Himap Hicam

1. The document describes Hyundai's HIMAP and HICAM devices for intelligent measuring, protection, and communication in power systems. 2. HIMAP is a multifunctional digital protection relay that protects lines, motors, transformers and measures electrical parameters. It communicates via four ports and records faults. 3. HICAM is a communication and measuring device that facilitates communication between HIMAP devices and power management systems for monitoring and control.

Uploaded by

kailashpaliwal29
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
214 views35 pages

Himap Hicam

1. The document describes Hyundai's HIMAP and HICAM devices for intelligent measuring, protection, and communication in power systems. 2. HIMAP is a multifunctional digital protection relay that protects lines, motors, transformers and measures electrical parameters. It communicates via four ports and records faults. 3. HICAM is a communication and measuring device that facilitates communication between HIMAP devices and power management systems for monitoring and control.

Uploaded by

kailashpaliwal29
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 35

HIMAP &

HICAM
We build a better future!

CONTENTS HIMAP HICAM


Characteristics ・・・・・・・・・・・ 04 Characteristics ・・・・・・・・・・・ 30
Display ・・・・・・・・・・・・・・・ 10 Display ・・・・・・・・・・・・・・・ 32
Power Management System Using Connection Diagram ・・・・・・・・ 34
HIMAP & HICAM(HIPMS) ・・・・・・ 12 View & Dimension ・・・・・・・・・ 35
Setting Range ・・・・・・・・・・・ 14
Connection Diagram ・・・・・・・・ 18
Terminal Block Pin Specification ・・・25
Characteristic Curve ・・・・・・・・ 26
Order Form ・・・・・・・・・・・・ 28
View & Dimension ・・・・・・・・・ 29
Hyundai Intelligent Hyundai Intelligent
Measuring & Communication &
Protection Device Measuring Device

Protection
Relay
Function

Event
Record
Function

Fault Wave
Record
Function

Circuit Breaker
Communication Measuring
Remote Control
Function Function
Function
Hyundai Intelligent Measuring & Protection Device

HIMAP is a multifunctional digital protection relay that has a


protection function to protect incoming and feeder lines, the
motor and the transformer.
It also has various kinds of measuring functions to check
synchronization and a communication function for the Power
Management System(HIPMS) to supervise operating conditions.
1 Easy Installation and Maintenance
HIMAP is designed with a removable
case so that the external electric lines can
be connected to the inner part for easy
installation and maintenance.

2 Use of a Digital Filter


HIMAP uses a digital filter, which prevents
any harmonic effects from the high
frequency on the power line.

3 Self-diagnosis Function
HIMAP has a self-diagnosis function set
to observe any system failures, send an
alarm signal, and display it on the VFD
window.
HIMAP | Hyundai Intelligent Measuring & Protection Device |

Characteristics

▶ Excellent operating characteristics using a 32 bit microprocessor.

▶ Easy to operate using an interactive menu system.

▶ Easy to connect monitoring system & local computer using four communication channels.

▶ Increased reliability using a self-diagnostic function.

▶ Designed for operator’s convenience.

Fault / Event Recording Function


HIMAP saves fault events up to 100. Each event data has a fault phase, pick up ratio, operating time and fault date.
Also, for the latest fault, HIMAP saves a fault wave which is 300 cycles with the resolution 36 sampling / cycle.
This can be transfer to monitoring system by communication port.

Circuit Breaker Remote Control Function


HIMAP remotely controls circuit breakers by means of the command from SCADA Systems and
controls the load of power in the computer through RS-485 communication port.
If there is interfacing with another company’s monitoring system, it is easy to connect both systems
because our communication control device provides various interface ports and protocols.
◀06 | 07▶

Harmonic Analysis Function


▶ Harmonic contents(1st~11th) for three phase current can be measured. (THD, TDD)
▶ Harmonic contents for three phase fault wave can be analyzed using HIMAP manager program.

Vector Diagram

+90°

1a = 3.56 ∠ 181.85°

a 1b = 3.53 ∠ 352.31°

c 1c = 3.57 ∠ 183.83°

180° c▼ 0° Vab = 0.23 ∠ 260.47°

Vbc = 0.22 ∠ 259.81°

Vca = 0.16 ∠ 260.56°

-90°

Harmonic Analysis

1a 1b 1c
100.0
THD(0) =
68.90(%)
80.0

60.0
1CPU

THD(1) =
69.57(%)
40.0

20.0
THD(2) =
68.63(%)
0.0
2 3 4 5 6 7 8 9 10 11
HIMAP | Hyundai Intelligent Measuring & Protection Device |

Characteristics

Protection Relay Function


Model Protection Object Relay Function

•OCR(50/51) •OCGR(50G/51G) •DGR(67G)


HIMAP–FI Incoming Feeder •SGR(67G) •OVR(59) •OVGR(64)
•UVR(27R/27M/27S) •PSR(47P/47N) •Closing/Trip coil supervision(94)(Option)

•OCR(50) •51LR •THR(49) •NSR(46)


HIMAP–M Motor •NCHR(66) •UCR(37) •OCGR(50G/51G) •DGR(67G)
•SGR(67G) •DFR(87M) •Closing/Trip coil supervision(94)(Option)

•DFR(87T) •OCR(50/51P)✽ •OCR(50/51S)✽


HIMAP-T Transformer •OCGR(50G/51G) •DGR(67G)
•SGR(67G) •Closing/Trip coil supervision(94)(Option)

HIMAP-SC Syncro-Check •SCR(25) •UVR(27)

※ HIMAP-T Type has 2 OCRs. P means primary and S means secondary.

Measuring Function
HIMAP has a measuring function as shown in the below table. It displays the value of each measurement on the
VFD window by operating a menu key and then transfers and displays the data on the HIMIX window, which has an
outside digital indicator connected by a communication cable.
Various kinds of measuring values are converted to a primary value by input of a CT/PT ratio and then displayed on
the VFD window.

Measuring Display Accuracy (%)

Voltage(Vrs, Vst, Vtr, Vo, Vps, Vns, Vavg, Vomax) 0~999999 V ±0.5

Current(Ir, Is, It, Io, Ips, Ins, Iavg, ITHD, ITDD) 0~999999 A ±0.5

Real Power 0~99999999 kW ±0.5

Reactive Power 0~99999999 kvar ±1.0

Apparent Power 0~99999999 kVA ±1.0


Power

Accumulated Real Energy 0~99999999 kWh ±1.0

Accumulated Reactive Energy 0~99999999 kvarh ±1.0

Power Factor -1.0~1.0 PF ±0.5

Frequency 45~65 Hz ±0.01 Hz

※ CT/PT ratio will be set by using relay control keys and then displayed via VFD window.
The values will be saved at flash memory even though the power line will be off.
◀08 | 09▶

Communication Function
HIMAP has four communication ports. RS-485 ports transfer all information related to relay operation status,
measuring information, and operation status of circuit breakers. This information is then perceived by HIMAP and
sent to communication control device at the speed of 62.5 K bps, using RS-485 HDLC frame protocol and NRZI
mode of synchronous communication.

The communication control device connects a master PC to the Power Management System (HIPMS) at the speed
of 10M bps by Ethernet, TCP/IP. Please refer to the HIPMS manual for details on the monitoring function.

HIMIX communication port transfers kinds of measuring values optional to HIMIX at the speed of 9600 bps.

The external port of HIMAP transfers the fault record from a site to the PC for analysis, changes the relay element
value to a correct one, and is an RS-232C communication port to monitor the status of all kinds of protection relay.

Interface with SCADA


Communication Control Device Type of Communication Protocol

HiCM860S Ethernet Modbus / TCP

HiCM-PC RS-232, 422, 485 Modbus / RTU


HIMAP | Hyundai Intelligent Measuring & Protection Device |

Display

Front View

Display Window(VFD)

Internal Case Exterior Case

System Status Indicator


CB Status (Normal Operation,
System Fail, Fault)
CB Control

Display Key
Input Key

Select Switch
& Led

RS232 Port Movement Key

Set ACK
◀10 | 11▶

Specification
Item 사양
Current 1 A or 5 A, Burden : Below 0.1 VA/Phase
Rating Voltage 110 V or 190 V, Burden : Below 0.3 VA/Phase

Frequency 50 Hz or 60 Hz

Measuring ±0.5 %
Accuracy
Protection Relaying ±2 %

Operation Guarantee -10 ℃ ~ 55 ℃


Temperature
Restoration Guarantee -25 ℃ ~ 70 ℃

Circuits-Ground 10 MΩ
Insulation
Between Circuits 5 MΩ
Resistance
Between Contacts 5 MΩ

Voltage Power Frequency AC 60 Hz 2000 V/1 Min


Withstand Lightning Impulse 1.2/50 ㎲ 5 kV

Current Circuit Rating Current × 3 : 3 hours / Rating Current × 20 : 2 sec


Overland
Voltage Circuit Rating Voltage × 3 : 3 hours
Withstand
Control Power Rating Voltage × 1.3 : 3 hours
Control Power Interruption Maximum 300 ms
Control Power AC/DC 95 V ~ 250 V 50/60 Hz
Standards IEC 60255 / KEMC 1120 / IEC 61000-4
Communication Type RS-485 Multi Drop
Protocol HD-BUS / DNP 3.0
Size 202.5 (W) × 156 (H) × 251.5 (D)
Weight 4.5 kg

I / O Point
Item Point Remark
AI Voltage 4 Default
Input AI Current 4 Default
DI 5 Default
Default(R1~R7) (21~34)
Output DO 7 31, 32(R6) : Remote CB On
33, 34(R7) : Remote CB Off
HIMAP | Hyundai Intelligent Measuring & Protection Device |

Power Management System Using HIMAP & HICAM (HIPMS)

System Configuration

Remote HIPMS Station

To Wide and
Enterprise Management Network Local Area Networks

Router Maintenance Operating


Management Management
HIPMS Server Operator Station System System

Redundant Ethernet Network 10/100Mbps(Fiber Optic)

FEP

HICM-860S or HICM-PC HICM-860S or HICM-PC HICM-860S or HICM-PC

HICAM
Net-MPM

HR-256 Module(RTU) HRC-Net Module(RTU) Max 32 Nodes

Display Configuration

Fault Analysis Network Status System Configuration Remote Setting

Alarm System Diagram Report Menu HIMAP Menu


◀12 | 13▶

Alarm Printer
External System
Graphic Panel Network

Report Printer

Graphic Driver
Color Hard Copler Gateway

HICM-860S or HICM-PC Web Server

HIMAP HIMIX

Web Client Web Client

Max 32 Nodes

S/S SWGR Configuration HIMAP Detail Trend

Trend Report Point Report Regular Report


HIMAP | Hyundai Intelligent Measuring & Protection Device |

Setting Range

FI Type
Mode Instant Definite Inverse, Very Inverse, Extremely Inverse
OCR
Current (1~18) × In (0.1 A Step) (0.2~2.4) × In (Time Delay) (0.1 A Step)
(50/51)
Time Below 0.05 sec 0.05~10.0 sec (0.01 sec Step) 0.05~10.0 Tap (Time Delay) (0.01 Step)
Mode Instant Definite Inverse, Very Inverse, Extremely Inverse
OCGR
Current (0.1~12) × In (0.1A Step) (0.02~1.0) × In (Time Delay) (0.1 A Step)
(50G/51G)
Time Below 0.05 sec 0.05~10.0 sec (0.01 sec Step) 0.05~10.0 Tap (Time Delay) (0.01 Step)
Mode - Definite -
UVR
Voltage - (0.2~0.5) × Vn (0.1 V Step) -
(27R)
Time - 0.1~10.0 sec (0.1 sec Step) -
Mode - Definite -
UVR
Voltage - (0.5~1.0) × Vn (0.1 V Step) -
(27M)
Time - 0.1~10.0 sec (0.1 sec Step) -
Mode - Definite -
UVR
Voltage - (0.5~1.0) × Vn (0.1 V Step) -
(27S)
Time - 0.1~10.0 sec (0.1 sec Step) -
Mode - Definite -
47P Voltage - (0.5~1.0) × Vn (0.1 V Step) -
Time - 0.1~10.0 sec (0.1 sec Step) -
POR
Mode - Definite -
47N Voltage - (0.02~0.5) × Vn (0.1 V Step) -
Time - 0.1~10.0 sec (0.1 sec Step) -
Mode - Definite Inverse
OVR
Voltage - (1.1~1.45) × Vn (0.1 V Step)
(59)
Time - 0.1~10.0 sec (0.1 sec Step) 0.05~10.0 Tap (Time Delay) (0.01 Step)
Mode Instant - Inverse
OVGR
Voltage (0.11~0.5) × Vn (0.1 V Step)
(64)
Time Below 0.05 sec - 0.05~10.0 Tap (Time Delay) (0.01 Step)
Mode Definite
Current (0.04~0.4) × In (0.1 A Step)
DGR
Voltage (0.1~0.2) × Vn (0.1 V Step)
(67GD)
Time 0.1~10.0 sec (0.1 sec Step)
Angle 10°~ 45°(1°Step)
Mode Definite
Current 1~10 mA (0.1 mA Step)
SGR
Voltage (0.1~0.2) × Vn (0.1 V Step)
(67GS)
Time 0.1~10.0 sec (0.1 sec Step)
Angle 45°~75°(1°Step)
※ - In: Rating Current, Vn: Rating Voltage
- Example HIMAP Setting; In: 5 A, OCR: (1~18)×In → 5~90 A
◀14 | 15▶

M Type
Thermal Current (0.1~1.2) × In (0.1 A Step)

THR Cold Limit 0.5~180 sec (0.1 sec Step)


(49) Hot Limit 0.5~180 sec (0.1 sec Step)
τc/τh 0.1~20 (0.1 Step)
Start Current (0.2~14.4) × In (0.1 A Step)
Start Time 1.0~60.0 sec (0.1 sec Step)
51LR
Rocked Rotor Current (0.2~6.0) × In (0.1 A Step)
Rocked Rotor Time 1.0~4.0 sec (0.1 sec Step)
Mode Instant Definite
OCR
Current (0.2~18) × In (0.1 A Step)
(50)
Time Below 0.05 sec 0.05~10.0 sec (0.01 sec Step)
Mode Instant
MPR 50H Current (0.1~4.0) × In (0.1 A Step)
Time Below 0.05 sec
Mode Definite

UCR Maximum Current (0.04~0.5) × In (0.1 A Step)


(37) Minimum Current (0.04~0.5) × In (0.1 A Step)
Time 0.1~10.0 sec (0.1 sec Step)
Mode Definite
NSR
Current (0.1~0.5) × In (0.1 A Step)
(46)
Time 0.1~10.0 sec (0.1 sec Step)
Allow Time 1~60 min (1 min Step)

NCHR Number of Start 1~16


(66) Limit Time 1~60 min (1 min Step)
Thermal Limit(θd) 40~100% (1% Step)
Mode Instant Definite
87M Current (0.04~0.4) × In (0.1 A Step)
Time Below 0.05 sec 0.05~10.0 sec (0.01 sec Step)
Mode Instant Definite Inverse, Very Inverse, Extremely Inverse
OCGR
Current (0.1~12) × In (0.1 A Step) (0.02~1.0) × In (Time Delay) (0.1 A Step)
(50G/51G)
Time Below 0.05 sec 0.05~10.0 sec (0.01 sec Step) 0.05~10.0 Tap (Time Delay) (0.01 Step)
Mode Definite
Current (0.04~0.4) × In (0.1 A Step)
DGR
Voltage (0.1~0.2) × Vn (0.1 V Step)
(67GD)
Time 0.1~10.0 sec (0.1 sec Step)
Angle 10°~45°(1°Step)
Mode Definite
Current 1~10 mA (0.1 mA Step)
SGR
Voltage (0.1~0.2) × Vn (0.1 V Step)
(67GS)
Time 0.1~10.0 sec (0.1 sec Step)
Angle 45°~75°(1°Step)
※ - In: Rating Current, Vn: Rating Voltage
- Example HIMAP Setting; In: 5 A, OCR: (1~18)×In → 5~90 A
HIMAP | Hyundai Intelligent Measuring & Protection Device |

Setting Range

T Type
Mode Instant

Prim. Current (0.2~1.2) × In (0.1 A Step)

Sec. Current (0.2~1.2) × In (0.1 A Step)

Inst. Ratio 500~1500% (1% Step)

DFR Diff. Ratio 20~50% (1% Step)


(87T) Bias Ratio 20~50% (1% Step)

2nd Harmonic Ratio 10~30% (1% Step)

TR Type Dy1, Dy11, Yd1, Yd11, ……………, Dd0, Yy0

Zero Comp. Enable, Disable

Time Below 0.05 sec

Mode Instant Definite Inverse, Very Inverse, Extremely Inverse


OCRP
Current (1~18) × In (0.1 A Step) (0.2~2.4) × In (Time Delay) (0.1 A Step)
(50P/51P)
Time Below 0.05 sec 0.05~10.0 sec (0.01 sec Step) 0.05~10.0 Tap (Time Delay) (0.01 Step)

Mode Instant Definite Inverse, Very Inverse, Extremely Inverse


OCRS
Current (1~18) × In (0.1 A Step) (0.2~2.4) × In (Time Delay) (0.1 A Step)
(50S/51S)
Time Below 0.05 sec 0.05~10.0 sec (0.01 sec Step) 0.05~10.0 Tap (Time Delay) (0.01 Step)

Mode Instant Definite Inverse, Very Inverse, Extremely Inverse


OCGR
Current (0.1~12) × In (0.1 A Step) (0.02~1.0) × In (Time Delay) (0.1 A Step)
(50G/51G)
Time Below 0.05 sec 0.05~10.0 sec (0.01 sec Step) 0.05~10.0 Tap (Time Delay) (0.01 Step)

Mode Definite

Current (0.04~0.4) × In (0.1 A Step)


DGR
Voltage (0.1~0.2) × Vn (0.1 V Step)
(67GD)
Time 0.1~10.0 sec (0.1 sec Step)

Angle 10°~45°(1°Step)

Mode Definite

Current 1~10 mA (0.1 mA Step)


SGR
Voltage (0.1~0.2) × Vn (0.1 V Step)
(67GS)
Time 0.1~10.0 sec (0.1 sec Step)

Angle 45°~75°(1°Step)

※ - In: Rating Current, Vn: Rating Voltage


- Example HIMAP Setting; In: 5 A, OCR: (1~18)×In → 5~90 A
◀16 | 17▶

SC Type
Mode Definite

Time 0.1~15.0 sec (0.1 sec Step)

25A Voltage (0.02~0.7) × Vn (0.1 V Step)

Phase 0°~100°(1°Step)

Frequency 0.01~5.0 Hz (0.01 Hz Step)

Mode Definite

Time 0.1~15.0 sec (0.1 sec Step)

25B Voltage (0.02~0.7) × Vn (0.1 V Step)

Phase 0°~100°(1°Step)

Frequency 0.01~5.0 Hz (0.01 Hz Step)

Mode Definite
UVR
Voltage (0.5~1.0) × Vn (0.1 V Step)
(27S)

Time 0.1~10.0 sec (0.1 sec Step)


HIMAP | Hyundai Intelligent Measuring & Protection Device |

Connection Diagram

HIMAP-FI(3CT, 3PT)

R S T

R1 21
PT / GPT
9 22
10 DISPLAY R2
11 23
12
13 24 Program-
14 mable
R3 25
Relay
CPU 26 Output
15
R4 27
16

28
CB GPT
3rd R5 29

1 30
2 R6
31 Local/
3 Remote
4 50 32
CB On

5 R7 33
CT 6 51 Local/
Remote
34 CB Off
7
8
50G
35
NA
51G 36

37
27 CCS
38
47P Option
39
TCS
R S T DC 24 V
47N 40

1 59 41
2 42
50
3
52a 64 43
44 NA
4
5 52b
51 67G 45
46
CT 6
47
52
Remote 48
Vp
60
Vn
7 53 61
DI1
ZCT 8 62 RS485
(Scada)
63
54
DI2 64
65
When using ZCT 59 KEYBOARD Vp
66
(SGR) Vn RS485
67 (HIMIX)
68 Option

P
Control
N
Power

FG
◀18| 19▶

HIMAP-FI/M(2CT, 2PT)

R S T

R1 21
PT × 2
9 22
10 DISPLAY R2
11 23
12
13 24 Program-
14 mable
R3 25
Relay
CPU 26 Output
15
R4 27
16

28
CB
R5 29

1 30
2 R6
31 Local/
3 Remote
CB On
4 50 32
5 R7 33
CT 6 51 Local/
Remote
CB Off
7 34
8
50G
35
NA
51G 36

37
27 CCS

ZCT 38
47P Option
39
TCS
R S T DC 24 V 47N 40

59 41
42
50
52a 64 43
44 NA

52b
51 67G 45
46
47
52
Remote 48
Vp
60
Vn
53 61
DI1
62 RS485
(Scada)
63
54
DI2 64
65
59 KEYBOARD Vp
66
Vn RS485
67 (HIMIX)
68 Option

P
Control
N
Power

FG
HIMAP | Hyundai Intelligent Measuring & Protection Device |

Connection Diagram

HIMAP-M

R S T

R1 21
PT / GPT
9 22
10
11
DISPLAY R2 23
12
13 24 Program-
mable
14 R3 25
Relay

CPU 26 Output
15
R4 27
16

GPT 28
CB 3rd R5 29

1 30

2 R6 31 Local/
3 Remote
CB On
4 MPR 32
5 R7 33 Local/
CT 6 (50H / Remote
CB Off
34
7
8
49 / 35
NA
51LR / 36

37
46 / CCS
38
37 / 39
Option

TCS

DC 24 V
66) 40

41
50
42
50
43
R S T 52a 50G
44 NA
1

2
52b
51 51G 45
46
3
52
67G 47
4 Remote 48
Vp
5 60
Vn
61
CT 6 53
DI1
62 RS485
(Scada)
63
54 64
7 DI2
65
ZCT 8
KEYBOARD Vp
59 66
Vn RS485
67 (HIMIX)
68 Option

When using ZCT P


(SGR) Control
N
Power

FG
◀20 | 21▶

HIMAP-M(87M)(Self-balancing Type)

R S T

R1 21
1
2
DISPLAY 22

3 R2 23
4
5 24 Program-
CT mable
6 CPU R3 25
7 Relay

8 26 Output
R4 27

28

R5 29

9 30
10

11
MPR R6 31 Local/
Remote
12 CB On

13
(50H / 32

R7 33
CT 14 Local/
49 / Remote
CB Off
34
15
16 51LR / 35
NA
GPT
3rd
46 / 36

37
37 / CCS
38
DC 24 V 66) 39
Option

TCS
87M 40
50
52a
41
50
42
51
52b 43
50G
44 NA

Remote
52 51G 45
R S T 46

1 53
67G 47
DI1 48
2 Vp
60
3 Vn
54 61
4 DI2
62 RS485
5 (Scada)
63
CT 59
6 64
KEYBOARD 65
Vp
66
Vn RS485
7 67 (HIMIX)
ZCT 68 Option
8
P
Control
N
Power

When using ZCT FG


(SGR)
HIMAP | Hyundai Intelligent Measuring & Protection Device |

Connection Diagram

HIMAP-M(87M)(Differential Type)

R S T

R1 21
1
2
DISPLAY 22

3 R2 23
4
5 24 Program-
CT mable
6 CPU R3 25
7 Relay

8 26 Output

R4 27
9
10 28

11 R5 29
12
13 30
14
MPR R6 31 Local/
15 Remote
CB On
16 (50H / 32

17 R7 33 Local/
18
49 / Remote
CB Off
34
19
CT
20
51LR / 35
NA
46 / 36

37
37 / CCS
38
DC 24 V 66) 39
Option

TCS
87M 40
50
52a
41
50
42
51
52b 43
50G
44 NA

Remote
52 51G 45
46

53
67G 47
DI1 48
Vp
60
Vn
54 61
DI2
62 RS485
(Scada)
63
59
64
KEYBOARD 65
Vp
66
Vn RS485
67 (HIMIX)
68 Option
P
Control
N
Power

FG
◀22 | 23▶

HIMAP-T

R S T

R1 21

22
CB DISPLAY
R2 23
1
2 24 Program-
3 mable
R3 25
4 Relay
CPU 26
5 Output
CT 6 R4 27

28

R5 29

30
TR R6 31 Local/
Remote
87T 32
CB On

R7
7 50P 33 Local/
Remote
8 CB Off
34
9
51P
35
10
11
50G 36
NA

CT 12
13
51G 37
CCS
14 38
50S Option
15 39
16 51S TCS
CB 40
GPT
3rd DC 24 V 67G 41
42

50 43
R S T 52a 44 NA

1 45
51 46
2 52b
47
3
48
4 52 Vp
Remote 60
5 Vn
61
CT 6
53 62 RS485
DI1 (Scada)
63
64
13 54
DI2 65
Vp
ZCT 14 KEYBOARD Vn
66
RS485
59 67 (HIMIX)
68 Option

When using ZCT P


Control
(SGR) N
Power

FG
HIMAP | Hyundai Intelligent Measuring & Protection Device |

Connection Diagram

HIMAP-SC

R S T R1 21

PT 22
1
2 DISPLAY R2 23
3
Bus A
4
5 24 Program-
mable
6 R3 25
Relay
R S T CPU 26 Output

PT R4
Bus B
9 27S 27

10
28

R5 29
R S T
25A
30
PT 11 R6
Bus C 31 Local/
12 Remote
CB On
32

R7 33
R S T Local/
25B Remote
CB Off
PT 34
13
Bus D
14 35
NA
36

37
CCS
38
Option
39
TCS
40
DC 24 V
41
42
43
50
52a 44 NA
45
51 46
52b
47
48
52 Vp
Remote 60
Vn
61
53 62 RS485
DI1 (Scada)
63
64
54
DI2 65
Vp

59
KEYBOARD Vn
66
RS485
67 (HIMIX)
68 Option

P
Control
N
Power

FG
◀24 | 25▶

Terminal Block Pin Specification

HIMAP-FI / M Type

41
P 42 21 22 1 2
43
N 44 23 24 3 4
45
46 25 26 5 6
47
48 27 28 7 8

60 29 30 9 10
61
62 50 31 32 11 12
63 51
64 52 33 34 13 14
65 53
54 35 36 15 16
55
56 37 38 17 18
66 57
67 58 39 40 19 20
68 59

Control Power Terminal Digital Output Analog Input


P (+) 41 21 R1 22 1 Ia 2
N (-) 42 23 R2 24 3 Ib 4
FG 43 25 R3 26 5 Ic 6
44 27 R4 28 7 Io 8
N.A
Communication Terminal 45 29 R5 30 9 Vab 10
60 Vp 46 31 R6(CB On) 32 11 Vbc 12
61 Vn 47 33 R7(CB Off) 34 13 Vca 14
62 S.G 48 35 N.A 36 15 Vo 16
63 Vp 37 CCS 38 17 N.A 18
64 Vn Digital Input 39 TCS 40 19 N.A 20
65 50 52a
51 52b Terminal No. Description Application
HIMIX Communication 52 Remote 50 CB On Status 52a Fixed
Terminal 51 CB Off Status 52b Fixed
53 D/I 1
66 Vp 52 Remote Input Fixed
54 D/I 2
67 Vn 53 General DI Variable
55
68 N.A 54 General DI Variable
56 21~22 R1
N.A
57 23~24 R2
Programmable
58 25~26 R3
Relay Output
59 Common 27~28 R4
29~30 R5
31~32 R6(CB On) Fixed
33~34 R7(CB Off) Fixed
35~36 N.A N.A
37~38 CCS Fixed
39~40 TCS Fixed
HIMAP | Hyundai Intelligent Measuring & Protection Device |

Characteristic Curve

OCR & OCGR


Inverse OP LEVEL 0.05~10.0 Very Inverse OP LEVEL 0.05~10.0

0.01 0.01

MPR
Extremely Inverse OP LEVEL 0.05~10.0 Current-Time Curve THR(49), 51LR, 50

Locked Rotor

Cold Thermal Limit

Hot Thermal Limit

Stalled Rotor

0.01
◀26 | 27▶

OVR OVGR
Inverse OP LEVEL 0.05~10.0 Very Inverse OP LEVEL 0.05~10.0

0.01 0.01

DGR / SGR
DGR SGR

Operation Area
Operation Area
HIMAP | Hyundai Intelligent Measuring & Protection Device |

Order Form

HIMAP – ❶ – ❷ ❸ – ❹ (Option)

Relay Type
FI : Feeder / Incoming
M : Motor
87M : Big(over than 3000 kW) Motor
T : Transformer
SC : Synchro Check

Ground Fault Type


C : OCGR
D : DGR
S : SGR

Communication Function
C : RS-485
X : N.A
※ TCS(Trip Coil Supervision)
Circuit breaker coil supervision with option. TCS Function
※ Specify followings separately
T : Required
X : N.A
- CT(Secondary) : 1 A - CB On/Off Switch N.A
- 87M : Differential Type - Frequency : 50 Hz ※ Refer to the following specification for more detail
relay function.

Relay Function

Table 1 (FI)
Item OCR OCGR DGR SGR OVR UVR OVGR PSR
C ● ● ● ● ● ●
D ● ● ● ● ● ●
S ● ● ● ● ● ●

Table 2 (M)
Item MPR OCGR DGR SGR
C ● ● Ordering Example
D ● ●
S ● ● HIMAP-M-SC-X
M : Motor Protection
Table 3 (87M)
S : SGR(None grounding sys.)
Item 87M MPR OCGR DGR SGR Remark
C : SCADA Communication
C ● ● ● ✽ 87M
D ● ● ● Self balancing( ) X : TCS N.A
Differential( )
S ● ● ●
HIMAP-FI-CC-T
Table 4 (T)
FI : Feeder Protection
Item DFR OCR P OCR S OCGR DGR SGR
C : OCGR
C ● ● ● ●
D ● ● ● ●
C : SCADA Communication
S ● ● ● ● T : TCS required
◀28 | 29▶

View & Dimension

Weight 4.3 Kg

HIMAP

156
202.5

32.9 218.6
Front View
251.5

Top View

41
42
43
21 22 1 2
44
45
23 24 3 4
46
47
25 26 5 6
48
27 28 7 8
60 29 30 9 10
138

61
62 50 31 32 11 12
63 51
64 52 33 34 13 14
65 53
54 35 36 15 16
55
56 37 38 17 18
66 57
67 58 39 40 19 20
68 59

Side View 184.5

Rear View
139

186

Panel Cut-out Dimension


Hyundai Intelligent Communication & Measuring Device

HICAM(Hyundai Intelligent Communication and Measuring


Device) has integrated as many as 14 analog meters in one body.
The measuring accuracy is below ±0.5% at rating.

For power monitoring system connection, HICAM has RS485 communication


port, communication control device (HICM series) and support modbus protocol.

Remote CB On/Off control is possible by the command from power monitoring


system.
1 Accuracy

±0.5% at rating

2 Voltage / Current Input


CT: 0.1~30 A / PT: 10~380 V

3 Various Measuring
14 measuring points

4 Compact Size and Display


- Various indicator and measuring display
- Size: 202.5 (W) × 156 (H) × 186 (D)

5 Power Management System Connection


- RS485 HD-Bus
- Modbus protocol by communication
control device (HICM Series)
- Optic fiber communication (Option)
HICAM | Hyundai Intelligent Communication & Measuring Device |

Display

Front View

Communication Address Display Window

Alarm Led Select Key

Current Bar Select Led


Graph Display

Set Key

D/I Status Led D/O Status Led

I / O Point
Item Point Remark
AI Voltage 4 Default
Input AI Current 4 Default

DI 8 Default(41~50)

Default(31~40)
37, 38(D04) : Remote CB On
Output DO 5
39, 40(D05) : Remote CB Off
31~36(D01~D03) use current demand output.
◀32 | 33▶

Specification
Item Specification
Current 1 A or 5 A(0.1 A~30.0 A)
Rating Voltage 110 V or 190 V(10 V~380 V)
Frequency 50 Hz or 60 Hz
Accuracy Measuring ±0.5 %
Operation Guarantee -10 ℃ ~ 55 ℃
Temperature
Restoration Guarantee -25 ℃ ~ 70 ℃
Circuit-Ground 100 ㏁
Insulation
Between Circuits 100 ㏁
Resistance
Between Contacts 100 ㏁

Voltage Power Frequency AC 60 Hz 2,000V/1 Min


Withstand Lightning Impulse 1.2/50 ㎲ 5 kV
Current Circuit Rating Current×3 : 3 hours / Rating Current×20 : 1 sec
Overland
Voltage Circuit Rating Voltage×3 : 3 hours
Withstand
Control Power Rating Voltage×1.3 : 3 hours
Control Power AC 85 ~ 264 V (50 / 60 Hz), DC 90 ~ 120 V
Communication Type RS–485 / Multi Drop
Protocol HD-BUS / Modbus
Standards KEMC1110, IEC1036
Size 202.5 (W)×156 (H)×186 (D)
Weight 1.5 Kg

Measuring
Measuring Display Accuracy Remark
Voltage 0~999999 V ±0.5% Line to Line Voltage
Current 0~999999 A ±0.5% Phase Current
Real Power 0~99999999 kW ±0.5%
Reactive Power 0~99999999 kvar ±1.0%
Apparent Power 0~99999999 kVA ±1.0%
Accumulated Real Energy 0~99999999 kWh ±1.0%
Accumulated Reactive Energy 0~99999999 kvarh ±1.0%
Power Factor -1.0~1.0 PF ±0.5%
Frequency 45~65 Hz ±0.01 Hz
Reverse Real Power 0~999999 kW ±1.0% (-) Sign
Reverse 0~999999 kWh ±1.0% (-) Sign
HICAM | Hyundai Intelligent Communication & Measuring Device |

Connection Diagram

3P 4W 3PT_3CT 3P 3W 2PT_2CT

Remote CB On : 37, 38 Terminal Remote CB On : 37, 38 Terminal


Remote CB Off : 39, 40 Terminal Remote CB Off : 39, 40 Terminal

3P 3W 3PT_3CT 3P 3W 2PT_3CT

Remote CB On : 37, 38 Terminal Remote CB On : 37, 38 Terminal


Remote CB Off : 39, 40 Terminal Remote CB Off : 39, 40 Terminal
◀34 | 35▶

View & Dimension

Top View
Right Side View

Front View Rear View

Panel Cut-out Dimension