Foam System Hydraulic Calculation Report
Foam System Hydraulic Calculation Report
: COOP-2021-15-D-3-
FF-HR-02
Foam System Hydraulic
Rev. : 04
Calculation Report Page : 1 of 18
Date : 15/02/2023
TABLE OF CONTENTS
1. INTRODUCTION
2. DEFINITION
3. REFERENCES
4. UNITS
5. CALCULATION BASIS
8. ATTACHMENTS
Doc. No. : COOP-2021-15-D-3-
FF-HR-02
Foam System Hydraulic
Rev. : 04
Calculation Report Page : 3 of 18
Date : 15/02/2023
1. INTRODUCTION
This calculation report covers the foam solution demand estimating for firefighting system to protect
equipment and facilities installed in CO-OPERATION Petroleum Company Suez Tank Farm, Arab
Republic of Egypt.
2. DEFINITIONS
3. REFERENCES
4. UNITS
Unless otherwise specified, metric, Celsius, kilogram and kg/cm2g units will be applied as the
measurement system However, nominal sizes of piping components will be in accordance with inch
system.
Doc. No. : COOP-2021-15-D-3-
FF-HR-02
Foam System Hydraulic
Rev. : 04
Calculation Report Page : 4 of 18
Date : 15/02/2023
5. CALULATION BASIS
Foam solution velocity in pipe including deluge valve manifold pipe taken from firewater main shall
not exceed 6 m/sec although 3.5 m/sec (block case 4 m/sec) for firewater main network pipe.
Foam Demand
The largest foam demand of one of the fire risk areas will be the maximum foam demand based on a single
major fire breaking out in one fire risk area in any one time.
The used foam shall be FP “Fluoroprotein” of 6% concentration” for storage tanks foam chambers only, all
remaining facilities in process areas shall use AFFF “Aqueous Film Forming Foam” of 3% concentration
including fire monitors.
Doc. No. : COOP-2021-15-D-3-
FF-HR-02
Foam System Hydraulic
Rev. : 04
Calculation Report Page : 5 of 18
Date : 15/02/2023
The following table in Attachment#1 “Fire Scenarios and Application Rates”, summarizes different fire
scenarios for fire that could develop in equipment/separate areas and the firefighting equipment used to protect
this equipment/area showing the application flow rates that will be used for the burning equipment as well as
any other adjacent equipment in fire radiation section as detailed in COOP-2021-15-D-3-FF-FP-01 Fire Fighting
Systems Philosophy
Calculation Result
Maximum Foam Demand for 3% AFFF foam type is Scenario # 1 “Storage Tank S-10 same as K-1 & K2” is
maximum foam demand case of maximum capacity of 20 m3 of concentrated foam required for 3 hrs of
operation to cover tank S-10 dike area with 2 fire monitors at 6.5 lpm/m2 application rate.
Maximum Foam Demand for 6% FP foam type is Scenario # 2 “Storage Tank S-10 same as K-1 & K2” is
maximum foam demand case of maximum capacity of 4 m3 of concentrated foam required for 30 min to operate
the foam chambers of the burning tank.
This manual calculation result and its required fire main size will be verified by Hydraulic Calculation Report
using (“PIPENET” programmed by SUNRISE SYSTEM LTD.) for flow analysis in pipe network in Hydraulic
Calculation Report.
8. ATTACHMENTS
Attachment # 1 “Foam System Scenarios and Application Rates”
Attachment #2 “Foam System Manual Calculation & Foam Solution Lines Sizing”
Attachment #3 “Spray Nozzles Catalogues”
Doc. No. : COOP-2021-15-D-3-
FF-HR-02
Foam System Hydraulic
Rev. : 04
Calculation Report Page : 6 of 18
Date : 15/02/2023
Attachment # 1
“Foam System Fire Scenarios and Application Rates”
Fire Water /Foam Demands Scenarios
Total
Fire Water Foam Demand Total Foam
Foam
Equipment on Fire Fixed Foam System Solution FP Concentrated Foam Demand AFFF Concentrated Foam Demand as Per NFPA 11
Fire Scenarios Firefighting Equipment Water Spray System Fire Monitor (*) Fire Hydrant Solution Remarks
Tag (Spray / Champer) (6%FP)
Activation Device Activation Method (3%AFFF)
m3/hr m3/hr m3/hr m3/hr m3/hr m3/hr m3/hr m3/hr
(*) 2 X Foam Monitors will be used for S-10 dike spillage control (application rate
1 S-10 Foam Champer (**) FDV-01 Automatic N/A 112 228 57 112 228 6.72 20.52
666 m3/hr/m2) for approximate 3 hrs with AFFF Foam
(*) 1 X Foam Monitors will be used for K-1 (or) K2 dikes spillage control
2 K-1 (OR) K-2 Foam Champer (**) FDV-03 (OR) FDV-04 Automatic N/A 112 114 57 112 114 6.72 6.84
(Application rate I 222 m3/hr/m2) for approximate 2 hrs with AFFF Foam
FDV-0016 Automatic
3 LOADING ARMS Water/Foam Spray System N/A 601.34 114 57 N/A 715 N/A 20.387304
FDV-0017 Automatic
P-1A
P-1B
P-3A
FDV-20
P-3B
P-3C
P-3D
Pump Shed Section-01
4 Automatic N/A 378.00 114 57 N/A 492.00 N/A 14.76
Water/Foam Spray System
P-3E
P-6
P-9A
FDV-25
P-9B
P-9C
P-20
Doc. No. : COOP-2021-15-D-3-
FF-HR-02
Foam System Hydraulic
Rev. : 04
Calculation Report Page : 8 of 18
Date : 15/02/2023
Attachment #2
“Foam System Manual Calculation & Foam Solution Lines Sizing”
Fire Water/Foam Manual Hydraulic Calculatuion Sheet
Equipment Data
Spray Nozzles Data Ring Pipe Data Foam Data
Minimum
Minimum Total Flow rate
Minimum Water Concentrated Foam
Water Demand required per
Actual Height Application Rate Demand Volume
Zone No. Deluge Valve No. Diameter Length Width Surface Area (3) Required Minimum No. of Total Maximum Actual Pipe Foam Equipment Foam Type
(2) Required No. of Rings / Nozzle Flow Total Nozzles Total Nozzles Horz. Distance Actual Velocity Concentrated Foam
Equipment Type Equipment Tag Equipment Description Spray Nozzle Model Spray Angle K-Factor (4) Discharge Nozzles Per Number of Ring Circumfrance overlap % (8) Velocity Diameter Application
Branches (6,9) Rate (4) Flow rate Flow rate Between Nozzles inside Pipe Volume
Pressure (5) Ring (7) Nozzles Inside Pipe Used Duration (10)
1"
Laoding Arms Shed LA-3D Gas Oil Loading Arm N/A 65 12 N/A N/A 780 6.5 5070 304.2 Pendent / Upright 43.2 2.1 22 4 63 88 5544 332.64 N/A 3 66.7 4 8 2.9 30 4.9896 332.64 4.9896
FOAM/WATER SPRAY NOZZLE
1"
Common Metering Skids All All loading Arms N/A 6 1 1 12 6.5 78 56.16 Pendent / Upright 43.2 2.1 2 2 63 4 252 181.44 N/A 3 66.7 4 2 2.1 30 2.7216 181.44 2.7216
FOAM/WATER SPRAY NOZZLE
1"
Common Metering Skids All All loading Arms N/A 6 1 1 6 6.5 39 56.16 FOAM/WATER Ground Sweep 90 deg Vendor to Confirm 7 1 2 60.6 24 1454.4 87.26 N/A N/A N/A 4 1.5 1.8 30 1.30896 87.26 1.30896
Nozzles
FDV-05 FOAM CHAMPER FC-S1 S-1 Bunker Gas Oil Storage Tank 20 N/A N/A 7.5 314 4.1 1287.4 77.244 N/A N/A Vendor to Confirm 3.5 N/A N/A 1287.4 1 1287.4 78 N/A N/A N/A 4 4 2.7 30 2.34 78 2.34
FDV-06 FOAM CHAMPER FC-S2 S-2 Bunker Gas Oil Storage Tank 20 N/A N/A 7.5 314 4.1 1287.4 77.244 N/A N/A Vendor to Confirm 3.5 N/A N/A 1287.4 1 1287.4 78 N/A N/A N/A 4 4 2.7 30 2.34 78 2.34
FDV-07 FOAM CHAMPER FC-S3 S-3 Gas Oil Storage Tank 16 N/A N/A 13.75 200.96 4.1 823.936 49.43616 N/A N/A Vendor to Confirm 3.5 N/A N/A 823.936 1 823.936 50 N/A N/A N/A 4 4 1.7 30 1.5 50 1.5
FDV-08 FOAM CHAMPER FC-S4 S-4 Gas Oil Storage Tank 16 N/A N/A 13.75 200.96 4.1 823.936 49.43616 N/A N/A Vendor to Confirm 3.5 N/A N/A 823.936 1 823.936 50 N/A N/A N/A 4 4 1.7 30 1.5 50 1.5
FDV-09 FOAM CHAMPER FC-S5 S-5 Summer Diesel Storage TanK 16 N/A N/A 13.75 200.96 4.1 823.936 49.43616 N/A N/A Vendor to Confirm 3.5 N/A N/A 823.936 1 823.936 50 N/A N/A N/A 4 4 1.7 30 1.5 50 1.5
FDV-02 FOAM CHAMPER FC-S11 S-11 Gasoline 95 Storage Tank 16 N/A N/A 13.75 200.96 4.1 823.936 49.43616 N/A N/A Vendor to Confirm 3.5 N/A N/A 823.936 1 823.936 50 N/A N/A N/A 4 4 1.7 30 1.5 50 1.5
FOAM CHAMPER FC-S10-1 S-10 Gasoline 92 Storage Tank 24 N/A N/A 15 452.16 4.1 926.928 55.61568 N/A N/A Vendor to Confirm 3.5 N/A N/A 926.928 1 926.928 56 N/A N/A N/A 4 4 2 30 1.68 56
FDV-01 3.36
FOAM CHAMPER FC-S10-2 S-10 Gasoline 92 Storage Tank 24 N/A N/A 15 452.16 4.1 926.928 55.61568 N/A N/A Vendor to Confirm 3.5 N/A N/A 926.928 1 926.928 56 N/A N/A N/A 4 4 2 30 1.68 56
Water/Foam Champers (12) 6% FP
FOAM CHAMPER FC-K1-1 K-1 Gas Oil Storage Tank 24 N/A N/A 13.215 452.16 4.1 926.928 55.61568 N/A N/A Vendor to Confirm 3.5 N/A N/A 926.928 1 926.928 56 N/A N/A N/A 4 4 2 30 1.68 56
FDV-03 3.36
FOAM CHAMPER FC-K1-2 K-1 Gas Oil Storage Tank 24 N/A N/A 13.215 452.16 4.1 926.928 55.61568 N/A N/A Vendor to Confirm 3.5 N/A N/A 926.928 1 926.928 56 N/A N/A N/A 4 4 2 30 1.68 56
FOAM CHAMPER FC-K2-1 K-2 Bunker Gas Oil Storage Tank 24 N/A N/A 13.215 452.16 4.1 926.928 55.61568 N/A N/A Vendor to Confirm 3.5 N/A N/A 926.928 1 926.928 56 N/A N/A N/A 4 4 2 30 1.68 56
FDV-04 3.36
FOAM CHAMPER FC-K2-2 K-2 Bunker Gas Oil Storage Tank 24 N/A N/A 13.215 452.16 4.1 926.928 55.61568 N/A N/A Vendor to Confirm 3.5 N/A N/A 926.928 1 926.928 56 N/A N/A N/A 4 4 2 30 1.68 56
FDV-13 FOAM CHAMPER FC-S6 S-06 Solar Bunker Storage Tank 16 N/A N/A 13.215 200.96 4.1 823.936 49.43616 N/A N/A Vendor to Confirm 3.5 N/A N/A 823.936 1 823.936 50 N/A N/A N/A 4 4 1.7 30 1.5 50 1.5
FDV-12 FOAM CHAMPER FC-S7 S-07 Solar Bunker Storage Tank 16 N/A N/A 13.215 200.96 4.1 823.936 49.43616 N/A N/A Vendor to Confirm 3.5 N/A N/A 823.936 1 823.936 50 N/A N/A N/A 4 4 1.7 30 1.5 50 1.5
FDV-10 FOAM CHAMPER FC-SA1 SA-1 Bunker Storage Tank 8.98 N/A N/A 10.5 63.302714 4.1 259.5411274 15.57246764 N/A N/A Vendor to Confirm 3.5 N/A N/A 259.541127 1 259.5411274 16 N/A N/A N/A 4 2 2.2 30 0.48 16 0.48
FDV-11 FOAM CHAMPER FC-SB1 SB-1 Solar Bunker Storage Tank 12 N/A N/A 12 113.04 4.1 463.464 27.80784 N/A N/A Vendor to Confirm 3.5 N/A N/A 463.464 1 463.464 28 N/A N/A N/A 4 3 1.7 30 0.84 28 0.84
Fire Water/Foam Manual Hydraulic Calculatuion Sheet
Equipment Data
Spray Nozzles Data Ring Pipe Data Foam Data
Minimum
Minimum Total Flow rate
Minimum Water Concentrated Foam
Water Demand required per
Actual Height Application Rate Demand Volume
Zone No. Deluge Valve No. Diameter Length Width Surface Area (3) Required Minimum No. of Total Maximum Actual Pipe Foam Equipment Foam Type
(2) Required No. of Rings / Nozzle Flow Total Nozzles Total Nozzles Horz. Distance Actual Velocity Concentrated Foam
Equipment Type Equipment Tag Equipment Description Spray Nozzle Model Spray Angle K-Factor (4) Discharge Nozzles Per Number of Ring Circumfrance overlap % (8) Velocity Diameter Application
Branches (6,9) Rate (4) Flow rate Flow rate Between Nozzles inside Pipe Volume
Pressure (5) Ring (7) Nozzles Inside Pipe Used Duration (10)
N/A FM-0001 General Coverage N/A N/A N/A N/A N/A 463.4146341 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0002 General Coverage N/A N/A N/A N/A N/A 463.4146341 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0003 General Coverage N/A N/A N/A N/A N/A 463.4146341 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
FDV-20
N/A FM-0004 General Coverage N/A N/A N/A N/A N/A 463.4146341 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0005 General Coverage N/A N/A N/A N/A N/A 463.4146341 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0006 General Coverage N/A N/A N/A N/A N/A 463.4146341 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
Pumps Shed Section 1 1"
N/A FM-0007 General Coverage N/A
N/A 34
N/A 9
N/A N/A
N/A N/A
N/A 306
463.4146341 20.4
4.1 6242.4
1900 374.544
114 Pendent / Upright Vendor43.2 2.1 25 4 63 100 6300 378 N/A 1.36 68 44 24 34 30 5.67 378 5.67 3% AFFF
(General Exposure) FOAM/WATER/SPRAY
Jet Fog NOZZLE +80 to -15 to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 30 1.71 114 1.71
N/A FM-0008 General Coverage N/A N/A N/A N/A N/A 463.4146341 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0009 General Coverage N/A N/A N/A N/A N/A 463.4146341 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
Water/Foam Fire Monitors FOAM MONITOR (11) 3% AFFF
N/A FM-0010 General Coverage N/A N/A N/A N/A N/A 463.4146341 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0011 General Coverage N/A N/A N/A N/A N/A 463.4146341 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0012 General Coverage N/A N/A N/A N/A N/A 463.4146341 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0013 General Coverage N/A N/A N/A N/A N/A 463.4146341 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
Water/Foam Spray System
N/A FM-0014 General Coverage N/A N/A N/A N/A N/A 463.4146341 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0015 General Coverage N/A N/A N/A N/A N/A 463.4146341 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0016 General Coverage N/A N/A N/A N/A N/A 463.4146341 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0017 General Coverage N/A N/A N/A N/A N/A 463.4146341 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
N/A FM-0018 General Coverage N/A N/A N/A N/A N/A 463.4146341 4.1 1900 114 Jet / Fog +80 to -15 Vendor to Confirm 5 N/A N/A 1900 1 1900 114 N/A N/A N/A 4 4 4 30 1.71 114 1.71
P-5001
Water/Foam Spray System FDV-0023 Fire Pumps Room P-5002 General Coverage 2"X16 Branch each of 4 Foam Nozzles with estimated QTY. of 62 spray Nozzle 3% AFFF
P-5003
Water/Foam Spray System FDV-0028 Ware House #1 WH-01 General Coverage 2"X11 Branch each of 5 Foam Nozzles with estimated QTY. of 55 spray Nozzle 3% AFFF
FDV-0018/
Water/Foam Spray System Ware House #2 WH-02 General Coverage 2"X25 Branch each of 5 Foam Nozzles with estimated QTY. of 125 spray Nozzle 3% AFFF
FDV-0019
Water/Foam Spray System FDV-0015 Hazard Waste Building HWB-01 General Coverage 2"X8 Branch each of 6 Foam Nozzles with estimated QTY. of 48 spray Nozzle 3% AFFF
General Notes
1. Due to the shortage of information provided by COOP, some data have been assumed i.e. Working Volume for some Tanks, Tanks Roof Height,….. Etc.
2. Since the shell to shell distance between tanks complies with NFPA 30 Table # 4.3.2.2, The whole tank height was considered
3. Sufeace Area Equation used for Tanks Shell: ΠDH
Surface area Equation used for Tanks Roof: ΠRL where L is the slant height of the cone
4. K-Factor value can be obtained from the equation in NFPA 15 parag. 5.5.1.5
5. Minimum discharge pressure as per NFPA 15 of any protection nozzles at an outdoor hazard is 1.4bar, accordingly 2.1bar was used as an avarage design pressure to ensure that while including pressure friction losses due to pipes
material roughness and fitting, the nozzles pressure will always be maintane above 1.4bar
6. For estimating the required number of spray rings of each tank please refer to NFPA 15 parag. 4.5.2 and API RP 2030 sec. 7.3.13
7. In oreder to calcuate the number of nozzles per ring, please refer to NFPA 15 parag. 4.1.4
8. Nozzles overlaping shall meet the coverage distances mentioned in NFPA 15 parag. 4.1.4, parag. 4.5.2 & API RP 2030 sec. 7.3.13 with recommended overlap precentage 60%
11. Monitor minimum flow rate shall not be less than (250GPM to 500GPM) as per API RP2030 sec. 7.2.1 accordingly for High Expansion system, 500GPM is recommended (refer to Design Basis COOP-2021-15-D-3-FF-DB-01)
Attachment #3
“Spray Nozzles Catalogues”
Foam Top
Pourer Set Mk4
The Angus Fire Top Pourer Set (TPS) Foam Tube Length
Mk4 is designed for use in foam
The standard or minimum length of
systems for the protection of fixed roof
the foam dispersal tube projecting
flammable liquid storage tanks with
into the tank interior is shown in the
Nitrogen inerted blankets or where
below table under “E”. It is designed
tank internal pressures may reach 0.35
for pourers mounted (usually using
bar (5 psi) The Mk4 combines foam
the Angus Fire mounting kit) directly
generation, vapour sealing and foam
on to the tank wall. This positions
pouring in a robust, low-maintenance
the deflector plate at the optimum
design and represents over 35 years of
position inside the tank to spread the
product development and operating
foam evenly around the interior.
experience. Each unit is factory
Other lengths of the foam dispersal
calibrated to perform at a fixed flow
tube can be specified by the customer.
and pressure point and can perform
to the precise pressure and flow Glass Vapour Seal Disc
standards laid down by Underwriters
TPS Mk4 units are fitted with a
Laboratories (UL) and NFPA.
replaceable glass bursting disc suitable
Units without a vapour seal are available for tank internal pressures up to
for total flooding of open roof tanks. 0.34 bar (5psi).
Four basic body sizes cover flow ranges Positive Bursting Disc Mechanism
from 75 l/min (20 US gal/min) to
When the Mk4 TPS is activated, the
3,300 l/min (870 US gal/min) at inlet
liquid foam and water mixture is driven
pressures between 3 bar (45 psi) and
up the pourer inlet pipe under full
10 bar (150 psi).
operating pressure. The liquid pressure
The discharge is enhanced by a causes the air inlet flap valves at the ANSI RF #150 inlet / outlet flange sizes*
deflector plate fitted to the outlet which base of the pourer to close. The liquid, Inlet outlet
disperses the finished foam against the still under full pressure, travels up the TPS 50 2” 4”
tank wall. This ensures a rapid spread tube, past the foam maker and bursts TPS 80 3” 6”
across the surface of the fuel, whilst the heavy duty glass vapour seal disc,
TPS100 4” 8”
lowering the application velocity, allowing access to the tank interior.
TPS150 6” 10”
reducing contamination of the foam by
the fuel and minimising splash. *ISO and DIN flanges also available
Performance Envelope
3000
400
300 1200
FLOW l.p.m.
FLOW l.p.m.
1000 2000
FLOW l.p.m.
2200
FLOW l.p.m.
200 800
100 400
0 0 0 0
0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 10
PRESSURE bar PRESSURE bar PRESSURE bar PRESSURE bar
Foam Top Pourer Set Mk4
Installation Options A hole is cut into the tank side. Then the need for access to the inside of
the Angus mounting kit flange is the tank. The TPS body with its foam
The Angus mounting kit allows the TPS
secured from outside by passing the deflector is then bolted on to the
to be sited without the need for access
stud nuts through the access hole. adapter kit flange in the normal way.
from inside the tank.
They are then tightened on the inside
WARNING: Before any cutting work by reaching through the access hole
is done to the tank wall, which could from outside the tank, removing
cause sparks and hot spots, it must be
ensured that the tank is empty and
purged of any flammable vapour.
Notes:
1. All inlets should be positioned equally around the circumference of the tank, but the
distance between any 2 pourers should not exceed 30m on fixed cone roof tanks.
2. Consideration may have to be given to ensuring the foam application does reach
the centre of large tanks.
Worldwide
www.tyco-fire.com
Contacts
AGITATOR
AGITATOR
7/16" 5-15/16"
(11,1 mm) 3/8" DIA. (150,8 mm)
NOMINAL (9,5 mm)
MAKE-IN
BODY
1"
(25,4 mm)
1/2" ACROSS
NPT WRENCH DEFLECTOR
WRENCHING FLATS 2-1/8" DIA.
AREA (54,0 mm)
UPRIGHT PENDENT
FIGURE 1
MODEL B-1 FOAM-WATER UPRIGHT AND PENDENT SPRINKLERS
NOMINAL DIMENSIONS
DATA KEY
WATER DISCHARGE FOAM DISCHARGE
8 or 10 INCH
RADIUS, METERS RADIUS, FEET ADJUSTABLE
3,0 2,0 1,0 0 2 4 6 8 10 WRENCH
0 0
DISTANCE BELOW
DISTANCE BELOW
CEILING, METERS
0,5
2
CEILING, FEET
APPLY TO
1,0 WRENCH
4 FLATS
1,5 ONLY
6
2,0
8 FIGURE 2
2,5
UPRIGHT WRENCH FLATS
RADIUS, METERS RADIUS, FEET
0
3,0 2,0 1,0 0 2 4 6 8 10
0
Limited
Warranty
DISTANCE BELOW
DISTANCE BELOW
CEILING, METERS
0,5
2
CEILING, FEET
For warranty terms and conditions, visit
1,0 www.tyco-fire.com.
4
1,5
6
Ordering
2,0
Procedure
2,5 8 Contact your local distributor for avail-
PENDENT
ability. When placing an order, indi-
GRAPH A cate the full product name, including
NOMINAL DISCHARGE PATTERNS description and part number (P/N).
(SHOWN FOR REFERENCE ONLY — NOT SUITABLE FOR DESIGN PURPOSES)
Upright Foam-Water Sprinklers
Specify: Model B-1 Upright Foam-
Care and Frequent visual inspections are recom-
mended to be initially performed for
Water Sprinkler, P/N 49-210-1-001
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association