(RMU) OCR - Manual - EN - 201909

This document provides specifications and safety guidelines for an RMU OCR device. It includes: - Safety cautions to prevent electric shock or injury from incorrect use. - Features like self-powering, wide temperature range, and fault monitoring capabilities. - Interface descriptions including LED status displays, buttons, and connection ports. - Technical specifications such as voltage/frequency ratings, protection functions, setting ranges for pickup values and time curves, and inverse time calculation formulas. - Dimensional drawings and diagrams of the protection blocks and connection compositions.

Uploaded by

Phong Dang
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
78 views20 pages

(RMU) OCR - Manual - EN - 201909

This document provides specifications and safety guidelines for an RMU OCR device. It includes: - Safety cautions to prevent electric shock or injury from incorrect use. - Features like self-powering, wide temperature range, and fault monitoring capabilities. - Interface descriptions including LED status displays, buttons, and connection ports. - Technical specifications such as voltage/frequency ratings, protection functions, setting ranges for pickup values and time curves, and inverse time calculation formulas. - Dimensional drawings and diagrams of the protection blocks and connection compositions.

Uploaded by

Phong Dang
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

Table of contents

1. Safety caution ....................................................................................3

2. Feature ...............................................................................................6

3. Operation environment…………………………………………….6

4. Dimension..........................................................................................7

5. Interface .............................................................................................8

6. Specification .................................................................................... 11

7. PC manager .....................................................................................19

8. Type test ...........................................................................................20

2
1. Safety caution
Please read carefully before product being taken into service to ensure
safety and proper operation of RMU OCR.

∙ Please keep the safety caution to prevent any accident may happen by
using the products incorrectly.

∙ Safety caution is classified with caution and danger and indication of


them as follows.

Caution Not following the instruction may result in serious


injury or even death.

Danger Not following the instruction may result in serious


injury or property damage

Symbols used in this manual indicate as follows.

This symbol is for warning the hazardousness under the specific condition.

This symbol is for warning the electric shocks or any accidents under the specific
condition.

This instruction shall be kept in the nearest place of RMU OCR

3
Caution
∙ Please do not wiring when applied with power or on the operation; it may result in electric shock.

∙ Please do not all the wiring operation with the live bus bar; it may result in electric shock or fire and

property damage by charging voltage of current transformer.

∙ Please put to earth; it may result in electric shock.

∙ Please do not attempt to disassemble even when the power not applied; it may result in electric

shock by charging current remained in the product.

∙ Please do not wire or operate with wet hands; it may result in electric shock.

∙ Please do not use any damaged cable; it may result in electric shock.

Danger
■ Safety caution for installation & terminal wiring

∙ Please keep away product from screws, metals, water, or oil; it may result in fire.

∙ Please keep the rated load and polarity of input & output contacts; it may result in property damage

or fire.

∙ Please wire to the terminal block after checking the terminal number; it may result in property

damage or fire.

∙ Specialist help shall be sought for the installation and maintenance of product; it may result in

malfunction or accident.

∙ Please do not wiring when applied with power or on the operation; it may result in electric shock.

4
■ Inspection item before power supply being applied

∙ Check the wiring condition of input/output terminal.

■ Caution for storage & handling

∙ Please store at dry & clean place.

∙ Please do not throw or put force on it during transport; it may result in malfunction or wrong
operation.

∙ Please stock the products in the way of FIFO (First-in First-out).

∙ Please do not load over 5 stories

■ Caution for disposal

∙ Please dispose of it in accordance with industrial waste regulation.

5
2. Feature

■ Self-powerd precision protected relay

■ Wide operating temperature : -40 ~ 80℃

■ Protection Function :

▶ Over current protection (51D, 51T), Over current ground protection (51ND)

■ Free voltage remote command : AC 110 ~ 220V

■ Measuring display in PC Manager

■ Fault event view in PC Manager

▶ User can view fault data using PC Manager

3. Operation environment

■ Operating temperature : -40℃ ~ +80℃

■ Storage temperature : -50℃ ~ +85℃

■ Relative Humidity : 10 ~ 100%

■ Elevation : 1500m or less

6
4. Dimension

[Figure 4-1]

7
5. Interface

■ Setting
As shown in the figure below, Operator can set the setting values of 51T, 51D, 51ND.

[Figure 5-1] Rotary switch

■ Device status display

▶ LED display
* Power : If power (More than 90% of CT Ratio) is supplied, LED will light.(Color : Green)
* Trip : If protection element of OCR is picked up, LED will be blinking and If OCR is tripped,
LED will light.(Color : Red)

8
■ Service Button
When you want to initialize CPU, you can use CPU/RESET switch. But please don’t press this
button normally.

■ Connection
There are four connections in OCR for other device or command.

▶ Remote Trip Input Connection


Number 1 and 5 of pin are operation for Remote Trip and if operator supply 110~220V, OCR will
be tripped.

[Figure 5-2] Remote Trip Input Connection

▶ PC Manager Connection
If OCR connects to PC through PC Manager Connection, OCR can communicate PC Manager
without power supply.

PC Manager Connection
(RS-485)

[Figure 5-3] PC Manager Connection/

9
▶ CT Current Input connection.

OCR performs measurement and relay if CT current is supplied. It’s composed of Main Current

Structure and Test Current Structure.

[Figure 5-4] Connect Composition

▶ Test Connection.
If you supplies current into Test Connection, You can firm OCR normal operation

[Figure 5-5] Test Current Composition

10
6. Specification

■ Nominal : 60Hz or 50Hz (Selection)

■ Protection
OCR has 3 current Protection function(51D, 51T, 51ND)

[Figure 6-1] Protection Block Diagram

▶ Rating Current Setting


Operation Value of NEW RMU OCR will be calculated by 1 st CT Ratio and You can set Rating
Current with front Rotary Switch. (Description : In)

[Figure 6-2] In Rotary Switch

[Table 6-1] In Setting

11
▶ Fast Short circuit protection and overload protection (51D)
.

[Figure 6-3] 51D Block diagram

* Phase current Setting : 1 ~ 20 In (16 Steps)


* Operation Time Setting : Definite Time 0.04~3.0(16 Steps)

[Figure 6-4] I >> Setting [Figure 6-5] tI >> Setting

[Table 6-2] Fast Short Circuit Protection Setting


SW 0 1 2 3 4 5 6 7 8 9 A B C D E F
I>> 1 2 3 4 5 6 7 8 9 10 12 14 16 18 20 N/A
tI>> 0.04 0.07 0.1 0.15 0.2 0.25 0.3 0.4 0.6 0.8 1.0 1.4 1.8 2.2 2.6 3.0

* N/A : It means “Not Use”.

12
▶ Overload Protection (51T)

[Figure 6-6] 51T Block Diagram

* Phase current Setting : 0.9 ~ 2.5In (16 Steps)


* Operation Time Setting : Definite Time and Inverse Time 16 Steps

[Figure 6-7] I > Setting [Figure 6-8] tI > Setting

[Table 6-3] 51T( I>) Setting


SW 0 1 2 3 4 5 6 7 8 9 A B C D E F
I> 0.9 0.95 1.0 1.05 1.1 1.15 1.2 1.3 1.4 1.5 1.6 1.8 2 2.25 2.5 N/A

[Table 6-4] 51T( tI >) Setting


SW a b c d e f g h i j k l m n o p
DT 0.04 0.3 0.6 1 2 3 4 6 8 10 15 30 60 120 210 300
Lever 0.05 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 8 10

* N/A : It means “Not Use”.

13
* Inverse Time Curve : IEC SI, VI, EI, LI, ANSI SI, VI, EI, KEPCO SI, VI
* Inverse Time Formula :

* Is : Setting Current Value , If : Fault Current Value


[Table 6-5] Inverse Curve Parameter
A B C
IEC SI 0.14 0.02 0
IEC VI 13.5 1 0
IEC EI 80 2 0
IEC LI 120 1 0
ANSI SI 0.0515 0.02 0.114
ANSI VI 19.61 2 0.491
ANSI EI 28.2 2 0.1217
KEPCO SI 0.11 0.02 0.42
KEPCO VI 39.85 1.95 1.084

* Inverse Time Operation Curve

IEC SI Curve IEC VI Curve

14
IEC EI Curve IEC LI Curve

[Figure 6-9] IEC Time/Current Curve

ANSI SI Curve ANSI VI Curve

15
ANSI EI Curve
[Figure 6-10] ANSI Time/Current Curve

KEPCO SI Curve KEPCO VI Curve


[Figure 6-11] KEPCO Time/Current Curve

16
▶ Over Current Ground Protection (51ND)
OCR determines the accident on the basis of Zero phase current. (Average of 3-Phase Current)

[Figure 6-12] 51ND Block Diagram

* Phase Current Setting : 0.2 ~ 2.5In( 16 Steps)


* Operation Time Setting : 0.1~20(16 Steps)

[Figure 6-13] IE > Setting [Figure 6-14] tIE > Setting

[Table 6-6] 51ND Setting


SW 0 1 2 3 4 5 6 7 8 9 A B C D E F
IE> 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.2 1.4 1.6 1.8 2.0 2.5 N/A
tIE> 0.1 0.2 0.4 0.6 0.8 1 1.5 2 2.5 3 3.5 4 6 8 10 20

* Normal Operation Condition : Sum of 3-Phase current RMS value is more than 90% of at least
CT Ratio
* N/A : It means “Not Use”.

17
■ Accuracy

▶ Trip Level
* 51D, 51T
5P80 CT used : ±10% of setting value in all range or ±15% of minimum of In setting
10P80 CT used : ±15% of setting value in all range or ±20% of minimum of In Setting
* 51ND
5P80 CT used : ±10% of sum of input current in three phase or ±15% of minimum of
In setting.
10P80 CT used : ±15% of sum of input current in three phase or ±20% of minimum
of In setting.

▶ Trip Time
* 51D : A high value of the ±15% of nominal trip time or ±40msec
* 51T : A high value of the ±15% of nominal trip time or ±40msec
* 51ND : A high value of the ±15% of nominal trip time or ±40msec
* In non-energized state, When the test current is lower than 2 times of minimum of In
Setting, Absolute accuracy of trip time will be ±200msec

■ Measurement

▶ NEW RMU OCR can measure 3-Phase Current (A/B/C) with PC Manager.

▶If input current is lower than 30% of minimum of In, display value is 0 (zero)

▶ OCR Accuracy

* 30% of minimum of In~100% of minimum of In : ±10%

* 100% of minimum of In~150% of maximum of In : ±5%

▶ CT Accuracy (No guarantee under the rated range)

* 5P80 : at CT rating ±1% / over CT rating : ±5%

* 10P80 : at CT rating ±3% / over CT rating : ±10%

▶ OCR + CT Accuracy

* CT accuracy + OCR accuracy

* ex> The error in CT rating when using 5P80 CT

: CT accuracy 1% + OCR accuracy ±10% = ±11%)

18
■ Remote Trip
NEW RMU OCR can control Trip Operation through Remote Trip Connection.

▶ Remote Trip Input : 1 Point ▶ Trip delay: within 1sec

▶ Input voltage range : 110V ~ 220V


[Table 6-7] Remote input operation voltage
Voltage Level Lower than 50V 50 ~ 85V Upper than 85V
State Must be Off Don’t Care Must be ON

■ Test Connection

▶ Test Connection connects to C,D connection of 3-Phase CT.

▶ If you supply 1/50 times of 1 st CT current, you can supply the same as 2 nd CT current to

OCR(ex. 1 st 14.4A = Test Connection 0.288A => 2 nd 0.075A)

■ Fault Information

▶ OCR saves a up-to-date fault event.

▶ It can save fault phase, fault current, and kind of accident..

▶ You can confirm fault event with PC manager.

7. PC manager

■ Installation

▶ If you want to use PC manager, you need USB cable, 485 Converter, OCR cable.

[Figure 7-1] Installation Component

19
▶ You can use PC Manager and 485 Converter driver program after purchase.

▶ The supported OS is Windows XP, Vista, 7, 10.

8. Type Test

■ Safety and Environment related type test


- IEC 60068-2-2 Basic environment testing procedure : Part 2 Test Ba. Dry heat (Storage)
- IEC 60068-2-1 Environment testing Part 2-1. Tests – Test Ab : Cold (Storage)
- IEC 60068-2-30 Environment testing Part 2-30. Tests – Test Db : Damp Heat, cyclic
- IEC 60068-2-78 Environment testing Part 2-78. Tests – Test Cab : Damp heat, steady state
- IEC 60068-2-2 Basic environment testing procedure : Part 2 Test Bd. Dry heat (Operating)
- IEC 60068-2-1 Environment testing Part 2-1. Tests – Test Ad : Cold (Operating)
- IEEE Std C37.90-2005 Insulation Test : Impulse Voltage Test
- IEEE Std C37.90-2005 Dielectric power frequency test.

■ Electromagnetic Compatibility
- IEC 61000-4-8 Power frequency magnetic field immunity test
- IEC 60255-22-1 1MHz burst disturbance tests Class III
- IEC 60255-22-2 Electrostatic discharge tests
- IEC 60255-22-3 Radiated electromagnetic field immunity
- IEC 60255-22-4 Electrical fast transient/burst immunity test
- IEC 60255-22-5 Surge immunity test
- IEC 60255-22-6 Immunity to conducted disturbances induced by radio frequency fields
- IEC 60255-25 Electromagnetic emission tests for measuring relays and protection equipment