-1, CP343-1 BACnet
(6FL4343-1CX10-0XE0) inclusive. The engineering data of the CP are saved to the
CPU. This allows for module group exchange without PG.
See
https://mall.automation.siemens.com/de/guest/guiRegionSelector.asp?lang=en
for a description of the SIMATIC NET products.
6/8
7/8
What DESIGO S7
Configured alarm recipient 30
(Number of entries on the NC recipient list).
BACnet references
COV server resource COV subscription execute. approx. 50-200
BACnet references
COV-Client COV subscriptions………………… approx. 400
Resources.
BACnet object in the CP for building integration. approx. 1000
Number of BACnet I/O objects including typical HVAC
application (*) for building solution
CPU 314 ..314-1AG13 / 96 KB approx. 20
CPU 314 ..314-1AG14 / 128 KB approx. 40
CPU 315-2DP ..315-2AG10 / 128 KB approx. 40
CPU 315-PN/DP ..315-2AH14 / 256 KB approx. 150
CPU 315-PN/DP ..315-2EG10 / 128 KB approx. 40
CPU 315-PN/DP ..315-2EH13 / 256 KB approx. 50
CPU 317-2DP ..317-2AJ10 / 512 KB approx. 200
CPU 317-PN/DP ..315-2EJ13 / 512 KB approx. 200
CPU 317-PN/DP ..315-2EK13 / 1000 KB approx. 200
CPU 317-PN/DP ..317-2EK14 / 1000 KB approx. 800
CPU 319-PN/DP ..318-3EL00 / 1400 KB approx. 800
Number of function block instances in the CFC chart. 32767
Trend Log – limited only be available RAM in the CPU. Depends on RAM.
Scheduler – limited only be available RAM in the CPU. Depends on RAM.
Calendar – limited only be available RAM in the CPU. Depends on RAM.
Max. number of TP177 on a CPU. 3
Maximum number of CPUs on a TP177. 4
Physical data points, see datasheet for the CPU. Depends on CPU.