This document outlines the specification and bill of quantity for a 3000 kVA dry-type transformer for Kopiko Philippines Corporation Phase 3 project. The transformer specifications include a capacity of 3000 kVA, dry type construction with IP30 housing, on-load tap changer, copper windings, 34.5 kV high voltage and 380-410V low voltage. Accessories such as lugs, lifting eyes, bushings and busbar connections are required. Protections include temperature sensors and an automatic voltage regulator.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
30 views

Outiline Spec. & BQ M&E (SS) R.xls/Trafo Dry 1/1

This document outlines the specification and bill of quantity for a 3000 kVA dry-type transformer for Kopiko Philippines Corporation Phase 3 project. The transformer specifications include a capacity of 3000 kVA, dry type construction with IP30 housing, on-load tap changer, copper windings, 34.5 kV high voltage and 380-410V low voltage. Accessories such as lugs, lifting eyes, bushings and busbar connections are required. Protections include temperature sensors and an automatic voltage regulator.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

PROJECT : KOPIKO PHILIPPINES CORPORATION PHASE 3

SUBJECT : OUTLINE SPECIFICATION & BILL OF QUANTITY TRANSFORMER 3000 kVA (DRY)
REV. / DATE : 0 / SEPTEMBER 2022
PREPARED BY : PT. METAKOM INTI PERKASA

UNIT PRICE TOTAL UNIT PRICE


ITEM DESCRIPTION UNIT QTY REMARKS
(₱) (₱)

1 TRANSFORMER 3000 kVA (DRY)

1.1 Capacity : 3000 kVA Unit 1 -


a Type : Dry type with housing IP 30 with on load tap changer (OLTC)
b Function : Step down from high to low voltage system
c Standard : IEC 726-82, IEEE C57.12.01-1998
d Insulation Level : L1170 AC70 for 35 kV

Detail Specification
a Phase : 3
b Frequency : 60 Hz
c Winding : Copper - Copper
d High Voltage : 34,5 kV
e Low Voltage : 380 - 410 Volt

1.2 Cooling
a Air : Natural Cooling (NA) & Forced Air (AF)
b Insulation Class H

1.3 On Load Tap Changer : 4 Taps (±4 x 2.5%)

1.4 Vector Group : Follow Philippines Standard / Regulation

1.5 Electrical Characteristic


a Ambient Temperature : Max. 65
No Load :ossed : Max. 0,5%
Load Losses : Max. 2%
b Impedance Voltage : 6% for 3000 kVA
c Noise Level : According to NEMA (60 dB)

1.6 Accessories
Transformer must be included :
a Lugs
b Lifting Eye
c Bushing
d Busbar Copper Connection (Outgoing)
e Air Cooling Fan
f Winding Temperature Indicator c/w Contact
g Switching for Fan & exhaust fan

1.7 Protection Transformer : Temperature Sensor

1.8 Automatic Voltage Regulator : MR (Germany)

1.9 Guide Rail

1.10 Unloading on Foundation (as Per Transformer Location)

CARRIED TO GRAND SUMMARY Rp. -