With Ruhstrat transformers you provide the right voltage for the widest range of applications. With their
durability and reliability – and availability with extensive approvals on request – our transformers can
be used worldwide.
Individual solutions, which need to fulfill special requirements regarding operation type, minimal noise
and low-loss design, connection technologies, cooling systems as well as transport and assembly, are
always possible.
2
CONTENTS
GENERAL 4
CAST-RESIN TRANSFORMERS – 10 KV 6
CAST-RESIN TRANSFORMERS – 20 KV 7
DETAILED VIEW 8
TECHNICAL INFORMATION –
ACCESSORIES AND MONITORING 10
THIS IS RUHSTRAT 15
3
GENERAL
Certified safety
4
Standard design of Ruhstrat cast-resin transformers
■ HV material: Aluminium or copper
■ LV material: Aluminium or copper
■ Insulation class: F
■ Climate class C2 / Environmental class E2 / Fire class F1
according to IEC/EN 60076-11:2004
Project-specific types
Individual solutions, which fulfil special requirements with re-
spect to the operating mode, low-noise and low-loss design,
connection technology, cooling, transport and setup are pos-
sible at any time.
5
CAST-RESIN TRANSFORMERS – 10 KV
Frequency 50 Hz
Vcc 6%
Environmental class/ E2 - C2 - F1
Climate class/Fire class (Type Test Certificate CESI A9032391)
Power No-load losses Load loss Weight Width Depth Height Distance between
Losses Io Lwa
[kVA] [W] [W] [kg] [mm] [mm] [mm] wheels [mm]
100 AoAk-Reg548 280 1800 1,8 51 830 1200 600 1260 520
100 AoBk-Reg548 280 2050 1,8 51 800 1200 600 1200 520
160 AoAk-Reg548 400 2600 1,6 54 950 1200 600 1350 520
160 AoBk-Reg548 400 2900 1,6 54 1000 1250 600 1330 520
200 AoAk-Reg548 450 2955 1,4 55 1050 1250 600 1360 520
200 AoBk-Reg548 450 3300 1,4 55 1100 1250 600 1350 520
250 AoAk-Reg548 520 3400 1,2 57 1200 1350 600 1340 520
250 AoBk-Reg548 520 3800 1,2 57 1120 1300 600 1360 520
315 AoAk-Reg548 615 3875 1,1 58 1350 1350 750 1400 670
315 AoBk-Reg548 615 4535 1,1 58 1350 1350 750 1400 670
400 AoAk-Reg548 750 4500 1 60 1570 1350 750 1480 670
400 AoBk-Reg548 750 5500 1 60 1500 1350 750 1480 670
500 AoAk-Reg548 900 5630 0,9 60 1650 1350 750 1620 670
500 AoBk-Reg548 900 6410 0,9 60 1650 1400 750 1600 670
630 AoAk-Reg548 1100 7100 0,9 62 2000 1500 850 1700 670
630 AoBk-Reg548 1100 7600 0,9 62 1950 1450 850 1670 670
800 AoAk-Reg548 1300 8000 0,8 64 2400 1500 850 1800 670
1000 AoAk-Reg548 1550 9000 0,7 65 2900 1600 1000 1940 820
1250 AoAk-Reg548 1800 11000 0,7 67 3300 1650 1000 2050 820
1600 AoAk-Reg548 2200 13000 0,5 68 4050 1800 1000 2120 820
2000 AoAk-Reg548 2600 16000 0,5 70 4850 1900 1310 2160 1070
2500 AoAk-Reg548 3100 19000 0,4 71 5950 2050 1400 2340 1070
3150 AoAk-Reg548 3800 22000 0,4 74 7000 2150 1400 2360 1070
6
CAST-RESIN TRANSFORMERS – 20 KV
Frequency 50 Hz
Vcc 6%
Environmental class/ E2 - C2 - F1
Climate class/Fire class (Type Test Certificate CESI A9032391)
Power No-load losses Load loss Weight Width Depth Height Distance between
Losses Io Lwa
[kVA] [W] [W] [kg] [mm] [mm] [mm] wheels [mm]
100 AoAk-Reg548 280 1800 1,8 51 920 1250 600 1280 520
100 AoBk-Reg548 280 2050 1,8 51 900 1250 600 1280 520
160 AoAk-Reg548 400 2600 1,6 54 1040 1250 600 1360 520
160 AoBk-Reg548 400 2900 1,6 54 1050 1250 600 1360 520
200 AoAk-Reg548 450 2955 1,4 55 1200 1350 600 1370 520
200 AoBk-Reg548 450 3300 1,4 55 1140 1350 600 1370 520
250 AoAk-Reg548 520 3400 1,2 57 1350 1350 680 1360 520
250 AoBk-Reg548 520 3800 1,2 57 1350 1350 680 1360 520
315 AoAk-Reg548 615 3875 1,1 58 1450 1350 750 1420 670
315 AoBk-Reg548 615 4535 1,1 58 1420 1350 750 1420 670
400 AoAk-Reg548 750 4500 1 60 1680 1450 750 1490 670
400 AoBk-Reg548 750 5500 1 60 1600 1450 750 1490 670
500 AoAk-Reg548 900 5630 0,9 60 1790 1450 750 1620 670
500 AoBk-Reg548 900 6410 0,9 60 1800 1450 750 1620 670
630 AoAk-Reg548 1100 7100 0,9 62 2150 1550 850 1730 670
630 AoBk-Reg548 1100 7600 0,9 62 2150 1550 850 1730 670
800 AoAk-Reg548 1300 8000 0,8 64 2550 1550 850 1840 670
1000 AoAk-Reg548 1550 9000 0,7 65 3150 1650 1000 1980 820
1250 AoAk-Reg548 1800 11000 0,7 67 3650 1750 1000 2070 820
1600 AoAk-Reg548 2200 13000 0,5 68 4600 1900 1000 2150 820
2000 AoAk-Reg548 2600 16000 0,5 70 5550 2000 1310 2230 1070
2500 AoAk-Reg548 3100 19000 0,4 71 6300 2150 1310 2350 1070
3150 AoAk-Reg548 3800 22000 0,4 74 8250 2300 1400 2510 1070
7
DETAILED VIEW
LV connections
upwards (standard) or downwards version (on request)
Lifting eyebolts
conform to the DIN-580 standards with safety hooking at 4 points
Rating plate
HV connections
upwards (standard) or downwards version (on request)
LV windings
made of aluminium strip foil (available in copper) impregnated in resin
under vacuum
HV windings
made of aluminium strip coils (available in copper) and cast in resin under
vacuum
8
Terminal box
for temperature probes
Temperature monitoring
The operating temperature is checked by
Pt100 sensor or PTC which are mounted in the LV windings
Delta connection
Earthing terminals
Pulling holes
9
TECHNICAL INFORMATION – ACCESSORIES AND MONITORING
10
Weight Length Width Height
CRT Power [kVA]
[kg] [mm] [mm] [mm]
components are additionally galvanized and the ventilation power reduction as compared with the open version with pro-
slots are made of seawater-proof unpainted sheet aluminium. tection type IP00.
All enclosure parts are earthed by means of earthing bolts. As
standard equipment, the enclosure features two cable holders Increased power with cross-flow fans
for cables routed from below. The cables are guided within the To increase the power output, the cast-resin transformer with
enclosure to the transformer connections. For connections rout- natural cooling (AN) can be converted to forced cooling (AF) by
ed from above or from the side, cable entries or flanged frames installing cross-flow fans. The power output can be increased
can be provided on request in the top or the side walls. by up to 40 % in this way. This option gives planning personnel
further freedom in the design of the plant.
The natural ventilation within the enclosure and the construc-
tion of the enclosure surface is designed so that there is no
11
TECHNICAL INFORMATION – ACCESSORIES AND MONITORING
Electrical connections
Generally, it is possible to make use of the increased power
output in forced cooling mode (AF) in normal operation without High-voltage and low-voltage connections are located oppo-
affecting the service life. site each other on the side walls of the transformer. The high-
voltage connection points are mechanically and electrically in-
The safety concept preferably provides for a distributor network tegrated in the high-voltage cast resin coil, together with the
with two or more cast-resin transformers. If the transformers tapping bars for the voltage conversion (standard ± 2 × 2.5 %).
are dimensioned so that approx. 70 % of the power output is The low-voltage connecting rails, including the star point, lead
required in normal operation – an optimal design for reasons of out through the top.
economy – in the event that one transformer fails, the increased
power output due to forced cooling of the other transformer These are the standard connections for the Dyn5 vector group;
would be sufficient to compensate for the total output of the other project-specific connections are available on request.
failed transformer without restrictions.
12
HV winding connections with ball connection bolts LV winding connections Temperature sensor
Temperature monitoring
PTC thermistor sensors with a high resistance value at the re- Suitable monitoring and triggering devices are available for
spective response temperature are provided for temperature monitoring of the cast-resin transformers.
monitoring of each cast-resin transformer. Since the LV and
HV windings are in thermal equilibrium, the thermistors are
attached to the LV winding for insulation purposes. Above all,
they protect the vacuum cast high-voltage windings against
excessive temperatures, which can occur in case of overloads,
insufficient cooling and/or high ambient temperatures. On re-
quest, thermistor sensors are also available for core monitoring
via PT100.
13
TRANSFORMERS FOR MARINE APPLICATIONS
14
THIS IS RUHSTRAT
When the brothers Adolf and Ernst Ruhstrat opened their small
electrical shop in 1888 in Göttingen, our company’s success
story was still unwritten.
The entire staff uses our expertise, based on more than 125
years of experience, to absolutely satisfy the requirements of
our demanding customers at all times. This is made possible by
custom solutions, which we develop in close cooperation with
our customers. Our only mass produced products are those that You wish for more information regarding Ruhstrat
meet specific customer requirements. and our products? Just visit our website:
www.ruhstrat.com
The expert knowledge about the technology of electrical testing
solutions, voltage optimizers, transformers and systems with You have questions regarding our cast-resin transformers and/
control cabinets, control and PLC, makes us a strong and inno- or you require an offer? Under the link
vative partner to our customers. http://tinyurl.com/request-offer you will find various means to
contact us.
It goes even quicker by scanning our QR-code (shown on the left
side) using your smartphone or tablet.
15
Ruhstrat Power Technology GmbH
Heinestraße 12 · 37120 Bovenden · Germany
Phone: +49 55 93 9 37 22-0 · E-Mail: [email protected]
www.ruhstrat.com
All rights reserved. All texts, photos and images are subject to copyright and other laws for the protection of intellectual property.
Use of the content requires the prior permission of RPT Ruhstrat Power Technology GmbH. All information, descriptions and illustrations are subject to technical modification,
especially with a view toward the further development of our products in accordance with the current state of the art. There will be no special announcement of changes to information, descriptions and illustrations.
Errors excepted. Technical characteristics can vary from country to country.